tekmar 265 User Manual

- Data Brochure
Boiler Control 265
D 265
07/10
The tekmar Boiler Control 265 can control the supply water temperature on up to three modulating boilers based on outdoor temperature or setpoint requirements. The control can be set to control up to two modulating boilers based on outdoor temperature or domestic hot water requirements. A large easy to read display provides current system temperatures and operating status. The control has outputs for a primary pump, individual boiler pumps, and either a combustion air damper or an alert.
Additional functions include:
• Outdoor Reset
• Sequential or Parallel Modulation
• Installer and Advanced access levels
• Primary pump output
• Individual boiler pump outputs
• Pump purging
• Boiler demand for space heating loads
Menu Item
Boiler Control 265
Three Modulating Boiler & DHW / Setpoint
Do not apply power
1
2
3
4
5
Input
Universal Sensor
Included
Input
Universal Sensor
Included
Com
Boil
Boil
Out
Sup
Ret
6+7
UnO
+
Sw
Boiler Demand
DHW / Setpoint Demand
WWSD
Modulation
Boiler Output (x10,000 BTU/hr)
External Input Signal
Offset / Priority Override
8
9 10 11 12 13
Mod2 mAMod1 mA
–+–+–
Prim
Mod3 mA Power Boiler Boiler
L14N
P1
• DHW demand for domestic hot water loads
• Setpoint demand for setpoint loads
• 0 – 10 V (dc) BAS / EMS input
• Test sequence to ensure proper component operation
• Setback input for energy savings
• CSA C US certified
• Pump exercising
Parallel
Alert
Boiler
Pump 1
CA. Exercise Sequential
Off
Boiler
Pump 2
External Input Advanced
Installer Stand Alone
Made in Canada by tekmar Control Systems Ltd.
Power 115 V ±10% 60 Hz 600 VA Relays 230 V (ac) 5 A 1/3 hp, pilot duty 240 VA Demands 20 to 260 V (ac) 2 VA
Signal wiring must be rated at least 300 V.
15 16 17118119220221 22 23 24 25 26 27 28 29
C.A./ Alert
Boiler 3 /
DHW
Soft Stop
Off
Boiler
Pump 3
Test
Dem
Boil
Rotate
Fixed Lead First On / Last Off
First On / First Off
not t
off red testing red tes
For maximum heat, press & hold T 3 seconds.
Meets Class B: Canadian ICES FCC Part 15
30
31
Com
Setp/
Dem
DHW
esting
ting paused
est for
Date Code
H2037B
Note:
Boiler, DHW, or setpoint demand must be powered with 20 to 260 V (ac) before the boiler is able to fire.
Input
Setpoint
or DHW
Demand
Input
Boiler
Demand
Output
Pump
Output
Boiler
Enable
or
Pump
Input
Outdoor Sensor
Included
or
Input
0-10 V (dc) External Signal
Input
Timer or Switch
Optional
Output
Modulating
Boiler
Output
Modulating
Boiler
Output
Modulating
Boiler
Output
Primary
Pump
Input
115 V (ac)
Power Supply
or
Output
Combustion Air
or Alert
Output
Boiler
Enable
1 of 36 © 2010 D 265 - 07/10
How To Use The Data Brochure
This brochure is organized into four main sections. They are: 1) Sequence of Operation, 2) Installation, 3) Control Settings, and
4) Testing and Troubleshooting. The Sequence of Operation section has seven sub-sections. We recommend reading Section A: General of the Sequence of Operation, as this contains important information on the overall operation of the control. Then read the sub sections that apply to your installation.
The Control Settings section (starting at DIP Switch Settings) of this brochure describes the various items that are adjusted and displayed by the control. The control functions of each adjustable item are described in the Sequence of Operation.
Table of Contents
User Interface ..................................................Pg 2
Display ............................................................. Pg 3
Sequence of Operation ..................................Pg 4
Section A: General Operation .............. Pg 4
Section B: Boiler Operation..................Pg 6
Section C: Outdoor Reset ..................... Pg 10
Section D: DHW Operation ...................Pg 13
Section E: Setpoint Operation .............Pg 16
Section F: External Input Operation .... Pg 17
Installa tion ....................................................... Pg 19
DIP Switch Settings ........................................Pg 26
Control Settings ..............................................Pg 28
View Menu ..............................................Pg 28
Adjust Menu ........................................... Pg 29
Testing the Control .........................................Pg 34
Error Messages ...............................................Pg 35
Techni c a l D a t a .................................................Pg 36
Limited Warranty ............................................Pg 36
Section G: Pump Operation ..................Pg 18
User Interface
The 265 uses a Liquid Crystal Display (LCD) as the method of supplying information. You use the LCD in order to setup and monitor the operation of your system. The 265 has four push buttons (Menu, Item, , ) for selecting and adjusting settings. As you program your control, record your settings in the ADJUST Menu table which is found in the second half of this brochure.
Menu
All of the items displayed by the control are organized into various menus. These menus are listed on the left hand side of the display (Menu Field). To select a menu, use the Menu button. By pressing and releasing the Menu button, the display will advance to the next available menu. Once a menu is selected, there will be a group of items that can be viewed within the menu.
Menu Item
Item
The abbreviated name of the selected item will be displayed in the item field of the display. To view the next available item, press and release the Item button. Once you have reached the last available item in a menu, pressing and releasing the Item button will return the display to the first item in the selected menu.
The items can be quickly scrolled through by holding the Item button and then pressing the ▼ button. To rapidly scroll through the items in the reverse order, hold the Item button and press the button.
Adjust
To make an adjustment to a setting in the control, begin by selecting the appropriate menu using the Menu button. Then select the desired item using the Item button. Finally, use the and / or button to make the adjustment.
Additional information can be gained by observing the Status field of the LCD. The status field will indicate which of the control’s outputs are currently active. Most symbols in the status field are only visible when the VIEW Menu is selected.
© 2010 D 265 - 07/10 2 of 36
Menu Item
Menu Item
Display
Menu Field
Displays the current menu
Item Field
Displays an abbreviated name of the selected item
Status Field
Displays the current status of the control's inputs, outputs and operation
Number Field
Displays the current value of the selected item
Boiler Demand DHW / Setpoint Demand WWSD Modulation Boiler Output (x10,000 BTU/hr) External Input Signal Offset / Priority Override
Buttons
Selects Menus, Items and adjust settings
Symbol Description
Stage
Displays which boiler relays are turned on.
Primary Pump
Displays when the primary pump relay is turned on.
Boiler Pump
Displays which boiler pump relays are turned on.
Combustion Air Damper
Displays when the Combustion Air Damper relay is turned on.
Delta T
The current difference between the supply and return temperatures.
°F, °C, min, hr
Units of measurement.
UnOccupied Schedule
Displays when the control is in UnOccupied Mode.
Occupied Schedule
Displays when the control is in Occupied Mode.
Installer Access Level
Displays when the Advanced / Installer Dip switch is set to Installer.
Pointer
Displays the control operation as indicated by the text.
Warning / Alert
Displays when an error exists or the alert relay is turned on.
Modulating Output Scale
Displays the total modulation output level of the boilers.
DHW
Displays when the DHW relay is turned on.
3 of 36 © 2010 D 265 - 07/10
Definitions
The following defined terms and symbols are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning the life of the product.
- Warning Symbol: Indicates presence of hazards which can cause severe personal injury, death or substantial property damage if ignored.
INSTALLATION
CATEGORY II
- Double insulated
- Local level, appliances
Sequence of Operation
Section A
General
Operation
Page 4 - 6
Section E
Setpoint
Operation
Page 16
Section B
Boiler
Operation
Page 6 - 10
Section F
External
Input Operation
Page 17 - 18
Section C
Outdoor
Reset
Page 10 - 12
Section G
Pump
Operation
Page 18 - 19
Section D
DHW
Operation
Page 13 - 15
Section A: General Operation
POWERING UP THE CONTROL
When the control is powered up, all segments in the LCD are turned on for 2 seconds. Next, the control displays the control type number in the LCD for 2 seconds. Next, the software version is displayed for 2 seconds. Finally, the control enters into the normal operating mode.
BOILER TARGET TEMPERATURE
The control operates up to three modulating boilers to control the supply water temperature to a hydronic space heating system or setpoint. When using the control to provide Domestic Hot Water (DHW) requirements, only two modulating boilers can be operated. The supply water temperature is based on boiler reset, an external 0 – 10 V (dc) signal, DHW requirements, or a setpoint temperature.
Design SupplyDesign Supply
Boiler Reset (Stand Alone)
When a boiler demand signal from the heating system is present, the control operates the boiler(s) to maintain the supply temperature based on the outdoor air temperature and the Characterized Heating Curve settings. Refer to section C.
Terminal UnitTerminal Unit
Indoor DesignIndoor Design Outdoor DesignOutdoor Design
DHW
When a DHW demand is present, the control operates the boiler(s) to maintain the supply water temperature at least as hot as the DHW exchange setting. Refer to section D.
Decreasing Outdoor Temperature
Increasing Water Temperature
Setpoint
When a setpoint demand signal is present, the control operates the boiler(s) to maintain the supply water temperature at least as hot as the Setpoint setting. Refer to section E.
External Input 0 – 10 V (Dc) or 2 – 10 V (Dc)
When an external input signal is present, the control converts the signal to a target supply temperature. The control operates the boiler(s) to maintain the required supply water temperature. Refer to section F.
© 2010 D 265 - 07/10 4 of 36
SETBACK (OCC and UNOCC)
To provide greater energy savings, the control has a setback feature. With setback, the supply water temperature in the system is reduced when the building is unoccupied. By
Com
2
1
Boil
Boil
Ret
Sup
5
4
3
UnO
Out
Sw
+
reducing the supply water temperature, the air temperature in the space may be reduced even when thermostat(s) are not turned down. Any time the UnO Sw (5) and the Com (1) terminals are shorted together, the control operates in the unoccupied mode. When in the unoccupied mode, the UNOCC segment is displayed in the LCD. The control adjusts the supply water temperature based on the UNOCC settings in the control.
Timer Switch
COMBUSTION AIR OR ALERT CONTACT
The control has an isolated contact that can be used as either a combustion air damper contact or an alert contact. This selection is made using the C.A. / Alert DIP switch.
Combustion Air (C.A.)
When the DIP switch is set to C.A., terminals 15 and 16 can be used as a switch to operate a combustion air damper. This contact closes prior to the first boiler operating on the control. The amount of time that the contact closes prior to the first boiler firing is set using the combustion delay setting.
The combustion air contact remains closed for a minimum of 15 seconds after the last boiler is turned off.
Alert
When the DIP switch is set to Alert, terminals 15 and 16 can be used as a switch to operate an alert circuit. This contact closes whenever an error message is present on the control display. When the alert contact is activated, refer to the Error Messages section of this brochure to determine the cause of the alert. Once the fault has been fixed, pressing either the Menu, Item, or button will clear the alert.
Boiler Alert
The control can monitor the boiler supply temperature and provide an alert if the temperature does not increase within a certain amount of time. The amount of time can be set using the Boiler Alert setting. This alert can be used to determine if the boilers have failed to fire. To reset the alert, press and hold the ▲ and ▼ buttons for 5 seconds while in the VIEW menu.
ROTATION
The control includes an Equal Run Time feature which changes the firing order of the boilers whenever one boiler accumulates 48 hours more running time than any other boiler. After each rotation, the boiler with the
12
least running hours is the first to fire and the boiler with the most running hours is the last to fire. This function ensures that all of the boilers that are being rotated receive equal amounts of use. When the Rotate / Off
720 hours 672 hours
DIP switch is set to the Off position, the firing sequence always begins with lowest boiler to the highest boiler.
Fixed Lead Rotation
21
In some applications, it may be desirable to have the first boiler fire first at all times while the firing sequence of the remaining boilers is changed using Equal Run Time Rotation. This rotation option is selected by
672 hours 720 hours
setting the Fixed Lead / Off DIP switch to the Fixed Lead position.
First On / Last Off or First On / First Off
When using the Fixed Lead rotation option, a selection must be made between First On / Last Off and First On / First Off using the DIP switch. When First On / Last Off is selected, the lead boiler is always modulated first and shut off last. When First On / First Off is selected, the lead boiler is always modulated first and shut off first. This DIP switch is only read by the control when the Fixed Lead / Off DIP switch is set to Fixed Lead.
Resetting the Rotation Sequence
To reset the rotation sequence, set the Rotate / Off DIP switch to the Off setting for 5 seconds and then return the DIP switch to the Rotate setting.
RUNNING TIMES
The control displays the accumulated running time of each boiler in the VIEW menu.
Resetting the Running Times
To reset the running time for each boiler, select the appropriate running time in the VIEW menu. Next press the and buttons simultaneously until CLr is displayed.
5 of 36 © 2010 D 265 - 07/10
EXERCISING
The control has a built-in exercising feature that is selected through the Exercise / Off DIP switch. To enable the exercising feature set the Exercise / Off DIP switch to Exercise. If exercising is enabled, the control ensures that each pump is operated at least once every 3 days. If a pump has not been operated at least once every 3 days, the control turns on the output for 10 seconds. This minimizes the possibility of the pump seizing during a long period of inactivity. While the control is exercising, the Te st LED flashes quickly.
Note: The exercising function does not work if power to the control or pumps is disconnected.
FACTORY DEFAULTS
The control comes preset with several factory defaults. These defaults are based on the terminal unit selection (see section C). To fine-tune building requirements, these defaults may be changed.
To reload the factory defaults listed in the ADJUST Menu, power down the control and wait for 10 seconds. Power up the control while simultaneously holding the Menu and ▼ buttons. An E01 error occurs forcing the installer to go through the ADJUST menu to ensure the settings are correct.
Section B: Boiler Operation
Section B1
Boiler
Modulation
Section B1: Boiler Modulation
MODULATION
The control provides three modulating output signals, three boiler enable contacts, and three boiler pumps contacts to operate up to three modulating boilers. The boiler enable contact may not be required, depending on the make and model of the boiler(s).
The control operates a boiler by first closing the boiler pump contact. The boiler enable contact is closed next and then the control provides a modulating output signal to the boiler.
The modulation output signal is then modulated from the minimum modulation using Proportional, Integral and Derivative (PID) logic in order to satisfy the boiler target temperature.
SEQUENTIAL MODULATION
The control offers a sequential modulation option. This is selected by setting the Sequential / Parallel DIP switch to Sequential. Sequential modulation should be used on boilers that are more efficient when operating at high fire.
SEQUENTIAL MODULATION
100% MOD OFF
In sequential modulation, the first boiler is turned on and is modulated to satisfy light loads. Once the first boiler does not have enough capacity to satisfy the load, the first boiler reduces its modulation to provide a smooth transition when the second boiler fires at low fire. The first boiler then modulates up to maximum modulation as the load increases. Only then is the second boiler able to increase its output as the load continues to increase. When the third boiler is required, the second boiler reduces its modulation to allow the third boiler to operate at low fire. As the load continues to increase, the second boiler is modulated to its maximum and then the third boiler is modulated. The operation is reversed
Boiler 1 Boiler 2 Boiler 3
when shutting off the boilers.
PARALLEL MODU L ATION
The control offers a parallel modulation option. This is selected by setting the Sequential / Parallel DIP switch to Parallel. Parallel modulation should be used on boilers that are more efficient when operating at low fire.
In parallel modulation, the first boiler turns on at low fire and begins to increase its modulation. Once the first boiler’s output is greater than the combined output of the first and second boiler’s low fire, the first boiler is modulated down to low fire and the second boiler is fired at low fire. The two boilers now modulate together. Once the two boiler’s combined output is greater than the combined output of all three boilers operating at low fire, the first and second boilers are modulated down to low fire, and all three boilers are operated at low fire. The boilers are then modulated as the load increases. The operation is reversed when shutting off the boilers.
PARALLEL MODULATION
MOD MOD MOD
Boiler 1 Boiler 2 Boiler 3
© 2010 D 265 - 07/10 6 of 36
MODULATION RANGE (4 to 20 mA or 0 to 20 mA)
The modulation output (Mod 1, Mod 2, and Mod 3) for each boiler can be adjusted from a 4 to 20 mA output range to a 0 to 20 mA output range using the Boil Modulation 1, Boil Modulation 2, or Boil Modulation 3 setting. The resulting modulation output signal can be converted to a 0 to 5 V (dc), 1 to 5 V (dc), 0 to 10 V (dc), and 2 to 10 V (dc) output using external resistors. The modulation output signal can be converted to a 0 to 135 Ω (W R B) output using a 0 - 135 Ω Converter 005. Refer to the Modulation Output section in Step 4 of the Installation section.
MINIMUM MODULATION
The minimum modulation defines the minimum output signal from the control to the boiler burner. It is based on a percentage of the control’s output signal range.
The minimum modulation setting for boilers with power burners is typically set to 0%.
For boilers with electronic operators, the boiler’s input signal range may not match the output signal range of the 265 control. The Minimum Modulation setting limits the control output range in order to match the boiler’s input range.
To calculate the Minimum Modulation, use the following formulae:
MINIMUM MODULATION
For 4 to 20 mA:
Minimum Modulation = 4 - 20 mA
4 mA – Boiler’s Minimum Input Signal
For 0 to 10 V (dc):
Minimum Modulation = 0 – 10 V (dc)
0 V (dc) – Boiler’s Minimum Input Signal
For 2 to 10 V (dc):
Minimum Modulation = 2 – 10 V (dc)
2 V (dc) – Boiler’s Minimum Input Signal
x 100%
x 100%
x 100%
Control's
Output
Signal
Range
Minimum Modulation
100%10 V (dc) 10 V (dc)
Boiler's Input Signal Range
18%
0%0 V (dc)
1.8 V (dc)
Boiler's Minimum
Input Signal
Example 1:
A boiler requires a 1.8 V (dc) signal to fire the boiler at low fire. The boiler can be modulated to 10 V (dc) where it reaches high fire. This means the boiler’s input signal range is 1.8 to 10 V (dc). The 265 control has an output signal range of 0 to 20 mA which can be externally converted to 0 to 10 V (dc) using a 500 Ω resistor (Refer to Modulation Output section in Step 4 of the Installation section).
To make the two signal ranges the same, the Minimum Modulation required is:
0 V – 1.8 V
Minimum Modulation 0 V – 10 V
=
x 100% = 18%
Example 2:
If the boiler’s input signal range is 6 to 20 mA the required Minimum Modulation is:
Minimum Modulation = 4 mA – 20 mA
4 mA – 6 mA
x 100% = 13%
MAXIMUM MODULATION
The maximum modulation defines the maximum output signal from the control to the boiler burner. It is based on a percentage of the control’s output signal range.
The maximum modulation setting for boilers with power burners is typically set to 100%.
For boilers with electronic operators, the boiler’s input signal range may not match the output signal range of the 265 control. The Maximum Modulation setting limits the control output range in order to match the boiler’s input range.
To calculate the Maximum Modulation, use the following formulae:
For 4 to 20 mA:
Maximum Modulation = 4 – 20 mA
4 mA – Boiler’s Maximum Input Signal
x 100%
For 0 to 10 V (dc):
Maximum Modulation = 0 – 10 V (dc)
0 V (dc) – Boiler’s Maximum Input Signal
x 100%
For 2 to 10 V (dc):
Maximum Modulation = 2 – 10 V (dc)
7 of 36 © 2010 D 265 - 07/10
2 V (dc) – Boiler’s Maximum Input Signal
x 100%
Maximum
Modulation
MAXIMUM MODULATION
Control's
Output
Signal
Range
100%10 V (dc)
88%
9 V (dc)
Boiler's Input Signal Range
0%2 V (dc)
2 V (dc)
Boiler's
Maximum
Input Signal
Example 1:
A boiler’s input signal range is 2 to 9 V (dc). The 265 control has an output signal range of 2 to 10 V (dc). To make the two signal ranges the same, the Maximum Modulation required is:
Maximum Modulation = 2 V – 10 V
2 V – 9 V
x 100% = 88%
Example 2:
If the boiler’s input signal range is 6 to 19 mA the required Maximum Modulation is:
Maximum Modulation = 4 mA – 20 mA
4 mA – 19 mA
x 100% = 94%
MINIMUM BOILER OUTPUT
In order to accommodate different boiler capacities in the same system, a minimum boiler output for each boiler can be set. This allows the control to properly operate the boilers using either sequential or parallel modulation. The minimum boiler output range is from 10,000 BTU / hour to 19,990,000 BTU / hour.
Each boiler typically has a rating plate that specifies the minimum output. This information is also available in the boiler manual. The Minimum Boiler Output setting has units of 10,000 BTU / hour. Divide the minimum output rating by 10,000 and enter the number as the Minimum Boiler Output setting.
For example, if a boiler has a minimum output of 20 MBH:
Minimum Boiler Output = 10,000
20,000 BTU/hr
= 2 x 10,000 BTU/hr
MAXIMUM BOILER OUTPUT
In order to accommodate different boiler capacities in the same system, there is a maximum boiler output for each boiler. This allows the control to properly operate the boilers using either sequential or parallel modulation. The maximum boiler output range is from 10,000 BTU / hour to 19,990,000 BTU / hour.
Each boiler typically has a rating plate that specifies the maximum output. This information is also available in the boiler manual. The Maximum Boiler Output setting has units of 10,000 BTU / hour. Divide the maximum output rating by 10,000 and enter the number into the Maximum Boiler Output setting.
For example, if a boiler has a maximum output of 100 MBH:
Maximum Boiler Output = 10,000
100,000 BTU/hr
= 10 x 10,000 BTU/hr
MOTOR SPEED
The Motor Speed is the amount of time the boiler requires to go from 0% modulation to 100% modulation. The control includes a Motor Speed setting for each individual boiler.
Gas valve actuating motors have a design time from fully closed to fully opened which can be found in the manufacturer’s manual. The Motor Speed should be set to this time.
The Motor Speed setting for a Variable Frequency Drive (VFD) is the amount of time required to go from a stopped position to 100% fan speed. Since a VFD has a very quick response rate, it may be necessary to increase the Motor Speed setting in order to increase the stability of the boiler modulation.
BOILER MASS
The boiler mass setting allows the installer to adjust the control to the thermal mass of the type of heat sources used in the application. There is a boiler mass setting for each boiler. The modulation of the boiler can become unstable if the incorrect Boiler Mass setting is chosen. A key sign of the boiler modulation being unstable is the flame will continue to increase and then decrease in short periods of time. By choosing a lower boiler mass setting, the boiler response will become more stable.
Lo (1)
The Lo setting is selected if the boiler that is used has a low thermal mass. This means that the boiler has a very small water content and has very little metal in the heat exchanger. A boiler that has a low thermal mass comes up to temperature quite rapidly when fired. This is typical of many copper fin-tube boilers.
The Lo mass setting provides a fast response to the heating system.
© 2010 D 265 - 07/10 8 of 36
Med (2)
The Med setting is selected if the boiler that is used has a medium thermal mass. This means that the boiler either has a large water content and a low metal content or a low water content and a high metal content. This is typical of many modern residential cast iron boilers or steel tube boilers.
The Med mass setting provides a moderate response to the heating system.
Hi (3)
The Hi setting is selected if the boiler that is used has a high thermal mass. This means that the boiler has both a large water content and a large metal content. A boiler that has a high thermal mass is relatively slow in coming up to temperature. This is typical of many commercial cast iron and steel tube boilers.
The Hi mass setting provides a slow response to the heating system.
DIFFERENTIAL
A modulating boiler must be operated with a differential while operating in low fire. The boiler differential is divided around the boiler target temperature. The boiler starts at low fire when the supply water temperature is ½ of the differential setting below the boiler target temperature. The boiler is shut off in low fire as the supply temperature reaches at least ½ of the differential above the boiler target temperature. With the control, either a fixed or an auto differential may be selected.
When the boiler is modulating above low fire, the differential does not apply. Instead, the modulation output signal is determined using Proportional, Integral and Derivative (PID) logic in order to satisfy the boiler target temperature.
Desired temperature
Fixed Differential
If the user desires to have a fixed differential, this is set using the boiler differential setting in the ADJUST menu.
160°F (71°C)
Boiler Off
Boiler On
165°F (74°C)
Time
e
r
u
t
a
r
e
p
m
e
T
155°F (68°C)
e
s
i
r
T
e
m
p
Differential
10°F (6°C)
e
r
a
t
u
r
e
f
a
l
l
Auto Differential
If the Auto Differential is selected, the control automatically determines the best differential as the load changes. This reduces potential short cycling during light load conditions.
BOILER MINIMUM
The boiler minimum is the lowest temperature that the control is allowed to use as a boiler target temperature. During mild conditions, if the control calculates a boiler target temperature that is below the boiler minimum setting, the boiler target temperature is adjusted to at least the boiler minimum setting. During this condition, if the boiler(s) is operating, the minimum segment is turned on in the display when viewing either the boiler supply temperature or the boiler target temperature. Set the boiler minimum setting to the boiler manufacturer’s recommended temperature.
BOILER MAXIMUM
The boiler maximum is the highest temperature that the control is allowed to use as a boiler target temperature. If the control does target the boiler maximum setting, and the boiler temperature is near the boiler maximum temperature, the maximum segment will be turned on in the display while either the boiler target temperature or the boiler supply temperature is being viewed. At no time does the control operate the boiler(s) above 248°F (120°C).
Differential
MIN Segment On
MAX Segment
On
Off
Time
On
MAX Segment
Increasing Load
On
9 of 36 © 2010 D 265 - 07/10
FIRE DELAY
The Fire Delay is the time delay that occurs between the time that the control closes a boiler enable contact to fire a boiler and when the boiler fires at low fire.
STAGE DELAY
The stage delay is the minimum time delay between the firing of stages. After this delay has expired the control can fire the next stage if it is required. This setting can be adjusted manually or set to an automatic setting. When the automatic setting is used, the control determines the best stage delay based on the operation of the system.
Boiler 1 Contact Closes
Fire
Delay 1
Boiler 1 Fires
Stage Delay
Boiler 2 Contact Closes
Fire
Delay 2
Time
Boiler 2 Fires
Stage Delay
Boiler 3 Contact Closes
Fire
Delay 3
Boiler 3 Fires
SOFT STOP
It is possible to thermally shock a boiler when it is shut off at high fire. The Soft Stop feature forces the boiler to modulate down to minimum before turning off. This is designed to prevent large volumes of cold air being introduced into the combustion chamber of the boiler when it is shut off. This can occur in applications where the burner includes a fan.
Once all demands are removed, the control allows for the firing rate to be modulated down to the MIN Modulation setting prior to turning off the burner. This feature is enabled by setting the Soft Stop / Off DIP switch to the Soft Stop position. If the Soft Stop / Off DIP switch is in the Off position, the control turns off the boiler at the current firing rate once all demands are removed.
COPY BOILER 1 SETTINGS
Many boiler installations will have multiple identical boilers. To reduce the number of settings required, the settings of boiler 1 (Fire Delay, Boiler Mass, Motor Speed, Minimum Boiler Output, Maximum Boiler Output, Boiler Modulation, Minimum Modulation, Maximum Modulation, and Purge Boiler Pump) are copied to boiler 2 by setting the Boiler 2 setting to CP1. Likewise, setting Boiler 3 to CP1 copies the settings of boiler 1 to boiler 3. Boiler 2 and Boiler 3 settings are set to CP1 by default.
The setting of CP1 allows the control to enable the boiler similar to the setting of Au (automatic). If a boiler is set to OFF, the control disables that boiler.
If required, each of the three modulating boilers can have individual boiler settings. This allows for three different type, size, and make of modulating boilers. To select individual boiler settings for boiler 2, set Boiler 2 to Au (automatic). Likewise, to select individual boiler settings for boiler 3, set Boiler 3 to Au (automatic).
Section C: Outdoor Reset
Section C1
Boiler Reset
(Stand Alone)
Section C1: Boiler Reset (Stand Alone)
Boiler Reset operation only applies when the Stand Alone / External Input DIP switch is set to Stand Alone.
BOILER DEMAND
A boiler demand is required in order for the control to provide heat to the heating system. A boiler demand is generated by applying a voltage between 24 and 230 V (ac) across the Boil Dem and Com Dem terminals (29 and 30). Once voltage is applied, the Boiler Demand pointer is displayed in the LCD. If the control is not in Warm Weather Shut Down (WWSD), the control closes the primary pump contact. The control calculates a boiler target supply temperature based on the outdoor air temperature and the characterized heating curve settings. The control then fires the boiler(s), if required, to maintain the target supply temperature.
© 2010 D 265 - 07/10 10 of 36
24 to 230 V (ac)
Boil
Dem
29
Com
Dem
30
-20
(-29)
210 (99)
190 (88)
170 (77)
150 (66)
130 (54)
110 (43)
90 (32)
70 (21)
50°F (10°C)
CHARACTERIZED HEATING CURVE
The control varies the supply water temperature based on the outdoor air temperature. The control takes into account the type of terminal unit that the system is using. Since different types of terminal units transfer heat to a space using different proportions of radiation, natural convection and forced convection, the supply water temperature must be controlled differently. Once a terminal unit is selected, the control varies the supply water temperature according to the type of terminal unit. This improves the control of the air temperature in the building.
OUTDOOR DESIGN TEMPERATURE
The outdoor design temperature is the outdoor air temperature that is the typical coldest temperature of the year where the building is located. This temperature is used when doing the heat loss calculations for the building. If a cold outdoor design temperature is selected, the boiler supply temperature rises gradually as the outdoor temperature drops. If a warm outdoor design temperature is selected, the boiler supply temperature rises rapidly as the outdoor temperature drops.
BOILER DESIGN TEMPERATURE
Boiler Characterized
Boiler Characterized
Heating Curve
Heating Curve
BOIL MIN
BOIL INDR
80
(27)
60
(16)
Outdoor Air Temperature
OUT DSGN
WWSD OCC
WWSD UNOCC
ROOM OCC
ROOM UNOCC
40
(5)
BOIL DSGN
20
(-7)
BOIL MAX
0
(-18)
The boiler design supply temperature is the supply water temperature required to heat the building when the outdoor air temperature is as cold as the outdoor design temperature.
BOILER INDOOR DESIGN TEMPERATURE
The indoor design temperature is the room temperature that was used in the original heat loss calculations for the building. This setting establishes the beginning of the characterized heating curve.
Supply Water Temperature
ROOM
The ROOM setting is the desired room temperature for the building and provides a parallel shift of the heating curve. The room temperature desired by the occupants is often different from the design indoor temperature. If the room temperature is not correct, adjusting the room setting increases or decreases the amount of heat available to the building. A room setting is available for both the occupied (day) and unoccupied (night) periods.
BOILER TARGET TEMPERATURE
The boiler target temperature is determined from the characterized heating curve settings and the outdoor air temperature. The control displays the temperature that it is currently trying to maintain as the boiler supply temperature. If the control does not presently have a requirement for heat, it does not show a boiler target temperature. Instead, “– – –” is displayed in the LCD.
TERMINAL UNITS
The control provides for a selection between six different terminal unit types: two types of radiant floor heat, fancoil, fin-tube convector, radiator and baseboard. When a terminal unit is selected, the control automatically loads the design supply temperature, maximum supply temperature, and minimum supply temperature. The factory defaults are listed below. These factory defaults can be changed to better match the installed system.
Terminal Unit High Mass
Radiant (1)
Low Mass
Radiant (2)
Fancoil
(3)
Fin-Tube
Convector (4)
Radiator
(5)
Baseboard
(6)
BOIL DSGN 120°F (49°C) 140°F (60°C) 190°F (88°C) 180°F (82°C) 160°F (71°C) 150°F (66°C)
BOIL MAX 140°F (60°C) 160°F (71°C) 210°F (99°C) 200°F (93°C) 180°F (82°C) 170°F (77°C)
BOIL MIN OFF OFF 140°F (60°C) 140°F (60°C) 140°F (60°C) 140°F (60°C)
High Mass Radiant (1)
This type of a hydronic radiant floor is embedded in either a thick concrete or gypsum pour. This heating system has a large thermal mass and is slow acting.
Low Mass Radiant (2)
This type of radiant heating system is either attached to the bottom of a wood sub-floor, suspended in the joist space, or sandwiched between the sub-floor and the surface. This type of radiant system has a relatively low thermal mass and responds faster than a high mass system.
11 of 36 © 2010 D 265 - 07/10
Loading...
+ 25 hidden pages