Compact
Combination 24V dc
Sink Input/Source
Output BOOLEAN
Control Module
1769-BOOLEAN
Reference Manual
Important User Information
SHOCK HAZARD
Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Safety Guidelines for the Application,
Installation and Maintenance of Solid State Controls (publication SGI-1.1
available from your local Rockwell Automation sales office or online at
http://literature.rockwellautomation.com
) describes some important
differences between solid state equipment and hard-wired electromechanical
devices. Because of this difference, and also because of the wide variety of uses
for solid state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is
acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect
or consequential damages resulting from the use or application of this
equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with any
particular installation, Rockwell Automation, Inc. cannot assume responsibility
or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to
use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without
written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of
safety considerations.
WARNING
IMPORTANT
ATTENTION
Identifies information about practices or circumstances that can cause
an explosion in a hazardous environment, which may lead to personal
injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and
understanding of the product.
Identifies information about practices or circumstances that can
lead to personal injury or death, property damage, or economic
loss. Attentions help you identify a hazard, avoid a hazard, and
recognize the consequence
Labels may be located on or inside the equipment, for example, a drive
or motor, to alert people that dangerous voltage may be present.
BURN HAZARD
Labels may be located on or inside the equipment, for example, a drive
or motor, to alert people that surfaces may be dangerous
temperatures.
Allen-Bradley, Compact I/O, MicroLogix 1500, RSLogix 500, CompactLogix, RSLogix 5000, RSNetWorx, and RSLinx are trademarks of
Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Read this preface to familiarize yourself with the rest of the manual. This
preface covers the following topics:
• Who should use this manual
• How to use this manual
• Related publications
• Conventions used in this manual
Who Should Use This
Manual
How to Use This Manual
Use this manual if you are responsible for designing, installing, programming,
or troubleshooting control systems that use the Allen-Bradley Compact I/O
system.
As much as possible, we organized this manual to explain, in a task-by-task
manner, how to install, configure, program, operate, and troubleshoot a
control system using the 1769 BOOLEAN module.
7Publication 1769-RM016A-EN-P - July 2006
8
Related Documentation
The table below provides a listing of publications that contain important
information about using Compact I/O modules.
ForRead this documentDocument number
A user manual containing information on how to install,
use and program your MicroLogix 1500 controller.
A user manual containing information on how to install,
and use your 1769-ADN DeviceNet adapter.
A user manual containing information on how to install,
use and program your 1769-L20 and 1769-L30
CompactLogix controllers.
A user manual containing information on how to install,
use and program your 1769-L31, 1769-L32C, 1769-L32E,
1769-L35CR and 1769-L35E CompactLogix controllers.
An overview of 1769 Compact I/O modules.Compact I/O System Selection Guide1769-SG002
In-depth information on grounding and wiring
Allen-Bradley programmable controllers.
MicroLogix 1500 User Manual1764-UM001
DeviceNet Adapter User Manual1769-UM001
CompactLogix User Manual1769-UM007
CompactLogix System User Manual1769-UM011
Allen-Bradley Programmable Controller Grounding and
Wiring Guidelines
1770-4.1
If you would like a manual, you can:
• download a free electronic version from the Internet at
http://literature.rockwellautomation.com
• purchase a printed manual by contacting your local distributor or
Rockwell Automation representative.
Conventions Used in This
Manual
Publication 1769-RM016A-EN-P - July 2006
We use the following conventions throughout this manual.
• Bulleted lists (like this one) provide information, not procedural steps.
• Numbered lists provide sequential steps or hierarchical information.
• Bold type is used for emphasis.
Module Operation
Chapter
1
Overview
This chapter contains information about the following.
• Module description
• Module block diagram
• Input and output circuit diagrams
• Controlling outputs using Boolean expressions
– Format of Boolean expression
– Allowed variations of Boolean expressions
– Operands
– Operators
– Output delay control
– Output duration control
– Delay/Duration control rules and examples
TopicPage
About the 1769-BOOLEAN Module1
Module Description11
Boolean Expressions12
1769-BOOLEAN Module Block Diagram13
Wire the 1769-BOOLEAN Module14
Control Outputs Using Boolean Expressions15
Boolean Expression Configuration Restrictions15
Boolean Control Mode Examples19
9Publication 1769-RM016A-EN-P - July 2006
10 Module Operation
About the 1769-BOOLEAN
Module
The 1769-BOOLEAN module is a 24V dc combination input/output module.
The module outputs can be either directly controlled from your program or
independently controlled by the module using configured Boolean
expressions. These Boolean expressions are simple, logical combinations of
the module hardware input states and soft inputs controlled by your program.
When controlled by Boolean expression, the 1769-BOOLEAN module output
states can be conditioned using configured delay and duration settings. The
1769-BOOLEAN module supports interrupts to the system controller on
both input and output change of states
(1)
.
The Compact I/O system is suitable for use in an industrial environment
when installed in accordance with these instructions. Specifically, this
equipment is intended for use in clean, dry environments (Pollution degree
(2)
) and to circuits not exceeding Over Voltage Category II
2
(4)
60664-1)
.
(3)
(IEC
Publication 1769-RM016A-EN-P - July 2006
(1)
Interrupts from the module to the controller may not be supported by all controllers. Refer to your controller's
user manual for more information.
(2)
Pollution Degree 2 is an environment where, normally, only nonconductive pollution occurs except that occasionally a
temporary conductivity caused by condensation is expected.
(3)
Over Voltage Category II is the load-level section of the electrical distribution system. At this level, transient voltages are
controlled and do not exceed the impulse voltage capability of the product’s insulation.
(4)
Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC) designations.
Module Description
1
5
b
Module Operation 11
7a
10a
10b
8a
10
0
2
1
3
0246
IN OUT
BOOLEAN
7531
7a
2a
DANGER
Do Not Remove RTB Under Power
Unless Area is Non-Hazardous
+VDC
OUT 0
OUT 1
OUT 2
OUT 3
OUT DC
COM
N.C.
N.C.
N.C.
IN 0
IN 1
IN 2
IN 3
IN 4
IN 5
IN 6
IN 7
IN DC
COM
Ensure Adjacent
Bus Lever is Unlatched/Latched
Before/After
Removing/Inserting Module
1769-BOOLEAN
2b
3
4
Item Description
1Bus lever (with locking
function)
2aUpper panel mounting tab
2bLower panel mounting tab
3Module status LED
4Module door with terminal
identification label
5aMovable bus connector
with female pins
5bStationary bus connector
with male pins
6Nameplate label
0
2
1
3
0246
IN OUT
7531
BOOLEAN
a
9
0
1
2
3
0
1
2
3
4
5
6
7
0
1
2
3
0
IN OUT
2
1
46
3
Boolean
5
7
7aUpper
tongue-and-groove slots
7bLower
tongue-and-groove slots
5
8aUpper DIN rail latch
8bLower DIN rail latch
9Write-on label (user ID tag)
The 1769-BOOLEAN module contains a removable terminal block. The
module input circuits are isolated from the output circuits. Single-ground
applications can be supported by wiring the IN DC COM and the OUT DC
COM terminals together; however, this eliminates the isolation between the
input and output circuits provided by the module.
Module configuration is normally done via the controller programming
software. In addition, some controllers support configuration via the user
program. In either case, the controller memory stores the module
configuration. Refer to your controller's user manual for more information.
Publication 1769-RM016A-EN-P - July 2006
12 Module Operation
Boolean Expressions
An expression is any legal combination of symbols that represents a value. An
expression that results in a value of either TRUE or FALSE is called a Boolean
expression. Every Boolean expression (except a null expression) consists of at
least one operand and can have one or more operators. Operands are values,
whereas operators are symbols that represent particular logical actions. For
example, in the expression
OUT = A AND B,
the value of OUT is either TRUE or FALSE and is determined by the value of
the expression “A AND B”. A and B are operands that also have a value of
TRUE or FALSE. The operator in the expression is the logical operator AND.
Other examples of logical operators are OR and XOR (exclusive-OR).
The 1769-BOOLEAN module outputs can be controlled based upon the
value of Boolean expressions configured by the program. An output state
(when in Boolean control mode) is determined by the state of that output’s
configured Boolean expression, with a value of TRUE corresponding to the
ON state and a value of FALSE corresponding to the OFF state.
Refer to Chapter 3, Module Data, Status, and Configuration on page 41, for
information on configuring control of the 1769-BOOLEAN module outputs
using Boolean expressions.
Publication 1769-RM016A-EN-P - July 2006
Module Operation 13
1769-BOOLEAN Module
Block Diagram
The following figure is the block diagram for the 1769-BOOLEAN module.
1769-BOOLEAN Module Block Diagram
Publication 1769-RM016A-EN-P - July 2006
14 Module Operation
Wire the 1769-BOOLEAN
Module
Each terminal accepts as many as two wires with these restrictions.
Wire TypeWire SizeTerminal
Screw Torque
SolidCu-90 °C (194 °F) 2.08…0.34 mm
(14…22 AWG)
StrandedCu-90 °C (194 °F) 1.31…0.34 mm
(16…22 AWG)
2
0.68 Nm (6 lb-in)0.46 Nm (4.1
2
0.68 Nm (6 lb-in)0.46 Nm (4.1
Retaining
Screw Torque
lb-in)
lb-in)
Input and Output Circuit Diagrams
The following figures illustrate the simplified input and output circuits.
Simplified Input Circuit Diagram
Publication 1769-RM016A-EN-P - July 2006
Simplified Output Circuit Diagram
+VDC
OUT x
OUT DC COM
Module Operation 15
Control Outputs Using
Boolean Expressions
You can configure the 1769-BOOLEAN module outputs to be controlled by
Boolean expression (Boolean control mode).
Format of Boolean Expression
Each output is controlled with a separate expression. The fixed format of each
Boolean expression is assumed to be of the form:
Output State = (A x B) y C
where A, B, and C are operands and x and y are logical operators you select.
The location of the parentheses in the fixed format indicates that the logical
operation represented by x is performed on operands A and B first, with the
result of that operation then used as the first operand for the logical operation
represented by y (with C being the second operand).
The parameter names assigned in the 1769-BOOLEAN module configuration
file that correspond to the operands and operators of the fixed format
Boolean expression above are:
A: Operand_A_#
Boolean Expression
Configuration Restrictions
B: Operand_B_#
C: Operand_C_#
x: Operator_1_#
y: Operator_2_#
where the # symbol indicates the module output (OUT0 through OUT3).
The Boolean expressions controlling the output states have default values
assigned to each operand and operator. These default values assign “None” to
each operand and operator resulting in a “Null” expression. A “Null”
expression will be accepted by the module but will result in an output that will
always be in the OFF state.
The module will only accept the following variations of Boolean expressions
as valid (based on the fixed format expression (A x B) y C).
Publication 1769-RM016A-EN-P - July 2006
16 Module Operation
Variations of Boolean Expressions
VariationDescription
NullAll operands and operators assigned a value of “None”.
AOnly the first operand assigned a non-default value, all other
operands and all operators assigned a value of “None”.
A x BOnly the first two operands and the first operator assigned a
non-default value, final operand and final operator assigned
a value of “None”
(A x B) y CAll operands and operators assigned non-default values)
Operands
The operands in each output's Boolean expression can be configured to be
one of the following.
• None (default)
• Current state of one of the module's eight, real inputs
• Inverted, current state of one of the module's eight, real inputs
• Current state of one of the module's eight, virtual inputs (controlled by
the user program via the module's output data file)
• Inverted, current state of one of the module's eight, virtual inputs
Refer to Chapter 3, Module Data, Status, and Configuration on page 41, for
details on configuring the Boolean expression operands.
Operators
The operators in each output Boolean expression can be configured to be one
of the following (the operator's effect on a pair of operands is described).
Boolean Expression and the Related Operator Effect
ExpressionOperator Effect
NoneDefault, no logical operation performed.
ORIf either operand in TRUE, the result is TRUE.
ANDBoth operands must be TRUE for the result to be TRUE.
Publication 1769-RM016A-EN-P - July 2006
XORExclusive - OR, one operand must be TRUE and the other
FALSE for the result to be TRUE.
Refer to Chapter 3, Module Data, Status, and Configuration on page 41, for
details on configuring the Boolean expression operators.
Module Operation 17
Output Delay
When configured for Boolean control, the module's outputs are directed ON
when the Boolean expression for each output channel is TRUE. The module
can be configured to add a delay between an output's Boolean expression
becoming TRUE and the output being placed into the ON state. The length of
this delay time for an output operating in Boolean control mode can be
configured to be between 0 (default) and 1 second in 1 ms increments.
Refer to Chapter 3, Module Data, Status, and Configuration on page 41, for
details on configuring the Boolean expression output delay.
Output Duration
When configured for Boolean control, if an output is directed ON as the result
of the output's Boolean expression becoming TRUE, and the Output Delay
time for that output has been satisfied, then the length of time an output stays
ON can be controlled by designating an Output Duration. The length of this
duration time for an output operating in Boolean control mode can be
configured to be either a fixed amount of time between 1 ms and 1 second (in
1 ms increments), or, the output can be configured to remain ON only as long
as its Boolean expression remains TRUE (duration time set to 0, this is the
default setting).
Refer to Chapter 3, Module Data, Status, and Configuration on page 41, for
details on configuring the Boolean expression output duration.
Publication 1769-RM016A-EN-P - July 2006
18 Module Operation
Output Delay and Duration Operation
Since an output's Boolean expression can change in real time, configuring a
delay and/or duration time when an output is in Boolean control mode could
cause confusion.
The module shall operate in the following manner when output delay and/or
duration times are configured to non-default values (while an output is
configured for Boolean control).
When the Boolean expression controlling an output transitions from FALSE
to TRUE, the output will be directed ON after the delay time has expired only
if:
Case 1
• The output's duration time is not equal to 0. In this case the output
should be directed ON for the length of the duration time regardless of
the state of the output's Boolean expression and then should be directed
OFF regardless of the state of the Boolean expression.
• In Case 1 a “One-shot” type of function has been configured. The
output will be turned ON with a single pulse of configured delay time
and duration time when the output's Boolean expression becomes
TRUE. The length of time the Boolean expression remains TRUE does
not determine whether the “One-shot” pulse occurs. As long as the
duration time of the output has been configured to a value greater than
0, then a “One-shot” ON pulse will occur and the output will remain
ON for the length of the duration time. The output will then turn OFF
regardless of the state of the output's Boolean expression.
• Retriggering of the output is not supported. Any additional transitions
of the output's Boolean expression from FALSE to TRUE after the
initial transition to TRUE are ignored for a length of time equal to the
configured delay time added to the configured duration time. Once the
output's “One-shot” pulse duration is complete, and the output is
turned OFF, a FALSE to TRUE transition of the Boolean expression
will cause another “One-shot” ON pulse to occur.
Case 2
• The output's duration is equal to 0 and the output's Boolean expression
has maintained a state of TRUE for the entire delay time. The output
should then be directed OFF when the output's Boolean expression
becomes FALSE.
Publication 1769-RM016A-EN-P - July 2006
Module Operation 19
• In Case 2 the output will follow the state of the Boolean expression as
long as the configured delay time has expired and the Boolean
expression has maintained a TRUE state. When an output's Boolean
expression transitions from FALSE to TRUE, the output will be turned
ON only if the Boolean expression has maintained a state of TRUE for
the entire length of the delay time. If the output's Boolean expression
transitions to FALSE before the configured delay time expires, then the
delay time should be terminated and the output should not be turned
ON. If the output's Boolean expression has maintained a TRUE state
for the full length of the delay time, the output will be turned ON and
will remain ON until the Boolean expression becomes FALSE.
• If an output's Boolean expression is configured with both the delay and
duration times set to 0, then the output simply follows the state of the
Boolean expression, ON when the expression is TRUE and OFF when
it is FALSE.
Boolean Control Mode
Examples
The following examples illustrate the module's operation when an output is
configured in Boolean control mode. Examples 1…5 show module output
operation for Case 1 where the configured duration time is greater than 0.
Examples 6 and 7 show module operation for Case 2 where the configured
duration time is equal to 0.
Example 1: Duration > 0, Delay > TRUE Time
In this example, the output is configured with a duration time greater than 0, a
delay time greater than 0, and the configured delay time is longer than the time
that the Boolean expression remains TRUE.
Since the configured duration time is greater than 0, a “One-shot” pulse
occurs on the output. The pulse starts an amount of time after the FALSE to
TRUE transition of the Boolean expression equal to the configured delay time.
The “One-shot” pulse lasts as long as the configured duration time even
though the Boolean expression transitions to FALSE. The second “One-shot”
pulse occurs on the output since there was a FALSE to TRUE transition in the
Boolean expression after the first “One-shot” pulse is completed.
Publication 1769-RM016A-EN-P - July 2006
20 Module Operation
Publication 1769-RM016A-EN-P - July 2006
Module Operation 21
Example 2: Duration > 0, Delay < TRUE Time
In this example, the output is configured with a duration time greater than 0, a
delay time greater than 0, and the configured delay time is shorter than the
time that the Boolean expression remains TRUE.
Again, since the configured duration time is greater than 0, a “One-shot” pulse
occurs on the output. The pulse starts an amount of time after the FALSE to
TRUE transition of the Boolean expression equal to the configured delay time.
The “One-shot” pulse again lasts only as long as the configured duration time
even though the Boolean expression remains TRUE. The second “One-shot”
pulse occurs on the output since there was a FALSE to TRUE transition in the
Boolean expression after the first “One-shot” pulse is completed.
Publication 1769-RM016A-EN-P - July 2006
22 Module Operation
Example 3: Duration > 0, Delay < TRUE Time, Retriggering Ignored
In this example, the output is configured with a duration time greater than 0, a
delay time greater than 0, and multiple transitions of the Boolean expression
occur before the initial “One-shot” pulse duration is completed.
The first FALSE to TRUE transition of the Boolean expression causes a
“One-shot” pulse to occur. The pulse starts an amount of time after the
FALSE to TRUE transition of the Boolean expression equal to the configured
delay time. The “One-shot” pulse lasts as long as the configured duration time.
Since the second FALSE to TRUE transition of the Boolean expression occurs
before the initial “One-shot” pulse is completed, that transition of the Boolean
expression is ignored by the module. The third FALSE to TRUE transition of
the Boolean expression again causes a “One-shot” pulse, with the fourth
FALSE to TRUE transition of the Boolean expression again ignored by the
module since it occurs before the second “One-shot” pulse is complete.
Publication 1769-RM016A-EN-P - July 2006
Module Operation 23
Example 4: Duration > 0, Delay = 0, Duration > TRUE Time
In this example, the output is configured with a duration time greater than 0, a
delay time equal to 0, and the configured duration time is longer than the time
that the Boolean expression remains TRUE.
Since the configured duration time is greater than 0, a “One-shot” pulse
occurs on the output. The pulse starts at the same time as the FALSE to
TRUE transition of the Boolean expression because the configured delay time
is equal to 0. The “One-shot” pulse lasts as long as the configured duration
time even though the Boolean expression transitions to FALSE.
Publication 1769-RM016A-EN-P - July 2006
24 Module Operation
Example 5: Duration > 0, Delay = 0, Duration < TRUE Time
In this example, the output is configured with a duration time greater than 0, a
delay time equal to 0, and the configured duration time is shorter than the time
that the Boolean expression remains TRUE.
Again, since the configured duration time is greater than 0, a “One-shot” pulse
occurs on the output. The pulse starts at the same time as the FALSE to
TRUE transition of the Boolean expression because the configured delay time
is equal to 0. The “One-shot” pulse again lasts only as long as the configured
duration time even though the Boolean expression remains TRUE. The
second “One-shot” pulse occurs on the output since there was a FALSE to
TRUE transition in the Boolean expression after the first “One-shot” pulse is
completed.
Publication 1769-RM016A-EN-P - July 2006
Module Operation 25
Example 6: Duration = 0, Delay < TRUE Time
In this example, the output is configured with a duration time equal to 0 (the
output will remain ON only if the Boolean expression remains TRUE), a delay
time greater than 0, and the Boolean expression continuously remains TRUE
for a length of time greater than the configured delay time.
Since the delay time is greater than 0, the output does not turn ON until the
Boolean expression has maintained a TRUE condition for a period of time
equal to the configured delay time. The output remains ON until the Boolean
expression becomes FALSE. The output immediately turns OFF since the
configured duration time is 0.
Publication 1769-RM016A-EN-P - July 2006
26 Module Operation
Example 7: Duration = 0, Delay > TRUE Ti me
In this example, the output is configured with a duration time equal to 0 (the
output will remain ON only if the Boolean expression remains TRUE) and a
delay time greater than 0. Conditions where the Boolean expression remains
TRUE both for less than and longer than the configured delay time are
illustrated.
Publication 1769-RM016A-EN-P - July 2006
The first instance that the Boolean expression goes to the TRUE state, but
does not remain continuously TRUE for a period of time exceeding the
configured delay time, it does not cause the output to turn ON. When this first
TRUE condition ends, the corresponding delay time event also ends. The next
time the Boolean expression becomes TRUE, a new delay time event begins.
This second TRUE event does continuously remain TRUE for longer than the
configured delay time and the output turns ON. The output remains ON until
the Boolean expression becomes FALSE, at which point it immediately turns
OFF since the configured duration time is 0.
Installation and Wiring
Chapter
2
Overview
This chapter tells you how to:
• determine the power requirements for the module.
• avoid electrostatic damage.
• install the module.
• wire the module’s terminal block.
• wire input devices.
• wire output devices.
TopicPage
Compliance to European Union Directives27
Power Requirements28
General Considerations28
System Assembly31
Mount the Module32
Replace a Single Module Within a System34
Field Wiring Connections35
Wire the Module38
Compliance to European
This product is approved for installation within the European Union and EEA
regions. It has been designed and tested to meet the following directives.
Union Directives
EMC Directive
The analog modules are tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) and the following standards, in whole
or in part, documented in a technical construction file:
• EN 61000-6-4:2001
Electromagnetic Compatibility (EMC) - Part 6-4: Generic Standards Emission Standard for Industrial Environments
• EN 61000-6-2:2001
Electromagnetic Compatibility (EMC) - Part 6-4: Generic Standards Immunity for Industrial Environments
This product is intended for use in an industrial environment.
27Publication 1769-RM016A-EN-P - July 2006
28 Installation and Wiring
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low Voltage, by
applying the safety requirements of EN 61131-2 Programmable Controllers,
Part 2 – Equipment Requirements and Tests.
For specific information required by EN61131-2, see the appropriate sections
in this publication, as well as the following Allen-Bradley publications:
• Industrial Automation Wiring and Grounding Guidelines for Noise
Immunity, publication 1770-4.1
• Automation Systems Catalog, publication B113
Power Requirements
General Considerations
The module receives power through the bus interface from the +5V dc/+24V
dc system power supply. The maximum current draw for the
1769-BOOLEAN module is:
• 5V dc: 220 mA.
• 24V dc: 0 mA.
The Compact I/O system is suitable for use in an industrial environment
when installed in accordance with these instructions. Specifically, this
equipment is intended for use in clean, dry environments (Pollution degree
(1)
) and to circuits not exceeding Over Voltage Category II
2
60664-1).
(3)
(2)
(IEC
Publication 1769-RM016A-EN-P - July 2006
(1)
Pollution Degree 2 is an environment where, normally, only nonconductive pollution occurs except that
occasionally a temporary conductivity caused by condensation shall be expected.
(2)
Over Voltage Category II is the load level section of the electrical distribution system. At this level transient
voltages are controlled and do not exceed the impulse voltage capability of the product’ s insulation.
(3)
Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC)
designations.
Installation and Wiring 29
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or
nonhazardous locations only. The following attention statement applies to use
in hazardous locations.
ATTENTION
Explosion Hazard
• Substitution of components may impair suitability for Class I,
Division 2.
• Do not replace components or disconnect eq uipment unless
power has been switched off or the area is known to be
nonhazardous.
• Do not connect or disconnect components unless power has
been switched off or the area is known to be nonhazardous.
• This product must be installed in an enclosure.
• All wiring must comply with N.E.C. article 501-4(b).
Prevent Electrostatic Discharge
ATTENTION
Electrostatic discharge can damage integrated circuits or
semiconductors if you touch th e bus connector pins or the
terminal block on the module. Follow these guidelines when
you handle the module:
• Touch a grounded object to discharge static potential.
• Wear an approved wrist-strap grounding device.
• Do not touch the bus connector or connector pins.
• Do not touch circuit components inside the module.
• Use a static-safe work station, if available.
• Keep the module in its static-shield box when it is not in
use.
Publication 1769-RM016A-EN-P - July 2006
30 Installation and Wiring
Remove Power
ATTENTION
Remove power before removing or inserting this module. When
you remove or insert a module with power applied, an electrical
arc may occur. An electrical arc can cause personal injury or
property damage by:
• sending an erroneous signal to your system’s field devices,
causing unintended machine motion.
• causing an explosion in a hazardous environment.
Electrical arcing causes excessive wear to contacts on both the
module and its mating connector and may lead to premature
failure.
Reduce Noise
Most applications require installation in an industrial enclosure to reduce the
effects of electrical interference. Group your modules to minimize adverse
effects from radiated electrical noise and heat. Consider the following
conditions when selecting a location for the module. Position the module:
• away from sources of electrical noise such as hard-contact switches,
relays, and ac motor drives.
• away from modules that generate significant radiated heat, such as the
1769-IA16 module. Refer to the module’s heat dissipation specification.
Publication 1769-RM016A-EN-P - July 2006
Protect the Circuit Board from Contamination
The printed circuit board of the module must be protected from dirt, oil,
moisture, and other airborne contaminants. To protect the printed circuit
board, the system must be installed in an enclosure suitable for the
environment. The interior of the enclosure should be kept clean and the
enclosure door should be kept closed whenever possible.
Loading...
+ 68 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.