Compact™ 8-Bit
Low Resolution
Analog I/O
Combination
Module
(Catalog Number 1769-IF4XOF2)
User Manual
Important User Information
Because of the variety of uses for the products described in this
publication, those responsible for the application and use of this
control equipment must satisfy themselves that all necessary steps
have been taken to assure that each application and use meets all
performance and safety requirements, including any applicable laws,
regulations, codes and standards.
The illustrations, charts, sample programs and layout examples shown
in this guide are intended solely for purposes of example. Since there
are many variables and requirements associated with any particular
installation, Allen-Bradley does not assume responsibility or liability
(to include intellectual property liability) for actual use based upon
the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the
Application, Installation and Maintenance of Solid-State Control
(available from your local Allen-Bradley office), describes some
important differences between solid-state equipment and
electromechanical devices that should be taken into consideration
when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole
or part, without written permission of Rockwell Automation, is
prohibited.
Throughout this manual we use notes to make you aware of safety
considerations:
ATTENTION
Identifies information about practices or
circumstances that can lead to personal injury or
death, property damage or economic loss
!
Attention statements help you to:
• identify a hazard
• avoid a hazard
• recognize the consequences
IMPORTANT
MicroLogix, Compact, RSLogix and RSLinx are trademarks of Rockwell Automation.
Belden is a trademark of Belden, Inc.
DeviceNet is a trademark of Open DeviceNet Vendor Association (ODVA).
Identifies information that is critical for successful
application and understanding of the product.
Overview
Table of Contents
Preface
Who Should Use This Manual . . . . . . . . . . . . . . . . . . . . . . P-1
How to Use This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Read this preface to familiarize yourself with the rest of the manual.
This preface covers the following topics:
• Who Should Use This Manual on page P-1
• How to Use This Manual on page P-1
• Related Documentation on page P-2
• Conventions Used in This Manual on page P-2
• Rockwell Automation Support on page P-3
Who Should Use This
Manual
How to Use This Manual
Use this manual if you are responsible for designing, installing,
programming, or troubleshooting control systems that use
Allen-Bradley Compact™ I/O.
As much as possible, we organized this manual to explain, in a
task-by-task manner, how to install, configure, program, operate and
troubleshoot a control system using the analog I/O modules.
Manual Contents
If you want...See
An overview of the analog combination moduleChapter 1
A quick start guide for experienced usersChapter 2
Installation and wiring guidelinesChapter 3
Module addressing, configuration and status informationChapter 4
Information on module diagnostics and troubleshootingChapter 5
Specifications for the combination moduleAppendix A
Information on addressing and configuration using MicroLogix 1500
and RSLogix 500
Information on configuring the module using CompactLogix and
RSLogix 5000
Information on understanding two’s complement binary numbersAppendix D
Definitions of terms used in this manualGlossary
1Publication 1769-UM008A-EN-P - November 2001
Appendix B
Appendix C
P-2
Related Documentation
The table below provides a listing of publications that contain
important information about MicroLogix 1500 systems.
ForRead this documentDocument number
A user manual containing information on how to install,
use and program your MicroLogix 1500 controller.
A user manual containing information on how to install,
and use your 1769-ADN DeviceNet Adapter.
A user manual containing information on how to install,
use and program your CompactLogix controller.
An overview of 1769 Compact Discrete I/O modules1769 Compact Discrete Input/Output Modules Product
An overview of the MicroLogix 1500 System, including
1769 Compact I/O.
In-depth information on grounding and wiring
Allen-Bradley programmable controllers.
MicroLogix™ 1500 User Manual1764-UM001A-US-P
DeviceNet Adapter User Manual1769-UM001A-US-P
CompactLogix User Manual1769-UM007C-EN-P
1769-2.1
Data
MicroLogix™ 1500 System Overview1764-SO001B-EN-P
Allen-Bradley Programmable Controller Grounding and
Wiring Guidelines
1770-4.1
If you would like a manual, you can:
• download a free electronic version from the internet at
www.theautomationbookstore.com
• purchase a printed manual by:
– contacting your local distributor or Rockwell Automation
representative
– visiting www.theautomationbookstore.com and placing
your order
– calling 1.800.963.9548 (USA/Canada) or 001.330.725.1574
(Outside USA/Canada)
Conventions Used in This
Manual
Publication 1769-UM008A-EN-P - November 2001
The following conventions are used throughout this manual:
• Bulleted lists (like this one) provide information not procedural
steps.
• Numbered lists provide sequential steps or hierarchical
information.
• Italic type is used for emphasis.
• Text in this font indicates words or phrases you should type.
P-3
Rockwell Automation
Support
Rockwell Automation offers support services worldwide, with over
75 Sales/Support Offices, 512 authorized distributors and 260
authorized Systems Integrators located throughout the United States
alone, plus Rockwell Automation representatives in every major
country in the world.
Local Product Support
Contact your local Rockwell Automation representative for:
• sales and order support
• product technical training
• warranty support
• support service agreement
Technical Product Assistance
If you need to contact Rockwell Automation for technical assistance,
please review the information in Chapter 5, Module Diagnostics and Troubleshooting first. Then call your local Rockwell Automation
representative.
Your Questions or Comments on the Manual
If you find a problem with this manual, please notify us. If you have
any suggestions for how this manual could be made more useful to
you, please contact us at the address below:
Rockwell Automation
Automation Control and Information Group
Technical Communication, Dept. A602V
P.O. Box 2086
Milwaukee, WI 53201-2086
Publication 1769-UM008A-EN-P - November 2001
P-4
Publication 1769-UM008A-EN-P - November 2001
Chapter
Overview
This chapter explains how analog data is used and describes the
1769-IF4XOF2 combination analog I/O module. Included is
information about:
• How to Use Analog I/O on page 1-1
• General Description of the Module’s Hardware and Diagnostic
Features on page 1-2
• Overview of the Analog System on page 1-4
1
How to Use Analog I/O
Analog refers to the representation of numerical quantities by the
measurement of continuous physical variables. Analog applications
are present in many forms. The following application shows a typical
use of analog data.
In this application, the processor controls the amount of fluid in a
holding tank by adjusting the valve opening. The valve is initially
open 100%. As the fluid level in the tank approaches the preset point,
the processor modifies the output to close the valve 90%, 80%, and so
on, continuously adjusting the valve to maintain the fluid level.
Analog output
wired to valve
Valve
Controller
Level Sensor
Analog input wired
to tank
Analog I/O
Module
1Publication 1769-UM008A-EN-P - November 2001
1-2 Overview
General Description of the
Module’s Hardware and
Diagnostic Features
The analog input channels convert and digitally store analog data for
retrieval by controllers, such as the MicroLogix™ 1500 and
CompactLogix, and from network adapters like the 1769-ADN (Series
B) DeviceNet Adapter. The module supports connections from any
combination of up to four voltage or current analog sensors. The four
high-impedance input channels can be wired as either single-ended or
differential inputs.
The output channels provide two single-ended analog outputs, each
individually configurable for voltage or current.
The module provides the following input/output types/ranges:
Table 1.1 Normal and Full Input and Output Ranges
Normal Operating Range
0 to +10V dc0.0 to +10.5V dc
0 to 20 mA0 to 21 mA
(1) The module provides an overrange band of 0.5V for the 0 to 10V range and 1 mA for the 0 to 20 mA
range.
Full Module Range
(1)
The modules provide the data as raw/proportional data. If scaling to
engineering units is required, it must be done in your control
program.
Hardware Features
The module has a removable terminal block. The module’s four input
channels can be wired as either single-ended or differential inputs.
The module’s two output channels are single-ended only. Module
configuration is done via proper wiring of the I/O and the controller’s
programming software. In addition, some controllers support
configuration via the user program. In either case, the module
configuration is stored in the memory of the controller. Refer to your
controller’s user manual for more information.
Publication 1769-UM008A-EN-P - November 2001
Overview 1-3
The following illustration shows the hardware features of the Compact
combination analog I/O module.
8a
10a
10
10b
1
OK
Analog
2a
DANGER
Do Not Remove RTB Under Power
Unless Area is Non-Hazardous
0
in
V
+
1
in
V
/I in
V
-
1
/I in
V
1
I in
+
1
I in
2
in
V
+
3
in
V
/I in
V
-
3
/I in
V
2
I in
+
3
I in
G
N
A
m
o
C
L
G
N
A
m
o
C
t 0
u
o
V
+
t 1
u
o
V
t 0
u
I o
+
t 1
u
I o
Ensure Adjacent
Bus Lever is Unlatched/Latched
Before/After
Removing/Inserting Module
O
X
4
-IF
9
6
7
1
2b
7a
3
OK
Analog
7a
5a
+
-
0
+
+
-
2
+
L
+
+
9
4
2
F
7b
7b
5b
6
8b
ItemDescription
1bus lever (with locking function)
2aupper panel mounting tab
2blower panel mounting tab
3green module status OK LED
4module door with terminal identification label
5amovable bus connector (bus interface) with female pins
5bstationary bus connector (bus interface) with male pins
6nameplate label
7aupper tongue-and-groove slots
7blower tongue-and-groove slots
8aupper DIN rail latch
8blower DIN rail latch
9write-on label for user identification tags
10removable terminal block (RTB) with finger-safe cover
10aRTB upper retaining screw
10bRTB lower retaining screw
Publication 1769-UM008A-EN-P - November 2001
1-4 Overview
General Diagnostic Features
The module contains diagnostic features that can help you identify the
source of problems that may occur during power-up or during normal
channel operation. These power-up and channel diagnostics are
explained in Chapter 5, Module Diagnostics and Troubleshooting.
Overview of the Analog
System
The module communicates to the controller through the bus interface.
The module also receives 5 and 24V dc power through the bus
interface.
You can install as many analog modules as your power supply can
support. However, the 1769-IF4XOF2 module has a power supply
distance rating of 8, which means that it may not be located more than
8 modules away from the system power supply. The illustration below
shows how power supply distance is determined.
MicroLogix 1500 Controller
with Integrated System
Power Supply
OR
Compact I/O
Compact I/O
1
234
Compact I/O
Compact I/O
End Cap or Cable
Power Supply Distance
Publication 1769-UM008A-EN-P - November 2001
Adapter
Compact I/O
or I/O Communication
CompactLogix Controller
Compact I/O
Compact I/O
System Power Supply
Compact I/O
(e.g. 1769-PA2)
1123432
Compact I/O
Compact I/O
Power Supply Distance
End Cap or Cable
Overview 1-5
System Operation
At power-up, the module performs a check of its internal circuits,
memory, and basic functions. During this time, the module status LED
remains off. If no faults are found during power-up diagnostics, the
module status LED is turned on.
After power-up checks are complete, the module waits for valid
channel configuration data. If an invalid configuration is detected, the
module generates a configuration error. Once a channel is properly
configured and enabled, it begins the analog-to-digital or
digital-to-analog conversion process.
Input Channels
Each time an input channel is read by the module, that analog data
value is tested by the module for an over-range condition (e.g. input
voltage greater than 10V dc). If such a condition is detected, a unique
bit is set in the channel status word. The channel status word is
described in Input Data File on page 4-3.
The controller reads the analog data from the module. This typically
occurs at the end of the program scan or when commanded by the
control program. If the controller and the module determine that the
bus data transfer was made without error, the data is used in your
control program.
Output Channels
The module monitors output channels for over-range conditions. If
such a condition is detected, a unique bit is set in the channel status
word. The channel status word is described in Output Data File on
page 4-7.
The module receives proportional binary values from the bus master
(e.g. controller). This typically occurs at the end of the program scan
or when commanded by the control program. If the controller and the
module determine that the bus transfer was completed without error,
the module converts the data to an analog output signal.
Publication 1769-UM008A-EN-P - November 2001
1-6 Overview
Input
Vin+
Iin+
CH0
Module Operation
Module Block Diagram
The module’s input channel circuitry consists of four differential
analog inputs multiplexed into a single analog-to-digital (A/D)
converter. The A/D converter reads the selected input signal and
converts it to a digital value which is presented to the controller. The
multiplexer sequentially switches each input channel to the module’s
A/D converter. The module’s output channel uses a digital-to-analog
(D/A) converter to read the digital output data from the controller and
convert it to an analog output signal. See the block diagram below.
Galvanic
Isolation
TXD
VA2
VA3
VA1VS1
AIN+
A/D
(same as CH0)
CH1 CH2 CH3
Output
V/Iin-
A-GND
Multiplexer
CH0
Vout+
Iout+
A-GND
ANLG COM
A-GND
Vref
Channel Select
VA2
VA3
VA2
CH1
(same as CH0)
VREF
D/A
MCU
A-GND
RXD
VA2
VA3
VA1
A-GND
ASIC
DC/DC
Power
Supply
Bus
VS1
VS2
S-GND
Publication 1769-UM008A-EN-P - November 2001
Module Calibration
The module’s input/output channel calibration is guaranteed by its
design. No field calibration is required.
Quick Start for Experienced Users
Chapter
2
Before You Begin
Required Tools and
Equipment
This chapter can help you to get started using the analog module. We
base the procedures here on the assumption that you have an
understanding of Allen-Bradley controllers. You should understand
electronic process control and be able to interpret the ladder logic
instructions required to generate the electronic signals that control your
application.
Because it is a start-up guide for experienced users, this chapter does not
contain detailed explanations about the procedures listed. It does,
however, reference other chapters in this book where you can get more
information about applying the procedures described in each step.
If you have any questions or are unfamiliar with the terms used or
concepts presented in the procedural steps, always read the referenced chapters and other recommended documentation before trying to apply
the information.
Have the following tools and equipment ready:
• medium blade or cross-head screwdriver
• analog input or output device
• shielded, twisted-pair cable for wiring (Belden™ 8761 or equivalent)
• controller (for example, a MicroLogix™ 1500 controller)
• analog combination (1769-IF4XOF2) module
• programming device and software (for example, RSLogix 500™)
1Publication 1769-UM008A-EN-P - November 2001
2-2 Quick Start for Experienced Users
What You Need To Do
Step 1:
This chapter covers:
• Verify power supply is adequate on page 2-2
• Attach and lock the module. on page 2-2
• Mount the I/O bank. on page 2-3
• Wire the module. on page 2-4
• Configure the module on page 2-5
• Start the system. on page 2-6
• Monitor the module status. on page 2-6
Verify power supply is adequate
Ensure that your power supply has sufficient current output to
support your system configuration. The modules maximum current
draw is shown below.
Module5V dc24V dc
1769-IF4XOF2120 mA160 mA
Reference
Chapter 3
(Installation and Wiring)
Step 2:
TIP
Attach and lock the module.
a. Check that the bus lever of the module to be installed is in the
unlocked (fully right) position.
b. Use the upper and lower tongue-and-groove slots to secure the
modules together (or to a controller).
c. Move the module back along the tongue-and-groove slots until
the bus connectors line up with each other.
d. Push the bus lever back slightly to clear the positioning tab. Use
your fingers or a small screwdriver.
The module cannot be located more than 8 modules
away from the system power supply.
Reference
Chapter 3
(Installation and Wiring)
Publication 1769-UM008A-EN-P - November 2001
Quick Start for Experienced Users 2-3
e. To allow communication between the controller and module,
move the bus lever fully to the left until it clicks. Ensure it is
locked firmly in place.
ATTENTION
When attaching I/O modules, it is very important
that the bus connectors are securely locked
together to ensure proper electrical connection.
!
f. Attach an end cap terminator to the last module in the system by
using the tongue-and-groove slots as before.
g. Lock the end cap bus terminator.
ATTENTION
Remove power before removing or inserting this
module. When you remove or insert a module
with power applied, an electrical arc may occur.
!
Step 3:
Mount the I/O bank.
Be sure to observe minimum spacing guidelines on page 3-7 for
adequate ventilation.
Reference
Chapter 3
(Installation and Wiring)
Publication 1769-UM008A-EN-P - November 2001
2-4 Quick Start for Experienced Users
Step 4:
Wire the module.
The terminal connections are shown below:
V in 1 +
V/I in 1 -
I in 1 +
V in 3 +
V/I in 3 -
I in 3 +
ANLG Com
V out 1 +
I out 1 +
V in 0 +
V/I in 0 -
I in 0 +
V in 2 +
V/I in 2 -
I in 2 +
ANLG Com
V out 0 +
I out 0 +
Reference
Chapter 3
(Installation and Wiring)
DANGER
Do Not Remove RTB Under Power
Unless Area is Non-Hazardous.
V/I in 1 I in 1 +
I in 3 +
ANLG
Com
1769-IF4XOF2
V in 0 +
V/I in 0 -
I in 0 +
V in 2 +
V/I in 2 -
I in 2+
ANLG
Com
V out 0 +
I out 0 +
V in 1 +
V in 3 +
V/I in 3 -
V out 1 +
I out 1 +
Ensure Adjacent Bus Lever is
Unlatched/Latched Before/After
Removing/Inserting Module
Be sure to follow the system wiring guidelines on page 3-10. See
the 1769-IF4XOF2 Wiring Diagram Showing Differential Inputs on
page 3-18 and the Wiring Single-ended Sensor/Transmitter Input
Types on page 3-19 for examples of wiring using differential and
single-ended inputs.
Publication 1769-UM008A-EN-P - November 2001
Quick Start for Experienced Users 2-5
Step 5:
Table 2.1 Configuration Data File
Word
1514131211109876543210
0
1
2SGN
3SGN
4SGN
5SGN
Not Used
Channel 0 Fault Value
Channel 0 Program (Idle) Value
Channel 1 Fault Value
Channel 1 Program (Idle) Value
Configure the module
The 1769-IF4XOF2 module is configured for current or voltage
operation by proper wiring of the analog I/O device to the module.
However, a channel is enabled using its configuration file.
Bit Position
(1)
Not Used
(1)
(2)
(2)
EI3EI2EI1EI0
(2)
(2)
Reference
Chapter 4
(Module Data, Status, and
Configuration Channel for
1769-IF4XOF2)
(2)
FM0
EO1EO0
FM1
(2)
0000000
0000000
0000000
0000000
PM0
PM1
(2)
Not
(1)
Used
(2)
Not
(1)
Used
PFE0
PFE1
(2)
(2)
(1) Any attempt to write a non-valid (1’s) bit configurations into any not used selection field results in a module configuration er ror.
(2) Not all controllers support these functions. Refer to your controller’s user manual for details.
The configuration file is typically modified using the programming
software configuration screen. It can also be modified through the
control program, if supported by the controller. See the configuration
file chart on page 4-8.
For an example of module configuration using MicroLogix 1500 and
RSLogix 500, see Appendix B. For an example of module
configuration using CompactLogix and RSLogix 5000, see Appendix C.
Publication 1769-UM008A-EN-P - November 2001
2-6 Quick Start for Experienced Users
Step 6:
Step 7:
Start the system.
a. Apply power.
b. Download your program, which contains the analog module
configuration settings, to the controller and put the controller into
Run mode.
c. During a normal start-up, the module status LED turns on.
d. If the module status LED does not turn on, cycle power. If the
condition persists, replace the module.
Monitor the module status.
Module and channel configuration errors are reported to the
controller. These errors are typically reported in the controller’s I/O
status file. Check the controller’s I/O file.
Reference
Chapter 5
(Module Diagnostics and
Troubleshooting)
Reference
Chapter 6
(Module Diagnostics and
Troubleshooting)
Channel status data is also reported in the module’s input data table,
so these bits can be used in your control program to flag a channel
error. See Input Data File on page 4-3.
Publication 1769-UM008A-EN-P - November 2001
Chapter
Installation and Wiring
This chapter tells you about:
• Compliance to European Union Directives on page 3-1
• Power Requirements on page 3-2
• General Considerations to Avoid Electrostatic Damage on page
3-2
• System Assembly on page 3-5
• Mounting the Module on page 3-6
• Field Wiring Connections on page 3-10
• Analog Input Wiring on page 3-16
• Analog Output Wiring on page 3-21
3
Compliance to European
Union Directives
This product is approved for installation within the European Union
and EEA regions. It has been designed and tested to meet the
following directives.
EMC Directive
The analog modules are tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) and the following standards, in
whole or in part, documented in a technical construction file:
• EN 50081-2
EMC – Generic Emission Standard, Part 2 - Industrial
Environment
• EN 50082-2
EMC – Generic Immunity Standard, Part 2 - Industrial
Environment
This product is intended for use in an industrial environment.
1Publication 1769-UM008A-EN-P - November 2001
3-2 Installation and Wiring
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low
Voltage, by applying the safety requirements of EN 61131-2
Programmable Controllers, Part 2 – Equipment Requirements and
Tests.
For specific information required by EN61131-2, see the appropriate
sections in this publication, as well as the following Allen-Bradley
publications:
• Industrial Automation, Wiring and Grounding Guidelines for
Noise Immunity, publication 1770-4.1
• Automation Systems Catalog, publication B113
Power Requirements
General Considerations to
Avoid Electrostatic Damage
The module receives its power through the bus interface from the +5V
dc/+24V dc system power supply.
The maximum current drawn by the module is shown in the table
below.
Module5V dc24V dc
1769-IF4XOF2120 mA160 mA
Compact I/O is suitable for use in an industrial environment when
installed in accordance with these instructions. Specifically, this
equipment is intended for use in clean, dry environments (Pollution
(1)
degree 2
) and to circuits not exceeding Over Voltage Category II
(IEC 60664-1).
(3)
(2)
Publication 1769-UM008A-EN-P - November 2001
(1) Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that
occasionally a temporary conductivity caused by condensation shall be expected.
(2) Over Voltage Category II is the load level section of the electrical distribution system. At this level transient
voltages are controlled and do not exceed the impulse voltage capability of the product’s insulation.
(3) Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC)
designations.
Installation and Wiring 3-3
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B,
C, D or non-hazardous locations only. The following WARNING
statement applies to use in hazardous locations.
WARNING
!
EXPLOSION HAZARD
• Substitution of components may impair suitability
for Class I, Division 2.
• Do not replace components or disconnect
equipment unless power has been switched off
or the area is known to be non-hazardous.
• Do not connect or disconnect components unless
power has been switched off or the area is
known to be non-hazardous.
• This product must be installed in an enclosure.
• All wiring must comply with N.E.C. article
501-4(b)
Prevent Electrostatic Discharge
ATTENTION
Electrostatic discharge can damage integrated circuits
or semiconductors if you touch bus connector pins
or the terminal block. Follow these guidelines when
you handle the module:
!
• Touch a grounded object to discharge static
potential.
• Wear an approved wrist-strap grounding device.
• Do not touch the bus connector or connector
pins.
• Do not touch circuit components inside the
module.
• If available, use a static-safe work station.
• When not in use, keep the module in its
static-shield box.
Publication 1769-UM008A-EN-P - November 2001
3-4 Installation and Wiring
Remove Power
ATTENTION
Remove power before removing or inserting this
module. When you remove or insert a module with
power applied, an electrical arc may occur. An
electrical arc can cause personal injury or property
damage by:
!
• sending an erroneous signal to your system’s field
devices, causing unintended machine motion
• causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on
both the module and its mating connector. Worn
contacts may create electrical resistance.
Reducing Electrical Noise Interference
Most applications require installation in an industrial enclosure to
reduce the effects of electrical interference. Analog inputs and outputs
are highly susceptible to electrical noise. Electrical noise coupled to
the analog inputs will reduce the performance (accuracy) of the
module.
Group your modules to minimize adverse effects from radiated
electrical noise and heat. Consider the following conditions when
selecting a location for the analog module. Position the module:
• away from sources of electrical noise such as hard-contact
switches, relays, and AC motor drives
• away from modules which generate significant radiated heat,
such as the 1769-IA16. Refer to the module’s heat dissipation
specification.
In addition, route shielded, twisted-pair analog input and output
wiring away from any high voltage I/O wiring.
Publication 1769-UM008A-EN-P - November 2001
Installation and Wiring 3-5
Protecting the Circuit Board from Contamination
The printed circuit boards of the analog modules must be protected
from dirt, oil, moisture, and other airborne contaminants. To protect
these boards, the system must be installed in an enclosure suitable for
the environment. The interior of the enclosure should be kept clean
and the enclosure door should be kept closed whenever possible.
System Assembly
The module can be attached to the controller or an adjacent I/O
module or power supply before or after mounting. For mounting
instructions, see Panel Mounting Using the Dimensional Template on
page 3-7, or DIN Rail Mounting on page 3-8. To work with a system
that is already mounted, see Replacing a Single Module within a
System on page 3-9.
The following procedure shows you how to assemble the Compact
I/O system.
C
D
B
A
A
E
F
1. Disconnect power.
2. Check that the bus lever of the module to be installed is in the
unlocked (fully right) position.
3. Use the upper and lower tongue-and-groove slots (A) to secure
the modules together (or to a controller or power supply).
4. Move the module back along the tongue-and-groove slots until
the bus connectors (B) line up with each other.
5. Push the bus lever back slightly to clear the positioning tab (C).
Use your fingers or a small screwdriver.
Publication 1769-UM008A-EN-P - November 2001
3-6 Installation and Wiring
6. To allow communication between the controller and module,
move the bus lever fully to the left (D) until it clicks. Ensure it is
locked firmly in place.
Mounting the Module
ATTENTION
When attaching I/O modules, it is very
important that the bus connectors are securely
locked together to ensure proper electrical
connection.
!
7. Attach an end cap terminator (E) to the last module in the
system by using the tongue-and-groove slots as before.
8. Lock the end cap bus terminator (F).
IMPORTANT
ATTENTION
A 1769-ECR or 1769-ECL right or left end cap
must be used to terminate the end of the
communication bus.
During panel or DIN rail mounting of all devices, be
sure that all debris (metal chips, wire strands, etc.) is
kept from falling into the module. Debris that falls
into the module could cause damage on power up.
Publication 1769-UM008A-EN-P - November 2001
!
Installation and Wiring 3-7
Minimum Spacing
Maintain spacing from enclosure walls, wireways, adjacent equipment,
etc. Allow 50 mm (2 in.) of space on all sides for adequate ventilation,
as shown below:
Top
SideSide
Host Controller
Compact I/O
Bottom
Compact I/O
Compact I/O
Compact I/O
End Cap
Compact I/O
Panel Mounting
Mount the module to a panel using two screws per module. Use M4
or #8 panhead screws. Mounting screws are required on every
module.
Panel Mounting Using the Dimensional Template
For more than 2 modules: (number of modules-1) X 35 mm (1.38 in.).
Refer to host controller documentation for this dimension.
35
(1.38)
28.5
(1.12)
NOTE: All dimensions are in mm (inches).
Hole spacing tolerance: ±0.04 mm (0.016 in.).
132
(5.197)
122.6±0.2
(4.826±0.008)
Compact I/O
Compact I/O
Compact I/O
Host Controller
Publication 1769-UM008A-EN-P - November 2001
Right End Cap
3-8 Installation and Wiring
Panel Mounting Procedure Using Modules as a Template
The following procedure allows you to use the assembled modules as
a template for drilling holes in the panel. Due to module mounting
hole tolerance, it is important to follow these procedures:
1. On a clean work surface, assemble no more than three modules.
2. Using the assembled modules as a template, carefully mark the
center of all module-mounting holes on the panel.
3. Return the assembled modules to the clean work surface,
including any previously mounted modules.
4. Drill and tap the mounting holes for the recommended M4 or #8
screw.
5. Place the modules back on the panel, and check for proper hole
alignment.
6. Attach the modules to the panel using the mounting screws.
TIP
7. Repeat steps 1 to 6 for any remaining modules.
If mounting more modules, mount only the
last one of this group and put the others aside.
This reduces remounting time during drilling
and tapping of the next group.
DIN Rail Mounting
The module can be mounted using the following DIN rails:
35 x 7.5 mm (EN 50 022 - 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x
15).
Before mounting the module on a DIN rail, close the DIN rail latches.
Press the DIN rail mounting area of the module against the DIN rail.
The latches will momentarily open and lock into place.
Publication 1769-UM008A-EN-P - November 2001
Loading...
+ 74 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.