TAC Xenta® 121/230
02-00045-01-en
Hardware Platform for general Fan Coil
and Heat Pump Applications
Installation instructions
Installationsanvisning
126 (5.0)
110 (4.3)
112 (4.4)
98 (3.9)
118 (4.6)
126 (4.8)
50 (2.0)
The controller is only intended for mounting inside an enclosure providing required cable clamping and necessary
GB
protection against electrical shock. For information on communication cable lengths, please refer to the TAC Xenta
280/300/401 Handbook, 0-004-7768. Other cable lengths: max 30 m, min 0.7 mm
2
(AWG19).
Regulatorn är endast avsedd för inbyggnad i skåp med dragavlastning för kablar och skydd för elektriska stötar. För information om längder av kommunikationskabel, se TAC Xenta 280/300/401 Handbok, 0-004-7767.
SE
Övriga kabellängder: max 30 m, min 0.7 mm
02-00045-01-en, Nov 2009 1 (2)
2
.
English - Svenska
TAC Xenta 121/230
Example on the connection of a 2-pipe Fan-Coil.
Other applications (like a 4-pipe Fan-Coil or
a Heat Pump with isolation and reversing valves)
are also possible.
Närvarogivare
Occupancy sensor
Fönsterkontakt
Window Contact
Discharge air temp. sensor
Frånluftstemperaturgivare
STR101-107 Wall module / Rumsenhet
LED
Mx
Switch
16 15 14 13 11 12
Pot/Pot+RMTherm
STR150 Wall module / Rumsenhet
Mode
M
11 13 12
5678910
Data
Y1 M X1 R1 M B1
TAC Xenta 121/230
Aux. relay or Electrical Reheater
Extra relä eller el.eftervärmare
LON
12
X2
C1 C2 M U1 V1 G V2 V3 G V4
15
Water Temperature
Vattentemperatur
TAC Xenta OP
4 5 6 78 910
3
M X3 B2 Y1 M X1 R1 M B1
TAC Xenta 121/230
24 V AC
21 22
Dec
23 24
24 V AC
Stage 2
Stage 1
2-stage Reheat
contactors
2-stegs
värmning
efter
17
16
19 20
18
Inc
Com
Heating Valve
actuator
Ställdon,
värmeventil
Thermal actuators
(alternatively)
Termoställdon
(alternativt)
11 12 13 14
K4 KC2 N L
230 V AC
K3 K2 K1 KC1
26
25
Sp3
3 Speed fan
3-stegs fläkt
27 28
2
Com1
!
CAT III (IEC 664)
Class II (EN 61010-1)
Note:
Each controller or group of controllers must be fi tted with max. 16 A fuses.
It must be easy to cut off the power supply for the controller or for the complete installation.
For TAC Xenta 121/230 KC2/K4 may also be connected to 24V, but must in this case be wired according to the
230 V mains safety rules, since isolation clearance to the G0 terminal does not meet 6.5 mm safety requirement.
!
Obs:
Varje regulator eller grupp av regulatorer måste försörjas via säkringar på max 16 A.
Det måste vara enkelt att bryta nätspänningne till regulatorn eller till hela anläggningen.
TAC Xenta 121/230 KC2/K4 får även anslutas till 24 V, men då i enlighet med reglerna för 230 V nätspänning efter-
som isolationavståndet till G0-plinten inte uppfyller säkerhetskravet 6.5 mm.
2 (2) 02-00045-01-en, Nov 2009
English - Svenska