For More Information..............................................................................28
Publication 1769-IN067B-EN-P - September 2005
2 Compact I/O 1769-IF8 Analog Input Module
Module Description
V/I in 0-
ANLG Com
V/I in 1-
ANLG Com
V/I in 2-
ANLG Com
V/I in 3-
ANLG Com
NC
2a
WARNING -Do Not
Remove RTB Unless
Area is Non-Hazardous
V in 0+
V/I in 4-
I in 0+
ANLG Com
V in 1+
V/I in 5-
I in 1+
ANLG Com
V in 2+
V/I in 6-
I in 2+
ANLG Com
V in 3+
V/I in 7-
I in 3+
ANLG Com
NC
1769-IF8
2b
3
V in 4+
I in 4+
V in 5+
I in 5+
V in 6+
I in 6+
V in 7+
I in 7+
NC
NC
1
OK
INPUT
Analog
10a
10
10b
8a
7a
7a
5a
9
7b
7b
8b
Item Description
1bus lever
(with locking function)
2aupper panel mounting tab
2blower panel mounting tab
3module status LED
4module door with terminal
identification label
4
5amovable bus connector
with female pins
5bstationary bus connector
with male pins
6nameplate label
7aupper
tongue-and-groove slots
7blower
5b
tongue-and-groove slots
8aupper DIN rail latch
6
8blower DIN rail latch
9write-on label (user ID tag)
10removable terminal block (RTB)
with finger-safe cover
10aRTB upper retaining screw
10bRTB lower retaining screw
Publication 1769-IN067B-EN-P - September 2005
Compact I/O 1769-IF8 Analog Input Module 3
Module Installation
Compact I/O is suitable for use in an industrial environment when installed in
accordance with these instructions. Specifically, this equipment is intended for use
in clean, dry environments (Pollution degree 2
Over Voltage Category II
(2)
(IEC 60664-1).
Prevent Electrostatic Discharge
(1)
) and to circuits not exceeding
(3)
ATTENTION
Remove Power
ATTENTION
Electrostatic discharge can damage integrated circuits or
semiconductors if you touch bus connector pins or the terminal
block. Follow these guidelines when you handle the module:
• Touch a grounded object to discharge static potential.
• Wear an approved wrist-strap grounding device.
• Do not touch the bus connector or connector pins.
• Do not touch circuit components inside the module.
• If available, use a static-safe work station.
• When not in use, keep the module in its static-shield box.
Remove power before removing or inserting this module. When
you remove or insert a module with power applied, an electrical
arc may occur. An electrical arc can cause personal injury or
property damage by:
• sending an erroneous signal to your system’s field devices,
causing unintended machine motion
• causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create
electrical resistance.
(1)
Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that occasionally a
temporary conductivity caused by condensation shall be expected.
(2)
Over Voltage Category II is the load level section of the electrical distribution system. At this level transient voltages are
controlled and do not exceed the impulse voltage capability of the product’s insulation.
(3)
Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC) designations.
Publication 1769-IN067B-EN-P - September 2005
4 Compact I/O 1769-IF8 Analog Input Module
System Assembly
The module can be attached to the controller or an adjacent I/O module before or
after mounting. For mounting instructions, see “Panel Mounting” on page 6, or
“DIN Rail Mounting” on page 7. To work with a system that is already mounted, see
“Replacing a Single Module within a System” on page 7.
The following procedure shows you how to assemble the Compact I/O system.
3
4
2
1. Disconnect power.
2. Check that the bus lever of the module to be installed is in the unlocked
(fully right) position.
3. Use the upper and lower tongue-and-groove slots (1) to secure the modules
together (or to a controller).
4. Move the module back along the tongue-and-groove slots until the bus
connectors (2) line up with each other.
5. Push the bus lever back slightly to clear the positioning tab (3). Use your
fingers or a small screwdriver.
1
1
5
6
30536-M
Publication 1769-IN067B-EN-P - September 2005
Compact I/O 1769-IF8 Analog Input Module 5
6. To allow communication between the controller and module, move the bus
lever fully to the left (4) until it clicks. Ensure it is locked firmly in place.
ATTENTION
When attaching I/O modules, it is very important that the bus
connectors are securely locked together to ensure proper
electrical connection.
7. Attach an end cap terminator (5) to the last module in the system by using
the tongue-and-groove slots as before.
8. Lock the end cap bus terminator (6).
IMPORTANT
A 1769-ECR or 1769-ECL right or left end cap must be used to
terminate the end of the communication bus.
Mounting Expansion I/O
ATTENTION
During panel or DIN rail mounting of all devices, be sure that all
debris (metal chips, wire strands, etc.) is kept from falling into the
module. Debris that falls into the module could cause damage on
power up.
Minimum Spacing
Maintain spacing from
enclosure walls,
wireways, adjacent
equipment, etc. Allow 50
mm (2 in.) of space on all
sides for adequate
ventilation, as shown:
Top
Host Controller
SideSide
Compact I/O
Bottom
Compact I/O
Compact I/O
End Cap
Compact I/O
Compact I/O
Publication 1769-IN067B-EN-P - September 2005
6 Compact I/O 1769-IF8 Analog Input Module
Panel Mounting
Mount the module to a panel using two screws per module. Use M4 or #8 panhead
screws. Mounting screws are required on every module.
Panel Mounting Using the Dimensional Template
Spacing for one-and-a-half-wide modules 52.5 mm (2.067 in).
Spacing for single-wide modules 35 mm (1.378 in).
Refer to host controller documentation for this dimension.
NOTE: Overall hole spacing
tolerance: ±0.4 mm (0.016 in.)
l Mounting
Locate holes every 17.5 mm (0.689 in) to allow for a
mix of single-wide and one-and-a-half-wide modules
(e.g., 1769-OA16).
Host Controller
Panel Mounting Procedure Using Modules as a Template
The following procedure allows you to use the assembled modules as a template
for drilling holes in the panel. If you have sophisticated panel mounting equipment,
you can use the dimensional template provided on
mounting hole tolerance, it is important to follow these procedures:
1. On a clean work surface, assemble no more than three modules.
2. Using the assembled modules as a template, carefully mark the center of all
module-mounting holes on the panel.
3. Return the assembled modules to the clean work surface, including any
previously mounted modules.
4. Drill and tap the mounting holes for the recommended M4 or #8 screw.
5. Place the modules back on the panel and check for proper hole alignment.
6. Attach the modules to the panel using the mounting screws.
NOTE
If mounting more modules, mount only the last one of this
group and put the others aside. This reduces remounting time
during drilling and tapping of the next group.
page 6. Due to module
7. Repeat steps 1 to 6 for any remaining modules.
Publication 1769-IN067B-EN-P - September 2005
Compact I/O 1769-IF8 Analog Input Module 7
DIN Rail Mounting
The module can be mounted using the following DIN rails: 35 x 7.5 mm (EN 50 022
- 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15).
Before mounting the module on a DIN rail, close the DIN rail latches. Press the DIN
rail mounting area of the module against the DIN rail. The latches will momentarily
open and lock into place.
Replacing a Single Module within a System
The module can be replaced while the system is mounted to a panel (or DIN rail).
Follow these steps in order:
1. Remove power. See important note on page 3.
2. On the module to be removed, remove the upper and lower mounting
screws from the module (or open the DIN latches using a flat-blade or
phillips-style screwdriver).
3. Move the bus lever to the right to disconnect (unlock) the bus.
4. On the right-side adjacent module, move its bus lever to the right (unlock)
to disconnect it from the module to be removed.
5. Gently slide the disconnected module forward. If you feel excessive
resistance, check that the module has been disconnected from the bus and
that both mounting screws have been removed (or DIN latches opened).
NOTE
6. Before installing the replacement module, be sure that the bus lever on the
module to be installed, and on the right-side adjacent module are in the
unlocked (fully right) position.
7. Slide the replacement module into the open slot.
8. Connect the modules together by locking (fully left) the bus levers on the
replacement module and the right-side adjacent module.
9. Replace the mounting screws (or snap the module onto the DIN rail).
It may be necessary to rock the module slightly from front to
back to remove it, or, in a panel-mounted system, to loosen
the screws of adjacent modules.
Publication 1769-IN067B-EN-P - September 2005
8 Compact I/O 1769-IF8 Analog Input Module
Module Spare/Replacement Parts
• Terminal block, catalog number 1769-RTBN18 (1 per kit)
Field Wiring Connections
Grounding the Module
This product is intended to be mounted to a well-grounded mounting surface such
as a metal panel. Additional grounding connections from the module’s mounting
tabs or DIN rail (if used), are not required unless the mounting surface cannot be
grounded. Refer to Industrial Automation Wiring and Grounding Guidelines,
Allen-Bradley publication 1770-4.1, for additional information.
System Wiring Guidelines
Consider the following when wiring your system:
• All module commons (ANLG COM) are connected in the analog module.
The analog common (ANLG COM) is not connected to earth ground inside
the module.
• Do not use the analog module’s NC terminals as connection points.
• Channels are not isolated from each other.
• Use Belden™ 8761, or equivalent, shielded wire.
• Under normal conditions, the drain wire and shield junction must be
connected to earth ground via a panel or DIN rail mounting screw at the
analog I/O module end. Keep the shield connection to ground as short as
possible.
• To ensure optimum accuracy, limit overall cable impedance by keeping your
cable as short as possible. Locate the I/O system as close to your sensors or
actuators as your application will permit.
• If multiple power supplies are used with analog inputs, the power supply
commons must be connected.
(1)
In environments where high-frequency noise may be present, it may be necessary to directly ground cable shields to earth
at the module end and via a 0.1µF capacitor at the sensor end.
Publication 1769-IN067B-EN-P - September 2005
(1)
Compact I/O 1769-IF8 Analog Input Module 9
+
–
–
• The 1769-IF8 module does not provide loop power for analog inputs. Use a
power supply that matches the input transmitter specifications.
• Differential analog inputs are more immune to noise than single-ended
analog inputs.
• Voltages on Vin+, V/Iin-, and Iin+ of the 1769-IF8 module must be within
±10V dc of analog common.
ATTENTION
Be careful when stripping wires. Wire fragments that fall into a
module could cause damage at power up. Once wiring is
complete, ensure the module is free of all metal fragments.
Wiring Differential Inputs
Belden 8761 cable (or equivalent)
V/I in 0-
ANLG Com
V/I in 1-
ANLG Com
V/I in 2-
ANLG Com
V/I in 3-
ANLG Com
NC
V in 0+
I in 0+
V in 1+
I in 1+
V in 2+
I in 2+
V in 3+
I in 3+
NC
+
earth ground the
shield locally at
the module
V/I in 4-
ANLG Com
V/I in 5-
ANLG Com
V/I in 6-
ANLG Com
V/I in 7-
ANLG Com
NC
analog source
V in 4+
I in 4+
V in 5+
I in 5+
V in 6+
I in 6+
V in 7+
I in 7+
NC
Publication 1769-IN067B-EN-P - September 2005
10 Compact I/O 1769-IF8 Analog Input Module
–
–
Wiring Single-Ended Sensor/Transmitter Types
Sensor/Trans
mitter
Supply
1The sensor power supply
must be rated Class 2.
+
-
(1)
Current
Transmitter
+
Signal
Voltage
Transmitter
+
Ground
Voltage
Transmitter
+
Ground
Signal
Signal
1769-IF8 Terminal Block
V in 0 +
in
0
-
V/I
I in 0 +
AN
LG
C
o
m
V in 1 +
in
1
-
V/I
I in 1 +
AN
LG
C
o
m
V in 2 +
V/I in 2
-
I in 2 +
AN
LG
C
o
m
V in 3 +
V/I
in
3
-
I in 3 +
AN
LG
C
o
m
NC
NC
Wiring for channels 4-7 are identical.
Wiring Mixed Transmitter Types
Single-ended
Signal
Voltage
Transmitter
+
–
Signal
Differential
Voltage
Transmitter
Supply
Differential
Current
Transmitter
Supply
2-Wire
Current
Transmitter
+
–
+
–
Signal
+
+
Signal
+
1769-IF8 Terminal Block
V in 0 +
V/I in 0 I in 0 +
ANLG Com
V in 1 +
V/I in 1 I in 1 +
ANLG Com
V in 2 +
V/I in 2 I in 2 +
ANLG Com
V in 3 +
V/I in 3 I in 3 +
ANLG Com
NC
NC
Sensor/
Transmitter
Supply
+
(1)
–
Publication 1769-IN067B-EN-P - September 2005
1The sensor power supply
must be rated Class 2.
Wiring for channels 4-7 are identical.
Compact I/O 1769-IF8 Analog Input Module 11
Labeling the Terminals
A removable, write-on label is provided with the module. Remove the label from
the door, mark the identification of each terminal with permanent ink, and slide the
label back into the door. Your markings (ID tag) will be visible when the module
door is closed.
upper retaining screw
lower retaining screw
wiring the
finger-safe
terminal block
Removing the Finger-Safe Terminal Block
When wiring field devices to the module, it is not necessary to remove the terminal
block. If you remove the terminal block, use the write-on label on the side of the
terminal block to identify the module slot location and type. RTB position can be
indicated by circling either the ‘R’ for right side or ‘L’ for left side.
To remove the terminal block, loosen the upper and lower retaining screws. The
terminal block will back away from the module as you remove the screws. When
replacing the terminal block, torque the retaining screws to 0.46 Nm (4.1 in-lbs).
Publication 1769-IN067B-EN-P - September 2005
12 Compact I/O 1769-IF8 Analog Input Module
Wiring the Finger-Safe Terminal Block
When wiring the terminal block, keep the finger-safe cover in place.
1. Loosen the terminal screws to be wired.
2. Route the wire under the terminal pressure plate. You can use the bare wire
or a spade lug. The terminals will accept a 6.35 mm (0.25 in.) spade lug.
NOTE
The terminal screws are non-captive. Therefore, it is possible
to use a ring lug [maximum 1/4 inch o.d. with a 0.139 inch
minimum i.d. (M3.5)] with the module.
3. Tighten the terminal screw making sure the pressure plate secures the wire.
Recommended torque when tightening terminal screws is 0.68 Nm (6 in-lbs).
NOTE
If you need to remove the finger-safe cover, insert a screw
driver into one of the square wiring holes and gently pry the
cover off. If you wire the terminal block with the finger-safe
cover removed, you will not be able to put it back on the
terminal block because the wires will be in the way.
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires with the following restrictions:
The manipulation of the bits from this file is normally done with programming
software (e.g. RSLogix 500, RSNetworx for DeviceNet, etc.) during initial
configuration of the system. In that case, graphical screens are provided by the
programmer to simplify configuration. However, some systems, like the 1769-ADN
DeviceNet Adapter, also allow the bits to be altered as part of the control program,
using communication rungs. In that case, it is necessary to understand the bit
arrangement. Refer to the Compact™ Analog I/O User Manual, publication number
1769-UM002 for additional details.
Bit Position
1514131211109876543210
Word
0Real Time Sample Value
1 ERTSReserved
2ECReservedEAALEIReservedInput Filter Sel Chl0
3ReservedInpt Dta Fm Chl0ReservedInpt Tp/RngeSel Chl0
4SProcess Alarm High Data Value Channel 0
5SProcess Alarm Low Data Value Channel 0
6SAlarm Dead Band Value Channel 0
7Pad
8ECReservedEAALEIReservedInpt Filter Sel Chl1
9ReservedInpt Dta Fm Chl1ReservedInpt Tp/RngeSel Chl1
10SProcess Alarm High Data Value Channel 1
11SProcess Alarm Low Data Value Channel 1
12SAlarm Dead Band Value Channel 1
13Pad
14ECReservedEAALEIReservedInput Filter Sel Chl2
15ReservedInpt Dta Fm Chl2ReservedInpt Tp/RngeSel Chl2
16SProcess Alarm High Data Value Channel 2
17SProcess Alarm Low Data Value Channel 2
18SAlarm Dead Band Value Channel 2
19Pad
20ECReservedEAALEIReservedInput Filter Sel Chl3
21ReservedInpt Dta Fm Chl3ReservedInpt Tp/RngeSel Chl3
22SProcess Alarm High Data Value Channel 3
23SProcess Alarm Low Data Value Channel 3
24SAlarm Dead Band Value Channel 3
25Pad
26ECReservedEAALEIReservedInput Filter Sel Chl4
Publication 1769-IN067B-EN-P - September 2005
16 Compact I/O 1769-IF8 Analog Input Module
Bit Position
1514131211109876543210
Word
27ReservedInpt Dta Fm Chl4ReservedInpt Tp/RngeSel Chl4
28SProcess Alarm High Data Value Channel 4
29SProcess Alarm Low Data Value Channel 4
30SAlarm Dead Band Value Channel 4
31Pad
32ECReservedEAALEIReservedInput Filter Sel Chl5
33ReservedInpt Dta Fm Chl5ReservedInpt Tp/RngeSel Chl5
34SProcess Alarm High Data Value Channel 5
35SProcess Alarm Low Data Value Channel 5
36SAlarm Dead Band Value Channel 5
37Pad
38ECReservedEAALEIReservedInput Filter Sel Chl6
39ReservedInpt Dta Fm Chl6ReservedInpt Tp/RngeSel Chl6
40SProcess Alarm High Data Value Channel 6
41SProcess Alarm Low Data Value Channel 6
42SAlarm Dead Band Value Channel 6
43Pad
44ECReservedEAALEIReservedInput Filter Sel Chl7
45ReservedInpt Dta Fm Chl7ReservedInpt Tp/RngeSel Chl7
46SProcess Alarm High Data Value Channel 7
47SProcess Alarm Low Data Value Channel 7
48SAlarm Dead Band Value Channel 7
49Pad
• EC = Enable Channel
• Inpt Dta Fm Chlx = Input Data Format Select.
• EA = Enable Alarm.
• AL = Alarm Latch.
• EI = Enable Interrupt.
• Inpt Tp/Rnge Sel Chlx = Input Type/Range Select.
Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to
1000 MHz.
height including mounting tabs is 138 mm
4.65 in. (height) x 3.43 in (depth) x 2.07 in (width)
height including mounting tabs is 5.43 in.
450g (0.99 lbs.)
(20G, 11 ms DIN rail mounted)
Non-Operating: 40G panel mounted
(30G DIN rail mounted)
• UL 508 listed
• CE compliant for all applicable directives
C-UL under CSA C22.2 No. 213)
+900 MHz keyed carrier
• 10 V, 0.15 to 80MHz
(1)
Publication 1769-IN067B-EN-P - September 2005
Compact I/O 1769-IF8 Analog Input Module 25
Input Specifications
Specification1769-IF8
Analog Normal Operating
(1)
Ranges
Full Scale Analog Ranges
Number of Inputs8 differential or single-ended
Bus Current Draw (max.)120 mA at 5V dc
Heat Dissipation3.24 Total Watts (The Watts per point, plus the minimum Watts, with all
Converter TypeDelta Sigma
Response Speed per ChannelInput filter and configuration dependent. See your user’s manual.
Resolution (max.)
Rated Working Voltage
(2)
(3)
Common Mode Voltage Range
Common Mode Rejectiongreater than 60 dB at 50 and 60 Hz with the 10 Hz filter selected,
Normal Mode Rejection Ratio-50 dB at 50 and 60 Hz with the 10 Hz filter selected, respectively.
Input ImpedanceVoltage Terminal: 220K Ω (typical)
Overall Accuracy
(1)
The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will
continue to convert the analog input up to the maximum full scale range. The flag automatically resets when within the
normal operating range.
(2)
Resolution is dependent upon your filter selection. The maximum resolution is achieved with the 10 Hz filter selected. For
resolution with other filter selections, refer to the user manual, publication 1769-UM002A-EN-P.
(3)
Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input
signal and the value that floats above ground potential (for example, 10V dc input signal and 20V dc potential above
ground).
(4)
For proper operation, both the plus and minus input terminals must be within ±10V dc of analog common.
(5)
Includes offset, gain, non-linearity and repeatability error terms.
(5)
Voltage: ± 10V dc, 0 to 10V dc, 0 to 5V dc, 1 to 5V dc
Current: 0 to 20 mA, 4 to 20 mA
(1)
Voltage: ± 10.5V dc, 0 to 10.5V dc, 0 to 5.25V dc, 0.5 to 5.25V dc
Current: 0 to 21 mA, 3.2 to 21 mA
70 mA at 24V dc
points energized.)
16 bits (unipolar)
15 bits plus sign (bipolar)
30V ac/30V dc
(4)
±10V dc maximum per channel
respectively.
Current Terminal: 250 Ω
Voltage Terminal: ±0.2% full scale at 25°C
Current Terminal: ±0.35% full scale at 25°C
Publication 1769-IN067B-EN-P - September 2005
26 Compact I/O 1769-IF8 Analog Input Module
Specification1769-IF8
Accuracy Drift with TemperatureVoltage Terminal: ±0.003% per °C
Current Terminal: ±0.0045% per °C
CalibrationThe module performs autocalibration on channel enable and on a
Non-linearity (in percent full scale) ±0.03%
Repeatability
(1)
Module Error over Full
Temperature Range
(0 to +60°C [+32°F to +140°F])
Input Channel Configurationvia configuration software screen or the user program (by writing a unique
Module OK LEDOn: module has power, has passed internal diagnostics, and is
Channel DiagnosticsOver- or under-range by bit reporting, process alarms
Maximum Overload at Input
(2)
Terminals
System Power Supply Distance
Rating
Recommended CableBelden™ 8761 (shielded)
Input Group to Bus Isolation500V ac or 710V dc for 1 minute (qualification test)
Vendor I.D. Code1
Product Type Code10
Product Code38
(1)
Repeatability is the ability of the input module to register the same reading in successive measurements for the same input
signal.
(2)
Damage may occur to the input circuit if this value is exceeded.
configuration change between channels.
±0.03%
Voltage: ±0.3%
Current: ±0.5%
bit pattern into the module’s configuration file). Refer to your controller’s
user manual to determine if user program configuration is supported.
communicating over the bus.
Off: Any of the above is not true.
Voltage Terminal: ±30V dc continuous, 0.1 mA
Current Terminal: ±32 mA continuous, ±7.6 V dc
8 (The module may not be more than 8 modules away from the system
power supply.)
30V ac/30V dc working voltage (IEC Class 2 reinforced insulation)
Publication 1769-IN067B-EN-P - September 2005
Compact I/O 1769-IF8 Analog Input Module 27
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or
non-hazardous locations only. The following ATTENTION statement applies to use
in hazardous locations.
WARNING
EXPLOSION HAZARD
• Substitution of components may impair suitability for Class
I, Division 2.
• Do not replace components or disconnect equipment
unless power has been switched off or the area is known
to be non-hazardous.
• Do not connect or disconnect components unless power
has been switched off or the area is known to be
non-hazardous.
• This product must be installed in an enclosure.
• All wiring must comply with N.E.C. article 501-4(b).
Environnements dangereux
Cet équipement est conçu pour être utilisé dans des environnements de Classe 1,
Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante
s’applique à une utilisation dans des environnements dangereux.
AVERTISSEMENT
DANGER D’EXPLOSION
• La substitution de composants peut rendre cet équipement
impropre à une utilisation en environnement de Classe 1,
Division 2.
• Ne pas remplacer de composants ou déconnecter
l'équipement sans s'être assuré que l'alimentation est coupée
et que l'environnement est classé non dangereux.
• Ne pas connecter ou déconnecter des composants sans s'être
assuré que l'alimentation est coupée ou que l'environnement
est classé non dangereux.
• Ce produit doit être installé dans une armoire.
Publication 1769-IN067B-EN-P - September 2005
28 Compact I/O 1769-IF8 Analog Input Module
For More Information
ForRefer to this DocumentPub. No.
A more detailed description of how to install
and use your Compact I/O with MicroLogix 1500
programmable controller.
Detailed information on installing,
programming, and troubleshooting your
Compact Analog I/O modules.
A detailed description of how to install and use
your Compact I/O with the 1769-ADN DeviceNet
Adapter.
An overview of the MicroLogix 1500 system,
including Compact I/O.
More information on proper wiring and
grounding techniques.
If you would like a manual, you can:
• download a free electronic version from the internet:
www.ab.com/micrologix or www.theautomationbookstore.com
• purchase a printed manual by:
– contacting your local distributor or Rockwell Automation representative
– visiting www.theautomationbookstore.com and placing your order
– calling 1.800.963.9548 (USA/Canada)
or 001.330.725.1574 (Outside USA/Canada)
MicroLogix 1500 Programmable
Controllers User Manual
Compact I/O Analog Modules User
Manual
1769-ADN DeviceNet Adapter User
Manual
MicroLogix 1500 Programmable
Controller with Compact I/O for
Expansion
Industrial Automation Wiring and
Grounding Guidelines
1764-UM001
1769-UM002
1769-UM001
1764-SO001
1770-4.1
MicroLogix and Compact are trademarks of Rockwell Automation.
Belden is a trademark of Belden, Inc.
Publication 1769-IN067B-EN-P - September 2005
Notes:
Compact I/O 1769-IF8 Analog Input Module 29
Publication 1769-IN067B-EN-P - September 2005
30 Compact I/O 1769-IF8 Analog Input Module
Notes:
Publication 1769-IN067B-EN-P - September 2005
Notes:
Compact I/O 1769-IF8 Analog Input Module 31
Publication 1769-IN067B-EN-P - September 2005
Rockwell Automation Support
Rockwell Automation provides technical information on the web to assist you in using our
products. At http://support.rockwellautomation.com, you can find technical manuals, a
knowledge base of FAQs, technical and application notes, sample code and links to software
service packs, and a MySupport feature that you can customize to make the best use of
these tools.
For an additional level of technical phone support for installation, configuration and
troubleshooting, we offer TechConnect Support programs. For more information, contact your
local distributor or Rockwell Automation representative, or visit
http://support.rockwellautomation.com.
Installation Assistance
If you experience a problem with a hardware module within the first 24 hours of installation,
please review the information that's contained in this manual. You can also contact a special
Customer Support number for initial help in getting your module up and running:
United States1.440.646.3223 Monday – Friday, 8am – 5pm EST
Outside United States Please contact your local Rockwell Automation representative for any technical
New Product Satisfaction Return
Rockwell tests all of our products to ensure that they are fully operational when shipped from
the manufacturing facility. However, if your product is not functioning and needs to be
returned:
United StatesContact your distributor. You must provide a Customer Support case number (see
Outside United States Please contact your local Rockwell Automation representative for return procedure.
support issues.
phone number above to obtain one) to your distributor in order to complete the return
process.
Publication 1769-IN067B-EN-P - September 2005PN 40071-171-01(2)