Important User Information2
North American Hazardous Location Approval3
Module Description5
Prevent Electrostatic Discharge6
System Assembly6
Mounting Expansion I/O7
Replacing a Single Module within a System9
Replacement Part10
System Wiring Guidelines10
I/O Memory Mapping14
Specifications18
Additional Resources23
1769-IF4I
2 CompactLogix Isolated Analog Input Module
IMPORTANT
Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical equipment.
Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication
available from your local Rockwell Automation sales office or online at
equipment and hard-wired electromechanical devices. Because of this difference, and also because of the
wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy
themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many
variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot
assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can
cause an explosion in a hazardous environment, which may lead to personal
injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can
lead to personal injury or death, property damage, or economic loss. Attentions
help you identify a hazard, avoid a hazard and recognize the consequences.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, drive
or motor, to alert people that dangerous voltage may be present.
) describes some important differences between solid-state
Publication 1769-IN074C-EN-P - March 2011
BURN HAZARD: Labels may be on or inside the equipment, for example, drive
or motor, to alert people that surfaces may reach dangerous temperatures.
Identifies information that is critical for successful application and
understanding of the product.
CompactLogix Isolated Analog Input Module 3
North American Hazardous Location Approval
The following information applies when operating
this equipment in hazardous locations.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for
use in Class I Division 2 Groups A, B, C, D, Hazardous
Locations and nonhazardous locations only. Each product is
supplied with markings on the rating nameplate indicating
the hazardous location temperature code. When combining
products within a system, the most adverse temperature
code (lowest "T" number) may be used to help determine the
overall temperature code of the system. Combinations of
equipment in your system are subject to investigation by the
local Authority Having Jurisdiction at the time of installation.
WARNING:
Explosion Hazard -
•Do not disconnect equipment unless
power has been removed or the area is
known to be nonhazardous.
•Do not disconnect connections to this
equipment unless power has been
removed or the area is known to be
nonhazardous. Secure any external
connections that mate to this
equipment by using screws, sliding
latches, threaded connectors, or other
means provided with this product.
• Substitution of components may impair
suitability for Class I, Division 2.
•If this product contains batteries, they
must only be changed in an area known
to be nonhazardous.
Informations sur l’utilisation de cet équipement en
environnements dangereux.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent
qu'à une utilisation en environnements de Classe I Division 2
Groupes A, B, C, D dangereux et non dangereux. Chaque produit
est livré avec des marquages sur sa plaque d'identification qui
indiquent le code de température pour les environnements
dangereux. Lorsque plusieurs produits sont combinés dans un
système, le code de température le plus défavorable (code de
température le plus faible) peut être utilisé pour déterminer le
code de température global du système. Les combinaisons
d'équipements dans le système sont sujettes à inspection par les
autorités locales qualifiées au moment de l'installation.
AVERTISSEMENT:
Risque d’Explosion –
•Couper le courant ou s'assurer que
l'environnement est classé non dangereux
avant de débrancher l'équipement.
•Couper le courant ou s'assurer que
l'environnement est classé non dangereux
avant de débrancher les connecteurs. Fixer
tous les connecteurs externes reliés à cet
équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou autres
moyens fournis avec ce produit.
•La substitution de composants peut rendre
cet équipement inadapté à une utilisation
en environnement de Classe I, Division 2.
•S'assurer que l'environnement est classé
non dangereux avant de changer les piles.
Publication 1769-IN074C-EN-P - March 2011
4 CompactLogix Isolated Analog Input Module
Environment and Enclosure
ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC 60664-1), at
altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to
IEC/CISPR 11. Without appropriate precautions, there may be difficulties with
electromagnetic compatibility in residential and other environments due to
conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an
enclosure that is suitably designed for those specific environmental conditions that
will be present and appropriately designed to prevent personal injury resulting from
accessibility to live parts. The enclosure must have suitable flame-retardant
properties to prevent or minimize the spread of flame, complying with a flame
spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the
enclosure must be accessible only by the use of a tool. Subsequent sections of this
publication may contain additional information regarding specific enclosure type
ratings that are required to comply with certain product safety certifications.
Besides this publication, see:
• Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
for additional installation requirements, .
• NEMA Standards publication 250 and IEC publication 60529, as applicable, for
explanations of the degrees of protection provided by different types of
enclosure.
,
Publication 1769-IN074C-EN-P - March 2011
Module Description
1
2a
CompactLogix Isolated Analog Input Module 5
8a
7a
7a
OK
Analog
10a
10
10b
DANGER
Do Not Remove RTB Under Power
Unless Area is Non-Hazardous
N/C
Ch0_iRtn
N/C
Ch1+
Ch1_iRtn
Ch1-
Ch2_iRtn
N/C
Ch3+
Ch3_iRtn
Ch3-
Ensure Adjacent
Bus Lever is Unlatched/Latched
Before/After
Removing/Inserting Module
1769-IF4I
2b
3
OK
Analog
5a
Ch0+
Ch0-
N/C
Ch2+
Ch2-
N/C
N/C
9
4
7b
7b
8b
Item DescriptionItem Description
1
Bus lever (with locking function)
2a
Upper panel mounting tab
2b
Lower panel mounting tab
3
Module status indicator
4
Module door with terminal identification
7a
Upper tongue-and-groove slots
7b
Lower tongue-and-groove slots
8a
Upper DIN rail latch
8b
Lower DIN rail latch
9
Write-on label (user ID tag)
label
5a
Movable bus connector with female pins
10
Removable terminal block (RTB) with
finger-safe cover
5b
Stationary bus connector with male pins
6
Nameplate label
10a
RTB upper retaining screw
10b
RTB lower retaining screw
5b
6
Publication 1769-IN074C-EN-P - March 2011
6 CompactLogix Isolated Analog Input Module
1
1
2
6
5
4
30536-M
3
Prevent Electrostatic Discharge
ATTENTION: This equipment is sensitive to electrostatic discharge, which can
cause internal damage and affect normal operation. Follow these guidelines when
you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
Remove Power
WARNING: When you insert or remove the module while backplane power is on,
an electrical arc can occur. This could cause an explosion in hazardous location
installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Repeated electrical arcing causes excessive wear to contacts on both the module
and its mating connector. Worn contacts may create electrical resistance that can
affect module operation.
System Assembly
The module can be attached to the controller or an adjacent I/O module before or after
mounting. For mounting instructions, see Panel Mounting on page 8, or DIN Rail Mounting on
page 9. To work with a system that is already mounted, see Replacing a Single Module within a
System on page 9.
The following procedure shows you how to assemble the Compact I/O system.
Publication 1769-IN074C-EN-P - March 2011
CompactLogix Isolated Analog Input Module 7
IMPORTANT
1. Disconnect power.
2. Check that the bus lever of the module to be installed is in the unlocked (fully right)
position.
3. Use the upper and lower tongue-and-groove slots (1) to secure the modules together (or
to a controller).
4. Move the module back along the tongue-and-groove slots until the bus connectors (2)
line up with each other.
5. Push the bus lever back slightly to clear the positioning tab (3).
Use your fingers or a small screwdriver.
6. To allow communication between the controller and module, move the bus lever fully to
the left (4) until it clicks.
Be sure it is locked firmly in place.
ATTENTION: When attaching I/O modules, it is very important that the bus
connectors are securely locked together to ensure proper electrical connection.
7. Attach an end cap terminator (5) to the last module in the system by using the
tongue-and-groove slots as before.
8. Lock the end cap bus terminator (6).
Mounting Expansion I/O
A 1769-ECR or 1769-ECL right or left end cap must be used to terminate the end
of the communication bus.
ATTENTION: During panel or DIN rail mounting of all devices, be sure that all
debris (such as metal chips or wire strands) is kept from falling into the module.
Debris that falls into the module could cause damage on power up.
ATTENTION: When used in a Class I, Division 2, hazardous location, this
equipment must be mounted in a suitable enclosure with proper wiring method
that complies with the governing electrical codes.
Publication 1769-IN074C-EN-P - March 2011
8 CompactLogix Isolated Analog Input Module
l Mounting
Host Controller
Refer to host controller documentation for this dimension.
Spacing for single-wide modules 35 mm (1.378 in.).
NOTE: Overall hole spacing
tolerance: ±0.4 mm (0.016 in.).
Spacing for one-and-a-half-wide modules 52.5 mm (2.067 in.).
Locate holes every 17.5 mm (0.689 in.) to allow for a
mix of single-wide and one-and-a-half-wide modules
(for example, the 1769-OA16 module).
Grounding the Module
ATTENTION: This product is intended to be mounted to a well-grounded mounting
surface such as a metal panel. Additional grounding connections from the power
supply's mounting tabs or DIN rail (if used) are not required unless the mounting
surface cannot be grounded. Refer to Industrial Automation Wiring and Grounding
Guidelines, Rockwell Automation publication 1770-4.1
, for additional information.
Minimum Spacing
Maintain spacing from enclosure walls, wireways, and adjacent equipment. Allow 50 mm (2 in.)
of space on all sides for adequate ventilation, as shown.
Panel Mounting
Mount the module to a panel by using two screws per module. Use M4 or #8 panhead screws.
Mounting screws are required on every module.
Panel Mounting Using the Dimensional Template
Panel Mounting Procedure Using Modules as a Template
The following procedure allows you to use the assembled modules as a template for drilling holes
in the panel. If you have sophisticated panel mounting equipment, you can use the dimensional
template provided on page 8
this procedure.
Publication 1769-IN074C-EN-P - March 2011
1. On a clean work surface, assemble no more than three modules.
2. Using the assembled modules as a template, carefully mark the center of all
module-mounting holes on the panel.
3. Return the assembled modules to the clean work surface, including any previously
mounted modules.
. Due to module mounting hole tolerance, it is important to follow
CompactLogix Isolated Analog Input Module 9
TIP
TIP
4. Drill and tap the mounting holes for the recommended M4 or #8 screw.
5. Place the modules back on the panel and check for proper hole alignment.
6. Attach the modules to the panel using the mounting screws.
If mounting more modules, mount only the last one of this group and put the others
aside. This reduces remounting time during drilling and tapping of the next group.
7. Repeat steps 1
… 6 for any remaining modules.
DIN Rail Mounting
The module can be mounted using the following DIN rails:
35 x 7.5 mm (1.38 x 0.30 in.; EN 50 022 - 35 x 7.5)
35 x 15 mm (1.38 x 0.59 in.; EN 50 022 - 35 x 15)
Before mounting the module on a DIN rail, close the DIN rail latches. Press the DIN rail
mounting area of the module against the DIN rail. The latches will momentarily open and lock
into place.
Replacing a Single Module within a System
The module can be replaced while the system is mounted to a panel (or DIN rail). Follow these
steps.
1. Remove power.
See important note on page 6
2. On the module to be removed, remove the upper and lower mounting screws from the
module (or open the DIN latches by using a flat-blade or phillips-style screwdriver).
3. Move the bus lever to the right to disconnect (unlock) the bus.
4. On the right-side adjacent module, move its bus lever to the right (unlock) to disconnect
it from the module to be removed.
5. Gently slide the disconnected module forward.
.
If you feel excessive resistance, check that the module has been disconnected from the
bus and that both mounting screws have been removed (or DIN latches opened).
It may be necessary to rock the module slightly from front to back to remove it, or,
in a panel-mounted system, to loosen the screws of adjacent modules.
6. Before installing the replacement module, be sure that the bus lever on the module to be
installed and on the right-side adjacent module are in the unlocked (fully right) position.
Publication 1769-IN074C-EN-P - March 2011
10 CompactLogix Isolated Analog Input Module
7. Slide the replacement module into the open slot.
8. Connect the modules together by locking (fully left) the bus levers on the replacement
module and the right-side adjacent module.
9. Replace the mounting screws (or snap the module onto the DIN rail).
Replacement Part
Terminal block, catalog number 1769-RTBN18 (one per kit).
System Wiring Guidelines
ATTENTION: Use supply wires suitable for 20 °C (68 °F) above surrounding
ambient.
Consider the following when wiring your system:
• Do not use the analog module’s NC terminals as connection points.
• Channels are isolated from each other.
• Use Belden 8761, or equivalent, shielded wire.
• Under normal conditions, the drain wire and shield junction must be connected to earth
ground via a panel or DIN rail mounting screw at the analog I/O module end. Keep the
shield connection to ground as short as possible.
• To ensure optimum accuracy, limit overall cable impedance by keeping your cable as
short as possible. Locate the I/O system as close to your sensors or actuators as your
application will permit.
• If multiple power supplies are used with analog inputs, the power supply commons must
be connected.
• The 1769-IF4I module does not provide loop power for analog inputs. Use a power
supply that matches the input transmitter specifications.
• Differential analog inputs are more immune to noise than single-ended analog inputs.
(1)
(1) In environments where high-frequency noise may be present, it may be necessary to directly ground cable shields to earth
at the module end and via a 0.1µF capacitor at the sensor end.
Publication 1769-IN074C-EN-P - March 2011
CompactLogix Isolated Analog Input Module 11
IMPORTANT
Belden 8761 Cable
(or Equivalent)
Analog Source
• Voltages on Ch+, Ch-, and Ch_iRtn for a single, isolated channel of the 1769-IF4I
module must not exceed the maximum overload levels detailed in the
Input Specifications on page 21.
ATTENTION: To comply with UL restrictions, this equipment must be powered
from a source compliant with Class 2 or Limited Voltage/Current.
Be careful when stripping wires. Wire fragments that fall into a module could
cause damage at power up. Once wiring is complete, make sure that the module
is free of all metal fragments.
Wiring Differential Inputs
1769-IF4I input channels connected to current sources must have a jumper wire
placed between Ch#_iRtn and the Ch#- terminals for that channel.
A removable, write-on label is provided with the module. Remove the label from the door, mark
the identification of each terminal with permanent ink, and slide the label back into the door.
Your markings (ID tag) will be visible when the module door is closed.
Removing the Finger-safe Terminal Block
WARNING: When you connect or disconnect the removable terminal block (RTB)
with field side power applied, an electrical arc can occur. This could cause an
explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
When wiring field devices to the module, it is not necessary to remove the terminal block. If you
remove the terminal block, use the write-on label on the side of the terminal block to identif y the
module slot location and type. RTB position can be indicated by circling either the ‘R’ for right
side or ‘L’ for left side.
To remove the terminal block, loosen the upper and lower retaining screws. The terminal block
will back away from the module as you remove the screws. When replacing the terminal block,
torque the retaining screws to 0.46 N•m (4.1 lb•in).
Wiring the Finger-safe Terminal Block
When wiring the terminal block, keep the finger-safe cover in place.
1. Loosen the terminal screws to be wired.
2. Route the wire under the terminal pressure plate.
Publication 1769-IN074C-EN-P - March 2011
14 CompactLogix Isolated Analog Input Module
TIP
TIP
You can use the bare wire or a spade lug. The terminals will accept a 6.35 mm (0.25 in.)
spade lug.
The terminal screws are non-captive. Therefore, it is possible to use a ring lug
[maximum 1/4 inch o.d. with a 0.139 in. minimum i.d. (M3.5)] with the module.
3. Tighten the terminal screw, making sure the pressure plate secures the wire.
Recommended torque when tightening terminal screws is 0.68 N•m (6 lb•in).
If you need to remove the finger-safe cover, insert a screwdriver into one of the
square wiring holes and gently pry off the cover. If you wire the terminal block
with the finger-safe cover removed, you will not be able to put the cover back
on the terminal block because the wires will obstruct the cover.
Wire Size and Terminal Screw Torque
Each terminal accepts one or two wires with the following restrictions.
Wire TypeWire SizeTerminal Screw
SolidCu-90 °C (194°F)#14…#22 AWG0.68 N•m
StrandedCu-90 °C (194°F)#16…#22 AWG0.68 N•m
Torque
(6 lb•in)
(6 lb•in)
Retaining Screw
Tor qu e
0.46 N•m
(4.1 lb•in)
0.46 N•m
(4.1 lb•in)
I/O Memory Mapping
Input Data File
For each input module, slot x, words 0-3 in the input data file contain the analog values of the
inputs.
Bit Position
15 14131211109876543210
Word
0SGNAnalog Input Data Channel 0
1SGNAnalog Input Data Channel 1
2SGNAnalog Input Data Channel 2
3SGNAnalog Input Data Channel 3
4NuTime Stamp Value
5 Nu NuNuNuNuNuNuNuNuNuNuNuS3S2S1 S0
6 L3H3U3O3L2 H2U2O2L1 H1U1O1L0 H0U0O0
Publication 1769-IN074C-EN-P - March 2011
CompactLogix Isolated Analog Input Module 15
The bits are defined as follows:
• SGN = Sign bit in two’s complement format
• Nu = Not used. Bit set to 0
• Sx = General status bit for input channels 0…3
• Lx = Low alarm flag bits for input channels 0…3
• Hx = High alarm flag bits for input channels 0…3
• Ux = Under-range flag bits for channels 0…3
When set, the input signal is under normal range or an open circuit condition exists, in
the case of the 4…20 mA range.
• Ox = Over-range flag bits for channels 0…3
When set, the input signal is over normal range or an open circuit condition exists (open
circuit detection applies to voltage input ranges only).
Output Data File
For each input module, slot x, word 0 in the output data file contains the analog values of the
outputs.
Bit Position
1514131211109876543210
Word
0Nu Nu Nu Nu Nu Nu Nu Nu UL3 UH3 UL2 UH2 UL1 UH1 UL0 UH0
The bits are defined as follows:
• Nu = Not used. Bit set to 0
• UHx = Cancel High Process Alarm Latch x
Allows each high process alarm latch to be individually cancelled. Cancel = 1.
• ULx = Cancel Low Process Alarm Latch x
Allows each low process alarm latch to be individually cancelled. Cancel = 1.
Publication 1769-IN074C-EN-P - March 2011
16 CompactLogix Isolated Analog Input Module
Configuration Data File
The manipulation of the bits from this file is normally done with programming software (for
example, RSLogix 5000 or RSNetWorx for DeviceNet software) during initial configuration of
the system. In that case, graphical screens are provided by the programmer to simplify
configuration. However, some systems, like the 1769-ADN DeviceNet adapter, also allow the
bits to be altered as part of the control program, using communication rungs. In that case, it is
necessary to understand the bit arrangement.
Configuration Data Array
Bit Position
15 14131211109876543210
Word
0Real Time Sample Value
1ETSReserved
2ECReservedEA AL EIReservedInput Filter Sel Chl0
3ReservedInpt Dta Fm
Chl0
4SProcess Alarm High Data Value Channel 0
5SProcess Alarm Low Data Value Channel 0
6SAlarm Dead Band Value Channel 0
7Reserved
8ECReservedEA AL EIReservedInpt Filter Sel Chl1
9ReservedInpt Dta Fm
Chl1
10 SProcess Alarm High Data Value Channel 1
11 SProcess Alarm Low Data Value Channel 1
12 SAlarm Dead Band Value Channel 1
13 Reserved
14 ECReservedEA ALEIReservedInput Filter Sel Chl2
15 ReservedInpt Dta Fm
Chl2
16 SProcess Alarm High Data Value Channel 2
17 SProcess Alarm Low Data Value Channel 2
18 SAlarm Dead Band Value Channel 2
19 Reserved
20 ECReservedEA ALEIReservedInput Filter Sel Chl3
21 ReservedInpt Dta Fm
Chl3
22 SProcess Alarm High Data Value Channel 3
23 SProcess Alarm Low Data Value Channel 3
ReservedInpt Tp/RngeSel Chl0
ReservedInpt Tp/RngeSel Chl1
ReservedInpt Tp/RngeSel Chl2
ReservedInpt Tp/RngeSel Chl3
Publication 1769-IN074C-EN-P - March 2011
CompactLogix Isolated Analog Input Module 17
Configuration Data Array (cont.)
Bit Position
15 14131211109876543210
Word
24 SAlarm Dead Band Value Channel 3
25 Reserved
The bits are defined as follows:
• EC = Enable Channel
• Inpt Dta Fm Chlx = Input Data Format Select
• EA = Enable Alarm
• AL = Alarm Latch
• EI = Enable Interrupt
(1)
• Inpt Tp/Rnge Sel Chlx = Input Type/Range Select
• Inpt Filter Sel Chlx = Input Filter Select
• Reserved = Allows for future expansion
• ETS = Enable Time Stamp
Bit Definitions for Channel Configuration Words
DefineTo SelectMake these bit settings
15 14…11 10 987…43210
Input Filter Selection 60 Hz0000
50 Hz0001
28.5 Hz0010
300 Hz0011
360 Hz0100
Enable InterruptEnable1
Disable0
Enable Process
AlarmLatch
Enable Process
Alarms
Enable ChannelEnable1
Enable1
Disable0
Enable1
Disable0
Disable0
(1) MicroLogix 1500 and CompactLogix L3x controllers do not support interrupts.
Publication 1769-IN074C-EN-P - March 2011
18 CompactLogix Isolated Analog Input Module
Bit Definitions for Input Range and Input Data Configuration
DefineIndicate ThisThese bit settings
15…1110987…43210
Input Range Select-10…+10V DC0000
0…5V DC
0001
0…10V DC0010
4…20 mA
0011
1…5V DC0100
0…20 mA
Input Data Select Raw/Proportional
000
0101
Counts
Engineering Units001
Scaled for PID010
Percent Range011
Specifications
Technical Specifications 1769-IF4I
Attribute1769-IF4I
Enclosure type ratingNone (open-style)
Dimensions, HxWxD (approx.)118 mm x 35 mm x 87 mm
Height including mounting tabs is 138 mm
4.65 in. x 1.38 in. x 3.43 in.
Height including mounting tabs is 5.43 in.
Approximate shipping weight
(with carton)
Enclosure type ratingNone (open-style)
Wire size…0.32…2.1 mm
Wiring category
(1)
North American temp codeT4A
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication 1770-4.1
300 g (0.66 lb)
2
(22…14 AWG) solid copper wire
2
or 0.32…1.3 mm
(22…16 AWG) stranded
copper wire rated at 90 °C (194 °F ) insulation
max
channel to system and channel to channel
Type tested at 710V DC for 60 s
Publication 1769-IN074C-EN-P - March 2011
CompactLogix Isolated Analog Input Module 21
Input Specifications
Attribute1769-IF4I
Analog normal operating
(1)
ranges
Full scale analog ranges
Number of inputs4 isolated differential
Bus current draw (max)145 mA at 5V DC
Heat dissipation3.0 Total Watts (The Watts per point, plus the minimum Watts, with
Converter typeDelta Sigma
Response speed per channel Input filter and configuration dependent. See your user manual.
Resolutions (max)
(2)
Rated working voltage
Common mode rejectionGreater than 60 dB at 50 and 60 Hz with the 10 Hz filter selected,
Normal mode rejection ratio -50 dB at 50 and 60 Hz with the 10 Hz filter selected, respectively.
Input impedanceVoltage Terminal: 1M Ω (typical)
Overall accuracy
(1) The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will
continue to convert the analog input up to the maximum full scale range. The flag automatically resets when within the
normal operating range.
(2) Resolution is dependent upon your filter selection. The maximum resolution is achieved with the 10 Hz filter selected.
(3) Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input
signal and the value that floats above ground potential (for example, 10V DC input signal and 20V DC potential above
ground).
(4) Includes offset, gain, non-linearity and repeatability error terms.
(4)
Voltage: ± 10V DC, 0…10V DC, 0…5V DC, 1…5V DC
Current: 0…20 mA, 4…20 mA
(1)
Voltage: ± 10.5V DC, 0…10.5V DC, 0…5.25V DC, 0.5…5.25V DC
Current: 0…21 mA, 3.2…21 mA
125 mA at 24V DC
all points energized.)
16 bits (unipolar)
15 bits plus sign (bipolar)
(3)
30V AC
30V DC
respectively.
Current Terminal: 249 Ω
Voltage Terminal: ±0.2% full scale at 25 °C (77 °F)
Current Terminal: ±0.35% full scale at 25 °C (77 °F)
Publication 1769-IN074C-EN-P - March 2011
22 CompactLogix Isolated Analog Input Module
Input Specifications (cont.)
AttributeValue
Accuracy drift with
temperature
CalibrationThe module performs only initial factory calibration.
Non-linearity (in percent full
scale)
Repeatability
(1)
Module error over full
temperature range
(0…60 °C [+32…140 °F])
Input channel configurationVia configuration software screen or the user program (by writing
Module OK status indicatorOn: module has power, has passed internal diagnostics, and is
Channel diagnosticsOver- or under-range by bit reporting, process alarms
Maximum overload at input
(1) Repeatability is the ability of the input module to register the same reading in successive measurements for the same input
signal.
(2) Damage may occur to the input circuit if this value is exceeded.
Voltage terminal: ±0.003% per °C
Current terminal: ±0.0045% per °C
±0.03%
±0.03%
Voltage: ±0.3%
Current: ±0.5%
a unique bit pattern into the module’s configuration file). Refer to
your controller’s user manual to determine if user program
configuration is supported.
communicating over the bus.
Off: Any of the above is not true.
Voltage Terminal: ±24V DC continuous, 0.1 mA
Current Terminal: ±28 mA continuous, ±7.0V DC
8 (The module may not be more than 8 modules away from the
system power supply)
Publication 1769-IN074C-EN-P - March 2011
CompactLogix Isolated Analog Input Module 23
Certifications 1769-IF4I
Certifications
(when product is marked)
c-UL-usUL Listed for Class I, Division 2 Group A,B,C,D
CEEuropean Union 2004/108/EC EMC Directive,
(1)
1769-IF4I
Hazardous Locations, certified for U.S. and
Canada. See UL File E10314.
(1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification
details.
Additional Resources
These documents contain additional information concerning related Rockwell Automation
products.
ResourceDescription
CompactLogix I/O Analog Modules
User Manual, publication 1769-UM002
MicroLogix 1500 Programmable
Controllers User Manual, publication
1764-UM001
1769-ADN DeviceNet Adapter User
Manual, publication1769-UM001
You can view or download publications at http://www.rockwellautomation.com/literature/
order paper copies of technical documentation, contact your local Rockwell Automation
distributor or sales representative.
Provides detailed information on installing,
programming, and troubleshooting CompactLogix
analog I/O modules.
Provides a detailed description for installing and using
Compact I/O modules with a MicroLogix 1500
programmable controller.
Provides a detailed description of how to install and use
Compact I/O modules with the 1769-ADN DeviceNet
adapter.
Publication 1769-IN074C-EN-P - March 2011
. To
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At
http://www.rockwellautomation.com/support/
technical and application notes, sample code and links to software service packs, and a MySupport feature that
you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and troubleshooting, we offer
TechConnect support programs. For more information, contact your local distributor or Rockwell Automation
representative, or visit http://www.rockwellautomation.com/support/
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's
contained in this manual. You can also contact a special Customer Support number for initial help in getting your
product up and running.
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the
manufacturing facility. However, if your product is not functioning and needs to be returned, follow these
procedures.
, you can find technical manuals, a knowledge base of FAQs,
.
at
, or contact
United States
Outside United States
Contact your distributor. You must provide a Customer Support case number (call the
phone number above to obtain one) to your distributor to complete the return process.
Please contact your local Rockwell Automation representative for the return
procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to
improve this document, complete this form, publication RA-DU002
http://www.rockwellautomation.com/literature/
Allen-Bradley, CompactLogix, RSLogix , RSNetWorx, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell
Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
.
Publication 1769-IN074C-EN-P - March 2011PN-101424