The Boiler Control 262 is a micro processor based control designed to maximize the comfort and efficiency of a hydronic heating system.
The control is designed to operate in two distinct modes.
MODE —1— (Two Stage Boiler & DHW) allows for the control of two separate on /off boiler stages (or one low / high fire) based on outdoor
air temperature, control for indirect Domestic Hot Water (DHW) generation and a Setpoint load. For single zone temperature control
with indoor temperature feedback, a Room Temperature Unit (RTU) or indoor sensor may be connected to the 262. Multiple zone
temperature control is achieved by using either a conventional thermostat system or by connecting a tekmar Zone Control to the 262.
MODE —2— is designed specifically for dedicated DHW applications. In Mode 2, the 262 can stage and rotate two on / off boiler stages
(or one low / high fire) in order to provide heat to a DHW storage system.
The 262 control includes a large Liquid Crystal Display (LCD) in order to view system status and operating information. The same LCD
is used when setting up and installing the control. Standard features include Equal Run Time Rotation, intelligent boiler operation, digital
temperature readouts, and pump exercising. With the addition of a monitoring feature, it is now possible to track pump and boiler running
hours, DHW tank temperature, outdoor and system high and low temperatures, boiler firing cycles, plus many other useful items.
Several energy saving features have been incorporated into the 262 such as Warm Weather Shut Down (WWSD), DHW post purge,
system setback, DHW priority and an automatic differential for boiler operation.
Reset Ratio
Characterized
Heating Curve
1 Two Stage Boiler & DHW
2 Two Stages for DHW
Do not apply power
16
18 19
15
tN1/
UnO
Com
10KOut
tN2
Sw
20
DHW17Com
Test
21 22
Boil
off
not testing
red
testing
red
For maximum heat,
Tes t
press and hold
button for 3 seconds.
Meets Class B:
Canadian ICES
FCC Part 15
Date Code
H1109F
Input
Outdoor
Sensor
Input
Universal
Sensor
Input
Universal
Sensor
Included
Optional
Input
tekmar
Timer
Included
Note:
Boiler, DHW, or setpoint
demand must be powered
with 20 to 260 V (ac)
before the boiler is able
to fire.
Input
Boiler
Demand
signal
Input
DHW Demand
signal
Input
Setpoint
Demand
signal
Input
120 V (ac)
Power
Supply
View
F
°
1
2
1
Item
Menu
Boiler Control 262
Two Stage Boiler & DHW / Two Stage DHW
7
6
8
10
Boiler
231
4
5
Com
DHW
Setp
Dem
Dem
Dem
Power
NL
Boil
P1
9
DHW
Pmp / Vlv
Boiler Demand
DHW Demand
Setpoint Demand
WWSD
Minimum
Maximum
12
11
14
13
Stage
Stage
11 2 2
Setback
None
Operating Modes
See product literature
INSTALLATION CATEGORY II
Made in Canada by
tekmar Control Systems Ltd.
tektra 929-03
Power115 V ±10% 60 Hz 900 VA
Relays230 V (ac) 7.5 A 1/3 hp, pilot duty 240 VA
Demands20 to 260 V (ac) 2 VA
Signal wiring must be rated at least 300 V.
Wiring must be rated 194°F (90°C) minimum
The 262 uses a Liquid Crystal Display (LCD) as the method of supplying information. You use the LCD in order to setup and monitor
the operation of your system. The 262 uses four push buttons (Menu, Item, , ) for selecting and adjusting settings. As you program
your control, record your settings in the actual settings column of the Adjust Menu. The table is found in the second half of this brochure.
All of the items displayed by the control are organized into various menus. These menus are
listed on the left hand side of the display (Menu Field). To select a menu, use the
button. By pressing and releasing the
available menu. Once a menu is selected, there will be a group of items that can be viewed
within that menu.
The abbreviated name of the selected item will be displayed in the item field of the display.
To view the next available item, press and release the
the last available item in a menu, pressing and releasing the
display to the first item in the selected menu.
To make an adjustment to a setting in the control, begin by selecting the appropriate menu
using the
and / or button to make the adjustment.
Additional information can be gained by observing the Status field of the LCD. The status field will indicate which of the control’s outputs
are currently active. Most symbols in the status field are only visible when the View Menu is selected.
When the Boiler Control 262 is powered up, the control displays the control type number in the LCD for 2 seconds. Next, the software
version is displayed for 2 seconds. Finally, the control enters into the normal operating mode and the LCD defaults to displaying the
current outdoor air temperature.
MODES OF OPERATION (MODE)
The Boiler Control 262 has two operating modes. The mode of operation
for which the control is to operate is selected in the
Mode 1
(MODE = —1—)
Mode 1 is designed for one or two stages of Heating, Domestic Hot
Water (DHW), and Setpoint operation.
Mode 2
(MODE = —2—)
Mode 2 is designed for dedicated DHW operation. In this mode, the 262
controls one or two stages of heat for DHW generation (see Section C3
Dedicated DHW).
Adjust Menu
.
STAGING
The 262 controls up to two stages in order to supply the required target
temperature. After each stage is turned on in the firing sequence, the
control waits a minimum amount of time before turning on the next stage.
The minimum time between stages is the total of the fire delay (FIRE DLY)
setting plus the minimum inter-stage delay selected by the boiler mass
(Boil MASS) setting. After the minimum time delay between stages has
expired, the 262 examines the control error to determine when the next
stage is to fire. The control error is determined using Proportional, Integral,
and Derivative (PID) logic.
Proportional
- compares the actual supply temperature to the boiler target
(Boil TRG) temperature. The colder the supply water temperature, the
sooner the next stage is turned on.
Integral
- compares the actual supply temperature to the Boil TRG
temperature over a period of time.
Derivative
- determines how fast or slow the supply water temperature is
changing. If the supply temperature is increasing slowly, the next stage is
turned on sooner. If the supply temperature is increasing quickly, the next
stage is turned on later, if at all.
Each stage has a minimum on time and a minimum off time.
FIRE DELAY (FIRE DLY)
The Fire Delay is the delay time that may occur between the time that the
262 closes a stage contact and the burner fires for that stage. This delay
is usually the result of burner pre-purge or other forms of time delay built
into the burner’s safety circuits.
BOILER MASS (Boil MASS)
The Boiler Mass setting allows the installer to adjust the control to the
thermal mass of different types of heat sources used.
The LITE setting is selected if the boiler(s) that is used has a low thermal mass. This means that the boiler(s) has a very small water
content and has very little metal in the heat exchanger. A boiler that has a low thermal mass comes up to temperature quite rapidly
when fired. This is typical of many copper fin-tube boilers. The minimum inter-stage delay for the LITE setting is two minutes.
Medium
The Medium setting is selected if the boiler(s) that is used has a medium thermal mass. This means that the boiler(s) either has a
large water content and a low metal content or a low water content and a high metal content. This is typical of many modern residential
cast iron boilers or steel tube boilers. The minimum inter-stage delay for the MED setting is four minutes.
Heavy
The Heavy setting is selected if the boiler(s) that is used has a high thermal mass. This means that the boiler(s) has both a large water
content and a large metal content. A boiler that has a high thermal mass is relatively slow in coming up to temperature. This is typical
of many commercial cast iron and steel tube boilers. The minimum inter-stage delay setting for the HEVY setting is six minutes.
BOILER DIFFERENTIAL (BOIL DIFF)
An on / off heat source must be operated with a differential in order to prevent short cycling. With the 262, either a fixed or an auto
differential maybe selected.
Fixed Differential
The boiler differential is divided around the Boil TRG temperature. The
first stage contact will close when the supply water temperature is 1/2 of
the differential setting below the Boil TRG temperature, and will open
when the supply water temperature is 1/2 of the differential setting above
the Boil TRG temperature. The second stage operates if the first stage
cannot bring the water temperature up to the Boil TRG temperature.
Auto Differential
If the Auto Differential is selected, the 262 automatically determines the
best differential as the load changes. This reduces potential short
cycling during light loads.
(MED)
(HEVY)
(AUTO)
Off
Differential
Time
On
Heating Load
Sequence, Section A
STAGE 1&2 (STAGE)
The stage 1 and 2 setting may be selected to AUTO or OFF. When AUTO
is selected, the stage is activated and the control operates the appropriate
boiler. When OFF is selected, the control does not fire the stage.
ROTATION (ROTATE)
The ROTATE item is an adjustable setting that is factory set at 48 hours.
The firing order of the boilers changes whenever one stage’s accumulated
running time exceeds the other stage’s accumulated running time by more
than the ROTATE setting. After each rotation, the stage with the least
running hours is the first to fire and the stage with the most running hours
is the last to fire. This function ensures that both stages receive equal
amounts of use. When this item is set to the OFF setting, Stage 1 is always
the first stage to fire.
BOILER PURGE (PURGE)
After the boiler demand is satisfied, the 262 continues to operate the boiler
pump (
Boil P1
, terminal 8) for a period of time. The length of time that the
boiler pump continues to run is adjustable (PURGE). This setting allows
purging of any excess heat out of the boiler after the burner is shut off. This
also helps to prevent the water in the boiler from flashing into steam after
the boiler is shut off. The boiler pump continues to run either until the
purging time has elapsed or the boiler supply (Boil SUP) temperature
drops more than a differential below the boiler minimum (Boil MIN) setting.
SETBACK (UNOCCUPIED)
To provide greater energy savings, the 262 has setback capability. With setback, the supply water temperature in the system is reduced
when the building is not used (AWAY) or when the building is UnOccupied. By reducing water temperature, air temperature in the space
can be reduced even when thermostat(s) are not turned down. This feature is enabled by setting the
Setback
Note: AWAY does not require the DIP switch = Setback.
position, and providing either an external signal or an internal override.
An external signal can place the 262 into an UnOccupied mode. Any time the
Com Sen
and the
mode. When in the UnOccupied mode, the
262 adjusts the supply water temperature based on the
(19) terminals are shorted together, the control operates in the UnOccupied
UnOcc
segment is displayed in the LCD. The
UnOcc
setting made in the control.
UnO Sw
(18)
18
UnO
Sw
19
Com
Internal Overrides
The 262 has a number of setback overrides that are selected through the
. These setback overrides have priority over any external setback signal. Any time an
Menu
override is in effect, the
(OVERRIDE)
Ovr
segment is displayed in the LCD.
Schedule (Schd)
Timer Switch
Temporary (TMPY)
If a temporary OVERRIDE is selected, the 262 operates in the selected override mode for
3 hours. Once over, the control reverts to the previous operation.
Permanent (PERM)
If a permanent OVERRIDE is selected, the 262 operates in the selected override mode
until a new OVERRIDE is selected.
Schd
UnOcc
Ovr
Away (AWAY)
If the AWAY override is selected, the 262 operates with a fixed WWSD of 62˚F (17˚C) and a fixed room temperature of 62˚F (17˚C).
Any DHW demand is ignored. The setpoint operation is not affected by the AWAY
EXERCISING (EXERCISE)
The 262 has a built in pump exercising function. The exercising period setting is adjustable and is factory set at 70 hours. If a pump output
on the control has not been operated at least once during every exercising period, the control turns on the output for 10 seconds. This
minimizes the possibility of the pump seizing during a long period of inactivity.
Note: The exercising function does not work if power to the control or pump(s) is disconnected.
override.
Section B —Boiler Reset (Mode = —1—)
Section B1
General Boiler
Operation
Section B2
Alternate Boiler
Demands
Section B1 —General Boiler Operation
BOILER DEMAND
A boiler demand is generated by applying a voltage between 24 and 240 V (ac) across the
applied, the
boiler pump and the control turns on the boiler pump segment in the LCD. The 262 calculates a Boil TRG supply temperature based
on the outdoor air temperature and settings. The 262 then fires the boiler(s), if required, to maintain the target supply temperature.
Boiler Demand
pointer is displayed in the LCD. If the 262 is not in WWSD, it closes the
CHARACTERIZED HEATING CURVE OR RESET RATIO
The 262 has two methods of varying the supply water temperature based on the outdoor air temperature. The installer can select either
a
Characterized Heating Curve
Characterized Heating Curve
The
Characterized Heating Curve
temperature and optionally indoor temperature. The control takes into account the type of terminal unit that the system is using. Since
different types of terminal units transfer heat to a space using different proportions of radiation, convection and conduction, the supply
water temperature must be controlled differently. Once the control is told what type of terminal unit is used, the control varies the supply
water temperature according to the type of terminal unit. This improves the control of the air temperature in the building.
Reset Ratio
The
not take into account the type of terminal unit that the heating system is using and therefore is not as accurate as a
Heating Curve
Reset Ratio
method of controlling the supply water temperature is based solely on the outdoor air temperature. This method does
.
or a
Reset Ratio
.
is the most accurate method of controlling the supply water temperature based on outdoor air
The Boil STRT temperature is the boiler supply water temperature that the
heating system requires when the outdoor air temperature equals the
OUT STRT air temperature setting.
OUTDOOR START (OUT STRT)
(
RESET RATIO
)
The OUT STRT temperature is the outdoor air temperature at which the
control provides the Boil STRT supply water temperature
OUTDOOR DESIGN (OUT DSGN)
(
RESET RATIO
&
CHARACTERIZED HEATING CURVE
)
to the system.
The OUT DSGN is the outdoor air temperature that is the typical coldest
temperature of the year where the building is located. This temperature is
used when doing heat loss calculations for the building.
BOILER DESIGN (Boil DSGN)
(
RESET RATIO
&
CHARACTERIZED HEATING CURVE
)
The Boil DSGN temperature is the supply water temperature required to
heat the boiler zones when the outdoor air is as cold as the OUT DSGN
temperature.
Boiler Reset
Ratio
Boil MIN
Boil STRT
OUT STRT
80
(27)
OUT DSGN
WWSD Occ
WWSD Unocc
60
(16)
40
(5)
Outdoor Air Temperature
Boil DSGN
Boil SETB
20
(-7)
Boil MAX
0
(-18)
-20
(-29)
210
(99)
190
(88)
170
(77)
150
(66)
130
(54)
110
(43)
90
(32)
70
(21)
Supply Water Temperature
Sequence, Section B1
BOILER MINIMUM (Boil MIN)
(
RESET RATIO
&
CHARACTERIZED HEATING CURVE
)
The Boil MIN is the lowest water temperature that the control is allowed to
use as a Boil TRG temperature. During mild conditions, if the 262 calculates
a Boil TRG temperature that is below the Boil MIN setting, the Boil TRG
temperature is adjusted to at least the Boil MIN setting. During this
condition, if the boiler is operating, the
Minimum
pointer turns on in the LCD
while the Boil TRG or the Boil SUP temperature is viewed. If the installed
boiler(s) is designed for condensing operation, set the Boil MIN adjustment
to OFF.
BOILER MAXIMUM (Boil MAX)
(
RESET RATIO
&
CHARACTERIZED HEATING CURVE
)
The Boil MAX is the highest water temperature that the control is allowed to
use as a Boil TRG temperature. If the control does target Boil MAX, and the
Boil SUP temperature is near the Boil MAX temperature, the
Maximum
pointer turns on in the LCD while the Boil TRG or the Boil SUP temperature is
viewed. At no time does the control operate the boiler(s) above 248˚F (120˚C).
WARM WEATHER SHUT DOWN (WWSD) OCC & UNOCC
(
RESET RATIO
&
CHARACTERIZED HEATING CURVE
)
When the outdoor air temperature rises above the WWSD setting, the 262
turns on the
Weather Shut Down, the
WWSD
pointer in the display. When the control is in Warm
Boiler Demand
pointer is displayed if there is a
demand. However, the control does not operate the heating system to
satisfy this demand. The control does respond to either a
or a
Setpoint Demand
BOILER SETBACK (SETBACK)
and operates as described in Section C.
(
RESET RATIO
)
DHW Demand
The boiler SETBACK is the amount that the boiler supply water temperature
is reduced when the 262 is placed into an
UnOccupied
mode, using an
internal or an external setback as described in Section A. This setting is
only available if the
DIP switch is set to
BOILER INDOOR (Boil INDR)
(
CHARACTERIZED HEATING CURVE
Reset Ratio
Setback
.
DIP switch is selected and
)
Setback / None
The Boil INDR is the room temperature used in the heat loss calculations
done for the building. This setting establishes the beginning of the
terized Heating Curve
for the boiler zones. This single setting replaces the
Charac-
Boil STRT water temperature and OUT STRT air temperature settings used
by the
The ROOM is the desired room temperature for the boiler zone(s) and it provides a parallel shift of the
The room temperature desired by the occupants is often different from the designed indoor temperature (Boil INDR). If the room
temperature is not correct, adjusting the ROOM setting increases or decreases the amount of heat available to the building. If the
Setback / None
DIP switch is set to
)
Characterized Heating Curve
Setback
, a ROOM setting must be made for both the
Occupied
and
UnOccupied
modes.
.
TERMINAL UNITS (TERMINAL)
When using a
unit. The terminal unit determines the shape of the
to how the terminal unit delivers heat into the building space. The 262 provides for selection
between six different terminal unit types: two types of hydronic radiant floor heat, fancoil, fin–
tube convector, radiator, and baseboard.
Characterized Heating Curve
Hydronic Radiant Floor
HRF 1 is a heavy, or high mass, hydronic radiant floor system. This type of a hydronic radiant
floor is embedded in either a thick concrete or gypsum pour. This heating system has a large
thermal mass and is slow acting.
Hydronic Radiant Floor
HRF 2 is a light, or low mass, hydronic radiant floor system. Most commonly, this type of
radiant heating system is either attached to the bottom of a wood sub floor, suspended in
the joist space, or sandwiched between the subfloor and the surface. This type of radiant
system has a relatively low thermal mass and responds faster than a high mass system.
Fancoil
A fancoil terminal unit or air handling unit (AHU) consists of an hydronic heating coil and
either a fan or blower. Air is forced across the coil at a constant velocity by the fan or blower
and is then delivered into the building space.
Fin-tube Convector
A convector terminal unit is made up of a heating element encased in fins. This type of
terminal unit relies on the natural convection of air across the heating element to deliver
heated air into the space. The amount of natural convection is dependant on the supply
water temperature to the heating element and the room air temperature.
(COIL)
(CONV)
(HRF 1)
(HRF 2)
, the control requires the selection of a terminal
Characterized Heating Curve
according
HRF 1
HRF 2
COIL
CONV
Radiator
A radiator terminal unit has a large heated surface that is exposed to the room. A radiator
provides heat to the room through radiant heat transfer and natural convection.
Baseboard
A baseboard terminal unit is similar to a radiator, but has a low profile and is installed at the
base of the wall. The amount of heat transferred by radiation from a baseboard is greater
than that from a fin-tube convector.
BOILER TARGET TEMPERATURE (BOIL TRG)
(
RESET RATIO
The Boil TRG temperature is determined from either the
temperature and optionally indoor temperature feed back. The control displays the temperature that it is currently trying to maintain as
the boiler supply temperature. If the control does not presently have a requirement for heat, it displays “- - -” in the LCD.
BOILER OPERATION
When the 262 determines that boiler operation is required, the
Boiler contact(s) is closed, the burner and stage segment in the LCD is displayed.
BOILER PUMP (P1) OPERATION
The
Boiler Pump
the control receives a boiler demand and the Boil TRG temperature is below the Boil MIN setting, the boiler pump may continue to operate
after the boiler demand is removed. For boiler pump contact operation during either DHW and / or Setpoint operation, refer to the DHW,
and Setpoint Section D.
Soft Start
The SOF STRT function allows the 262 to slowly ramp the water temperature up to the required supply temperature. By allowing the
temperature in the system to be adjusted slowly, the control reduces any thermal expansion noises and stresses that may be caused
by a quick change in supply water temperature.
contact (P1, terminal 8) closes whenever there is a
(SOF STRT)
Characterized Heating Curve
Boiler stage contact(s)
Boiler demand
8 of 36
and the 262 is not in WWSD. If 10K = INDR or SLAB,
RAD
BASE
or the
Reset Ratio
(11 and 12 and/or 13 and 14) close. While the
settings and the outdoor air
Page 9
Boosting
(BOOST)
When the control changes from the
it enters into a
Boosting
UnOccupied
to the
Occupied
mode,
mode. In this mode, the supply water temperature to the system is raised above its normal values for a period of time
to provide a faster recovery from the setback temperature of the building.
The maximum length of the
setting is only available if a
is not available for a
Typical settings for the
hours for a building that has a fast responding heating system. For a
building that has a slow responding heating system, a setting between
four hours and eight hours is typical. After a
Boost
is selected in the user interface. This
Characterized Heating Curve
Reset Ratio
Boost
or if a tekmar Zone Control is used.
function vary between 30 minutes and two
Boost
time is selected, the
is selected; It
Water Temperature
UnOcc to Occ
setback timer must be adjusted to come out of setback some time in
Boost
Occupied
setting.
advance of the desired
the same as the
If the building is not up to temperature at the correct time, the
time. This time in advance is normally
Boost
setting should be lengthened and the setback timer should be
adjusted accordingly. If the building is up to temperature before the required time, the
Boil TRG
Boil TRG
Boost setting - 20 minutes to 8 hours
Boost
Boost
(Occupied)
Self Adjusting
Water Temperature
(UnOccupied)
Time
setting should be shortened and the
setback timer should be adjusted accordingly. If the system is operating near its design conditions or if the supply water temperatures
are being limited by settings made in the control, the time required to bring the building up to temperature may be longer than expected.
Section B2 —Alternate Boiler Demands (Mode = —1—)
In addition to using conventional thermostats to provide a boiler demand as described in Section B1, the 262 can use a number of other
methods to provide a
10K INDOOR SENSOR (10K = INDR)
Set the 10K item to INDR to add an indoor sensor for temperature control of a single zone boiler
system. The indoor sensor is connected to the
power must be applied to the
With the indoor sensor connected, the 262 is able to sense the actual room temperature. With
this information, the 262 provides a more constant water flow through the system. At the same
time, indoor feedback fine tunes the supply water temperature in the system to prevent over
heating or under heating. To adjust the room temperature for the zone, use the ROOM
Occupied
or
UnOccupied
Boiler Demand
.
Com
and
10K
Boiler Demand
setting in the Adjust menu at the control.
terminals (1 and 2) as described in Section B1.
terminals (16 and 17). In addition,
tekmar
Indoor Sensor
tekmar
262 Control
Boiler Demand
Vie
DHW Demand
°
F
Setpoint Demand
WWSD
Occ
Minimum
1
Maximum
2
1
Item
Menu
Boiler Control 262
Two Stage Boiler & DHW / Two Stage DHW
NRTL/C
LR 58223
R
10K BOILER ZONE CONTROL (10K = ZoIn)
Set the 10K item to ZoIn to add indoor temperature feedback control of multiple zones. Control
of the zones is provided by connecting a tekmar Zone Control to the
(16 and 17) of the 262. The zone control provides its own internal
In this case, there is no need to provide an external
Boiler Demand
Com
and
10K
terminals
Boiler Demand
to the 262.
as described earlier in
tekmar
Zone Control
Power
Occupied
UnOccupied
Heat Required
Optimum Start / Stop
24 hr. Timer
System Pump
Timer Active
70°F
(21°C)
12 hrs.
Zone 1 / Lo stage /
1
Open / Cooling
• Dial the desired duration
618
of the UnOccupied period.
Zone 2 / Hi stage /
• Press start button at the time of day
2
Close / Ventilation
you want the UnOcc. period to begin.
Zone 3 / Lo stage
Timer Active light turns on.
3
Open
0
24
40
100
Zone 4 / Hi stage
(4)
(38)
UnOccupied
4
Close
UnOccupied
Duration
Zone 5 / Lo stage
5
Start
Open
Zone 6 / Hi stage
6
Close
0 = always Occupied
24 = always UnOccupied
Zone Control 367
One & Two Stage / One Stage & Floating
tekmar
262 Control
Boiler Demand
Vie
DHW Demand
°
F
Setpoint Demand
WWSD
Occ
Minimum
1
Maximum
2
1
Item
Menu
Boiler Control 262
NRTL/C
Two Stage Boiler & DHW / Two Stage DHW
LR 58233
E150539
LR 58223
Section B1. The zone control is capable of automatically adjusting the Boil TRG temperature
to improve building occupant comfort and system performance.
10K SLAB SENSOR (10K = SLAB)
Set the 10K item to SLAB to add a slab sensor for temperature control of a single zone system.
The 262 can use a slab sensor to control the actual slab temperature. A slab sensor is placed
in the slab and connected to the
applied to the
sensor connected, the 262 will limit the supply temperature in order to maintain the slab sensor
Boiler Demand
Com
and the
terminals (1 and 2) as described in Section B1. With the slab
10K
terminals (16 and 17). Power must be
tekmar
Slab Sensor
tekmar
262 Control
Boiler Demand
Vie
DHW Demand
°
F
Setpoint Demand
WWSD
Occ
Minimum
1
Maximum
2
1
Item
Menu
Boiler Control 262
Two Stage Boiler & DHW / Two Stage DHW
NRTL/C
LR 58223
between the SLAB MIN and SLAB MAX settings. This application is available only when
Boil MIN is set to OFF.
Slab Min
(SLAB MIN)
The SLAB MIN sets the minimum allowed core temperature of the slab as long as the control is not in a WWSD. Caution should be
used when adjusting the SLAB MIN setting as this may lead to overheating of the zone during mild conditions. If the AWAY setting
is selected in the
Slab Max
(SLAB MAX)
Schedule
menu, the 262 ignores the SLAB MIN setting.
The SLAB MAX sets the maximum allowed core temperature of the slab. If the slab is to be maintained at a fixed core temperature,
set SLAB MAX and SLAB MIN items to the same setting.
ROOM TEMPERATURE UNIT (RTU) (10K = NONE)
If the system consists of a single zone, temperature control of that zone can be provided by using an RTU. The RTU is connected to
the
Com
and tekmar NetTM
tN1 / tN2
terminals (15 and 16). In addition, power must be applied to the
2) as described in Section B1. With the RTU connected, the 262 measures the actual ROOM temperature. Indoor temperature feedback
fine tunes the supply water temperature in the system to prevent over heating or under heating. The RTU allows the user to adjust the
desired room temperature at the RTU. Remote sensor capability is also available through an RTU. See the Data brochure for the RTU
you are connecting.
Section C —Domestic Hot Water (DHW) and Setpoint (Mode = —1—)
Section C1
General Domestic
Hot Water (DHW)
Operation
Section C2
DHW Priority
Section C3
DHW with Low
Temperature
Boilers
Section C4
Dedicated
DHW
Section C1 —General Domestic Hot Water (DHW) Operation (Mode = —1—)
DHW DEMAND
A
DHW demand
demand from an aquastat or an internal demand from a 10K tekmar sensor. If an external and
internal demand is present simultaneously, the control stops operation of the DHW.
External Demand
The 262 registers an external demand for DHW when a voltage between 24 and 240 V (ac)
is applied across the
or setpoint control is used as a switch in the DHW demand circuit. Once the 262 detects a
DHW demand, the
described below.
Internal Demand
The 262 registers an internal demand for DHW when a sensor is connected across the
and the
indirect DHW tank temperature. When MODE –1– is selected, if the temperature at the DHW
sensor drops 3˚F (1.5˚C) below the DHW TANK setting, the
in the LCD and the control operates as described below.
An advantage to using the DHW sensor is that the control can display the current DHW TANK
temperature and record the highest and lowest DHW TANK temperatures. Also, the 262 can
control the DHW temperature with more accuracy than when using an aquastat.
is generated on the 262 by using one of two methods: either an external DHW
(DHW SENS = NONE)
Com Dem
DHW Demand
and the
pointer turns on in the LCD and the control operates as
(DHW SENS = DHW)
DHW
terminals (19 and 20). The DHW TANK setting is used to set the desired
DHW Dem
terminals (3 and 4). A DHW aquastat
DHW Demand
pointer turns on
Com
24 to 240 V (ac)
Aquastat
DHW
Storage Tank
Pump
P
Com
Dem
Com
3
19
4
DHW
Dem
20
DHW
DHW DEVICE (DHW THRU)
Once the 262 receives a
DHW device selected. The DHW device is selected using the DHW THRU item in the
menu.
DHW Pump
If PUMP is selected as the DHW device, the 262 assumes that the DHW pump provides
adequate flow through both the DHW tank heat exchanger and the boiler(s). To provide heat
to the DHW tank, the 262 closes the
boiler(s) to provide a sufficient boil supply temperature to the DHW tank. If using a primary
loop with the DHW tank piped in primary / secondary, select DHW VALV.
DHW Valve
If VALV is selected as the DHW device and there is a
Boil P1
The 262 operates the boiler(s) to provide a sufficient boiler supply temperature to the DHW tank.
(DHW THRU = PUMP)
(DHW THRU = VALV)
contact (7 and 8). The boiler pump provides flow through the DHW tank’s heat exchanger once the DHW valve is opened.
BOILER TARGET DURING DHW GENERATION (Boil TRG)
The Boil TRG temperature during DHW operation depends on whether an external or internal demand is present. The DHW demand
overrides the reset water temperature.
External Demand
If the control receives a
as the DHW heat exchanger setting (DHW XCHG).
, the sequence of operation depends on the type of
Adjust
P
DHW Pmp / Vlv
contact (9 and 10) and operates the
DHW Demand
, the 262 closes the
DHW Pmp / Vlv
Valve
contact (9 and 10) and the
through an external device such as an aquastat, the Boil TRG temperature is at least as hot
10 of 36
Page 11
Internal Demand
If the control receives a
Boil TRG temperature is at least as hot as the DHW TANK setting plus 40˚F (22˚C).
(DHW SENS = DHW)
DHW demand
from a DHW sensor attached to the
Com Sen
and the
DHW 10K
terminals (19 and 20), the
DHW DURING UNOCCUPIED
The DHW operation during an
that is being used. For this function to operate, the control must have the
External Demand
If an external
period or the control can ignore a call for DHW as long as the control is in an
Internal Demand
If an internal
as long as the control is in an
Away
If the AWAY setting is made in the
the DIP switch =
(Aquastat )
DHW Demand
(Sensor)
DHW Demand
Setback.
UnOccupied
period depends on the type of
is used, the control can either continue operation of the DHW system as it would during the
is used, a DHW TANK
UnOccupied
Schd
mode.
menu, any
Unocc
temperature can be set. This is the temperature that the tank maintains
DHW Demand
Section C2 —DHW Priority (Mode = —1—)
DHW PRIORITY (DHW PRI = BOIL)
It is often desirable to limit or even stop the flow of heat to the heating
system when the DHW tank calls for heat. This allows for a faster recovery
of the DHW tank. If DHW PRI is set to Boil, the boiler pump (P1) is turned
off on a call for DHW. This setting is available only if DHW THRU = PUMP
has been selected as the DHW device. If a valve is used as the DHW
device, DHW priority can not be used. Caution should be taken to ensure
that the flow rate of the DHW pump is adequate for both the DHW tank and
the boiler(s), as this will be the only pump providing flow through the
boiler(s).
DHW demand
Setback / None
that the 262 is receiving and the type of setback
DIP switch set to
Setback.
Occupied
UnOccupied
is ignored and the tank cools off. Note: AWAY does not require
mode.
P
DHW
P1
Sequence, Section C2
DHW PRIORITY OVERRIDE
To prevent the building from cooling off too much or the possibility of a
potential freeze up during DHW priority, the 262 limits the amount of time
for DHW priority. As the outdoor air temperature becomes colder, the
length of time that the 262 provides DHW priority is reduced. Once the
allowed time for priority has elapsed, the 262 overrides the DHW priority
and operates DHW and heating simultaneously.
CONDITIONAL DHW PRIORITY
If the boiler supply temperature is maintained at or above the required
temperature during DHW generation, this indicates that the boiler(s) has
enough capacity for DHW and possibly heating as well. As long as the
boiler supply temperature is maintained near its target, DHW and heating
occurs simultaneously.
DHW POST PURGE
After the
either the DHW pump or the DHW valve and the boiler pump. This purges the residual heat from the boiler(s) into the DHW tank. The
262 continues this purge for a maximum of four minutes or until the boiler supply water temperature drops 20˚F (11˚C) below the DHW
Boil TRG temperature. The 262 also stops the purge if the boiler supply temperature drops below the current Boil TRG temperature.
DHW Demand
DHW MIXING PURGE
After DHW operation, the boiler(s) is extremely hot. At the same time, the heating zones may
have cooled off considerably after being off for a period of time. To avoid thermally shocking
the boiler(s) after DHW priority, the 262 shuts off the boiler(s), but continues to operate the
DHW while restarting the heating system. This allows some of the DHW return water to mix
with the cool return water from the zones and temper the boiler return water.
Increasing Time
DHW priority demand time limit
Increasing Air Temperature
Outdoor air temperature
is removed, the 262 performs a purge on the boiler(s). The 262 shuts off the boiler(s) and continues to operate
Section C3 —DHW with Low Temperature Boilers (Mode = —1—)
If DHW is to be incorporated into a low temperature system such as a
radiant heating system, a mixing device is often installed to isolate the high
DHW supply temperature from the lower system temperature. If a mixing
device is not installed, high temperature water could be supplied to the low
temperature system while trying to satisfy the DHW demand. This may
result in damage to the low temperature heating system. The 262 is capable
of providing DHW in such a system while ensuring that the low temperature
in the heating system does not exceed its allowed maximum setting.
P1
DHW
To prevent high temperature water from being introduced into the heating
system, the boiler pump P1 must be turned off during a call for DHW. To do
this, DHW THRU must be set to PUMP, DHW PRI must be set to Boil and
Boil MIN must be set to OFF.
On a call for DHW, the 262 provides DHW priority by shutting off the boiler pump (P1) for a period of time. This time is based on the
outdoor air temperature as described in the DHW Priority Override section. However, if the
DHW Demand
is not satisfied within the
allotted time, the boiler(s) shuts off and the heat of the boiler is purged into the DHW tank.
Once the boiler supply temperature is sufficiently reduced, the DHW pump shuts off. The heating system is turned on for a period of
time to prevent the building from cooling off. After a period of heating, if the
DHW demand
is still present, the 262 shuts off the heating
system and provides heat to the DHW tank once again.
For correct operation, close attention must be paid to the mechanical layout of the system. When the 262 turns off the boiler pump (P1),
flow to the heating system must stop. If flow is not stopped, the temperature in the heating system can exceed the maximum desired
temperature and can result in damage to the heating system.
P
Section C4 —Dedicated DHW (MODE = —2—)
When MODE —2— is selected in the
for improved response to dedicated DHW loads. Connection of the outdoor sensor is no longer mandatory. If both an external and an
internal demand are used at the same time, the control displays an error message and stops DHW generation.
INTERNAL DEMAND (DHW SENS = DHW)
When the DHW SENS item is set to DHW, the 262 looks for a DHW sensor
on the
Com
and the
DHW
terminals (19 and 20). When the temperature at
the DHW sensor drops 1/2 of the DHW DIFF setting below the desired
temperature, the
DHW Demand
TANK setting is used to set the desired DHW storage tank temperature. An
advantage to using the DHW sensor is that the control is able to display the
current DHW tank temperature as well as recording the highest and lowest
DHW tank temperatures.
DHW DIFFERENTIAL (DHW DIFF)
When using the 262 control in MODE —2— operation, a differential setting that operates 1/2 above and below the DHW TANK is
selectable. A domestic hot water sensor is required (DHW SENS = DHW) to be connected to terminals
differential setting is small, a more precise tank temperature will be maintained, but the boiler(s) may fire more frequently.
DHW DEVICE
While MODE —2— is selected, the
Pump contact may be used to control a recirculation pump. This pump will run continuously when the control is in
off during
UnOccupied
.
Adjust
menu a number of menu and control operations change. The boiler staging logic is modified
pointer turns on in the LCD. The DHW
Boiler Pump
(Boil P1) contact is used to control the flow of heated water to the DHW tank. The DHW
The 262 can handle setpoint loads which are high temperature loads connected to the boiler
loop that are not heating or DHW loads.
SETPOINT DEMAND
The 262 registers a
across the
Setpoint Demand
pump P1. If a setpoint load is used, the installer must make sure that the setpoint device
provides its own flow through the boiler(s).
Com Dem
Setpoint Demand
and the
pointer turns on in the LCD. The
when a voltage between 24 or 240 V (ac) is applied
Setp Dem
terminals (3 and 5). Once voltage is applied, the
Setpoint Demand
does not turn on the boiler
24 to 240 V (ac)
Com
Dem
3
4
DHW
Dem
Setp
Dem
5
BOILER TARGET DURING SETPOINT DEMAND (BOIL TRG)
The Boil TRG temperature during a
long as the 262 has a
SETPOINT SETBACK
Setpoint Demand
If the 262 is placed into setback, the
operates normally. If a system override of AWAY is selected, the 262 operates the SETPOINT load at the
SETPOINT PRIORITY (SETP PRI = BOIL)
Setpoint Demand
.
Setpoint Demand
is increased to at least the SETPOINT setting. This temperature is maintained as
is ignored if the SETPOINT
UnOcc
setting is set to OFF. Otherwise, the setpoint
Occupied
setting.
For setpoint loads to have priority over the boiler zone(s), set SETP PRI to Boil. If this option is chosen, the boiler pump P1 turns off
during a
Setpoint Priority Override
Setpoint Demand.
In order to prevent the building from cooling off too much or the possibility of a potential freeze up during Setpoint Priority, the 262
limits the amount of time for setpoint priority. As the outdoor air temperature becomes colder, the length of time the 262 provides
Setpoint Priority is reduced. Once the allowed time for priority has elapsed, the 262 overrides the
Setpoint Priority
and operates
setpoint and heating simultaneously.
Conditional Setpoint Priority
If the Boil SUP temperature is maintained at or above the required temperature during setpoint generation, this indicates that the
boiler(s) has enough capacity for setpoint and possibly heating as well. As long as the Boil TRG temperature is maintained, setpoint
and heating occur at the same time.
Improper installation and operation of this control could result in damage to the equipment and possibly even personal injury. It is your
responsibility to ensure that this control is safely installed according to all applicable codes and standards. This electronic control is
not intended for use as a primary limit control. Other controls that are intended and certified as safety limits must be placed into the
control circuit.
STEP ONEGETTING READY
Check the contents of this package. If any of the contents listed are missing or damaged, please contact your wholesaler or tekmar sales
representative for assistance.
Type 262 includes:
One Boiler Control 262, One Outdoor Sensor 070, One Universal Sensor 071
Data Brochures D 262, D 070, D 001, User Brochure U 262, Application Brochures A 262,
Essay E 003.
Carefully read the details of the Sequence of Operation to ensure that you have chosen the proper control for your application.
Note:
STEP TWOMOUNTING THE BASE
Remove the control from its base by pressing down on the release clip in the wiring chamber and sliding the control upwards. The base
is then mounted in accordance with the instructions in the Data Brochure D 001.
STEP THREEROUGH-IN WIRING
All electrical wiring terminates in the control base wiring chamber. The base has standard 7/8” (22 mm) knockouts which accept common
wiring hardware and conduit fittings. Before removing the knockouts, check the wiring diagram and select those sections of the chamber
with common voltages. Do not allow the wiring to cross between sections as the wires interfere with safety dividers which should be
installed at a later time.
Power must not be applied to any of the wires during the rough-in wiring stage.
• Install the Outdoor Sensor 070 and Boiler Sensor 071 according to the instructions in the Data Brochure D 070 and run the wiring
back to the control.
• If a DHW Sensor 071 is used, install the DHW Sensor according to the installation instructions in the Data Brochure D 070 and run
the wiring back to the control.
• If a Room Temperature Unit (RTU) 062 or 063 is used, install the RTU according to the installation instructions in the Data Brochure
D 062 and run the wiring back to the control.
• If a Slab Sensor 072 or 073 is used, install the Slab Sensor according to the installation instructions in the Data Brochure D 070
and run the wiring back to the control or RTU.
• If a Remote Display Module (RDM) 040 is used, install the RDM according to the installation instructions in the Data Brochure
D 040 and run the wiring back to the control.
• If a tekmar Zone Control is used, run the wires from the Zone Control to the 262. Refer to the instructions supplied with the Zone
Control.
• Run wire from other system components (pumps, boilers, etc.) to the control.
• Run wires from the 120 V (ac) power to the control. Use a clean power source to ensure proper operation. Multi-strand 16 AWG
wire is recommended for all 120 V (ac) wiring due to its superior flexibility and ease of installation into the terminals.
• 120 V (ac) to be provided from a 15 A circuit breaker and must have a circuit disconnect installed.
• Connect ground wires to ground bus bar in wiring area.
STEP FOURELECTRICAL CONNECTIONS TO THE CONTROL
The installer should test to confirm that no voltage is present at any of the wires. Push the control into the base and slide it down until
it snaps firmly into place.
Powered Input Connections
120 V (ac) Power
Connect the 120 V (ac) power supply to the
Power N
This connection provides power to the microprocessor and display of the control. As well,
this connection provides power to the
To generate a Boiler Demand, a voltage between 24 V (ac) and 240 V (ac) must be
applied across the
Boiler Demand
terminals (1 and 2).
2
1
Boiler
Demand
DHW Demand
To generate a DHW Demand, a voltage between 24 V (ac) and 240 V (ac) must be applied
across the
Com Dem
and the
DHW Dem
terminals (3 and 4).
Setpoint Demand
To generate a Setpoint Demand, a voltage between 24 V (ac) and 240 V (ac) must be
applied across the
Com Dem
and the
Setp Dem
terminals (3 and 5).
Caution: The same power supply must be used for both the DHW demand and setpoint
demand circuits since they share the
Output Connections
Com Dem
terminals.
Boiler Pump Contact (Boil P1)
The boiler pump output terminal (8) on the 262 is a powered output. When the relay
contact in the 262 closes, 120 V (ac) line (L) is provided to the
the
Power L
terminal (7). To operate the boiler pump, connect one side of the boiler pump
circuit to terminal 8 and the second side of the pump circuit to the neutral (N) side of the
120 V (ac) power supply.
Boil P1
terminal (8) from
24 to 240 V (ac)
24 to 240 V (ac)
24 to 240 V (ac)
L
N
120 V (ac)
Com
Dem
N
Com
Dem
3
DHW
Dem
6
Power
3
L
4
7
4
DHW
Dem
Setp
Dem
Boil
P1
5
8
DHW Pump / Valve Contact
The
DHW Pump / Valve
terminals (9 and 10) are an isolated output in the 262. There is
no power available on these terminals from the control. These terminals are to be used
as a switch to either make or break power to the DHW pump or the DHW valve. Since
this is an isolated contact, it may switch a voltage between 24 V (ac) and 240 V (ac).
Boiler Contacts
The
Stage 1
and
Stage 2
terminals (11, 12 and 13, 14) are isolated outputs in the 262.
There is no power available on these terminals from the control. These terminals are to
be used as a switch to either make or break the boiler circuit. When the 262 requires the
boiler(s) to fire, it closes the contact between terminals 11 and 12 and/or 13 and 14.
Sensor and Unpowered Input Connections
Do not apply power to these terminals as this damages the control.
Outdoor Sensor
Connect the two wires from the Outdoor Sensor 070 to the
Out
terminals (19 and 22). The Outdoor Sensor is used by the 262 to
measure the outdoor air temperature.
Com
and
Com
Boiler Sensor
Connect the two wires from the Boiler Sensor 071 to the
terminals (19 and 21). The Boiler Sensor is used by the 262 to
measure the supply (outlet) water temperature from the boiler(s).
Connect the two wires from the DHW Sensor 071 to the
terminals (19 and 20). The DHW Sensor is used by the 262 to measure
the DHW tank temperature.
Com
and
DHW
10K Sensor
Either an Indoor Sensor, Slab Sensor, or Zone Control may be
connected to the
from the sensor to the
10K
input. If a sensor is used, connect the two wires
Com
and
10K
terminals (16 and 17).
Zone Control Input
If an external tekmar Zone Control is used, connect the wire from the
Com Sen
262. Connect the
terminal on the Zone Control to the
Zo Out
terminal on the Zone Control to the
Com
terminal (16) on the
terminal (17) on the 262.
Note: The wires from the Zone Control are polarity sensitive. The
communication does not operate correctly if the wires are reversed.
tekmar NetTM Device (tN1 / tN2)
A Room Temperature Unit (RTU) 062 or 063, or a Remote Display
Module (RDM) 040 may be connected to the
input. Connect the
Com
terminal (16) on the 262. Connect the
Com
terminal from the appropriate device to the
terminal from the appropriate device to the
terminal (15) on the 262.
Note: The wires from the RTU and the RDM are polarity sensitive. The
tekmar NetTM tN1 / tN2 device does not operate correctly if the wires
are reversed.
tekmar NetTM tN1 / tN2
tekmar NetTM tN1
or
tekmar NetTM tN1 / tN2
10K
tN2
19
20
Com
DHW
16
17
10K
Com
tekmar 262
16
17
10K
Com
View
°
F
UnOcc 1
Heat
ItemMenu
Zone Control
Com
Zo
Sen
Out
15
16
tN1 /
Com
tN2
UnOccupied Switch
If an external timer (tekmar Timer 032) or switch is used, connect the
two wires from the external switch to the
Com
and
UnO Sw
terminals
16
Com
17
10K
18
UnO
Sw
(16 and 18). When these two terminals are shorted together, the
control registers an UnOccupied signal.
Note: The setback override in the schedule menu of the control
overrides any external signal that is present at the UnOccupied Switch
Timer Switch
terminals.
STEP FIVE
Each terminal block
TESTING THE WIRING
must be unplugged
from its header on the control before power is applied for testing. To remove the terminal block,
pull straight down from the control.
The following tests are to be performed using standard testing practices and procedures and should only be carried out by properly
trained and experienced persons.
20
A good quality electrical test meter, capable of reading from at least 0 - 300
V (ac) and at least 0 - 2,000,000 Ohms, is essential to properly test the
wiring and sensors.
Test the Sensors
19
Com
Ω
Ω
V
DHW
Boil
22
21
Out
In order to test the sensors, the actual temperature at each sensor
location must be measured. A good quality digital thermometer with a
surface temperature probe is recommended for ease of use and accuracy.
Where a digital thermometer is not available, a spare sensor can be
strapped alongside the one to be tested and the readings compared. Test
the sensors according to the instructions in the Data Brochure D 070.
Make sure exposed wires and bare terminals are not in contact with other
wires or grounded surfaces. Turn on the power and measure the voltage
between the N and L terminals (6 and 7) using an AC voltmeter, the
reading should be between 108 and 132 V (ac).
7
6
Power
L
V
Ω
V
N
108 to 132 V (ac)
Test the Powered Inputs
Boiler Demand
If a
Boiler Demand
Demand
terminals (1 and 2). When the
heat, you should measure between 20 and 260 V (ac) at the terminals.
When the
Boiler Demand
is used, measure the voltage between the
Boiler Demand
device calls for
device is off, you should measure less than
Boiler
V
5 V (ac).
DHW Demand
If a
DHW Demand
Dem
and the
is used, measure the voltage between the
Com Dem
terminals (3 and 4). When the
DHW
DHW Demand
device calls for heat, you should measure between 20 and 260 V (ac)
at the terminals. When the
DHW Demand
device is off, you should
measure less than 5 V (ac).
Setpoint Demand
If a
Setpoint Demand
Dem
and the
Demand
device calls for heat, you should measure between 20 and
260 V (ac) at the terminals. When the
is used, measure the voltage between the
Com Dem
terminals (3 and 5). When the
Setpoint Demand
Setp
Setpoint
device is off,
V
you should measure less than 5 V (ac).
Testing the Outputs
Boiler Pump (Boil P1)
If a boiler pump is connected to the
terminal block is off and install a jumper between the
(7 and 8). When power is applied to the
boiler pump should start. If the pump does not turn on, check the wiring between the
terminal block and pump and refer to any installation or troubleshooting information
supplied with the pump. If the pump operates properly, disconnect the power and remove
the jumper.
Boil P1
terminal (8), make sure that power to the
Power N
Power L
and
Power L
and the
Boil P1
terminals (6 and 7), the
V
Ω
V
Ω
terminals
Com
Dem
L
120 V (ac)
N
3
DHW
Dem
1
Boiler
Demand
4
5
Setp
Dem
2
20 to 260 V (ac)
20 to 260 V (ac)
6
Power
N
8
7
Boil
L
P1
10
DHW Pump OR Valve (DHW Pmp/Vlv)
If a DHW pump or DHW valve is connected to the
make sure the power to the pump or valve circuit is off and install a jumper between those
terminals. When the DHW circuit is powered up, the DHW pump should turn on or the
DHW Pmp / Vlv
terminals (9 and 10),
M
or
9
DHW
Pmp/Vlv
DHW valve should open completely. If the DHW pump or valve fails to operate, check the
wiring between the terminals and the pump or valve and refer to any installation or
troubleshooting information supplied with these devices. If the DHW pump or valve
24 to 240 V (ac)
operates correctly, disconnect the power and remove the jumper.
Stage 1 and 2
If the boiler is connected to the
circuit is off and install a jumper between the terminals. When the boiler circuit is powered up, the boiler should fire. If the boiler does
not turn on, refer to any installation or troubleshooting information supplied with the boiler. (The boiler may have a flow switch that
prevents firing until the boiler pump (P1) is running.) If the boiler operates properly, disconnect the power and remove the jumper.
Stage 1
terminals (11 and 12) and/or
17 of 36
Stage 2
terminals (13 and 14), make sure power to the boiler
Make sure all power to the devices and terminal blocks is off and remove any
remaining jumpers from the terminals.
Reconnect the terminal blocks to the control by carefully aligning them with their respective
headers on the control and then pushing the terminal blocks into the headers. The terminal
blocks should snap firmly into place.
Install the supplied safety dividers between the unpowered sensor inputs and the powered
120 V (ac) or 24 V (ac) wiring chambers.
Apply power to the control. The operation of the control on power up is described in the
Sequence of Operation section of this brochure.
DIP Switch Settings
The DIP Switch settings on the control are very important and should be set
to the appropriate settings prior to making any adjustments to the control
through the User Interface. The DIP switch settings change the items that
are available to be viewed and/ or adjusted in the User Interface.
If a DIP switch is changed while the control is powered up, the control
responds to the change in setting by returning the display to the View menu.
This is true for all of the DIP switches except for the
DIP switch.
Lock / Unlock
Setback
None
7
6
Boil
Power
P1
L
N
Reset Ratio
Characterized
Heating Curve
8
10
9
DHW
Pmp/Vlv
LOCK / UNLOCK (FACTORYSETTINGISUNLOCK)
The
Lock / Unlock
DIP switch is used to lock and unlock the access level of the control and tekmar NetTM tN1/tN2 device. Once locked,
access levels cannot be changed. To determine if the control is currently locked or unlocked, a small segment representing a padlock
is viewed in the bottom right hand corner of the display. When the padlock is closed, the access level cannot be changed.
To change the access level, set the DIP switch to the
tN1/tN2 device is viewed in its Miscellaneous (
Unlocked
Misc
) menu. While viewing the access level, use the up and down keys to select between
, or down position. The current access level of the control or tekmar Net
the Limited (LTD), User (USER), Installer (INST), or Advanced (ADV) access levels.
To lock the access level, select the appropriate access level in the Miscellaneous (
Unlocked
Net
SETBACK / NONE (FACTORYSETTINGISNONE)
The
position to the
TM
tN1/tN2 device can no longer be viewed or adjusted in its Miscellaneous (
Locked
position. As long as the DIP switch is in the
Setback / None
DIP switch enables and disables the setback functions of the control. When the DIP switch is set to the
Locked
down position, the control ignores any external setback signal, and its user interface does not display the
When the DIP switch is set to the
setback signal generated on the
Setback
UnO Sw
position, the setback features in the control are enabled. The control responds to an external
terminal.
CHARACTERIZED HEATING CURVE / RESET RATIO (FACTORYSETTOCHARACTERIZEDHEATINGCURVE)
The
Characterized Heating Curve / Reset Ratio
switch is set to the
Characterized Heating Curve
DIP switch determines the type of Outdoor Reset that the control uses. When the DIP
setting, the control uses an Outdoor Reset method that matches the heating
Misc
) menu and move the DIP switch from the
position, the access level of the control or tekmar
Misc
) menu.
None
UnOccupied
adjustments.
characteristics of the type of terminal unit that is being used. See Sequence Of Operation, Section B for a description of terminal units.
When this setting is used, a desired indoor air setting, design outdoor setting and a design supply setting must be entered into the control.
TM
or
When the DIP switch is set to the
Reset Ratio
setting, the control uses an Outdoor Reset method that varies the supply setting based
only on the outdoor air temperature. When this setting is used, the Boil STRT temperature and OUT STRT temperature determines the
beginning point of the reset ratio. The design supply setting and the design outdoor setting determines the ending point of the reset ratio.
All temperatures between these two points fall on a straight line connecting these points.
Important: Once the control is programmed, this DIP switch should not be adjusted as the settings may change.
The tekmar Boiler Control 262 comes with four Access Level settings.
These Access Levels restrict the number of Menus, Items, and Adjustments
that can be accessed by the user. The four access levels are Limited (LTD),
User (USER), Installer (INST) and Advanced (ADV).
The access level of the control is found in the Miscellaneous (
when the
Advanced access level, all of the control settings are available to the user.
In the User access level, only a few of the menus and items are available.
The Limited access level is the most restricted of them all. The control’s
factory setting is Installer (INST). This access level is sufficient for the set
up of the control. Once the control is set up, the appropriate access level
should be selected for the people that deal with the control on a regular
basis.
The units of measure that all of the temperatures are to be
• • •
• • •
• • • •
displayed in by the control.
The operating mode for the back lighting on the LCD as well
as the time of keypad inactivity until the control automatically
returns to the default display.
(
BACKLITE = OFF
BACKLITE = 30 sec
BACKLITE = ON (returns after 90 seconds)
The access level that is to be used by the control.
DIP switch =
returns after 10 seconds)
(returns after 30 seconds)
Unlock
Room Temperature Units (RTUs) 062 and 063
View
°
F
UnOcc 1
Heat
ItemMenu
A single RTU may be connected to the Boiler Control 262 in order to provide the control with indoor
temperature feedback for the heating system in Mode = —1— (Refer to Essay E 002). When using an RTU,
several items related to the heating system are no longer available in the control’s User Interface. These
items are available only in the RTU’s User Interface. Also, the number of items that are available on the
RTU depends on the type of RTU that is connected to the control.
The Boiler Control 262 has a built in test routine which is used to test the main control functions.
The 262 continually monitors the sensors and displays an error message whenever a fault is
found. See the following pages for a list of the 262’s error messages and possible causes.
When the
are tested in the following test sequence.
TEST SEQUENCE
Each step in the test sequence lasts 10 seconds.
During the test routine, the test sequence is paused by pressing the
well as the word PAUS. If the
test routine. If the test sequence is paused, the
to rapidly advance through the test sequence. To reach the desired step, repeatedly press and release the
appropriate device and segment in the display turn on.
Step 1
Test
button is pressed, the
- The boiler pump
NOTE:
Only if there is a boiler demand can the control be paused in step 1.
Test
light is turned on. The individual outputs and relays
Test
button. While paused, the control displays the testing step as
Test
button is not pressed again for 5 minutes while the test sequence is paused, the control exits the entire
Test
button can be pressed again to advance to the next step. This can also be used
(Boil P1)
is turned on for 10 seconds.
Test
ADV, INST, USER, LTD
Default = INST
off
not testing
red
testing
red
testing paused
Test
button until the
Step 2
- The zccontact is turned on for 10 seconds.
NOTE:
Only if there is a boiler demand can the control be paused in step 2.
contact is turned on for 10 seconds. After 10 seconds, the
Only if there is a boiler demand can the control be paused in step 3.
Stage 1, Stage 2
and
Boil P1
contacts are shut off.
Step 4
Step 5
MAX HEAT (MAX HEAT)
The Boiler Control 262 has a function called
temperatures as long as there is a demand for heat. The control continues to operate in this mode for up to 24 hours or until either the
Item, Menu or Test button is pressed. This mode may be used for running all circulators during system start-up in order to purge air from
the piping. To enable the Max Heat feature, use the following procedure.
1) Press and hold the
2) Using the Up or Down buttons, select the word YES. After 3 seconds, the control flashes
- MODE —1—
If a DHW Pump is selected as the DHW device, the
If a DHW Valve is selected as the DHW device, the
are then shut off.
If NONE is selected as the DHW device, N/A is displayed for 1 second.
- MODE —2—
The
DHW Pmp / Vlv
NOTE:
Only if there is a
- After the test sequence is completed, the word COMPLETE is displayed for 1 second and the control resumes its
normal operation.
contact is turned on for 10 seconds and is then shut off.
DHW demand
can the control be paused in step 4.
DHW Pmp / Vlv
DHW Pmp / Vlv
contact is turned on for 10 seconds and is then shut off.
and
Boil P1
contacts are turned on for 10 seconds and
Max Heat
Test
button for more than 3 seconds. At this point, the control displays
the words MAX HEAT and the word NO.
the word MANUAL and Boil MAX is the target boiler supply water temperature.
. In this mode, the 262 turns on and operates the system up to the maximum set
Item
Menu
3) To cancel the
4) Once the
normal operation.
Max Heat
Max Heat
mode, press either the
mode has either ended or is cancelled, the control resumes
Item, Menu, or Test
button.
Menu
Item
or
Troubleshooting
When troubleshooting any heating system, it is always a good idea to establish a set routine to follow. By following a consistent routine,
many hours of potential headaches can be avoided. xxcBelow is an example of a sequence that can be used when diagnosing or
troubleshooting problems in a hydronic heating system.
Establish the problem. Get as much information from the customer as possible about the problem.
Establish the
Problem
Understand the
Sequence of
Operation
Is there too much heat, not enough heat, or no heat? Is the problem only in one particular zone or area
of the building or does the problem affect the entire system? Is this a consistent problem or only
intermittent? How long has the problem existed for? This information is critical in correctly diagnosing
the problem.
Understand the sequence of operation of the system. If a particular zone is not receiving enough heat,
which pumps or valves in the system must operate in order to deliver heat to the affected zone? If the
zone is receiving too much heat, which pumps, valves or check valves must operate in order to stop
the delivery of heat?
Press the Test button on the control and follow the control through the test sequence as described
in the Testing section. Pause the control as necessary to ensure that the correct device is operating
as it should.
28 of 36
Page 29
Sketch the
Piping in the
System
Document the
Control
Isolate the
Problem
Sketch the piping of the system. This is a relatively simple step that tends to be overlooked,
however it can often save hours of time in troubleshooting a system. Note flow directions in the
system paying close attention to the location of pumps, check valves, pressure bypass valves
and mixing valves. Ensure correct flow direction on all pumps. This is also a very useful step if
additional assistance is required.
Document the control for future reference. Before making any adjustments to the control, note
down all of the items that the control is currently displaying. This includes items such as error
messages, current temperatures and settings, and which devices should be operating as
indicated by the LCD. This information is an essential step if additional assistance is required
to diagnose the problem.
Isolate the problem between the control and the system. Now that the sequence of operation is
known and the system is sketched, is the control operating the proper pumps and valves at the
correct times? Is the control receiving the correct signals from the system as to when it should
be operating? Are the proper items selected in the menus of the control for the device that is to
be operated?
Test the Contacts
Voltages &
Sensors
Monitor the
System
Test the contacts, voltages and sensors. Using a multimeter, ensure that the control is receiving
adequate voltage to the power terminals and the demand terminals as noted in the technical
data. Use the multimeter to determine if the internal contacts on the control are opening and
closing correctly. Follow the instructions in the Testing the Wiring section to simulate closed
contacts on the terminal blocks as required. Test the sensors and their wiring as described in
the sensor Data Brochures.
Monitor the system over a period of time. Select the applicable items in the Monitor menu of
the control and reset them to zero. Allow the system and the control to operate over a known
period of time and then record the Monitor items. Use this information to help diagnose any
remaining problems.
262 Monitor Menu (1 of 3)
Note
: To clear the recorded information in the specific
Access
Level
Item
field, press and hold and .
DescriptionItem Field
Range
LTD
Section
USER
• • • •
• • • •
INST
• •
ADV
The highest recorded outdoor air temperature since this item
was last cleared. This can be used to diagnose if the Outdoor
Sensor 070 has been located correctly. If this reading is too
high, the 070 may be located in an area that receives direct
sunlight or is influenced by an exhaust vent. MODE = —1—
The lowest recorded outdoor air temperature since this item
was last cleared. This can be used to diagnose if the Outdoor
Sensor 070 has been located correctly. If this reading is too
high, there may not be adequate insulation behind the 070, or
there may be an exhaust vent nearby. MODE = —1—
The total number of running hours for Stage 1 since this item
was last cleared. This total time does not include the FIRE DLY
time set in the Adjust menu.
: To clear the recorded information in the specific
LTD
Section
USER
INST
Item
field, press and hold and .
Access
Level
DescriptionItem Field
ADV
The total number of firing cycles that Stage 1 has had since
this item was last cleared. This item can be used in conjunction
with the B1 FIRE item to determine the average cycle length
•
of Stage 1. If the cycle length is too short, a longer differential
may allow a longer cycle length.
Range
0 - 9999
• •
•
• •
• •
• •
• • •
The total number of running hours for Stage 2 since this item
was last cleared. This total time does not include the FIRE DLY
time set in the Adjust menu.
The total number of firing cycles that Stage 2 has had since
this item was last cleared. This item can be used in conjunction
with the B2 FIRE item to determine the average cycle length
of Stage 2.
The highest temperature recorded at the boiler sensor since
this item was last cleared.
The lowest temperature recorded at the boiler sensor since
this item was last cleared.
The total number of Boiler Pump (P1) running hours since
this item was last cleared.
The highest recorded temperature of the indirect Domestic
Hot Water tank since this item was last cleared.
The lowest recorded temperature of the indirect Domestic Hot
Water tank since this item was last cleared.
DHW SENS = DHW
The total number of DHW pump or valve running hours since
this item was last cleared.
DHW THRU ≠ NONEMODE = —1—
This item is an adjustable warning. If a DHW demand exists
continually for longer than this warning setting, the control will
display a warning message.
DHW THRU ≠ NONE
30 of 36
0 to 255˚F
(-18 to 124˚C)
0 to 9999 hr
0:10 to 20:00 hr,
OFF
Default = OFF
Page 31
262 Monitor Menu (3 of 3)
Note
: To clear the recorded information in the specific
LTD
Section
USER
INST
Item
field, press and hold and .
Access
Level
DescriptionItem Field
ADV
This item is an adjustable warning. If the air temperature
measured by the indoor air sensor exceeds this setting, the
control will display a warning message.
•
10K = INDR
MODE = —1—
Range
50 to 150˚F
(10 to 66˚C)
Default = 110°F (43°C)
This item is an adjustable warning. If the air temperature
measured by the indoor air sensor drops below this setting,
the control will display a warning message.
•
10K = INDR
MODE = —1—
This item is an adjustable warning. If the boiler supply water
temperature does not begin to increase within the set time,
•
the control displays a warning message.
The number of times that the microprocessor in the control
has had to reset itself since this item was last cleared. The
control will reset itself if it has experienced some form of
interference that has disrupted its operation. This can be used
•
to give an indication of the quality of the electrical environment
that the control has been installed in.
The number of times that the control has been powered up
since this item was last cleared. This number will increase if
there is a lowering of the input voltage beyond the control’s
•
usable range. This item can be used as an indication of the
quality of the power source.
The number of times that a communication error has been
detected between the control and either an RTU or RDM since
this item was last cleared. If the wires between the control and
the RTU or RDM are run in a noisy electrical environment,
•
this can cause interference in communication between the
control and the RTU or RDM.
MODE = —1—
0 to 80˚F
(-18 to 27˚C)
Default = 45°F (7°C)
3 to 40 min, OFF
Default = OFF
0 - 255
0 - 255
0 - 255
262 Error Messages (1 of 4)
Error DisplayedDescription of Error
The control was unable to store a piece of information into its EEPROM. This error can be caused by
a noisy power source. The control will display the error message and will continue to operate as normal.
Pressing either the Menu or Item button will clear this error.
The control was unable to read a piece of information stored in the Adjust menu. Because of this, the
control was required to load the factory settings into all of the items in the Adjust menu. The control
will stop operation until all of the items available in the Adjust menu of the control have been checked
by the user or installer.
The control was unable to read a piece of information stored in the Monitor menu. Because of this,
the control was required to load the factory settings into all of the items in the Monitor menu. The
control will continue to display the error message until all of the items available in the Monitor menu
of the control have been checked by the user or installer.
clear the error.
Note:
Access level must be ADV in order to clear the error.
The control was unable to read a piece of information stored in the Schedule menu. Because of this,
the control was required to load the factory settings into all of the items in the Schedule menu. The
control will continue to display the error message until all of the items available in the Schedule menu
of the control have been checked by the user or installer.
clear the error.
The control was unable to read a piece of information stored in the Miscellaneous menu. Because of
this, the control was required to load the factory settings into all of the items in the Miscellaneous
menu. The control will continue to display the error message until all of the items available in the
Miscellaneous menu of the control have been checked by the user or installer.
be ADV in order to clear the error.
The RTU was unable to store a piece of information to the EEPROM. This error can be caused by a
noisy power source to the control. The control will display the error message and will continue to
operate as normal. Pressing either the Menu or Item button will clear this error.
The RTU was unable to read a piece of information stored in the Adjust menu. Because of this, the
control was required to load the factory settings into all of the items in the Adjust menu. The control
will operate based on the
in the Adjust menu of the RTU have been checked by the user or installer.
be ADV in order to clear the error.
The RTU was unable to read a piece of information stored in the Monitor menu. Because of this, the
control was required to load the factory settings into all of the items in the Monitor menu. The control
will continue to display the error message until all of the items available in the Monitor menu of the
RTU have been checked by the user or installer.
the error.
Characterized Heating Curve
Note:
rorrE fo noitpircseDdeyalpsiD rorrE
Note:
Access level must be ADV in order to
Note:
Access level must
settings only until all of the items available
Access level must be ADV in order to clear
Note:
Access level must
The RTU was unable to read a piece of information stored in the Schedule menu. Because of this,
the control was required to load the factory settings into all of the items in the Schedule menu. The
control will continue to display the error message until all of the items available in the Schedule menu
of the RTU have been checked by the user or installer.
Note:
Access level must be ADV in order to
clear the error.
The RTU was unable to read a piece of information stored in the Miscellaneous menu. Because of
this, the control was required to load the factory settings into all of the items in the Miscellaneous
menu. The control will continue to display the error message until all of the items available in the
Miscellaneous menu of the RTU have been checked by the user or installer.
Note:
Access level must
be ADV in order to clear the error.
An incorrect device has been connected to the tekmar Net
been connected to the control and either the
Reset Ratio
or the control is in Mode —2—. Once the problem has been corrected, press either the
Heating Curve/Reset Ratio
TM
tN1/tN2 input terminal. An RTU has
DIP switch has been set to
Menu or Item button to clear the error message from the control.
A short circuit has been read between the tekmar Net
TM
tN1 / tN2 terminal and a Com terminal on the
control. Either the wires leading to the tekmar NetTM tN1 / tN2 device are shorted or the polarity of
the wires is reversed. Determine the cause and remove the short. The error message can be cleared
by pressing either the Menu or Item button.
The control is no longer able to read the information that is coming from the RTU. Reconnect the RTU
and press either the Menu or Item button to clear the error. If the RTU has been deliberately disconnected
from the control, remove power from the control for 10 seconds and then repower the control in order
to clear the error message.
The control is no longer able to read the Outdoor sensor due to a short circuit. In this case the control
assumes an outdoor temperature of 32˚F (0˚C) and continues operation. Locate and repair the problem
as described in the Data Brochure D 070. To clear the error message from the control after the sensor
has been repaired, press either the Menu or Item button.
The control is no longer able to read the Outdoor sensor due to an open circuit. In this case the control
assumes an outdoor temperature of 32˚F (0˚C) and continues operation. Locate and repair the problem
as described in the Data Brochure D 070. To clear the error message from the control after the sensor
has been repaired, press either the Menu or Item button.
The control is no longer able to read the Boiler Supply sensor due to a short circuit. The control will
not operate the boiler contacts. Locate and repair the problem as described in the Data Brochure
D 070. To clear the error message from the control after the sensor has been repaired, press either
the Menu or Item button.
The control is no longer able to read the Boiler Supply sensor due to an open circuit. The control will
not operate the boiler contact. Locate and repair the problem as described in the Data Brochure
D 070. To clear the error message from the control after the sensor has been repaired, press either
the Menu or Item button.
The control is no longer able to read the 10K input because of a short circuit. The control will continue
to operate as if there was nothing connected to the 10K input. To clear the error message from the
control after the sensor has been repaired, press either the Menu or Item button.
The control is no longer able to read the 10K input because of an open circuit. The control will continue
to operate as if there was nothing connected to the 10K input. Locate and repair the problem as
described in the Data Brochure D 070. To clear the error message from the control after the sensor
has been repaired, press either the Menu or Item button. If the 10K terminal was deliberately left
unused, set the 10K item to NONE.
The control is not able to read the DHW sensor because of a short circuit. The control does not operate
the DHW while the DHW sensor is shorted. Locate and repair the problem as described in the Data
Brochure D 070. To clear the error message from the control after the sensor has been repaired, press
either the Menu or Item button.
The control is not able to read the DHW sensor because of an open circuit. The control does not
operate the DHW while the DHW sensor is open circuit. Locate and repair the problem as described
in the Data Brochure D 070. If a DHW sensor was deliberately not installed, set the DHW SENS item
to NONE. To clear the error message from the control after the sensor has been repaired, press either
the Menu or Item button.
The air sensor in the RTU is being read as a short circuit. The RTU will continue operation using all
remaining sensors. If all of the sensors are unavailable, the control will continue to operate as if the
RTU was not connected to the control. This error message can be cleared once the sensor has been
repaired. To clear the error message from the control, press either the Menu or Item button.
The air sensor in the RTU is being read as an open circuit. The RTU will continue operation using all
remaining sensors. If all of the sensors are unavailable, the control will continue to operate as if the
RTU was not connected to the control. This error message can be cleared once the sensor has been
repaired. To clear the error message from the control, press either the Menu or Item button.
The Remote Sensor 1 attached to the RTU is being read as a short circuit. The RTU will continue
operation using all remaining sensors. If all of the sensors are unavailable, the control will continue
to operate as if the RTU was not connected to the control. This error message can be cleared once
the sensor has been repaired. Locate and repair the problem as described in the Data Brochure D 070.
To clear the error message from the control, press either the Menu or Item button. REM 1 ≠ NONE
The Remote Sensor 1 attached to the RTU is being read as an open circuit. The RTU will continue
operation using all remaining sensors. If all of the sensors are unavailable, the control will continue
to operate as if the RTU was not connected to the control. This error message can be cleared once
the sensor has been repaired. Locate and repair the problem as described in the Data Brochure D 070.
To clear the error message from the control, press either the Menu or Item button. REM 1 ≠ NONE
The Remote Sensor 2 attached to the RTU is being read as a short circuit. The RTU will continue
operation using all remaining sensors. If all of the sensors are unavailable, the control will continue
to operate as if the RTU was not connected to the control. This error message can be cleared once
the sensor has been repaired. Locate and repair the problem as described in the Data Brochure D 070.
To clear the error message from the control, press either the Menu or Item button. REM 2 ≠ NONE
The Remote Sensor 2 attached to the RTU is being read as an open circuit. The RTU will continue
operation using all remaining sensors. If all of the sensors are unavailable, the control will continue
to operate as if the RTU was not connected to the control. This error message can be cleared once
the sensor has been repaired. Locate and repair the problem as described in the Data Brochure D 070.
To clear the error message from the control, press either the Menu or Item button. REM 2 ≠ NONE
The Remote Sensor 3 attached to the RTU is being read as a short circuit. The RTU will continue
operation using all remaining sensors. If all of the sensors are unavailable, the control will continue
to operate as if the RTU was not connected to the control. This error message can be cleared once
the sensor has been repaired. Locate and repair the problem as described in the Data Brochure D 070.
To clear the error message from the control, press either the Menu or Item button. REM 3 ≠ NONE
The Remote Sensor 3 attached to the RTU is being read as an open circuit. The RTU will continue
operation using all remaining sensors. If all of the sensors are unavailable, the control will continue
to operate as if the RTU was not connected to the control. This error message can be cleared once
the sensor has been repaired. Locate and repair the problem as described in the Data Brochure D 070.
To clear the error message from the control, press either the Menu or Item button. REM 3 ≠ NONE
This error message is displayed if an external DHW demand (aquastat) and an internal demand
(sensor) are received at the same time. As long as this error exists, the control does not provide DHW
operation. Locate and repair the problem. To clear the error message from the control after the error
has been repaired, press either the Menu or Item button.
This warning message is displayed if a DHW demand exists continually for longer than the DHW LONG
setting in the Monitor Menu. If DHW priority is set, the DHW priority is overriden. To clear this warning,
press either the Menu or Item button.
This warning message will be displayed if the air temperature sensed by an indoor air sensor exceeds
the setting of the ROOM HOT item in the Monitor menu. The control will continue to operate as normal
with this warning. To clear this warning, press either the Menu or Item button.
This warning message will be displayed if the air temperature sensed by an indoor air sensor is below
the setting of the ROOM CLD item in the Monitor menu. The control will continue to operate as normal
with this warning. To clear this warning, press either the Menu or Item button.
This warning message will be displayed if the boiler supply does not increase to the target temperature
within a set time. The time limit is set using the NO HEAT item in the Monitor menu. To clear this
warning, press either the Menu or Item button.
Literature— D 262, A 262’s, D 001, D 070, E 003, U 262.
Control— Microprocessor PID control; This is not a safety (limit) control.
Packaged weight— 4 lb. (1810 g), Enclosure A, blue PVC plastic
Dimensions— 6-5/8” H x 7-9/16” W x 2-13/16” D (170 x 193 x 72 mm)
Approvals— CSA C US, CSA/UL 61010-1, meets Class B: ICES & FCC Part 15
Ambient conditions— Indoor use only, 36 to 104°F (2 to 40°C)
Setback
RH ≤80% to 88°F (31°C), down to 50% above 88°F (31°C)
Altitude <6560 ft (2000 m)
Installation Category II, Pollution Degree 2
Power supply— 115 V ± 10%, 60 Hz, 900 VA
(ac)
Relays— 230 V (ac) 7.5 A 1/3 hp, pilot duty 240 VA
Demands— 20 to 260 V (ac) 2 VA
Sensors included— NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892
Made in Canada by
tekmar Control Systems Ltd.
tektra 929-03
Power115 V ±10% 60 Hz 900 VA
Relays 230 V (ac) 7.5 A 1/3 hp, pilot duty 240 VA
Demands 20 to 260 V (ac) 2 VA
Signal wiring must be rated at least 300 V.
Wiring must be rated 194°F (90°C) minimum
15
tN1/
tN2
off
not testing
red
testing
red
testing paused
For maximum heat,
press and hold
Test
button for 3 seconds.
Meets Class B:
Canadian ICES
FCC Part 15
The installer must ensure that this control and its wiring are isolated and/or shielded from strong sources of electromagnetic noise.
Conversely, this Class B digital apparatus complies with Part 15 of the FCC Rules and meets all requirements of the Canadian
Interference-Causing Equipment Regulations. However, if this control does cause harmful interference to radio or television reception,
which is determined by turning the control off and on, the user is encouraged to try to correct the interference by reorienting or relocating
the receiving antenna, relocating the receiver with respect to this control, and/or connecting the control to a different circuit from that
to which the receiver is connected.
Cet appareil numérique de la classe B respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Date Code
H1109F
Caution The nonmetallic enclosure does not provide grounding between conduit connections. Use grounding type bushings and jumper
wires.
Attention Un boîtier nonmétallique n’assure pas la continuité électrique des conduits. Utiliser des manchons ou des fils de accord
spécialement conçus pour la mise á la terre.
Limited Warranty and Product Return Procedure
Limited Warranty The liability of tekmar Control Systems Ltd. and tekmar
Control Systems, Inc. (“tekmar”) under this warranty is limited. The purchaser,
by taking receipt of the tekmar product (“product”), acknowledges receipt of
the terms of the warranty and acknowledges that it has read and
understands same.
tekmar warrants each tekmar product against defects in workmanship and materials, if the product is installed and used in compliance with tekmar's instructions. The
warranty period is for a period of twenty-four (24) months from the production date
if the product is not installed during that period, or twelve (12) months from the
documented date of installation if installed within twenty-four (24) months from the
production date.
The liability of tekmar under this warranty shall be limited to, at tekmar's sole discretion: the cost of parts and labor provided by tekmar to repair defects in materials
and/or workmanship of the defective product; or to the exchange of the defective
product for a replacement product; or to the granting of credit limited to the original
cost of the defective product, and such repair, exchange or credit shall be the sole
remedy available from tekmar, and, without limiting the foregoing in any way,
tekmar is not responsible, in contract, tort or strict product liability, for any
other losses, costs, expenses, inconveniences, or damages, whether direct, indirect, special, secondary, incidental or consequential, arising from ownership or use
of the product, or from defects in workmanship or materials, including any liability
for fundamental breach of contract.
This warranty applies only to those products returned to tekmar during the
warranty period. This warranty does not cover the cost of the parts or labor
to remove or transport the defective product, or to reinstall the repaired or
replacement product. Returned products that are not defective are not covered by this warranty.
This warranty does not apply if the product has been damaged by negligence
by persons other than tekmar, accident, fire, Act of God, abuse or misuse; or
has been damaged by modifications, alterations or attachments made subsequent to purchase which have not been authorized by tekmar; or if the
product was not installed in compliance with tekmar’s instructions and the
local codes and ordinances; or if due to defective installation of the product;
or if the product was not used in compliance with tekmar’s instructions.
This warranty is in lieu of all other warranties, express or implied, which the
Governing Law (being the law of British Columbia) allows parties to contractually exclude, including, without limitation, warranties of merchantability,
fitness for a particular purpose, durability or description of the product, its
non-infringement of any relevant patents or trademarks, and its compliance
with or non-violation of any applicable environmental, health or safety legislation; the term of any other warranty not hereby contractually excluded is
limited such that it shall not extend beyond twenty-four (24) months from the
production date, to the extent that such limitation is allowed by the Governing Law.
Product Return Procedure Products that are believed to have defects in work-
manship or materials must be returned, together with a written description of the
defect, to the tekmar representative for that territory. If the address of the representative is not known, please request it from tekmar at the telephone number
listed below
.
tekmar Control Systems Ltd., Canada
Control Systems
tekmar Control Systems, Inc., U.S.A.
Head Office: 5100 Silver Star Road
Vernon, B.C. Canada V1B 3K4
Tel. (250) 545-7749 Fax. (250) 545-0650
Web Site: www.tekmarcontrols.com