Schneider Electric TAC Xenta 280 Data Sheet

Page 1
TAC Xenta® 280
Programmable Controller
The TAC Xenta® 280 is a family of programmable controllers designed for zone control or small-sized heating and air handling systems.
A TAC Xenta 280 controller contains basic HVAC functionality including control loops, curves, time control, alarm handling etc. The TAC Xenta 283 has a LONMARK Real Time Keeper object.
The Xenta 280 controller is available with three different I/O configurations, the TAC Xenta 281, 282 and 283. The controllers are designed for cabinet mounting.
They are simple to program and put into operation, using the TAC Menta® graphical software tool.
The controller communicates on a LONTALK® TP/FT-10 network via a twisted-pair, unpolarized cable. It is able to operate as a stand-alone unit and can be easily connected to a large LONWORKS based network.
TECHNICAL DATA
Supply voltage .... 24 V AC ±20%, 50/60 Hz or 19–40 V DC
Power consumption .............................................. max. 5 W
Transformer sizing ......................................................10 VA
Ambient temperature:
Storage ..............................–20 to +50 °C (–4 to +122 °F)
Operation.............................0 to +50 °C (+32 to +122 °F)
Humidity .............................. max. 90% RH non-condensing
Mechanical:
Enclosure............................................................. ABS/PC
Enclosure rating........................................................IP 20
Dimensions, mm (in.).......180 x 110 x 75 (7.1 x 4.3 x 3.0)
Weight ...................................................... 1.0 kg (2.2 lbs)
Real time clock:
Accuracy at +25 °C (77 °F)............. ±12 minutes per year
Power failure protection............................................. 72 h
Digital inputs (Xenta 281, 282, 283: X1–X2)
Voltage across open contact ............................... 33 V DC
Current through closed contact ................................ 4 mA
Pulse input duration ........................................ min. 20 ms
Universal inputs (Xenta 281, 282: U1–U4) – as Digital inputs;
Voltage across open contact ............................... 26 V DC
Current through closed contact ................................ 4 mA
Pulse input duration ........................................ min. 20 ms
– as Thermistor inputs;
TAC thermistor sensor............ 1800 ohm at 25 °C (77 °F)
Measuring range...........–50 to +150 °C (–58 to +302 °F)
– as Voltage inputs;
Input signal ......................................................0–10 V DC
Input resistance ................................................ 100 kohm
........................................ accuracy within 1% of full scale
Sensor inputs (B1–B2, only TAC Xenta 282)
TAC thermistor sensor.......... 1800 ohm at 25 °C (+77 °F)
Measuring range...........–50 to +150 °C (–58 to +302 °F)
Sensor inputs (B1–B4, only TAC Xenta 283)
TAC thermistor sensor.......... 1800 ohm at 25 °C (+77 °F)
......or (individually selectable) 10 kohm at 25 °C (+77 °F)
Measuring range.............–20 to +120 °C (–4 to +248 °F)
10 Oct 2003
®
For local use, the TAC Xenta OP operator panel can be connected. The OP has a display and push buttons for navigating and altering settings.
The operator panel can be snapped onto the TAC Xenta controller unit, mounted on the front of the cabinet, or used as a portable terminal.
Digital outputs (relays; Xenta 281: K1–K3, Xenta 282: K1–K4)
Control voltage, relay outputs................... up to 230 V AC
Ctrl curr., to be protected by max. 10 A fuse, ..... max. 2 A
Outputs V1–V6 (triac; TAC Xenta 283 only):
Control voltage ........................................... max. 30 V AC
Control current ................................................. max. 0.8 A
Total control current............................................ max. 3 A
Analog outputs (Xenta 281: Y1–Y3, Xenta 282: Y1–Y4)
Control voltage ................................................0–10 V DC
Control current, short-circuit proof ................... max. 2 mA
Deviation............................................................ max ±1%
Communication:
TAC Menta ................................. 9600 bps, RS232, RJ45
TAC Vista, also for application program download
..................................................TP/FT-10, screw terminal
TAC Xenta OP.............................TP/FT-10, modular jack
®
ONMARK
L
TAC Xenta 281, 282:
Interoperability ............ L
Application .. L TAC Xenta 283:
Interoperability ............ LONMARK Interop. Guidelines v 3.3
Application ..... L
Agency Compliances:
Emission .....................C-Tick, EN 50081-1, FCC Part 15
Immunity ........................................................ EN 50082-1
Safety:
Part numbers:
Electronics part TAC Xenta 281/N/P .............. 0-073-0030
Electronics part TAC Xenta 282/N/P .............. 0-073-0031
Electronics part TAC Xenta 283/N/P .............. 0-073-0032
Terminal part TAC Xenta 280/300..................0-073-0901
Operator terminal TAC Xenta OP................... 0-073-0907
TAC Xenta: Programming Serial Kit ...............0-073-0920
standard:
ONMARK Interop. Guidelines v 3.0
ONMARK Functional Profile: Plant Controller
ONMARK Funct. Profile: Real Time Keeper
CE ............................................................. EN 61010-1
UL 916 (Xenta 283 pending).Energy Mngmnt Equipm.
Flammability class, materials ....................... UL 94 V-0
ETL listing ................................ UL 3111-1, first edition
...................................CAN/CSA C22.2 No. 1010.1-92
Subject to modification.
1 (4) 0-003-2248-4 (EN)
Page 2
DESIGN
The TAC Xenta 280 controller has been designed as a general purpose unitary (one-to-one) controller. Thus it can be mounted in close proximity to the controlled equipment, minimizing the wiring required.
The TAC Xenta 280 is microprocessor based. It consists of a terminal and elec­tronics fitted together (Figure 1).
The Xenta 280 can be interfaced with a wide variety of field sensors/transducers and controlled devices. All terminations of field wires are done on the terminal part only. Thus the electronics part may be removed for service without affecting the terminal connections.
Local operator terminal
The TAC Xenta OP is a small operator terminal which can be connected to the unit through its enclosure. The operator can read the point status, perform manual override, read measured values, alter set points etc., from the TAC Xenta OP.
Functions are selected from menus. Ac­cess to the unit is enabled by using an access code. It is possible to access other TAC Xenta units on the same network.
Real-time clock
The clock provides data such as the year, month, date, day, hour, minute and second.
A built-in capacitor guarantees operation of the clock for at least 72 hours in the event of a power outage.
The TAC Xenta 283 is intended to be used as a Real Time Keeper. Real time is exposed as an output network variable, SNVT_time_stamp, which can be bound to other LonWorks devices.
Daylight Saving Time: European, Australian or USA/Canada
Once set, Daylight Saving Time (DST) is fully automatic. The change-over date and the number of hours to change are programmable. This function can also be disabled.
Digital Inputs
The DIs are used to sense alarm contacts, status indications, pulse counting, etc.
Each digital input can be used as a pulse counter (e.g. for flow measurement).
Another application is alarm monitoring. Each time an alarm is tripped, the corre­sponding counter can be incremented, providing data for operating statistics. The digital input circuits are internally powered.
Universal Inputs
The universal inputs can be individually configured as analog or digital inputs.
A high and a low limit can be set for each universal input. If configured as digital inputs, the universal inputs may be used, for example, for sensing switch positions.
The universal input types are selected via the application program.
Figure 1
Thermistor Inputs
The TAC Xenta 282 and 283 have thermistor inputs, 1800 ohm at 25 °C (+77 °F).
In the Xenta 283, these inputs are also individually configurable for 10 kohm at 25 °C (+77 °F).
Digital Outputs
There are digital outputs for controlling equipment such as fans, pumps or similar devices. The output signal can be pulse­width modulated.
In the TAC Xenta 283, the DOs are de­signed as TRIAC outputs.
Analog Outputs
There are analog outputs for controlling actuators or connections with controllers.
ONWORKS
L
®
SNVT support
The use of Standard Network Variable Types, in accordance with the Echelon specification, makes it possible to com­municate with nodes made by other manu­facturers.
Power outage protection
Using non-volatile (flash) memory, the unit will start up with user settings and work normally after a power outage.
®
I/O CONFIGURATIONS
The Xenta 280 controller is available with three different I/O configurations, the TAC Xenta 281, 282 and 283.
The table gives an overview of the different numbers of inputs and outputs.
No external I/O modules are used with
TAC Xenta DI UI TI DO AO
281 2 4 - 3 3 282 24244 283 2 - 4 6 -
the TAC Xenta 280.
SOFTWARE FEATURES
With the assistance of TAC Menta (4.0 or higher; for Xenta 283 4.10 or higher), a graphical programming tool using Functional Block Diagrams (FBDs), the TAC Xenta 280 may be easily adapted to different control and monitoring tasks.
The basic software includes pre­programmed routines for:
– reading Digital Inputs (alarms, pulse counting,
interlocks)
– reading Universal Inputs (individually selectable
as analog or digital) – controlling Digital Outputs – controlling Analog Outputs
0-003-2248-4 (EN) 2 (4)
– on and off delays – pulse counting (Digital Inputs only) – alarm handling; alarm conditions may be de-
tected via the digital or analog inputs. – equipment run time totals, on selected objects. – one-time schedule block with four entries (start
and stop times in hours and minutes): weekly
and/or holidays – programs for optimum start/stop – outdoor temp. compensating control curves – PID control loops (loops may be connected in
cascade) – trend logging (max. 5 kB) – local level operator interface via TAC Xenta OP – network communication according to the
L
ONTALK
®
protocol
DI (Xn): Digital input UI (Un): Universal input TI (Bn): Thermistor input
DO (Kn,Vn): Digital output AO (Yn): Analog output
The basic software is adapted to the current application by connecting pre­programmed Functional Blocks and by adjusting the relevant parameters. These connections and parameters are stored in non-volatile memory.
The parameters may be changed during operation either from the Central System or locally from the TAC Xenta Operator Panel.
Page 3
COMMUNICATION
2
M l
A l
F l
Communication capabilities
The TAC Xenta 280 has several communi­cation capabilities: within the network, with a central presentation system and with a hand-held Operator Panel.
ONWORKS connection
L
TAC Xenta controllers communicate with each other using a common network,
ONWORKS TP/FT-10, 78 kbps. A number
L of controllers can form a network and exchange data.
The LONTALK protocol makes it possible to use Network Variables defined in equip­ment made by other manufacturers.
The Functional Block applications are modeled as true LONMARK® Controller Objects.
The Network Variable interface (including the Standard Network Variable Types, SNVTs) can be customized, and External Interface Files (XIFs) can be generated in the field using the TAC Menta tool.
SYSTEM CONFIGURATIONS
TAC Vista presentation system
When connected to a TAC Vista Central System (version 4.0 or higher, for Xenta 283 version 4.10 or higher), the operating conditions of the fans, pumps, recovery units etc. can be monitored via color graphics or printed reports.
Temperatures and alarms can be read, while setpoints and time settings may be altered as required.
TAC Xenta controllers can be reached from TAC Vista in one of the following ways.
1 Any controller in the network via a
PCLTA card.
2 A specific controller via the RS232
connection.
3 Any controller in the network via the
TAC Xenta 901 LonTalk adapter.
Application programs generated in TAC Menta may be downloaded from TAC Vista via the network.
TAC Xenta OP port
The operator panel is also connected to the network and can thus act as an opera­tor panel for other units in the network. The connection is made via the modular jack on the front of the controller or di­rectly, using the network cable.
RS232 port
The TAC Xenta 280 controller has an RS232 port. This port is intended for con­nection to a PC using the TAC Menta programming tool for loading and com­missioning the application program.
The port can also be used for connec­ting between TAC Vista and specific TAC Xenta 280 units (see above). Connection via a modem is not supported.
The TAC Xenta 280 controllers can be used in different configurations.
• Stand-alone.
• Controllers and OPs in a network.
anagement
evel
TAC
Vista
TAC
Vista
IP Network
Web
browser
• Controllers, OPs and other equipment in a full network with suitable adapters, possibly connected to a TAC Vista Cen­tral System.
Figure 2 shows an example of a TAC Xenta network configuration.
utomation
evel
PCLTA
card
or
TAC Xenta 901
TP/FT-10
TAC Xenta 511
Sensors and actuators on the field level are mostly connected to the conventional inputs/outputs of the controllers.
TAC Xenta OP
TAC Xenta 281
TAC Xenta OP
TAC Xenta 28
Some external units, however, may be connected directly to the network to com­municate input/output data, using Stan­dard Network Variables (SNVTs).
ield
evel
+
-
Figure 2
TAC XENTA NETWORK AND UNIT PERFORMANCE
No. of TAC Xenta controllers .......... 400
No. of I/O modules .......................... 200
No. of Operator Panels ................... 100
No. of TAC Xenta Groups ................. 30
No. of Xenta controllers per Group ... 30
Trend logging in the TAC Xenta 280
Channels ............................... 1 – 50
Interval................. 10 s – 530 weeks
Total logging cap. .. ~ 650 float. no.s
..........................or ~ 1,300 integers
................or ~ 10,000 digital values
Optimized storage ..................... Yes
No. of subscriptions *
In ........................................ max. 15
Out...................................... max. 30
Time Channels.................................... 1
Application size
program and data .......... max. 56 kB
parameters .................... max. 64 kB
3 (4) 0-003-2248-4 (EN)
* Subscriptions can utilize standard SNVTs or TACNVs (TAC Network Variables). These can be combined if the following restrictions are observed: the sum of the TACNV subscriptions and the number of SNVT members (no. of values in structured SNVTs) does not exceed the stated figures.
Page 4
MOUNTING
)
The TAC Xenta 280 controller is cabinet­mounted on a TS 35 mm Norm rail EN 50 022.
The controller consists of two parts; a terminal part with the screw terminals, and an electronics part with the circuit boards. To simplify installation, the termi­nal can be pre-mounted in the cabinet (see Figure 1).
If the Xenta 280 controller is to be wall­mounted, a wide range of standardized boxes are available.
CABLES
G and G0:
Min. wire gauge 0.75 and 1.5 mm² (19 and 16 AWG).
Cable with modular jack for the RS232 serial communication port: Max. 10 m (32 ft.).
Terminals X:
Min. wire gauge 0.25 mm² (23 AWG). Max. cable length 200 m (650 ft.).
180 (7.1)
148 ± 2.0 (5.8 ± 0.1)
180 + 0.4 (7.1 + 0.02) to the next TAC Xenta 280/300/3000 174 + 0.4 (6.9 + 0.02) to the next TAC Xenta 400/500/900
110
(4.3)
Ø 4.0
(0.2)
48 ± 0,5
(1.9±0.02)
16.1 (0.6)
Terminals U, B, Y:
Min. wire gauge 0.25–0.75 mm² (23–19 AWG). Max. cable length 20–200 m (65 to 650 ft.) (see TAC Xenta 280/ 300/401 manual for details).
Terminals K, V:
Wire gauge 0.75–1.5 mm² (19–16 AWG). Max. cable length 200 m (650 ft.).
45
(1.8
77.4 (3.1)
C1 and C2: TP/FT-10 allows the user to wire the
control devices with virtually no topology restrictions. The max. wire distance in one segment depends on the type of wire and the topology, see the table below.
Cable doubly terminated distance, singly termi- singly terminated
Belden 85102, single twisted pair 2700 (9000) 500 (1600) 500 (1600) Belden 8471, single twisted pair 2700 (9000) 400 (1300) 500 (1600) UL Level IV 22 AWG, twisted pair 1400 (4600) 400 (1300) 500 (1600) Connect-Air 22 AWG, one or two pairs 1400 (4600) 400 (1300) 500 (1600) Siemens J-Y(st)Y 2x2x0.8 900 (3000) 320 (1000) 500 (1600)
4-wire helical twist, solid, shielded TIA568A Cat. 5 24 AWG, twisted pair 900 (3000) 250 (820) 450 (1500)
Max. bus length, Max. node-to-node Max. length,
bus topology m (ft.) nated free topology m (ft.) free topology m (ft.)
INSTALLATION
The three TAC Xenta 280 controllers have dif­ferent inputs and outputs. The adjacent table shows the terminal connections of the three TAC Xenta controllers.
There is a label on the front of the controller with the numbers and the names of the termi­nals (1 C1, 2 C2 and so on). The numbers are also moulded in the plastic of the terminal part.
Note! The installation of high volt­age cables must be performed by qualified personnel!
For detailed information, please refer to the TAC Xenta 280/300/401 Handbook.
Operator Panel
The Operator Panel can easily be connected to the network by means of the modular socket on the front of the controller.
LED indicator
An indicator on the electronic unit of the TAC Xenta 280 indicates when the application program is running.
Terminal connections: Inputs
Term. Term.name Description no. 281 282 283
1C1C1C1LONWORKSTP/FT-10 2C2C2C2 3 U1 U1 Universal 4 M M M Msrmnt. neutral 5 U2 U2 Universal 6 U3 U3 Universal 7 M M M Msrmnt. neutral 8 U4 U4 Universal 9 B1 B1 Thermistor 10 M M Msrmnt. neutral
11 B2 B2 Thermistor 12 B3 Thermistor 13 M M Msrmnt. neutral 14 B4 Thermistor 15 X1 X1 X1 Digital 16 M M M Msrmnt. neutral 17 X2 X2 X2 Digital 18 – 19 M M M Msrmnt. neutral 20
Service pin
To simplify network commissioning, there is a service pin on the electronic unit which, when pressed, identifies the unit on the network.
TAC and TAC products are trademarks and/or registered trademarks of TAC AB.
All other trademarks belong to their respective owners. Copyright 2003 ã TAC AB. All rights reserved.
0-003-2248-4 (EN) 4 (4)
MAINTENANCE
The only care necessary is to keep the controller dry and to clean it externally with a dry cloth.
Terminal connections: Outputs
Term. Term.name Description no. 281 282 283
21 G G G 24 V AC (or DC+) 22 G0 G0 G0 24 V AC common 23 Y1 Y1 – 0–10 V 24 M M Output neutral 25 Y2 Y2 – 0–10 V 26 Y3 Y3 – 0–10 V 27 M M Output neutral 28 Y4 0–10 V 29––– 30–––
31 V5 TRIAC out 32––– 33 V6 TRIAC out
34 K1 K1 V1 Relay; TRIAC out 35 KC1 KC1 – K1, K2 common 36 K2 K2 V2 Relay; TRIAC out
37 K3 K3 V3 Relay; TRIAC out 38 KC2 KC2 – K3, K4 common 39 K4 V4 Relay; TRIAC out
40 VC 24 V AC, TRIACs
Loading...