Congratulations on the purchase of your new tekmar thermostat.
This manual will step through the complete installation, programming and sequence
of operation for this control. At the back, there are tips for control and system
troubleshooting.
Installation
Caution
Improper installation and operation of this control could result in damage to the
equipment and possibly even personal injury or death. It is your responsibility
to ensure that this control is safely installed according to all applicable codes and
standards. This electronic control is not intended for use as a primary limit control.
Other controls that are intended and certified as safety limits must be placed into
the control circuit.
2. Press the button and set the heating temperature below the current room
temperature. There should be no H1 symbol on the display.
3. Set the electrical test meter to continuity.
4. Place probes between R (3) and W (4). There should be no continuity. If there
is continuity then there may be a wiring fault or the relay may be faulty.
5. Press the button and set the heating temperature above the current room
temperature. Make sure the display does not show “WWSD”. The “H1” symbol
should appear on the display.
6. There should be continuity between the R (3) and W (4) terminals.
Testing the tekm a r N et®4 Bus
-----------------------------------------
The symbol is shown on the display when communication is present. If the
thermostat is connected in a network and the communication is missing, there may
be an open or short circuit on the tN4 and C bus wires.
1. Remove the front cover from the thermostat.
2. To test for short circuits:
Disconnect the tN4 bus wires on one end.
•
Install wire nuts on each wire to ensure the wire ends are not touching.
•
Disconnect the tN4 bus wires on the other end.
•
Measure for continuity using an electrical meter.
•
If continuity is present, there is a short circuit fault along the wires. It is
•
recommended to replace the tN4 bus wires.
3. To test for open circuits:
Disconnect the tN4 bus wires on one end and connect them together.
•
Disconnect the tN4 bus wires on the other end.
•
Use an electrical meter to measure for continuity.
•
If there is no continuity, there is an open circuit fault along the wires. It is
•
recommended to replace the tN4 bus wires.
Mounting the Thermostat
To place the thermostat back on the
mounting base:
Place thermostat bottom tabs on
•
matching mounting base notches.
Pivot top of the thermostat
The thermostats’s exterior can be cleaned using a damp cloth. Moisten the cloth
with water and wring out prior to wiping the control. Do not use solvents or cleaning
solutions.
Switch Settings
538
ON
Setback
Off
Switch Settings:
1234
12 34
Scene
Off
1001-03
Mmm YYYY
Lot # 12345
Lock
Not used
Meets Class B:
Canadian ICES
FCC Part 15
Not used
Unlock
Switches are set to “On”
position from the factory, and
do not require changing for
most applications.
65
Sensor
No Power
Use at least 75°C conductors
For instructions see brochure
tN41C2R3W
4
tNt 538
One Stage Heat
Power: 24 V ±10% 50/60 Hz 1.8 VA
56 VA fully loaded
Relay: 24 V (ac) 2 A
Switch
1
2
3
4
Position
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Action
SETBACK
The thermostat follows a programmable setback schedule
as a schedule member if available. Requires the installation
of a Timer 033 to use this feature.
OFF
The thermostat does not follow a programmable setback
schedule.
SCENE
The thermostat responds to changes in the scene (system
wide manual overrides). Requires the installation of a User
Switch 479 to use this feature.
OFF
The thermostat does not respond to scenes.
LOCK ACCESS LEVEL
Locked to ‘User’ access level. Set to Lock when installation
completed.
UNLOCK ACCESS LEVEL
Unlock to allow ‘User’ and “Installer’ access level. Set to
Unlock during installation process.
tekmarNet® reset control must also be set to Unlocked
(Installer access level).
When using only a room temperature sensor, the thermostat operates the heating
system to maintain the Set Room Heat temperature.
When using only a floor temperature sensor, the thermostat operates the heating
system to maintain the Set Floor Heat temperature. In this case, the thermostat
does not try to control the air temperature. This is ideal for bathrooms and some
kitchen applications where the customer wants their feet to feel warm on the floor.
This is also ideal for garages so that the heating system is not affected by the
opening of the garage door in cold outdoor weather.
When using both a room temperature sensor and a floor temperature sensor, the
thermostat always maintains the Floor Minimum temperature, even when the air
temperature is satisfied. When the air temperature is below the Set Room Heat
temperature, the thermostat operates the heating system to maintain the Set Room
Heat temperature. The floor is never heated above the Floor Maximum setting in
order to protect the floor covering.
The H1 symbol is shown on the display when the thermostat is heating. The heat
can cycle on and off within +/- 1.5°F (1°C) of the Set Room Heat temperature.
Freeze Protection
The thermostat operates the heat whenever the room or floor temperature falls
below 40°F (4.5°C).
Exercising
When connected to a tekmarNet® reset control, the thermostat exercises the heat
relay for 10 seconds every 3 days. Exercising helps prevent zone valves or zone
pumps from failing due to precipitate buildup. During exercising, the thermostat
shows “TEST” on the display.
The flushing feature is for open-loop systems that use a domestic hot water tank
as a heat source. Flushing ensures that fresh potable water is circulated through
the system once each day. If the thermostat is connected to a tekmarNet® reset
control with the Flushing feature turned on, the thermostat display will display the
“FLUSH” icon for the duration of the flushing operation.
Hydronic System Supply Pump
When connected to a tekmarNet® system control, the thermostat’s Heat Supply
Pump setting affects how the primary pump or mix pump on the system control
operates. When connected to the boiler bus, the boiler system or primary pump is
operated. When connected to the mix bus, the mix system pump is operated.
If the thermostat operates a motorized or thermal motor zone valve, the Heat Supply
Pump setting should be set to On.
Supply Pump Delay setting to On. This provides a three minute delay to allow the
zone valve to open before the primary or mix pump is turned on.
In special applications with multiple zoning manifolds, the Heat Supply Pump setting
can be set to Off. This allows a Zone Group Pump located on the Zone Manager,
or Wiring Center to operate the pump for the manifold.
When a tekmarNet® reset control is heating an indirect Domestic Hot Water (DHW)
tank, the thermostat may shut off the heating zones to allow the DHW tank to recover
quickly. This is determined by the DHW priority of the tekmarNet® reset control.
Warm Weather Shut Down
--------------------------------------------
When the outdoor air temperature exceeds the Warm Weather Shut Down (WWSD)
setting on the tekmarNet® reset control, the heating system is shut off.
Air Group Operation
Section B
In order to prevent heating and cooling at the same time, this thermostat can operate
together with other thermostats on a tekmarNet® system to form an air group.
In an air group, one thermostat is assigned as the air group master. The air group
master operates the cooling equipment for the group. This thermostat can be set
to be a member of the air group.
When operating as an air group, the air temperature readings of all the air group
member thermostats are communicated to the air group master and a temperature
average is determined.
Air Group
When the air group master is in cooling
operation, the air group member thermostats
do not operate the heating system for air
heating.
If the Set Room Heat temperature is adjusted
while the air group is cooling, the snowflake
icon is flashed to alert the user that the cooling
is presently on. Once the cooling shuts off,
the heating can start operation.
Master
tekmarNet Communication
MemberMember
Floor Cooling
Section C
The thermostat has the option to support radiant floor cooling when connected to a
heat pump control using tekmarNet® communication. The floor cooling setting must
be set to On and the heating system must be in Warm Weather Shut Down (WWSD).
When the heat pump system control operates in cooling mode, all thermostats set for
floor cooling on the tekmarNet® bus all activate the first stage heating contact (H1)
at the same time to allow chilled water into the system. The thermostat continues
to operate the cooling until either the room temperature reaches the Set Heat
temperature plus 3°F (Set Heat+1.5°C) or reaches a minimum temperature of 74°F.
If only a floor sensor is installed, the floor cooling setpoint is 67°F (19.5°C).
Lowering the room temperature setting reduces the amount of fuel required to heat
the building resulting in energy savings.
This thermostat can follow a programmable schedule in order to automatically lower
the room temperature setting. A schedule master such as a Timer 033 is required
in order to gain programmable schedule functionality.
When operating on a programmable schedule, a
symbol is shown, as well as a
or a . The or indicates the current operating temperature.
If a symbol does not appear, there is no schedule available.
DisplayAction
Occupied temperature. No schedule.
Unoccupied temperature. No schedule.
Programmable schedule at
Programmable schedule at
occupied
unoccupied
temperature.
temperature.
When a programmable schedule is selected, there is a time delay for the temperature
to change from the temperature to the temperature.
The thermostat uses Optimum Start to predict the heat up and cool off rate of
the room. The optimum start feature allows the room to reach the set room
temperature by the time set in the programmable schedule. This applies for both
heating and cooling.
Scenes (System Override)
Section E
Scenes provide an easy way to save energy while away on vacation, or override a
pre-set schedule when plans change. tekmarNet® devices such as a User Switch
479 provide scene adjustment.
This thermostat responds to the following scenes:
SceneDisplayRoom Temperature Setting
1
2
or or
Away
Follows programmable schedule or
operates at the occupied temperature.
Away temperature.
3
Unoccupied temperature.
While in the Away scene, the room temperature cannot be changed using the or
buttons. Change the scene from Away to or to change the temperature.
H1 symbol indicates heat is on. Check if
zone valve or zone pump is operating.
Increase WWSD setting on tekmarNet®
reset control.
Flashing AwayChange User Switch to Normal scene 1.
Optimum start “learns” the heat up and
cool off rate of the room and starts the
heating or cooling early so that the room is
comfortable at the scheduled time.
Flashing Max
Installer can increase the Maximum Set
Room Heat.
Floor temperature has reached the Floor
Flashing Floor
Max
Maximum setting. If the floor is not heated,
then the floor sensor may be faulty and
require replacement.
Flashing Min
Installer can decrease the Minimum Set
Room Heat.
Floor minimum takes priority over the air
Floor Min
heating temperature. Recommend turning
down the floor minimum temperature
setting.
Limited Warranty The liability of tekmar und er this warranty is limited. The Purchas er, by taking receipt
of any tekmar product (“Product”), acknowledges th e terms of the Limited Warranty in effect at the time
of such Product s ale and acknowledges that it has read and unde rstands same.
The tekmar Limited Warranty to the Purchaser on the Products sold hereunder is a manufacturer’s passthrough warranty which the Purchaser is authorized to pass through to its customers. Under the Limited
Warranty, each tekmar Product is warranted against defects in workmanship and materials if the Product
is installed and used in compliance with tekmar’s instructions, ordinary wear and tear excepted. The passthrough warranty period is for a period of twenty-four (24) months from the production date if the Product is
not installed during that period, or twelve (12) months from the documented date of installation if installed
within twenty-four (24) months from the production date.
The liability of tekmar under the Limited Warranty shall be limited to, at tekmar’s sole discretion: the cost of par ts
and labor provided by tekmar to repair defects in materials and / or workmanship of the defective product; or to
the exchange of the defective product for a warranty replacement produc t; or to the granting of credit limited to
the original cost of the defective product, and such repair, exchange or credit shall be the sole remedy available
from tekmar, and, without limiting the foregoing in any way, tekmar is not responsible, in c ontract, tor t or strict
product liabilit y, for any other losses, costs, expenses, inconveniences, or damages, whether direct, indirect,
special, secondar y, incidental or c onsequential, arising from ownership or use of the product, or from defects in
workmanship or materials, including any liability for fundamental breach of contract.
The pass-through Limited Warranty applies only to those defective Products returned to tekmar during the warranty period. This Limited Warranty does not cover the c ost of the parts or labor to remove or transport the defective Product, or to reinstall the repaired or replacement Product, all such costs and expenses being subject to
Purchaser’s agreement and warranty with its customers.
Any representations or warranties about the Products made by Purchaser to its customers which are dif ferent
from or in excess of the tekmar Limited Warranty are the Purchaser’s sole responsibility and obligation. Purchaser
shall indemnify and hold tekmar harmless from and against any and all claims, liabilities and damages of any
kind or nature which arise out of or are relate d to any such representations or warranties by Purchaser to its
customers.
The pass-through Limited Warranty does not apply if the returned Product has been damaged by negligence by
persons other than tekmar, accident, fire, Act of God, abuse or misuse; or has been damaged by modifications,
alterations or attachments made subsequent to purchase which have not been authorized by tekmar; or if the
Product was not installed in compliance with tekmar’s instructions and / or the local codes and ordinances; or if
due to defective installation of the Product; or if the Product was not used in compliance with tek mar’s instructions.
THIS WARRANT Y IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IM PLIED, WHICH THE GOVERNIN G
LAW ALLOWS PARTIES TO CONTRACTUALLY EXCLUDE, INCLUDING , WITHOUT LIMITATION, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, DURABILITY OR DESCRIPTION OF THE PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS OR TRADEMARKS, AND
ITS C OMPLI AN CE WI TH OR NON -VIO L ATI ON O F A NY APPLIC AB LE EN VI RONME NTA L, HE ALTH O R S AFET Y
LEGISLATION; THE TERM OF ANY OTHER WARRANT Y NOT HEREBY CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT EXTEND BEYOND TWENTY-FOUR (24) MONTHS FROM THE PRODUCTION
DATE, TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY THE GOVERNING LAW.
Product Warranty Return Procedure All Products that are believed to have defects in workmanship or materials must be returned, together with a written description of the defect, to the tekmar Representative assigned to
the territory in which such Product is located. If tekmar receives an inquiry from someone other than a tekmar
Representative, including an inquir y from Purchaser (if not a tekmar Representative) or Purchaser’s customers,
regarding a potential warranty claim, tekmar’s sole obligation shall be to provide the address and other contact
information regarding the appropriate Representative.
tekmar Control Syste ms Ltd., Canada
tekmar Contr ol Syste ms, Inc ., U.S.A.
Head O ffice: 5100 Si lver St ar Roa d
Vernon, B.C. Can ada V1B 3K4
(250) 54 5-7749 Fax. (250) 54 5- 0650
Web Site: w ww.tek marco ntrols.com
All specifications are subject
to change without notice