tekmar 261 User Manual

- Data Brochure
D 261
Boiler Control 261
03/09
The Boiler Control 261 is designed to control two separate on / off boiler stages (or one low / high fire) in order to provide outdoor reset or setpoint operation. The control includes a Liquid Crystal Display (LCD) to view system status and operating information.
Additional functions include:
• User comfort adjustment to increase or decrease building space temperature
• Advanced settings to fine-tune building requirements
• Test sequence to ensure proper component operation
• Setback input for energy savings
• 120 V (ac) power supply
• CSA C US certified (approved to applicable UL standards)
• Powered boiler pump output
Note:
Boiler or setpoint demand must be powered with 20 to 260 V (ac) before the boiler is able to fire.
BOIL
OCC
Terminal Unit Boiler Demand
Setpoint
Fire Delay
Item
Boiler Control 261
Two Stage Boiler & Setpoint
2345 6
1
Setpoint
Boiler
Demand
Demand
VIEW
F
°
1 2
Setpoint Demand
7 8
Power
Boil
L
N
Pmp
N
To increase or decrease the building temperature:
Item
ADJUST
ROOM
11 12
Stage 2
, , buttons
menu
setting
C US
158033
2
VIEW
Do not apply power
13 14 15 16 17
UnO
Sw
Press the simultaneously for 1 sec. to enter the Use the , buttons to adjust the
Display defaults back to menu after 20 sec.
910
Stage
11
Advanced
Installer
Test
Made in Canada by tekmar Control Systems Ltd. tektra 910-02
Power: Relays: Demand:
Com
Boil
Return
Rotate
Off
ROOM OUTDR DSGN
outdoor temp.
Terminal Unit Set to
High Mass Radiant Low Mass Radiant Fan Coil Convector Radiator Baseboard
Setpoint - Set to desired setpoint temp.
Refer to brochure for more information
50/60 Hz 1300 VA
120 V 240 V (ac) 10 A 1/3 hp 20 to 260 V (ac) 2 VA
Signal wiring must be rated at least 300V.
Out
Com
Installer Instructions
- Set to desired room temp.
- Set to coldest (design)
1 2 3 4 5 6
Meets Class B: Canadian ICES FCC Part 15
Date Code
H1108D
Input
Boiler Demand
Signal
Setpoint Demand
Input
Signal
120 V (ac) Power
Input
Supply
Output
Boiler System
Pump
Output
Boiler
Output
Boiler
TIME
1
PRGM
AMPM
2
UNOCC OVR
S
SMWTFT
Input
tekmar Timer
Optional
Input
Outdoor
Included
Sensor
Input
Universal
Included
Sensor
Copyright © D 261 - 03/091 of 20
How To Use The Data Brochure
This brochure is organized into four main sections. They are: 1)
Troubleshooting
of the
Sequence of Operation
that apply to your installation. For quick installation and setup of the control refer to the followed by the
The
Control Settings
displayed by the control. The control functions of each adjustable item are described in the
Sequence of Operation
. The
, as this contains important information on the overall operation of the control. Then read the sub-sections
Quick Setup
section.
section (starting at
section has three sub-sections. We recommend reading Section A:
DIP Switch Settings
Sequence of Operation
) of this brochure, describes the various items that are adjusted and
, 2)
Installation
Table of Contents
User Interface ................................................ pg 2
Description of Display Elements ................. pg 3
Sequence of Operation ................................. pg 4
Section A: General Operation........
Section B: Boiler Reset ..................
Section C: Setpoint.........................
Installation ..................................................... pg 9
DIP Switch Settings .................................... pg 12
pg 4
pg 5
pg 8
Quick Setup ................................................. pg 13
Control Settings .......................................... pg 14
View Menu ........................................
Adjust Menu .....................................
Testing and Troubleshooting .....................pg 16
Error Messages ...............................
Technical Data ............................................. pg 20
Limited Warranty ......................................... pg 20
Installation
section,
Sequence of Operation
, 3)
Control Settings
General Operation
DIP Switch Settings
, and 4)
section,
.
pg 14
pg 14
pg 18
Reference Material: Essay E 003 “Characterized Heating Curve and Reset Ratio”
User Interface
The 261 uses a Liquid Crystal Display (LCD) as the method of supplying information. You use the LCD in order to set up and monitor the operation of your system. The 261 has three push buttons ( program your control, record your settings in the ADJUST menu table which is found in the second half of this brochure.
Item
The abbreviated name of the selected item will be displayed in the item field of the display. To view the next available item, press and release the have reached the last available item, pressing and releasing the the display to the first item.
Adjust
To make an adjustment to a setting in the control, press and hold simultaneously for 1 second, all 3 buttons. The display will then show the word ADJUST in the top right corner.
Then select the desired item using the to make the adjustment.
To exit the ADJUST menu, either select the ESC item and press the seconds.
When the
Additional information can be gained by observing the status field and pointers of the LCD. The status field will indicate which of the control’s outputs are currently active. Most symbols in the status field are only visible when the VIEW menu is selected.
Item
button is pressed and held in the VIEW menu, the display scrolls through all the adjust items in both access levels.
Item
button. Finally, use the
Item
, , ) for selecting, viewing, and adjusting settings. As you
Item
button. Once you
Item
button will return
and / or
or button, or leave the adjustment buttons alone for 20
button
Item
Item
Copyright © D 261 - 03/09 2 of 20
Display
Item Field
Displays an abbreviated name of the selected item
OUTDR BOIL
ROOM WWSD INDR
Terminal Unit
Status Field
Displays the current status of the control’s inputs, outputs and operation
DSGN
TARGET
MAXMIN
UN
OCC
Fire Delay
Item
DIFF
Setpoint
Setpoint Demand
Number Field
Displays the current value of the selected item
VIEW ADJUST
°
F
°
C
min
1 2
Boiler Demand
Buttons
Selects Menus, Items and
{
adjusts settings
Menu Field
Displays the current menu
Symbol Description
Pump
Displays when the boiler pump is in operation.
Burner
1 2
Displays when the stage 1 and / or stage 2 relay is turned on.
OCC
Occupied Schedule
Displays when the control is in occupied (Day) mode.
UNOCC
°
F, °C
Unoccupied Schedule
Displays when the control is in unoccupied (Night) mode.
°F, °C
Displays the unit of measure that all of the temperatures are to be displayed in the control.
Pointer
Displays the control operation as indicated by the text.
Copyright © D 261 - 03/093 of 20
Sequence of Operation
Section A
General Operation
Page 4
Section B
Boiler Reset
Page 5-8
Section C
Setpoint
Page 8
Section A — General Operation
POWERING UP THE CONTROL
When the Boiler Control 261 is powered up, the control displays the control type number in the LCD for 2 seconds. Next, the software version is displayed for 2 seconds. Finally, the control enters into the normal operating mode and the LCD defaults to displaying the current outdoor air temperature.
OPERATION
The 261 operates two on / off heat sources to control the supply water temperature to a hydronic system. The supply water temperature is based on either the current outdoor temperature, or a fixed setpoint.
Outdoor Reset
When a demand signal from the heating system is present, the 261 calculates a supply temperature based on the outdoor air tempera­ture and
Setpoint Control
When a demand signal from a setpoint system is present, the control operates the boiler(s) to maintain the supply water temperature at the
Setpoint
Characterized Heating Curve
setting. Refer to section C.
settings.
Design Supply
Terminal Unit
Indoor Design
Decreasing Outdoor Temperature
Outdoor Design
Increasing Water Temperature
SETBACK (UNOCCUPIED)
To provide greater energy savings, the 261 has a setback capability. With setback, the supply water temperature in the system is reduced when the building is unoccupied. By reducing the supply water temperature, air temperature in the space may be reduced even when thermostat(s) are not turned down. Any time the (14) terminals are shorted together, the control operates in the unoccupied (Night) mode. When in the unoccupied (Night) mode, the UNOCC segment is displayed in the LCD. The 261 adjusts the supply water temperature based on the UNOCC settings made in the control. This feature has no effect when the control is used in setpoint operation.
ROTATION
The 261s 48 hours more running time than the other stage. After each rotation, the stage with the least running hours is the first to fire, and the stage with the most running hours is the last to fire. This function ensures that both stages receive equal amounts of use. When the
Rotate / Off
EXERCISING
The 261 has a built-in exercising function. If the pump has not been operated at least once every 3 days, the control turns on the output for 10 seconds. This minimizes the possibility of the pump seizing during a long period of inactivity. While the control is exercising, the
Note:
Equal Run Time Rotation
DIP switch is set to the
Test
LED flashes.
The exercising function does not work if power to the control or pump is disconnected.
FACTORY DEFAULTS
The control comes preset with several factory defaults. These defaults are based on the terminal unit selection (see section B2). To fine-tune building requirements, these defaults may be changed. If a factory default value for a terminal unit is changed, the terminal unit number will flash when selected in the ADJUST menu.
14
13
Com
UnO
Sw
UnO Sw
function is fixed at 48 hours. The firing order of the boilers changes whenever one stage accumulates
Off
position, Stage 1 is always the first stage to fire.
(13) and the
Com
Timer switch
To reload the factory defaults listed in section B2, power down the control and wait for 10 seconds. Power up the control while simultaneously holding the than flashing.
Copyright © D 261 - 03/09 4 of 20
Item
and buttons. The terminal unit number should now be displayed constantly in the LCD rather
Section B: Boiler Reset
Section B1
General
Section B2
Installer
Section B3
Advanced
Section B1: General
BOILER DEMAND
A boiler demand is required in order for the 261 to provide heat to the heating system. A boiler demand is generated by applying a voltage between 24 and 240 V (ac) across the
Boiler Demand
displayed in the LCD. If the 261 is not in WWSD, the 261 closes the 261 calculates a boiler target (BOIL TARGET) supply temperature based on the outdoor air temperature and settings. The 261 then fires the boiler(s), if required, to maintain the target supply temperature.
BOILER PUMP OPERATION (BOIL PMP)
The boiler pump contact ( pump segment is displayed in the LCD. After the boiler demand has been satisfied, the 261 continues to operate the boiler pump for 20 seconds. This allows any excess heat to be purged out to the heating system. During WWSD, the boiler pump is operated based on the exercise function. For boiler pump contact operation during setpoint operation, refer to section C.
BOILER OPERATION
When the 261 determines that boiler operation is required, the boiler boiler contact(s) is closed, the burner and stage segment in the LCD is displayed.
terminals (1 and 2). Once voltage is applied, the
Boil Pmp
, terminal 7) closes whenever there is a boiler demand and the 261 is not in WWSD. The boiler
Boiler Demand
Boil Pmp
contact. The
Stage
contact(s) (9 and 10 and / or 11 and 12) close. While the
pointer is
24 to 240 V (ac)
1
Boiler
Demand
2
STAGING
The 261 controls up to two stages in order to supply the required target temperature. After the first stage is turned on in the firing sequence, the control waits a minimum amount of time before turning on the next stage. After the minimum time delay between stages has expired, the 261 examines the control error to determine when the next stage is to fire. The control error is determined using Proportional, Integral and Derivative (PID) logic.
Proportional - compares the actual supply temperature (BOIL) to the boiler target (BOIL TARGET) temperature. The colder the supply water temperature, the sooner the next stage is turned on.
Integral - compares the actual supply temperature (BOIL) to the boiler target (BOIL TARGET) temperature over a period of time.
Derivative - determines how fast or slow the supply water temperature is changing. If the supply temperature is increasing slowly, the next stage is turned on sooner. If the supply temperature is increasing quickly, the next stage is turned on later, if at all.
Each stage has a minimum on time, and a minimum off time.
CHARACTERIZED HEATING CURVE
The 261 varies the supply water temperature based on the outdoor air temperature. The control takes into account the type of terminal unit that the system is using. Since different types of terminal units transfer heat to a space using different proportions of radiation, convection and conduction, the supply water temperature must be controlled differently. Once the control is told what type of terminal unit is used, the control varies the supply water temperature according to the type of terminal unit. This improves the control of the air temperature in the building.
BOILER TARGET TEMPERATURE (BOIL TARGET)
The BOIL TARGET temperature is determined from the control displays the temperature that it is currently trying to maintain as the boiler supply temperature. If the control does not presently have a requirement for heat, it does not show a boiler target temperature. Instead, - - - is displayed in the LCD.
Characterized Heating Curve
settings and the outdoor air temperature. The
Copyright © D 261 - 03/095 of 20
Section B2: Installer
BOIL DSGN
OUTDOOR DESIGN (OUTDR DSGN)
The OUTDR DSGN is the outdoor air temperature that is the typical coldest temperature of the year where the building is located. This tem­perature is used when doing the heat loss calculations for the building. If a cold outdoor design temperature is selected, the boiler supply tem­perature rises gradually as the outdoor temperature drops. If a warm outdoor design temperature is selected, the boiler supply temperature
cold
OUTDR
DSGN
warm
rises rapidly as the outdoor temperature drops.
BOIL INDR
Increasing Water Temperature
Decreasing Outdoor Temperature
.
ROOM OCC & UNOCC (ROOM)
The ROOM is the desired room temperature for the boiler zones, and it provides a parallel shift of the
Characterized Heating Curve
. The room temperature desired by the occupants is often different from the design indoor temperature (BOIL INDR). If the room temperature is not correct,
p
m
e
T
l
a
u
t
c
A
o
N
n
g
i
s
e
D
l
a
m
r
adjusting the ROOM setting increases or decreases the amount of heat available to the building. A ROOM setting is available for both the occu­pied (Day) and unoccupied (Night) modes.
TERMINAL UNITS
When using a shape of the
Characterized Heating Curve
Characterized Heating Curve
Increasing Water Temperature
Decreasing OutdoorTemperature
, the control requires the selection of a terminal unit. The terminal unit determines the
according to how the terminal unit delivers heat into the building space (refer to Essay
ROOM
BOIL INDR
E 003). The 261 provides for selection between six different terminal unit types: two types of radiant floor heat, fancoil, fin-tube convector, radiator and baseboard. When a terminal unit is selected, the control automatically loads the design supply temperature (BOIL DSGN), maximum supply temperature (BOIL MAX), and minimum supply temperature (BOIL MIN). The factory defaults are listed below. To change defaults, refer to section B3. If a default has been changed, refer to section A to reload the factory defaults.
Terminal Unit
BOIL DSGN BOIL MAX BOIL MIN
High Mass Radiant
120°F (49°C) 140°F (60°C)
OFF
High Mass Radiant (1)
(1)
Low Mass Radiant
(2)
140°F (60°C) 160°F (71°C)
OFF
Fancoil
(3)
190°F (88°C) 210°F (99°C) 140°F (60°C)
Fin-tube Convector
180°F (82°C) 200°F (93°C) 140°F (60°C)
This type of a hydronic radiant floor is embedded in either a thick concrete or gypsum pour. This heating system has a large thermal mass and is slow acting. Default values: BOIL DSGN = 120°F (49°C), BOIL MAX = 140°F (60°C), BOIL MIN = OFF
Low Mass Radiant (2)
This type of radiant heating system is either attached to the bottom of a wood sub-floor, suspended in the joist space, or sandwiched between the sub-floor and the surface. This type of radiant system has a relatively low thermal mass and responds faster than a high mass system. Default values: BOIL DSGN = 140°F (60°C), BOIL MAX = 160°F (71°C), BOIL MIN = OFF
Copyright © D 261 - 03/09 6 of 20
(4)
Radiator
(5)
160°F (71°C) 180°F (82°C) 140°F (60°C)
Baseboard
(6)
150°F (66°C)
170°F(77°C)
140°F (60°C)
Loading...
+ 14 hidden pages