this document and reserves the right to make changes, additions or deletions. Schneider Electric Buildings AB assumes no responsibility for
possible mistakes or errors that might appear in this document.
Do not use the product for other purposes than those indicated in this document.
Only licensed users of the product and the document are permitted to use the document or any information therein. Distribution, disclosure,
copying, storing or use of the product, the information or the illustrations in the document on the part of non-licensed users, in electronic or
mechanical form, as a recording or by other means, including photo copying or information storage and retrieval systems, without the express
written permission of Schneider Electric Buildings AB, will be regarded as a violation of copyright laws and is strictly prohibited.
Trademarks and registered trademarks are the property of their respective owners.
Zone Controller, TAC Xenta 104-A1 Documentation and Terminology
1Documentation and Terminology
1.1Documentation
Enclosed Documentation
TAC Xenta 104 is delivered with an installation instruction:
•Installation instruction, TAC Xenta 104
Other Documentation
There is additional information about TAC Xenta 104 in the following
documents:
•Data sheet for TAC Xenta 104
•Data sheet for ZS 101–ZS 105
•Data sheet for STR100–STR107
•Data sheet for STR150
•Data sheet for STR350/351
•TAC Xenta Network Guide
•TAC Xenta OP Handbook
All the above mentioned documents can be found on the internet at
or can be ordered from your
nearest Schneider Electric service point.
Schneider Electric Buildings AB, Mar 20109 (74)
04-00068-01-en
1 Documentation and Terminology Zone Controller, TAC Xenta 104-A
1.2Terminology
This handbook contains some abbreviations and terms, which are specific for the zone controller’s applications and network communication.
The most common terms are explained in Table 1.1, “Terminology”.
Table 1.1: Terminology
neuron
A communication processor with built-in
protocol
node
A communication unit on the network
SNVTStandard Network Variable Type
nvixxxVariable that gets its value from another
unit on the network
nvoxxxVariable that is sent to another unit on the
network
ncixxx Configuration parameter; variable that
gets its value from another unit on the network and keeps it during a power failure
service pinFunction that can be used during installa-
tion on the network
wink
A confirmation that the connection to a
controller via the network is working (a
LED is lit for appr. 20 seconds)
LNS
LonWork
®
Network Services. System tool
for installation, configuration and maintenance of LonWorks network
10 (74)Schneider Electric Buildings AB, Mar 2010
04-00068-01-en
REFERENCE
2Zone Controller TAC Xenta 104
3Installation
4Configuration Parameters
5Functional Description
6Troubleshooting
7Technical Data
8Communication
Zone Controller, TAC Xenta 104-A2 Zone Controller TAC Xenta 104
2Zone Controller TAC Xenta 104
2.1General
The TAC Xenta® 104-A is a zone controller intended for roof top unit,
small AHU, and unit ventilator applications which have heating, cooling, and economizer functions. The controller maintains a constant zone
temperature by sequenced control of the heating, cooling, and OA/RA
dampers. By using a discharge air temperature sensor, the discharge and
zone temperatures may be controlled in cascade if the TAC Xenta 104A configuration properties are set accordingly.
Cascade control also allows minimum and maximum limiting of the discharge air temperature. The fan On/Off is controlled by a 24 VAC isolated relay contact. The fan mode may be selected to operate continuous
during the Occupied mode, or cycle with heating or cooling demand
from the zone.
The Controller’s Basic Functions
The controller has a number of built-in functions that are designed to
handle normal control situations. There are two operating modes to
choose from (occupied and unoccupied) and five application modes
(heating only, cooling only, auto changeover, fan only and off).
The zone temperature is measured using a permanent thermistor sensor
or a temperature node connected to the network. Setpoint calculations
are made in line with defined methods. Fan control during the comfort
mode can be either continuous or cycling with heating or cooling functions. The economizer will only function in the cooling or auto
changeover modes. If the outdoor air is useful for cooling, the economizer will use it and provide energy savings and prevent damper hunting when cooling is cycling on and off.
For a detailed functional description of all the basic please see
Chapter 5.2, “The Controller’s Basic Functions”, on page 40.
More About Functions
Apart from the controller’s basic functions, there are a number of other
functions for controlling the climate in the zone; these are described in
detail in Chapter 5.3, “More About Functions”, on page 45. Additional
external functions that can be connected are also described in this chapter, these include window contact sensor and occupancy sensor.
Schneider Electric Buildings AB, Mar 201013 (74)
04-00068-01-en
2 Zone Controller TAC Xenta 104 Zone Controller, TAC Xenta 104-A
Communication
The controller can work either as a stand-alone unit, without being connected to a network during operation, or be a part of a larger system with
several other units such as TAC Xenta 300/400 and other zone controllers in the TAC Xenta family.
TAC Vista is an excellent tool for reading variables as well as a configuration tool for commissioning and/or operation purposes. When TAC
Vista is not part of the system, reading and configuration of variables
can be made from the operating panel TAC Xenta OP, version 3.11 or
later.
The controller is LonMark
®
TP/FT-10 network via a twisted-pair, unpolarized cable. If you
Talk
want to know more about the LonWorks
®
approved and communicates on a Lon-
®
technology visit www.eche-
lon.com or www.lonmark.org.
2.2Wall Modules
A temperature sensor must be mounted within in the zone to be controlled. In the STR series of wall modules the temperature sensor is
combined with various types of user interface. Several STR models can
be used with the TAC Xenta 104-A; the choice is determined by the
desired functionality and user interface.
2.2.1STR350/351
•STR350/351. Wall unit with temperature sensor and LCD display.
Extensive functionality for zone control. Communicates with the
controller over LonWorks.
•STR150. Wall unit with temperature sensor and LCD display.
Incorporates the most common functions for zone control. Oneway serial communication with the controller.
•STR100-104. Wall module with temperature sensor and controls
for the most common zone control functions. STR100-104 signals
are hard-wired to TAC Xenta 104-A I/O.
STR350/351 communicates over LonWorks. LonWorks is used for all
data exchanges between the room unit and the controller.
STR350/351 has the following functionality when used with
TAC Xenta 104-A:
•Temperature sensor . Use either the built in thermistor element or
any other temperature sensor available on the LonWorks network
•Actual temperature display. The actual zone temperature ca n be
displayed on the LCD. It can also be hidden if preferred.
•Temperature setpoint display. The temperature setpoint can be
displayed, either as an absolute value or as an offset.
14 (74)Schneider Electric Buildings AB, Mar 2010
04-00068-01-en
Zone Controller, TAC Xenta 104-A2 Zone Controller TAC Xenta 104
Fig. 2.1: Wall module STR150
Bypass button
Increase/Decrease
buttons
Fan speed control
Display
•Temperature setpoint adjustment. The temperature setpoint can
be adjusted, either as an absolute value or as an offset.
•Bypass or on/off button. The bypass function forces the control-
ler to comfort mode for a configurable period of time. The same
button can also be used as an on/off button.
•Mode Indicator. An On/Off symbol in the LCD indicates the
mode of the control.
See STR350/351 configuration and data sheets for more details about
the technical characteristics listed above, additional functions and configuration details.
Use the LNS plug-in to configure STR350/351.
2.2.2STR150
STR150 is connected to TAC Xenta 104-A using two or three wires; the
third wire is used if mode indication in the LCD is required. On the other
two wires information is sent from the wall unit to the controller:
•Zone temperature. The temperature sensed by the thermistor ele-
ment.
•Temperature setpoint. The temperature setpoint is displayed as
an absolute temperature, but transmitted as an offset to the configured reference temperature.
•Bypass button. The bypass button forces the controller to comfort
mode for a fixed period of time (2h).
The mode indication signaled on the third wire is connected to the symbol of a man in the LCD:
•Comfort mode (On) is indicated by a steady symbol
Schneider Electric Buildings AB, Mar 201015 (74)
04-00068-01-en
2 Zone Controller TAC Xenta 104 Zone Controller, TAC Xenta 104-A
Fig. 2.2: Wall module STR104 as an example
Mode indicator
On/Off
Bypass button
Temperature
setting wheel
•Economy (Standby) mode is indicated by a flashing symbol.
•If the symbol is not shown (off) the zone is unoccupied.
There is no communication from the controller to the unit. This means
that if a setpoint is changed using TAC Vista, the new value cannot be
displayed on STR150.
STR150 is configured using the buttons and display on the unit. See
STR150 configuration and data sheets for details.
2.2.3STR100-104
STR100-104 is a series of room units that connect to the I/O terminals
of TAC Xenta 104-A. The functionality of the various models are
shown in the Table 2.1, “STR100-104 functionality”.
Table 2.1: STR100-104 functionality
ModelTemp Sensor
STR100X
STR101XX
STR102XXX
STR103XXX
STR104XXXX
Mode
Indicator
Setpoint
Adjustment
Bypass Button
Note
•The TAC Xenta OP is normally connected directly to the controller, not the wall module. The TAC Xenta 101-VF has a TAC
Xenta OP access connecter (type RJ-10) on the controller instead
of dedicated terminals for the wall module.
16 (74)Schneider Electric Buildings AB, Mar 2010
04-00068-01-en
Zone Controller, TAC Xenta 104-A2 Zone Controller TAC Xenta 104
Depending on model the following functionality may also be present:
•Temperature Sensor. All models have a 1.8Kohms@25°C ther-
mistor element.
•Temperature Adjustment. The temperature setpoint can be
adjusted. Using the plastic keys on the rear of the core panel the
adjustment range can be set.
•Mode Indicator. The green LED indicates the control mode:
•Comfort mode (On) is indicated by a steady green light
•If the LED is off the zone is unoccupied.
•Bypass button. The bypass button forces the controller to comfort
mode for fixed period of time (2h).
Refer to STR100-107 data sheet and installation sheet for details.
2.2.4Wall Module Configuration
Wall Module Choice
STR150 is enabled by nciAppOptions bit 14:
•0 = ZS, STR100-104 or STR350/351 (default)
•1 = STR150
This can be set using the LonMaker Xenta100 plug-ins in Toolpack ver-
sion 2.01 or higher, or by means of TAC Xenta OP.
Initial Start Up Status
•SpaceTemp in the application is set to +20.00 Celsius (This can
not be read in the nviSpaceTemp, however it can be read in nvoSpaceTemp)
•Fan is set to Fan Auto
TAC Xenta can now accept for data from the STR module.
If no room temperature readings are received within 10 minutes, the
SpaceTemp in the application is set to “invalid”. This is shown as
“invalid” in nvoSpaceTemp.
When the first update is received then the 10-minute limit is changed to
5 minutes.
Unless there is a restart, the Offset + Fan values are not cleared and the
last value is valid.
Note
•Fore more information on how to configure and engineer the
STR series of wall modules see respective product documents.
Schneider Electric Buildings AB, Mar 201017 (74)
04-00068-01-en
2 Zone Controller TAC Xenta 104 Zone Controller, TAC Xenta 104-A
2.2.5General
The controller is suitable for a variety of applications such as RTU
(Roof Top Units), small Unit Ventilators and small AHU (Air Handling
Units).
Cooling control is achieved by one or two cooling stages in sequence
based on zone temperature from the wall module.
Heating control is achieved by one or two heating stages based on zone
temperature or as an alternative tri-state valve control based on discharge air temperature.
For economizer control a sensor is connected in the mixed- or discharge
air stream depending of application.
A fan is controlled according to configuration settings.
Different configuration options can be chosen to fit both networked and
stand-alone applications.
The TAC Xenta 104 controller incorporates several features:
•a fan status switch to stop the heating and cooling functions, c an
be connected.
•an auxiliary alarm sensor can be connected.
•the fan can be configured to run continous or cycle on a call for
heating or cooling.
•A discharge air temperature sensor can be connected for controlling the discharge air temperature and the zone temperature in
cascade.
2.2.6HVAC Controller, Network Installation
In networked applications a SNVT supplies the out-door air temperature for economizer and compressor lockout functions.
For economizer control a sensor is connected in the mixed air stream in
both two stage and tri-state modes.
For detailed description about networked applications, please see
Chapter 5.3.5, “Networked Applications”, on page 48.
In stand-alone applications the outdoor air temperature for economizer
and compressor lockout functions is supplied by a physical input.
For economizer control a sensor is connected in the discharge air stream
in both two stage and tri-state modes.
18 (74)Schneider Electric Buildings AB, Mar 2010
04-00068-01-en
Zone Controller, TAC Xenta 104-A2 Zone Controller TAC Xenta 104
H1 H2C1 C2
Fig. 2.3: RTU application for HVAC controller network installation
Economizer
Mixed air temperature sensor
(input B2)
Heating
stage
Cooling
stage
Alarm
Fan
Fan
Status
Discharge air temperature sensor
(optional at input U1)
Wall
module
Fig. 2.4: AHU or Unit Ventilator applications for HVAC controller
network installation
Economizer
Mixed air temperature sensor
(input B2)
Heating
stage
Cooling
stage
Alarm
Fan
Fan
Status
Discharge air temperature sensor
(input U1)
Wall
module
For detailed description about stand-alone applications, please see
Chapter 5.3.6, “Stand-alone Applications”, on page 49.
Inc. Dec.C1 C2
2.2.7HVAC Controller, Stand-alone Installation
In stand-alone applications the outdoor air temperature for economizer
and compressor lockout functions is supplied by a physical input.
Schneider Electric Buildings AB, Mar 201019 (74)
04-00068-01-en
2 Zone Controller TAC Xenta 104 Zone Controller, TAC Xenta 104-A
H1 H2C1 C2
Economizer
Outdoor air
sensor
(input U1)
Heating
stage
Cooling
stage
Alarm
Fan
Fan
Status
Discharge air temperature
sensor (input B2)
Wall
module
Fig. 2.5: RTU application for HVAC controller, stand-alone
Economizer
Outdoor air
sensor
(input U1)
Heating
stage
Cooling
stage
Alarm
Fan
Fan
Status
Discharge air temperature
sensor (input B2)
Wall
module
Fig. 2.6: AHU or Unit Ventilator application for HVAC controller, stand-alone
For economizer control a sensor is connected in the discharge air stream
in both two stage and tri-state modes.
For detailed description about stand-alone applications, please see
Chapter 5.3.6, “Stand-alone Applications”, on page 49.
Inc. Dec.C1 C2
20 (74)Schneider Electric Buildings AB, Mar 2010
04-00068-01-en
Zone Controller, TAC Xenta 104-A3 Installation
Fig. 3.1: TAC Xenta 104-A fixed on a DIN rail
3Installation
3.1Mechanical Installation
3.1.1Fitting
The TAC Xenta 104-A can either be snapped onto a DIN rail (Fig. 3.1)
or fixed to a level surface with two screws. (Fig. 3.2).
Fastening the controller onto a DIN rail:
1Place the controller on the top of the rail as shown by arrow 1.
2Twist the controller downwards until it snaps onto the rail as
shown by arrow 2.
3T o remove use place a screwdriver to locate the lock on the bottom
of the controller and pull down. Lift the controller diagonally
upwards and off the rail.
Schneider Electric Buildings AB, Mar 201021 (74)
04-00068-01-en
3 Installation Zone Controller, TAC Xenta 104-A
Fig. 3.2: TAC Xenta 104-A fixed to a level surface
Fixing the controller to a level surface:
Use the two sockets provided for fixing the controller; the maximum
screw size is M4 or ST 3,5 (Ø 0.15"). The head of the screw should not
exceed 7,5 mm (0.3") in diameter.
3.2Electrical Installation
3.2.1General
1Each controller or group of controllers must use max. 6 A fuses.
2Avoid hanging or loose cables by using clamps to secure them to
the controller.
3A switch to cut off the power supply to the controller or compete
unit must be easily accessible.
4Connect U1 and M with a jumper when not used.
5When several Xenta controllers receive power from a common
transformer, it is important that all Gs are connected to each other
and that all G0s are connected to each other. They must not be
interchanged. An important exception: G0 on the wall module
should not be connected with the other G0’s. Instead it should be
connected to the terminal OP on the controller. At the transformer,
G0 should be connected to protective earth. This is to get an
grounding point for interference diversion.
6To ensure that the specified measuring accuracy is achieved, the
two M terminals must be connected to the wall module.
NOTE: This equipment has been tested and found to comply with the
limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
22 (74)Schneider Electric Buildings AB, Mar 2010
04-00068-01-en
Zone Controller, TAC Xenta 104-A3 Installation
These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed
and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that
interference will not occur in a particular installation. If this equipment
does cause harmful interference to radio or television reception, which
can be determined by turning the equipment off and on, the user is
encouraged to try to correct the interference by one or more of the following measures:
•Reorient or relocate the receiving antenna.
•Increase the separation between the equipment and receiver.
•Connect the equipment into an outlet on a circuit different from
that to which the receiver is connected.
•Consult the dealer or an experienced radio/TV technician for help.
Safety Standard
Transformers supplying the controller must comply to the safety standard EN 60 742 or any other relevant safety standard for ELV, 24 V AC.
ETL listing: UL 3111-1, first edition and CAN/CSA C22.2 No. 1010.1-
92. When connecting equipment that has an independent power supply,
the power supply must also comply with this norm.
Cable Lengths
For information on communication cable lengths, see TAC Xenta Network Guide, part number 0-004-7460. For all other cables, maximum
length is 30 m (100 feet) and min. area is 0,7 mm
2
(AWG-19).
The Wall Modules
The STR100-104 is primarily intended for use with the Xenta 104-A.
For more information about how to connect and configure wall modules, please refer to the documentation for each respective product.
Schneider Electric Buildings AB, Mar 201023 (74)
04-00068-01-en
Loading...
+ 51 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.