this document and reserves the right to make changes, additions or deletions. Schneider Electric Buildings AB assumes no responsibility for
possible mistakes or errors that might appear in this document.
Do not use the product for other purposes than those indicated in this document.
Only licensed users of the product and the document are permitted to use the document or any information therein. Distribution, disclosure,
copying, storing or use of the product, the information or the illustrations in the document on the part of non-licensed users, in electronic or
mechanical form, as a recording or by other means, including photo copying or information storage and retrieval systems, without the express
written permission of Schneider Electric Buildings AB, will be regarded as a violation of copyright laws and is strictly prohibited.
Trademarks and registered trademarks are the property of their respective owners.
6.2.1Submenu 6: Test dial..................................................................................................57
APPENDIX
AAppendix A Restart Values63
BAppendix B Restart Sequences67
Index71
6 (74)Schneider Electric Buildings AB, June 2011
04-00067-02-en
INTRODUCTION
1About this Manual
TAC Xenta, TAC Xenta 280/300/4011 About this Manual
1About this Manual
This manual describes a particular process. For information on certain
products, we refer you to the manual or the Help for the product in question.
For information on how to install software, we refer you to the instructions delivered with the software.
For information on third party products, we refer you to the instructions
delivered with the third party product.
If you discover errors and/or unclear descriptions in this manual, please
contact your Schneider Electric representative.
Note
1.1Structure
•We are continuously improving and correcting our documentation. This manual may have been updated.
Please check our Docnet site at www.tac.com for the latest version.
The manual is divided into the following parts:
•Introduction
The Introduction section contains information on how this manual
is structured and how it should be used to find information in the
most efficient way.
•Reference
The Reference section contains more comprehensive information
about various parts of the Getting Started section. It also provides
you with information on alternative solutions not covered by the
Getting Started section.
Schneider Electric Buildings AB, June 20119 (74)
04-00067-02-en
1 About this Manual TAC Xenta, TAC Xenta 280/300/401
!
1.2Typographic Conventions
Throughout the manual the following specially marked texts may occur.
Warning
•Alerts you that failure to take, or avoid, a specific action might
result in physical harm to you or to the hardware.
Caution
•Alerts you to possible data loss, breaches of security, or other
more serious problems.
Important
•Alerts you to supplementary information that is essential to the
completion of a task.
Note
•Alerts you to supplementary information.
Tip
•Alerts you to supplementary information that is not essential to
Advanced
•Alerts you that the following information applies to complex
1.3Prerequisites
To be able to profit from the contents in this manual, it is recommended
that you read the following documents:
•TA C Xenta 280 Programmable Controller datasheet
the completion of the task at hand.
tasks or tasks restricted by access.
•TA C Xenta 300 Programmable Controller datasheet
•TA C Xenta 400 Controller, freely programmable datasheet
The TAC Xenta 280/300/400 family consists of the following units:
•The TAC Xenta 280/300/401 controller. The controller contains
the database of the inputs and outputs of the TAC Xenta system. It
also contains the system and application software for all the functions that are to be performed by the controller and the connected
peripheral units.
•TAC Xenta OP. The operator panel includes control buttons while
a screen displays the values and menus. TAC Xenta OP can be
connected to any controller in the network.
I/O expansion modules. These can be used to extend the number of
inputs and outputs on a TAC Xenta 300/401 controller.
The I/O modules are described in a separate manual, TAC Xenta 400 I/O Modules.
Schneider Electric Buildings AB, June 201113 (74)
04-00067-02-en
Fig. 2.1: The basic units of the TAC Xenta: the controller, the operator
panel, and an I/O expansion module
A number of controllers and I/O modules can form a local network and
exchange data.
The TAC Xenta OP operator panel allows the user to:
•Obtain access to certain parameters
•Monitor the system status
•Adjust setpoints and time channels
•Display alarms (without communicating with a central system)
Up to two OPs may be connected to each controller.
2.2Configurations
The TAC Xenta controllers can be used in different configurations, for
example:
•As stand-alone units (for a TAC Xenta 401 with at least one I/O
module).
•With controllers and OPs in a network, with extra I/O modules as
required (no I/O modules for the TAC Xenta 280).
•With controllers, OPs, I/O modules and other equipment in a full
network with suitable adapters, possibly with connections to a
TAC Vista Central System.
The TAC Xenta units communicate with each other in a network using
a common bus, Echelon® L
10). Additional I/O units also connect to the network and may be added
as required. An I/O unit can only be associated with one controller.
Explicit L
operator panel and the controller.
The L
defined on foreign equipment.
The Functional Block applications are modeled as true L
troller Objects.
The Network Variable interface (including the Standard Network Variable Types, SNVTs) can be customized, and External Interface Files
(XIFs) can be generated in the field using the TAC Menta tool. Available SNVTs are listed in an appendix to the Engineering Applications in TAC Menta manual.
When connected to a TAC Vista Central System, the operating conditions of equipment such as fans, pumps, and recovery units can be displayed as graphs on the monitor and printed as reports. All temperatures
and alarms may be read, while setpoints and time settings may be
altered as required
TAC Xenta controllers can be reached from TAC Vista in many ways.
Using LonWorks in the Xenta controller, some examples are:
•From a PCLTA card in some form, directly on the PC.
ONWORKS® Free Topology 78 kbps (FTT-
ONTALK® messages are used in communications between the
ONTALK protocol makes it possible to use Network Variables,
ONMARK Con-
Schneider Electric Buildings AB, June 201115 (74)
04-00067-02-en
Red service diode
indicates a non-configured
node or a hardware fault
Green status diode indicates that the program is running
At distances greater than 10 m (32 ft.) between the TAC Xenta controller and the OP, an external power supply should be used. In addition, the
communications connection has to follow the same rules as for other
nodes.
Jack for the
RS232/modem
Fig. 3.3: Location of jacks on the TAC Xenta 280 controller
3.1.3LED Indicators and Service pin
The Service pin can be activated through a small hole on the front. Also
on the front, there are two LED indicators–one red and one green.
Jack for the
Operator panel
Fig. 3.4: LED Indicators and Service Pin
The red service diode is primarily an error indication. It also lights up if
the Service pin is activated.
The green status diode blinks once per second to indicate that the program is running.
Schneider Electric Buildings AB, June 201119 (74)
04-00067-02-en
•For a complete list of updated technical data for the Xenta 280
controller, see the TAC Xenta 280 Programmable Controller
datasheet (003-2248).
Program cycle timemin. 1 s
Universal inputs (TAC Xenta 281, 282: U1–U4):
A/D-resolution12 bits
–as Thermistor Inputs
Supply voltage0.6V DC
Thermistor inputs (B1–B2, only TAC Xenta 282):
A/D-resolution12 bits
Accuracy (Measuring range):
–50 °C to –30 °C (–58 °F to –22 °F)±4 °C (±7.2 °F)
–30 °C to –10 °C (–22 °F to +14 °F)±2 °C (±3.6 °F)
–10 °C to +10 °C (14 °F to 50 °F)±1 °C (±1.8 °F)
+10 °C to +30 °C (50 °F to 86 °F)±0.5 °C (±0.9 °F)
+30 °C to +60 °C (86 °F to 140 °F)±1 °C (±1.8 °F)
+60 °C to +120 °C (140 °F to 248 °F)±2 °C (±3.6 °F)
+120 °C to +150 °C (248 °F to 302 °F)±4 °C (±7.2 °F)
Thermistor inputs (B1–B4, only TAC Xenta 283):
A/D-resolution10 bits
Accuracy (Measuring range):
–20 °C to –10 °C (–4 °F to +14 °F)±2 °C (±3.6 °F)
–10 °C to +10 °C (14 °F to 50 °F)±1 °C (±1.8 °F)
+10 °C to +30 °C (50 °F to 86 °F)±0,5 °C (±0.9 °F
+30 °C to +60 °C (86 °F to 140 °F)±1 °C (±1.8 °F)
+60 °C to +90 °C (140 °F to 194 °F)±2 °C (±3.6 °F)
+90 °C to +120 °C (194 °F to 248 °F)±4 °C (±7.2 °F
TRIAC outputs (TAC Xenta 283 only, V1–V6)
Load may require auxiliary power
(term. 40) of up to
a. If the active sensor (0–10V), analog actuators and the TAC Xenta con-
troller itself are supplied by the same transformer, the following restrictions will ensure the specified accuracy (for thermistor inputs,
universal inputs, and analog outputs):
Cable length from controller to:
Transformer: 3 m (10 ft.)
Active sensor/actuator: 20 m (65 ft.)
Number of active sensors: max. 4
Number of actuators: max.6
Network communication (C1–C2, polarity insensitive):
ProtocolFTT-10, L
ONTALK®
Communication speed78 kbits/s
Other communication:
TAC MentaRS232, up to 9600 bits/
s, RJ45
TAC Vista (version IV or higher
TP/FT-10, screw term.
required), also for appl.pgm download
TAC Xenta OPTP/FT-10, modular
jack
3.2The TAC Xenta 300 Controller.
Fig. 3.5: The TAC Xenta 300 controller
3.2.1Terminals
TAC Xenta 301 and 302
TAC Xenta 300 has two I/O configurations: TAC Xenta 301 and TAC
Xenta 302.
Digital
inputs
Thermistor
inputs
Universal
inputs
Relay
outputs
Analog
outputs
Term. notation
Schneider Electric Buildings AB, June 201121 (74)
04-00067-02-en
The TAC Xenta 300 has two modular jacks–one for the TAC Xenta OP
operator panel and one for an RS232 connection with TAC Menta.
The socket for the operator panel provides it with 24V AC or DC,
depending on the supply.
At distances greater than 10 m (32 ft.) between the TAC Xenta controller and the OP, an external power supply should be used. In addition, the
communications connection has to follow the same rules as for other
nodes.
Jack for the
RS232/modem
Fig. 3.7: Location of jacks on the TAC Xenta 280 controller
3.2.3LED Indicators and Service pin
The Service pin can be activated through a small hole on the front. Also
on the front are two LED indicators–one red and one green.
Red service diode
indicates a non-configured
node or a hardware fault
Jack for the
Operator panel
Service pin
Green status diode indicates that the program is running
Fig. 3.8: LED Indicators and Service Pin
The red service diode is primarily an error indication. It also lights up if
the Service pin is activated.
The green status diode blinks once per second to indicate that the program is running.
Schneider Electric Buildings AB, June 201123 (74)
04-00067-02-en
Loading...
+ 53 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.