Schneider Electric TAC Xenta 104-A Data Sheet

TAC Vista
TAC Xenta® 104-A
Roof Top Unit Controller
The TAC Xenta 104-A is a zone controller for roof top units, small AHU, and unit ventilator app lications that have heating, cooling, and econo mizer functions. The con trol ler keeps a constant zone temperature through sequenced con trol of the heating, cooling and OA/RA dampers.
By using a discharge air temperature sensor, the discharge and zone temperatures may be controlled in cas cade if the TAC Xenta 104-A configuration properties are set ac cor ding ly. Cascade control also allows mini mum and max i mum limiting of the discharge air tem perature. The fan On/Off is controlled by a 24 VAC isolated relay con tact. The fan mode may be selected to operate conti nuous during the occupied mode, or cycle with heating or cool ing demand from the zone.
The controller is a LonMark compliant device that com municates on a LonTalk TP/FT-10 network via a twis ted-pair, polarity insensi­tive cable. It is able to operate both as a stand-alone unit and as part of a network sys tem. All network variables can be monitored and configu red via the network or by using the TAC Xenta OP (version 3.11 or higher).
A selection of wall modules with various options can be used with the TAC Xenta 104-A controller. The wall mo dules are from the STR100 series.
Supply voltage............ 24 V AC –10% +20%, 50–60 Hz
Power consumption:
Controller with TAC Xenta OP .................... 5 VA
Digital outputs ..................max. 4×19 VA = 76 VA
Total...................................max. 81 VA
Ambient Temperature
Storage ...............–25 °C to +50 °C (–13 °F to 122 °F)
Operation .............–25 °C to +50 °C (–13 °F to 122 °F)
Humidity ..................max. 90% RH non-condensing
Mechanical
Enclosure....................................ABS/PC
Enclosure rating.................................IP 30
Flammability class, materials ...................UL 94 5VB
Dimensions ................................ see Fig. 1
Weight ...............................0.4 kg (0.88 lb)
Inputs/Outputs
Inputs X2–X3 for fan status and alarm sensor:
Voltage across open contact............23 V DC ±1 V DC
Current through closed contact ...................4 mA
Minimum pulse input duration .....................17 s
Outputs V1–V4 for heating/cooling (triac):
Type of actuator..................... increase/decrease
Minimum output voltage ...........supply voltage – 1.5 V
Maximum load................................0.8 A
Relay outputs for fan on-off control, K1 and KC1:
Maximum voltage .......................... 24 V AC
Maximum load................................. 2 A
Input for bypass button on wall module:
Minimum pulse input duration .................. 250 ms
Inputs for zone temperature and discharge/mixed air sen sors, B1–B2:
Thermistor type ......... NTC, 1800 Ohm at 25 °C (77 °F)
Measuring range ........–10 °C to 50 °C (14 °F to 122 °F)
Accuracy ...........................±0,2 °C (±0.4 °F)
Input R1, setpoint adjustment on wall module:
Type.................... 10 kOhm linear potentiometer
Adjustment range....................... ±5 °C (±9 °F)
Accuracy ...........................±0,1 °C (±0.2 °F)
Application Program
Cycle time .......................................5 s
Indication LED Colors
Power On .....................................green
Service..........................................red
LonMark Standard
................... LonMark Interoperability Guidelines
..............LonMark Functional Profile: RTU Controller
Communication protocol ........................LonTalk
Physical channel ......................TP/FT-10, 78 kbps
Neuron type ............................3150, 10 MHz
Agency Compliances
Emission:
CE ..................EN 61000-6-3, C-Tick, FCC Part 15
Immunity:
CE ..................................EN 61000-6-1
Safety:
CE ....................................EN 61010-1
UL 916, C-UL US, Enclosed Energy Management Equipment (TAC Xenta 104-A/24) Approved for plenum installations (TAC Xenta 104-A/24)
RoHS directive............................2002/95/EG
Part Numbers
Controller ................................007305910
Manual .................................04-00068-01
Plug-in Terminal Blocks TAC Xenta 100 ..........007309140
03- 00132-02-en
Figure 1
Outdoor
A
ir Sensor
Economizer
Heating
stage
Alarm
Fan
Wall
Module
Discharge air
Temperature
sensor
G
Fan
Status
Cooling
stage
W1 W2 Y1 Y2
Mixed air
Temperature
sensor
1
2 2
2
03- 00132-02-en
APPLICATION EXAMPLE
Figure 2
1) Only relevant in stand alone installations.
2) One of the sensors can be used in a stand alone installation.
Both can be used in a network installation.