Schneider Electric TAC Xenta 121-HP Data Sheet

TAC Vista
TAC Xenta® 121-HP
Programmable Heat Pump Application
TAC Xenta 121-HP is an easily programmable controller intended for heat pumps, with or without re-heat. It can be configured for use with 1, 2, or 3 compressor heat pumps and for a multitude of re-heat types, such as electrical and gas heaters. The controller has different types of fan control and advanced fan control functions, including on/off delays, boosting, and conditioning.
The sequences for cooling, heating, and fan are completely user-programmable, allowing for numerous applications. For energy savings, the controller has built-in economizer functionality. Use TAC Xenta 121-HP with any TAC STR (1.8 kohm) room unit.
Set-up is done using the programming tool TAC ZBuilder, which can be run stand-alone or as a device plug-in to either TAC Vista® or an LNS-based tool. Using Vista or an LNS-based tool, the configuration settings are downloaded into a TAC Xenta 121, prepared with the necessary basic application software.
The controller is a LonMark® compliant device aimed at communicating on a LonTalk® TP/FT-10 channel. It is able to operate both as a stand-alone device and as part of a system. In- and output net work variables can be monitored via the TAC Xenta OP, but programming relies on the use of the TAC ZBuilder.
TECHNICAL DATA
Supply Voltage
HP/24 .....................24 V AC ±20%, 50–60 Hz
HP/230 ....................230 V AC ±10%, 50–60 Hz
Power Consumption
HP/24:
Controller with TAC Xenta OP ....................5 VA
Digital outputs ..................max. 4×19 VA = 76 VA
Total...................................max. 81 VA
HP/230:
Controller with TAC Xenta OP ....................5 VA
Digital outputs, individual outputs, and total ....max. 12 VA
Total...................................max. 20 VA
Ambient Temperature
Operation ................0 °C to +50 °C (32 °F to 122 °F)
................ –20 °C to +50 °C (–4 °F to 122 °F)
Storage Humidity
Enclosure
Material................................ABS/PC plastic
Enclosure rating Flammability class, materials Color Dimensions, mm (in.) Weight, kg (lb..)
Inputs X1–X3
Voltage across open contact .............23 V DC ± 1 V DC
Current through closed contact Minimum pulse input duration
Inputs for Sensors B1–B2
Thermistor type ..............NTC, 1800 W at 25 °C (77 °F)
Measuring range Accuracy
Universal Input U1
As temperature input..................... same as B(1–2)
As digital input As analog input
Input R1
Type ........................10 kW linear potentiometer
Adjustment range
..................max. 90% RH non-condensing
.................................IP 20
...................UL 94 5VB
...................................... gray/red
............. 122×126×50 (4.8x5.0x2)
....... HP/24: 0.3 (0.66), HP/230: 0.6 (1.3)
.....................4 mA
................... 250 ms
.........–10 °C to +50 °C (14 °F to 122 °F)
.............................±0.2 °C (±0.4 °F)
.........................same as X(1–3)
............................ 0–10 V DC
.................. software configurable
Triac Outputs V1–V4 for heating/cooling valve actuators, 24 V AC Internally Supplied
Maximum load per output...... HP/24: 0.8 A, HP/230: 0.5 A
Total output load
Relay Outputs K1–K3
Maximum voltage Maximum resistive load
Relay Output K4
Maximum voltage Maximum resistive load
Voltage Output Y1
................................... 0–10 V DC
Range Maximum load
Indication LED Colors
Power ........................................green
..........................................red
Service
Interoperability
Standard ................. TAC Xenta 121-HP conforms to
o n Ma r k Interoperability Guidelines 3.4 and
L
o n Ma r k Functional Profile: 8503 SCC – Heat Pump
L
Communication protocol Physical channel Neuron® type
Agency Compliances
Emission: CE ............EN 61000-6-3, C-Tick, FCC Part 15
Immunity: CE Safety: CE RoHS directive UL 916, C-UL US, Open Energy Management Equipment (TAC Xenta 121-HP/24) Approved for plenum installations
Part Numbers
Contr Zone TAC Xenta 121-HP/24 .............007306310
Contr Zone TAC Xenta 121-HP/230
..................................0-004-7692
Manual Plug-in Terminal Blocks TAC Xenta 100 Adapter RJ10 to Terminals
............. HP/24: 3.2 A, HP/230: 0.5 A
........................... 250 V AC
............................ 3 A
.......HP/24: 24 V AC, HP/230: 250 V AC
.......... HP/24: 3 A, HP/230: 12 A
.................................2 mA
........................LonTalk
......................TP/FT-10, 78 kbps
......................... 3150®, 10 MHz
............................EN 61000-6-1
................................EN 61010-1
............................2002/95/EG
............007306320
..........007309140
....................007309210
03-00135-04-en
2
03-00135-04-en
APPLICATION EXAMPLES
Window sensor
1-, 2- or
3-speed fan
Wall module
Occupancy sensor
Discharge air sensor
Reheating stage
Outside temp. sensor
Economizer
Heating/Cooloing
compressor
Isolation valve
CO
2
sensor
Reversing valve
Water temp. sensor
Control sequence heat pump (example)
-100 -83 -50 0
0 33 100
Fan
Primary Heating
Secondary Heating
Output signal
Cooling
Terminal Load
TAC Xenta 121-HP can be programmed to work with 1-3 compressors and an optional second heating device, which can have multistage, pwm, analog, or increase/decrease control.
A Heat Pump unit can have a reversing valve and an isolation valve (Fig. 1).
An electrical heater is common as the second device.
The user defines the sequence; there are no restrictions that a specific device be activated first, in parallel, in series, or so on.
Fan control outputs are always multi stage output (1, 2 or 3 stages) or an analog output.
Economizer control using an outside air damper, as well as CO2 control and %RH control are available.
When the temperature in the zone in­crea ses, the heat pump effect decreases, see Fig. 2. If there is still a cooling de­mand, the reversing valve changes, the heat pump effect increases, and the fan speed increa ses in steps until the highest fan speed is reached.
This sequen ce is reversed when the tem­perature drops.
Figure 1: HP with isolation and reversing valves
Figure 2
3
03-00135-04-en
CONTROL OPTIONS
The physical control options are as fol­lows:
Multistage: up to three compressors
1–3 digital outputs are used to give up to three levels of control. A special case of this is one stage, which is just on/off.
Each stage is initiated at a configurable load. Other configuration parameters are: hysteresis, minimum cycle time, and minimum inter-stage time.
It is configurable whether a lower stage shall remain active when the next stage is activated. To achieve an even wear, the stages can be cycled.
The following options are mainly intend­ed for the secondary heating, but may also be used for the primary heating:
Analog, 0–10V Incr/Decr (3-point) Pulse Width Modulation
One digital signal gives a modulating signal by using a variable duty cycle.
General
For the different types of control, differ­ent set-ups like scaling or signal limitation values, hysteresis, timing, and so on can be given.
Any type of control can be used with any equipment, but some types are more suit­able than others.
All control can be done either over physi­cal outputs of the controller or on other devices connected to the controller over a LON® network.
Available I/O
3 digital inputs (X)
2 temperature inputs (B) NTC 1.8 kohm
1 universal input (U), temperature or
digital
1 pot.meter input (R) linear 10 kohm
4 Triac outputs (V): valve actuators or
other devices
4 relay outputs (K): Fan or other devices
1 analog output, 0-10 V (Y): analog or
LED
INSTALLATION
To satisfy regulatory safety requirements, the controller must be built-in when line voltage is connected.
It may be mounted on a DIN rail or fastened onto a surface with screws. There are two sockets provided for that purpose.
Cable lengths
Communication cables: please refer to the TAC Xenta Network Guide, part no. 0-004-7460.
CONFIGURATION OPTIONS
By selecting among the Configuration Modules in the TAC ZBuilder, it is possible to achieve diffe rent options in TAC Xen ta 121-HP for the following:
Space (Wall module) and outside tem-
perature sensors
Discharge (Supply) Air temperature sen-
sor
Water temperature sensor
Setpoint adjustment
Outside air damper (Economizer control)
Relative Humidity sensors, space and
outside
CO2 sensor
Bypass or On/Off button
Room temperature offset scaling
Occupancy sensor
Fan status
Window contact
Freeze protection
Alarm output
TAC Xenta OP can be used to inspect nvi and nvo values. Due to the many con­figuration possibilities, it cannot be used to configure the controller.
OTHER FUNCTIONS
Exception Modes
Exception Mode is a common name for all kinds of situations where normal con­trol no longer can be used.
Up to eight different exception modes can be configured.
Each mode will have its predefined values on heating devices one and two, cooling device, fan status, speed, and outside air damper. If applicable, it can also be con­nected to a digital output.
Each of the eight exception modes has its own indicator in nvoSystemStatus.
When the exception mode situation clears, it is possible to configure if it is allowed to go out of the exception mode and, if so, the delay before normal control is resumed.
Examples where exception modes are useful:
Window contact
Smoke input
Freeze protection
Morning warm-up
Compressor (abort)
Resync
All outputs configured as inc/dec outputs will have a cyclic resync interval of 18 h. Resync can also be initiated via nvi­DOResync. It is configurable to synchro­nize toward open or closed position.
Installations Test – Checkout Mode
To facilitate the testing and installation, it is possible to override the physical out­puts. By setting a certain status override SNVT, all outputs will be controlled by the user, who can test them freely. No fan interlock or other logical conditions will be activated.
Forcing the Space temp makes it possible to verify the sequence.
Unused Digital Inputs and Outputs
Some digital outputs will have a SNVT input, which allows any other LON device to control these digital outputs.
A condition is that the application is not using the output. Some unused inputs will have the same functionality, using a SNVT output.
Not all digital inputs/outputs can have a mirror SNVT, due to the limitation of the SNVTs. If feasible, the same will be ap­plied for analog in/outputs.
Flexible Combinations
By using TAC ZBuilder stand-alone on a PC, you can easily explore the many features and the great versatility of this product.
Please refer to the TAC ZBuilder data sheet 0-003-3010 for further details about the easy way to program your TAC Xenta 121.
4
03-00135-04-en
Lo n Ma r k OBJECTS AND NETWORK VARIABLES
0 - Node Object
Object Type: 0
Mandatory
Network
Variables
Optional
Network
Variables
Configuration Properties
(The Configuration parameters are all handled by the Tool.)
nviRequest SNVT_obj_request
nvoStatus SNVT_obj_status
nvoFileDirectory SNVT_address
nv1
nv2
nv8
Additionally, the following objects are used, all with their con­figuration parameters handled by TAC ZBuilder:
Config. Param. Description
20023 Application Object
20024 Control Object
20026 Fan Object
20028 I/O Object
20025 Temperature Control Device Object
20027 Exception Mode Object
Figure 3
Figure 4
5
03-00135-04-en
HARDWARE INTERFACE
mm (in.)
No. Designation Description
1 X2 Input, digital
2 M Measurement neutral
3 X3 Input, digital
4 B2 Input, temperature sensor
5 Y1 Output, analog
6 M Measurement neutral
7 X1 Input, digital
8 R1 Input, setpoint offset dial on wall module
9 M Measurement neutral
10 B1 Input, temperature sensor
11 K4 Output, relay 4
12 KC2 Relay 4, common
13 G0 or N See 14
14 G or L HP/24: 24 V AC Supply
HP/230: Mains Supply
OP TAC Xenta OP RJ-10 access
connector
DIMENSIONS
No. Designation Description
15 C1 TP/FT-10 communication channel
16 C2 See above
17 M Measurement neutral
18 U1 Input, temp. sensor/digital/analog
19 V1 Output, Triac 24 V AC
20 G 24 V AC (L) output for V1 and V2
21 V2 Output, Triac 24 V AC
22 V3 Output, Triac 24 V AC
23 G 24 V AC (L) output for V3 and V4
24 V4 Output, Triac 24 V AC
25 K3 Output, relay 3
26 K2 Output, relay 2
27 K1 Output, relay 1
28 KC1 Relay 1-3, common
Figure 5
ROOM UNITS
The STR is a series of wall modules optimized for public facilities such as office build­ings, hotels, hospitals, schools, and shopping malls.
The following room units can be configured with the TAC Xenta 121-HP.
Model Temp.
Sensor
STR100 X
Mode Indicator
Setpoint Offset
Bypass Button
Fan Speed Control
Back Light
SNVT Binding Required
STR101 X X
STR102 X X X
STR103 X X X
STR104 X X X X
STR106 X X X X X*
STR107 X X X X X**
STR150 X X X X X***
STR350 X X X X X*** X
STR351 X X X X X*** X X
PART NUMBERS
STR100 .................004600100
STR100-W (White) ........004600110
STR101 .................004600200
STR102 .................004600300
STR103 .................004600700
STR104 .................004600400
STR106 .................004600500
STR107 .................004600600
STR150 .................004602800
LON Modules
STR350 .................004605000
STR351 .................004605100
* STR106 Fan speed: Auto-0-I-II-III ** STR107 Fan speed: Auto-Off-On *** STR150, 350/351 Fan speed: configurable
Copyright © 2008-2012, Schneider Electric All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice. All rights reserved.
03-00135-04-en Feb 2012
Loading...