tekmar 538 Installation

Page 1
D538
tekmarNet®4 Thermostat 538
Installation & Operation Manual
Introduction
The tekmarNet®4 Thermostat 538 provides operation for:
One Stage Heat
12/11
Zoning
Replaces:08/10
Features
Zone Synchronization
• Zone Post Purge
• Intelligent setback (Timer 033)
• Scenes (Away override)
• Auto Heating Cycle
• tekmarNet® 4 communication
• compatible
Requires 4 wires
• Pulse Width Modulation
• CSA C US Approved for use in
• USA and Canada
Outdoor temperature display
• Air Group member
• Backlight
• Freeze Protection
• Equipment Exercising
• Floor warming (Slab Sensor 079)
• 1 Auxiliary sensor input
• Room Temperature Limiting
• Supports Radiant Floor Cooling
D 538 - 12/11
Page 2
------------------------------------------------------
--------------------------------------------------
Table of Contents
Getting Started ..............................2
Installation .........................................2
Caution ..........................................2
Preparation ....................................2
Removing The Thermostat Base ...3
Mounting The Thermostat Base ....3
Thermostat Wiring .........................4
Testing the Thermostat Wiring ......4
Mounting the Thermostat ..............5
Cleaning the Thermostat ...............6
Switch Settings ..................................6
User Interface ....................................7
Display...........................................7
Button Operation ...........................7
Symbols Description .....................7
Settings ....................................8-14
Sequence of Operation .................... 15
Heating Operation ....................... 15
Air Group Operation .................... 16
Floor Cooling ...............................16
Schedules ................................... 17
Scenes (System Override) .......... 17
Troubleshooting ...............................18
Error Messages ......................18-21
Frequently Asked Questions .......22
Job Record ..................................23
Technical Data .............................23
Limited Warranty and Product
Return Procedure ........................24
Getting Started
Congratulations on the purchase of your new tekmar thermostat.
This manual will step through the complete installation, programming and sequence of operation for this control. At the back, there are tips for control and system troubleshooting.
Installation
Caution
Improper installation and operation of this control could result in damage to the equipment and possibly even personal injury or death. It is your responsibility to ensure that this control is safely installed according to all applicable codes and standards. This electronic control is not intended for use as a primary limit control. Other controls that are intended and certified as safety limits must be placed into the control circuit.
Preparation
Tools Re q uired
tekmar or jeweller screwdriver
• Phillips head screwdriver
Materials Required
2, #6 x 1” Wood Screws
• 18 AWG LVT Solid Wire
• (Low Voltage Connections)
------------------------------------------------------
Wire Stripper
--------------------------------------------------
Optional Adapter Plate 007 (for
• installation on 2” x 4” gang box)
2 of 24© 2011 D 538 - 12/11
Page 3
Installation Location
-------------------------------------------------
-------------------------------------------------
Choose the placement of the thermostats early in the construction process to enable proper wiring during rough-in.
Consider the following:
Interior Wall.
• Keep dry. Avoid potential leakage onto the control.
• Relative Humidity max 92% up to 104°F (40°C), 50% RH above 104°F (40°C).
• Non-condensing environment.
No exposure to extreme temperatures beyond 32-122°F (0-50°C).
• No draft, direct sun, or other cause for inaccurate temperature readings.
• Away from equipment, appliances, or other sources of electrical interference.
• Easy access for wiring, viewing, and adjusting the display screen.
• Approximately 5 feet (1.5 m) off the finished floor.
• The maximum length of wire is 500 feet (150 m).
• Strip wire to 3/8” (10 mm) for all terminal connections.
• Use standard 4 conductor, 18 AWG wire.
Removing The Thermostat Base
To remove the thermostat base:
Place a small slot screwdriver or similar
• tool into the slot located on the top of the thermostat.
While pushing down against the plastic
• tab, pull the thermostat away from the thermostat’s base.
1
Push tab
Remove thermostat
2
from base
Mounting The Thermostat Base
If a single gang switch box is used, an Adaptor Plate 007 is required to mount the thermostat to the box.
Fasten the base of the
• thermostat to the adaptor plate.
Feed the wiring through the
• openings in the back of the adaptor plate and thermostat.
Use the upper and lower screw
• holes to fasten the adaptor plate to the box.
Stud
Switch Box
1
/4
Thermostat
Base
007 Adaptor
Plate
3
(83 mm)
Mounted on switch box
3 of 24 © 2011 D 538 - 12/11
Page 4
If a switch box was not used, mount the
2
3
/8
(60 mm)
screwhole
---------------------------------------------------
thermostat directly to the wall.
Feed the wiring through the openings in
the back of the thermostat. Use screws in the screw holes to fasten the
Thermostat
Base
Stud
thermostat to the wall. At least one of the screws should enter a wall stud or similar rigid material.
3
2
/8
(60 mm)
screwhole
Wall
Mounted on wallboard
Thermostat Wiring
The thermostat operates a single heating system zone.
Connect tN4, C, R, and W terminals on the thermostat to the tN4, C, R, and W terminals on the tN4 Wiring Center or Zone Manager.
Connect the optional auxiliary sensor wires to the sensor terminals 5 and 6.
538
Slab Sensor 072, 073, 079
Indoor Sensor 076, 077, 084
OR
Outdoor Sensor 070
OR
65
Sensor
No Power
Use at least 75°C conductors For instructions see brochure
tN41C2R3W
4
tNt 538
One Stage Heat
Power: 24 V ±10% 50/60 Hz 1.8 VA 56 VA fully loaded Relay: 24 V (ac) 2 A
ON
Switch Settings:
1001-0 3
Lock
Scene
Setback
Unlock
Off
Off
1234
12 34
Not used
Not used
Mmm YYYY
Lot # 12345
Meets Class B:
Canadian ICES
FCC Part 15
tN4 Wiring Center
or
tN4 C W
R
tN4 Zone Manager
Testing the Thermostat Wiring
Testing the Power
1. Remove the front cover from the thermostat.
2. Use an electrical test meter to measure (ac) voltage between the R and C terminals. The reading should be 24 V (ac) +/– 10%.
3. Install the front cover.
---------------------------------------------------
4 of 24© 2011 D 538 - 12/11
Page 5
Testing the Heat Relay
-----------------------------------------------
-----------------------------------------
-----------------------------------------------
1. Remove the front cover from the thermostat.
2. Press the button and set the heating temperature below the current room temperature. There should be no H1 symbol on the display.
3. Set the electrical test meter to continuity.
4. Place probes between R (3) and W (4). There should be no continuity. If there is continuity then there may be a wiring fault or the relay may be faulty.
5. Press the button and set the heating temperature above the current room temperature. Make sure the display does not show “WWSD”. The “H1” symbol should appear on the display.
6. There should be continuity between the R (3) and W (4) terminals.
Testing the tekm a r N et®4 Bus
-----------------------------------------
The symbol is shown on the display when communication is present. If the thermostat is connected in a network and the communication is missing, there may be an open or short circuit on the tN4 and C bus wires.
1. Remove the front cover from the thermostat.
2. To test for short circuits:
Disconnect the tN4 bus wires on one end.
Install wire nuts on each wire to ensure the wire ends are not touching.
Disconnect the tN4 bus wires on the other end.
Measure for continuity using an electrical meter.
If continuity is present, there is a short circuit fault along the wires. It is
recommended to replace the tN4 bus wires.
3. To test for open circuits:
Disconnect the tN4 bus wires on one end and connect them together.
Disconnect the tN4 bus wires on the other end.
Use an electrical meter to measure for continuity.
If there is no continuity, there is an open circuit fault along the wires. It is
recommended to replace the tN4 bus wires.
Mounting the Thermostat
To place the thermostat back on the mounting base:
Place thermostat bottom tabs on
matching mounting base notches. Pivot top of the thermostat
towards wall, ensuring wires clear obstructions.
The top clasp makes a clicking
sound when properly closed.
Pivot Tab
5 of 24 © 2011 D 538 - 12/11
Page 6
12 34
1234
Mmm YYY
L t # 1234
Meets Class B:
Canadian ICES
Switch Settings:
Setback
Scene
Lock
Not used
ON
Not used
Unlock
Off
Off
Cleaning the Thermostat
The thermostats’s exterior can be cleaned using a damp cloth. Moisten the cloth with water and wring out prior to wiping the control. Do not use solvents or cleaning solutions.
Switch Settings
538
ON
Setback
Off
Switch Settings:
1234
12 34
Scene
Off
1001-03
Mmm YYYY
Lot # 12345
Lock
Not used
Meets Class B:
Canadian ICES
FCC Part 15
Not used
Unlock
Switches are set to “On” position from the factory, and do not require changing for most applications.
65
Sensor
No Power
Use at least 75°C conductors For instructions see brochure
tN41C2R3W
4
tNt 538
One Stage Heat
Power: 24 V ±10% 50/60 Hz 1.8 VA 56 VA fully loaded Relay: 24 V (ac) 2 A
Switch
1
2
3
4
Position
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Action
SETBACK
The thermostat follows a programmable setback schedule as a schedule member if available. Requires the installation of a Timer 033 to use this feature.
OFF
The thermostat does not follow a programmable setback schedule.
SCENE
The thermostat responds to changes in the scene (system wide manual overrides). Requires the installation of a User Switch 479 to use this feature.
OFF
The thermostat does not respond to scenes.
LOCK ACCESS LEVEL
Locked to ‘User’ access level. Set to Lock when installation completed.
UNLOCK ACCESS LEVEL
Unlock to allow ‘User’ and “Installer’ access level. Set to Unlock during installation process.
tekmarNet® reset control must also be set to Unlocked (Installer access level).
Not used
Not used
6 of 24© 2011 D 538 - 12/11
Page 7
User Interface
Display
SECONDARY DISPLAYMAIN DISPLAY
Button Operation
Press the or the button to select the room temperature.
Symbols Description
HEAT
Heat is turned on.
SUN
Operating at the occupied (day) temperature.
MOON
Operating at the unoccupied (night) temperature.
AWAY
Operating at the Away scene temperature.
AIR GROUP
The air group is cooling. Heating can start once the cooling is finished.
LOCK
Locked to ‘User’ access level.
CLOCK
Operating on a programmable schedule.
tekmarNet
Communication is present.
WARNING SYMBOL
Indicates an error is present.
WARM WEATHER SHUT DOWN
The heating system has been shut off for the summer.
7 of 24 © 2011 D 538 - 12/11
®
Page 8
®
and buttons for 2 seconds to go to the next step, OR
system control to Unlock to change Access level to Installer.
SET ROOM HEAT
Set the room heating temperature while in the
event.
Installer
User
SET ROOM HEAT
Set the room heating temperature while in the
Installer
User
event.
SET ROOM HEAT AWAY
Set the room heating temperature while in the Away
Installer
scene.
(21.0°C)
Default = 70°F
(4.5 to 35.0°C)
40 to 95°F
Press
• Press and hold down both the and buttons for 2 seconds to change from one step to the next.
• Release both buttons once the step has been reached.
• Press the or the button to change the setting, if available.
+
Together
• Press and hold down both the
• After 10 seconds of no button activity, the display goes back to normal operation.
Note: Set switch setting #3 and tekmarNet
40 to 95°F
Display Range Access Description Set to
Settings (1 of 7)
8 of 24© 2011 D 538 - 12/11
(18.5°C)
Default = 65°F
(4.5 to 35.0°C)
40 to 95°F
(4.5 to 35.0°C)
(16.5°C)
Default = 62°F
Continued on next page.
Page 9
SET FLOOR HEAT
Set the floor heating temperature while in the
event.
Available when:
Installer
A slab sensor is installed on the auxiliary sensor
input AND Sensor setting in the Adjust menu is set
User
to Floor AND Room Sensor setting in the Adjust
menu is set to Off.
SET FLOOR HEAT
Set the floor heating temperature while in the
A slab sensor is installed on the auxiliary sensor
event.
input AND Sensor setting in the Adjust menu is set
Available when:
Installer
User
to Floor AND Room Sensor setting in the Adjust
menu is set to Off.
BACKLIGHT
Select the backlight operation.
Off = Permanently Off
Installer
30 = Temporary on for 30 seconds
User
On = Permanently On
On + = On during and off during
40 to 122°F
(4.5 to 50.0°C)
(22.0°C)
Default = 72°F
40 to 122°F
(18.5°C)
Default = 65°F
(4.5 to 50.0°C)
On +
Off, 30 sec, On,
Default = 30 sec
Display Range Access Description Set to
Settings (2 of 7)
9 of 24 © 2011 D 538 - 12/11
Continued on next page.
Page 10
TEMPERATURE UNITS
Press the or the button to change from °F to
°C and vice versa.
Installer
User
DEVICE TYPE
Display alternates between the Device Type (large
Installer
number) with Software Version (upper right corner)
and the thermostat address.
User
MAXIMUM SET ROOM HEAT
Set the maximum room heating limit while in the
Installer
event.
MAXIMUM SET ROOM HEAT
Set the maximum room heating limit while in the
Installer
event.
MINIMUM SET ROOM HEAT
Set the minimum room heating limit.
Installer
°F or °C
Default = °F
Device Type with
Address
Software Version,
40 to 95°F
(4.5 to 35.0°C)
(29.5°C)
40 to 95°F
Default = 85°F
(29.5°C)
Default = 85°F
(4.5 to 35.0°C)
40 to 95°F
(7.0°C)
Default = 45°F
(4.5 to 35.0°C)
Display Range Access Description Set to
Settings (3 of 7)
10 of 24© 2011 D 538 - 12/11
Continued on next page.
Page 11
SET FLOOR MINIMUM
Set the floor minimum temperature while in the event.
The floor minimum heats the floor even when the room
temperature is satisfied.
The measured floor temperature is shown in the upper
right hand corner of the display.
Room Sensor setting in the Adjust menu is set to
On AND
A slab sensor is installed on the auxiliary sensor
Available when:
input AND
Sensor setting in the Adjust menu is set to Floor.
SET FLOOR MINIMUM
Set the floor minimum temperature while in the event.
The floor minimum heats the floor even when the room
temperature is satisfied.
The measured floor temperature is shown in the upper
right hand corner of the display.
Available when:
Room Sensor setting in the Adjust menu is set to
On AND
A slab sensor is installed on the auxiliary sensor
input AND
Sensor setting in the Adjust menu is set to Floor.
(Off, 4.5 to
Off, 40 to 122°F
User
Installer
50.0°C)
Default = 72°F
(22.0°C)
Installer
(Off, 4.5 to
Off, 40 to 122°F
User
50.0°C) Default = Off
Display Range Access Description Set to
Settings (4 of 7)
11 of 24 © 2011 D 538 - 12/11
Continued on next page.
Page 12
Room Sensor setting in the Adjust menu is set to
H1
ADJUST
FLOOR MAXIMUM
Set the floor maximum temperature in order to protect
the floor covering.
On AND
Available when:
A slab sensor is installed on the auxiliary sensor
input AND
Sensor setting in the Adjust menu is set to Floor.
SCHEDULE
Switch setting 1 is set to Setback (On Position).
Thermostat can follow schedule master 1, 2, 3, or 4.
Available when:
HEAT SUPPLY PUMP
During heating, select whether or not the system supply
pump should turn on or be off to allow a zone group
system.
®
A reset control is present on the tekmarNet
pump per manifold.
Available when:
Installer
Installer
Installer
Off)
(29.5°C)
Default = 85°F
(4.5 to 50.0°C,
40 to 122°F, Off
1, 2, 3, 4
Default = 1
OFF or On
Default = On
H1
Display Range Access Description Set to
ADJUST
Settings (5 of 7)
12 of 24© 2011 D 538 - 12/11
SUPPLY
Continued on next page.
Page 13
H1
ADJUST
system.
ADJUST
®
system.
®
system.
®
.
®
HEAT SUPPLY PUMP DELAY
A reset control is present on the tekmarNet
During heating, select whether or not the system supply
pump should be delayed by 3 minutes before coming
on (for thermal motor or wax actuator).
Available when:
HEAT CYCLES PER HOUR
Select either Auto cycle or Synchronize with other
thermostats on the tekmarNet
Choose Synchronize when zone heated using a boiler.
Installer
Installer
No reset control on the tekmarNet
Choose Auto when zone is non-hydronic heating.
Available when:
AIR GROUP
Select if this thermostat should be an air group member.
Select off if the thermsotat is not an air group member.
Select 1 though 16 to select the air group number.
The thermostat is connected to other thermostats
using tekmarNet
Available when:
ROOM SENSOR
Select whether the built-in air temperature sensor is
on or off.
Available when:
Installer
A floor sensor or room sensor is installed on the
auxiliary sensor input.
Auto,
OFF or On
Default = OFF
H1
SYn(Synchronize)
Default =
Sychronize
OFF, 1 to 16 Installer
On or Off
Default = On
Display Range Access Description Set to
ADJUST
Settings (6 of 7)
SUPPLY
ADJUST
Continued on next page.
13 of 24 © 2011 D 538 - 12/11
Page 14
AUXILIARY SENSOR
ADJUST
Select the type of auxiliary sensor.
Off = no auxiliary sensor, Room = Indoor Sensor,
Outdoor = Outdoor Sensor, Floor = Slab Sensor, Floor
ADDRESS
®
dSP = Floor sensor reading in upper number field.
Available when:
Auxiliary sensor automatically detected.
tekmarNet
The address is shown in the large number field. “Auto” is
shown in the upper number field when using automatic
addressing.
Press the or the button to manually select
an address.
The address can be returned to automatic “Auto”
addressing when address set above 24.
FLOOR COOLING
heat pump or chiller
®
Connected to a tekmarNet
Select if the thermostat should operate the heating relay
W for radiant floor cooling.
system control.
Available when:
ESCAPE
Press the or the button to return to normal
operation.
Installer
Off, Room,
Outdoor, Floor,
Floor dSP
Installer
01 to 24
b:01 to b:24
1:01 to 1:24
(no reset control),
(reset control - boiler),
(reset control - mixing)
Installer
OFF or On
COOL
FLOOR
Default = OFF
Installer
User
None
Display Range Access Description Set to
Settings (7 of 7)
14 o f 24© 2011 D 538 - 12/11
ADJUST
Page 15
Sequence of Operation
----------------------------------------------------
----------------------------------------------------------
------------------------------------------------------------
---------------------------------------
Heating Operation
When using only a room temperature sensor, the thermostat operates the heating system to maintain the Set Room Heat temperature.
When using only a floor temperature sensor, the thermostat operates the heating system to maintain the Set Floor Heat temperature. In this case, the thermostat does not try to control the air temperature. This is ideal for bathrooms and some kitchen applications where the customer wants their feet to feel warm on the floor. This is also ideal for garages so that the heating system is not affected by the opening of the garage door in cold outdoor weather.
When using both a room temperature sensor and a floor temperature sensor, the thermostat always maintains the Floor Minimum temperature, even when the air temperature is satisfied. When the air temperature is below the Set Room Heat temperature, the thermostat operates the heating system to maintain the Set Room Heat temperature. The floor is never heated above the Floor Maximum setting in order to protect the floor covering.
The H1 symbol is shown on the display when the thermostat is heating. The heat can cycle on and off within +/- 1.5°F (1°C) of the Set Room Heat temperature.
Freeze Protection
The thermostat operates the heat whenever the room or floor temperature falls below 40°F (4.5°C).
Exercising
When connected to a tekmarNet® reset control, the thermostat exercises the heat relay for 10 seconds every 3 days. Exercising helps prevent zone valves or zone pumps from failing due to precipitate buildup. During exercising, the thermostat shows “TEST” on the display.
----------------------------------------------------------
----------------------------------------------------
Section A
Flushing
The flushing feature is for open-loop systems that use a domestic hot water tank as a heat source. Flushing ensures that fresh potable water is circulated through the system once each day. If the thermostat is connected to a tekmarNet® reset control with the Flushing feature turned on, the thermostat display will display the “FLUSH” icon for the duration of the flushing operation.
Hydronic System Supply Pump
When connected to a tekmarNet® system control, the thermostat’s Heat Supply Pump setting affects how the primary pump or mix pump on the system control operates. When connected to the boiler bus, the boiler system or primary pump is operated. When connected to the mix bus, the mix system pump is operated.
If the thermostat operates a motorized or thermal motor zone valve, the Heat Supply Pump setting should be set to On.
------------------------------------------------------------
---------------------------------------
15 of 24 © 2011 D 538 - 12/11
Page 16
If the thermostat operates a thermal motor (wax actuator) zone valve, set the Heat
---------------------------------------------------
--------------------------------------------
Supply Pump Delay setting to On. This provides a three minute delay to allow the zone valve to open before the primary or mix pump is turned on.
In special applications with multiple zoning manifolds, the Heat Supply Pump setting can be set to Off. This allows a Zone Group Pump located on the Zone Manager, or Wiring Center to operate the pump for the manifold.
DHW Tank Priority
---------------------------------------------------
When a tekmarNet® reset control is heating an indirect Domestic Hot Water (DHW) tank, the thermostat may shut off the heating zones to allow the DHW tank to recover quickly. This is determined by the DHW priority of the tekmarNet® reset control.
Warm Weather Shut Down
--------------------------------------------
When the outdoor air temperature exceeds the Warm Weather Shut Down (WWSD) setting on the tekmarNet® reset control, the heating system is shut off.
Air Group Operation
Section B
In order to prevent heating and cooling at the same time, this thermostat can operate together with other thermostats on a tekmarNet® system to form an air group.
In an air group, one thermostat is assigned as the air group master. The air group master operates the cooling equipment for the group. This thermostat can be set to be a member of the air group.
When operating as an air group, the air temperature readings of all the air group member thermostats are communicated to the air group master and a temperature average is determined.
Air Group
When the air group master is in cooling operation, the air group member thermostats do not operate the heating system for air heating.
If the Set Room Heat temperature is adjusted while the air group is cooling, the snowflake icon is flashed to alert the user that the cooling is presently on. Once the cooling shuts off, the heating can start operation.
Master
tekmarNet Communication
MemberMember
Floor Cooling
Section C
The thermostat has the option to support radiant floor cooling when connected to a heat pump control using tekmarNet® communication. The floor cooling setting must be set to On and the heating system must be in Warm Weather Shut Down (WWSD). When the heat pump system control operates in cooling mode, all thermostats set for floor cooling on the tekmarNet® bus all activate the first stage heating contact (H1) at the same time to allow chilled water into the system. The thermostat continues to operate the cooling until either the room temperature reaches the Set Heat temperature plus 3°F (Set Heat+1.5°C) or reaches a minimum temperature of 74°F. If only a floor sensor is installed, the floor cooling setpoint is 67°F (19.5°C).
16 of 24© 2011 D 538 - 12/11
Page 17
Schedules
Section D
Lowering the room temperature setting reduces the amount of fuel required to heat the building resulting in energy savings.
This thermostat can follow a programmable schedule in order to automatically lower the room temperature setting. A schedule master such as a Timer 033 is required in order to gain programmable schedule functionality.
When operating on a programmable schedule, a
symbol is shown, as well as a
or a . The or indicates the current operating temperature.
If a symbol does not appear, there is no schedule available.
Display Action
Occupied temperature. No schedule.
Unoccupied temperature. No schedule.
Programmable schedule at
Programmable schedule at
occupied
unoccupied
temperature.
temperature.
When a programmable schedule is selected, there is a time delay for the temperature to change from the temperature to the temperature.
The thermostat uses Optimum Start to predict the heat up and cool off rate of the room. The optimum start feature allows the room to reach the set room temperature by the time set in the programmable schedule. This applies for both heating and cooling.
Scenes (System Override)
Section E
Scenes provide an easy way to save energy while away on vacation, or override a pre-set schedule when plans change. tekmarNet® devices such as a User Switch 479 provide scene adjustment.
This thermostat responds to the following scenes:
Scene Display Room Temperature Setting
1
2
or or
Away
Follows programmable schedule or operates at the occupied temperature.
Away temperature.
3
Unoccupied temperature.
While in the Away scene, the room temperature cannot be changed using the or
buttons. Change the scene from Away to or to change the temperature.
17 of 24 © 2011 D 538 - 12/11
Page 18
®
system control.
4 bus, press the and buttons
®
®
bus is at 24 or lower.
®
bus has exceeded 24. Devices include tekmarNet
®
buses.
®
Troubleshooting
4 communication bus has either an open or a short circuit. The result is that there
®
CONTROL ERROR
The thermostat was unable to correctly read settings from memory and has reloaded the factory
default settings. The thermostat does not operate the heating, cooling, or the fan while this error
message is present.
Error clears once all adjust menu settings in the Installer access level (unlocked) have been
checked. Set thermostat’s switch setting #3 to unlock and unlock the tekmarNet
Then press and hold and buttons together for 2 seconds to enter the adjust menu. Continue
until all settings have been reviewed.
BUS ERROR
The tekmarNet
are no communications. Check for loose wires. Check for short circuits between the tN4 and C
wires on the House Control, Wiring Center, or Zone Manager. Check for correct polarity between
the C and R wires.
Error clears automatically once wiring fault has been corrected.
If the thermostat is intentionally removed from the tekmarNet
together to clear the error message.
DEVICE LIMIT
The number of devices on the tekmarNet
Thermostats and Setpoint Controls. The device count must be lowered to 24 or less. If possible,
move devices to other tekmarNet
Error clears automatically once the number of devices on the tekmarNet
Error Message Description
Error Messages (1 of 4)
18 of 24© 2011 D 538 - 12/11
Page 19
address.
®
your wholesaler or tekmar sales representative for details on repair procedures.
ADDRESS ERROR
This thermostat and another device have been manually given the same tekmarNet
Error clears automatically once this thermostat is given a new manually set address or if the
thermostat is set to automatic addressing.
ROOM SENSOR SHORT CIRCUIT
The built-in air temperature sensor has a short circuit fault. Do not confuse this error with the auxiliary
room sensor short circuit error.
This error cannot be field repaired.
Contact your wholesaler or tekmar sales representative for details on repair procedures.
ROOM SENSOR OPEN CIRCUIT
The built-in air temperature sensor has an open circuit fault. Do not confuse this error with the
auxiliary room sensor short circuit error.
This error cannot be field repaired.
Contact
AIR GROUP MEMBER ERROR
The thermostat has been selected to join an air group as a member, yet there is no air group master
thermostat.
Error clears once the thermostat detects an air group master or the air group is set to OFF.
Error Message Description
Error Messages (2 of 4)
19 of 24 © 2011 D 538 - 12/11
Page 20
FLOOR SENSOR SHORT CIRCUIT
The auxiliary floor sensor has a short circuit. Check for damaged wires. Locate and repair the
problem as described in the Data Brochure D072 or D 079.
Error clears once the floor sensor fault is corrected.
FLOOR SENSOR OPEN CIRCUIT
The auxiliary floor sensor has an open circuit. Check for loose or damaged wires. Locate and repair
the problem as described in the Data Brochure D072 or D 079.
Error clears once the floor sensor fault is corrected.
If the floor sensor was intentionally removed, locate the Room Sensor setting in the Adjust menu
and set to On. Power the thermostat down and up to clear the error.
OUTDOOR SENSOR SHORT CIRCUIT
The auxiliary outdoor sensor has a short circuit. Check for damaged wires. Locate and repair the
problem as described in the Data Brochure D 070.
Error clears after the outdoor sensor fault is corrected.
OUTDOOR SENSOR OPEN CIRCUIT
The auxiliary outdoor sensor has an open circuit. Check for loose or damaged wires. Locate and
repair the problem as described in the Data Brochure D 070.
Error clears once the outdoor sensor fault is corrected.
If the outdoor sensor was intentionally removed, power the thermostat down and up to clear the
error.
Error Message Description
Error Messages (3 of 4)
20 of 24© 2011 D 538 - 12/11
Page 21
AUXILIARY ROOM SENSOR SHORT CIRCUIT
The auxiliary room sensor has a short circuit. Check for damaged wires. Locate and repair the
problem as described in the Data Brochure D 076, D077, or D084.
Error clears after the auxiliary room sensor fault is corrected.
AUXILIARY ROOM SENSOR OPEN CIRCUIT
The auxiliary room sensor has an open circuit. Check for loose or damaged wires. Locate and repair
the problem as described in the Data Brochure D 076, D077, or D084.
Error clears once the auxiliary room sensor fault is corrected.
If the auxiliary room sensor was intentionally removed, power the thermostat down and up to clear
the error.
Error Message Description
Error Messages (4 of 4)
21 of 24 © 2011 D 538 - 12/11
Page 22
Frequently Asked Questions
Symptom Look for... Corrective Action
No Heat
Heat on before scheduled time
Pressing button does not increase temperature
Pressing button does not decrease temperature
H1 Symbol
Flashing
WWSD
H1 symbol indicates heat is on. Check if zone valve or zone pump is operating.
Increase WWSD setting on tekmarNet® reset control.
Flashing Away Change User Switch to Normal scene 1.
Optimum start “learns” the heat up and cool off rate of the room and starts the heating or cooling early so that the room is comfortable at the scheduled time.
Flashing Max
Installer can increase the Maximum Set Room Heat.
Floor temperature has reached the Floor
Flashing Floor
Max
Maximum setting. If the floor is not heated, then the floor sensor may be faulty and require replacement.
Flashing Min
Installer can decrease the Minimum Set Room Heat.
Floor minimum takes priority over the air
Floor Min
heating temperature. Recommend turning down the floor minimum temperature setting.
22 of 24© 2011 D 538 - 12/11
Page 23
Job Record
Jobsite Location ________________________________________________
Thermostat Location _____________________________________________
Item Setting Item Setting
Set Room Heat
Set Room Heat Set Floor Max
Set Room Heat Away Schedule Member
Set Floor Heat
Set Floor Heat Heat Supply Pump Delay
Backlight Heat Cycles Per Hour
Units Air Group
Max Set Room Heat
Max Set Room Heat Sensor
Min Set Room Heat tekmarNet® Address
Set Floor Min
Set Floor Min
Heat Supply Pump
Room Sensor
Floor Cooling
Technic al Dat a
tekmarNet®4 Thermostat 538; One Stage Heat
Packaged weight 0.8 lb. (380 g)
Enclosure White PVC plastic, NEMA Type 1
Dimensions 2-7/8” H x 2-7/8” W x 13/16” D (73 x 73 x 21 mm)
Approvals CSA C US, meets Class B: ICES and FCC Part 15
Ambient conditions Indoor use only, 32 to 122°F (0 to 50°C).
RH max 92% to 104°F (40°C), and 50% above 104°F (40°C)
Altitude <9840 feet (3000 m), Installation Category II, Pollution Degree 2
Power supply
W Relay 24 V (ac) 2 A
Sensors: NTC thermistor, 10 kΩ @ 77°F (25°C ± 0.2°C) ß = 3892
– Optional tekmar type # 070, 072, 073, 076, 077, 079, 084
24 V (ac) ± 10% 50/60 Hz, 1.8 VA Standby, 56 VA fully loaded, NEC / CEC Class 2
23 of 24 © 2011 D 538 - 12/11
Page 24
Limited Warranty and Product Return Procedure
Limited Warranty The liability of tekmar und er this warranty is limited. The Purchas er, by taking receipt
of any tekmar product (“Product”), acknowledges th e terms of the Limited Warranty in effect at the time of such Product s ale and acknowledges that it has read and unde rstands same.
The tekmar Limited Warranty to the Purchaser on the Products sold hereunder is a manufacturer’s pass­through warranty which the Purchaser is authorized to pass through to its customers. Under the Limited Warranty, each tekmar Product is warranted against defects in workmanship and materials if the Product is installed and used in compliance with tekmar’s instructions, ordinary wear and tear excepted. The pass­through warranty period is for a period of twenty-four (24) months from the production date if the Product is not installed during that period, or twelve (12) months from the documented date of installation if installed within twenty-four (24) months from the production date.
The liability of tekmar under the Limited Warranty shall be limited to, at tekmar’s sole discretion: the cost of par ts and labor provided by tekmar to repair defects in materials and / or workmanship of the defective product; or to the exchange of the defective product for a warranty replacement produc t; or to the granting of credit limited to the original cost of the defective product, and such repair, exchange or credit shall be the sole remedy available from tekmar, and, without limiting the foregoing in any way, tekmar is not responsible, in c ontract, tor t or strict product liabilit y, for any other losses, costs, expenses, inconveniences, or damages, whether direct, indirect, special, secondar y, incidental or c onsequential, arising from ownership or use of the product, or from defects in workmanship or materials, including any liability for fundamental breach of contract.
The pass-through Limited Warranty applies only to those defective Products returned to tekmar during the war­ranty period. This Limited Warranty does not cover the c ost of the parts or labor to remove or transport the defec­tive Product, or to reinstall the repaired or replacement Product, all such costs and expenses being subject to Purchaser’s agreement and warranty with its customers.
Any representations or warranties about the Products made by Purchaser to its customers which are dif ferent from or in excess of the tekmar Limited Warranty are the Purchaser’s sole responsibility and obligation. Purchaser shall indemnify and hold tekmar harmless from and against any and all claims, liabilities and damages of any kind or nature which arise out of or are relate d to any such representations or warranties by Purchaser to its customers.
The pass-through Limited Warranty does not apply if the returned Product has been damaged by negligence by persons other than tekmar, accident, fire, Act of God, abuse or misuse; or has been damaged by modifications, alterations or attachments made subsequent to purchase which have not been authorized by tekmar; or if the Product was not installed in compliance with tekmar’s instructions and / or the local codes and ordinances; or if due to defective installation of the Product; or if the Product was not used in compliance with tek mar’s instruc­tions.
THIS WARRANT Y IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IM PLIED, WHICH THE GOVERNIN G LAW ALLOWS PARTIES TO CONTRACTUALLY EXCLUDE, INCLUDING , WITHOUT LIMITATION, IMPLIED WAR­RANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, DURABILITY OR DESCRIP­TION OF THE PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS OR TRADEMARKS, AND ITS C OMPLI AN CE WI TH OR NON -VIO L ATI ON O F A NY APPLIC AB LE EN VI RONME NTA L, HE ALTH O R S AFET Y LEGISLATION; THE TERM OF ANY OTHER WARRANT Y NOT HEREBY CONTRACTUALLY EXCLUDED IS LIM­ITED SUCH THAT IT SHALL NOT EXTEND BEYOND TWENTY-FOUR (24) MONTHS FROM THE PRODUCTION DATE, TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY THE GOVERNING LAW.
Product Warranty Return Procedure All Products that are believed to have defects in workmanship or materi­als must be returned, together with a written description of the defect, to the tekmar Representative assigned to the territory in which such Product is located. If tekmar receives an inquiry from someone other than a tekmar Representative, including an inquir y from Purchaser (if not a tekmar Representative) or Purchaser’s customers, regarding a potential warranty claim, tekmar’s sole obligation shall be to provide the address and other contact information regarding the appropriate Representative.
tekmar Control Syste ms Ltd., Canada tekmar Contr ol Syste ms, Inc ., U.S.A.
Head O ffice: 5100 Si lver St ar Roa d Vernon, B.C. Can ada V1B 3K4 (250) 54 5-7749 Fax. (250) 54 5- 0650
Web Site: w ww.tek marco ntrols.com
All specifications are subject to change without notice
Product design, software and literature are Copyright © 2011 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc.
24 of 24 D 538 - 12/11.
Loading...