Rockwell Automation 1756-EN2T, 1756-EN2TXT, 1756-ENBT, 1756-EN2F, 1756-EN2TP Installation Instructions Manual

...
Page 1
Installation Instructions
EtherNet/IP Modules
Catalog Numbers 1756-ENBT, 1756-EN2F, 1756-EN2T, 1756-EN2TP, 1756-EN2TPXT, 1756-EN2TR, 1756-EN2TXT, 1756-EN2TRXT, 1756-EN2TSC, 1756-EN3TR, 1756-EWEB, 1768-ENBT, 1768-EWEB, 1769-AENTR
Page 2

Important User Information

IMPORTANT
Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Page 3
Table of Contents
Summary of Changes New and Updated Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Preface Download the Add-on Profiles and Firmware. . . . . . . . . . . . . . . . . . . . . 7
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chapter 1 Install a 1756 EtherNet/IP Communication Module
Installation Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Grounding Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Set the Network IP Address on a Module . . . . . . . . . . . . . . . . . . . . . . . 14
Determine Module Slot Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Install the Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Connect the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Use the following information to wire the module. . . . . . . . . . . . 17
Connect the Module to an EtherNet/IP Network Via an RJ45
Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Connect the Module to an EtherNet/IP Network Via a Fiber
Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Connect to the Module Via the USB Port . . . . . . . . . . . . . . . . . . . . . . . 19
Apply Chassis Power and Check Status Indicators . . . . . . . . . . . . . . . 19
Install or Remove the Module Under Power (RIUP) . . . . . . . . . . . . . 21
Install a 1768 EtherNet/IP Communication Module
Install a 1769 EtherNet/IP Adapter
Chapter 2
Installation Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Grounding Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Set the Network IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Install the Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Mount the Module with Screws. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Mount on a DIN Rail. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Wire the Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Connect the Module to an EtherNet/IP Network via an RJ45
Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Apply Chassis Power and Check Status Indicators . . . . . . . . . . . . . . . 30
Remove the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Chapter 3
System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Example Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Installation Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Grounding Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Set the Network IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Install the Adapter in a 1769 System . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Adapter Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
System Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Mount the Adapter and I/O Modules . . . . . . . . . . . . . . . . . . . . . . . 41
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 3
Page 4
Table of Contents
Wire the Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Remove or Replace the Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Chapter 4
Set the Network IP Address Set the Network IP Address with the Rotary Switches . . . . . . . . 46
Set the Network IP Address with the BOOTP/DHCP Server . . . . 47
Use DHCP Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Set the Network IP Address with RSLinx Software or the Studio 5000™
Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Reset the Module IP Address to a Factory Default Value . . . . . . 54
Chapter 5
Configure a Workstation to Operate on an EtherNet/IP
Select the Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Configure the Ethernet Communication Driver . . . . . . . . . . . . . . . . . 56
Network
Chapter 6
USB Communication Set Up the Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Configure a Module Via the USB Port . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Set Up a USB Driver. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Load Firmware Through a USB Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Appendix A
1756 EtherNet/IP Status
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Indicators
Appendix B
1768 EtherNet/IP Module Status
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Indicators
Appendix C
1769 EtherNet/IP Adapter Status
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Indicators
Appendix D
Fiber Cable and LC Connector Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
4 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 5
This manual contains new and updated information.

Summary of Changes

New and Updated Information

This table contains the changes made in this revision.
Top ic Pag e
Added graphic of the 1756-EN2TP Parallel Redundancy Protocol Ethernet Communication Module. 19
Added content about the 1756-EN2TP module status indicators. 63
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 5
Page 6
Summary of Changes
Notes:
6 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 7

Preface

This manual describes how to install and start up EtherNet/IP module systems
with Logix5000
Use this manual if you program applications that use an EtherNet/IP network with one of these Logix5000 controllers:
CompactLogix
ControlLogix
Understand the following:
Networking concepts
How to the use Studio 5000
How to use RSLinx
controllers.
®
®
environment
Classic programming software

Download the Add-on Profiles and Firmware

If a communication module has a later firmware revision than recognized in the current version of the Logix Designer™ application, you must download the latest firmware. When you download the Add-on Profile (AOP) for the module, it can be recognized in the Controller Organizer.
Download the Add-on Profile and the latest module firmware from the Product Compatibility and Download website at http://www.ab.com
.
If the procedure is performed while the web pages are already enabled, they continue to be enabled and the password is reset to the serial number of the adapter.

Additional Resources

For more information on the products that are described in this publication, use these resources.
Resource Description
EtherNet/IP Modules Installation Instructions, publication ENET-IN002
EtherNet/IP Secure Communication User Manual, publication ENET-UM003
Ethernet Design Considerations Reference Manual, publication ENET-RM002
EtherNet/IP Socket Interface Application Technique, publication ENET-AT002 Describes the socket interface that you can use to program MSG instructions. These instructions
EtherNet/IP Embedded Switch Technology Application Guide, publication
ENET-AP005
Troubleshoot EtherNet/IP Networks Application Technique, publication
ENET-AT003
Provides information about how to complete these tasks with EtherNet/IP communication modules in a Logix5000 control system:
Install the module
Configure initial application setup
Troubleshoot application anomalies related to EtherNet/IP communication module use
Provides information on how to configure authentication, encryption, and firewalls, typical architectures, and diagnostics for modules equipped with secure communication function.
Provides details about how to use EtherNet/IP communication modules with Logix5000 controllers and communicate with other devices on the EtherNet/IP network.
communicate between a Logix5000 controller via an EtherNet/IP module and Ethernet devices that do not support the EtherNet/IP application protocol. These include bar code scanners, RFID readers, or other standard Ethernet devices.
Provides details about how to install, configure, and maintain linear and Device Level Ring (DLR) networks by using Rockwell Automation EtherNet/IP devices equipped with embedded switch technology.
Provides details about how to assign IP addresses to and how to troubleshoot EtherNet/IP networks and devices.
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 7
Page 8
Preface
Resource Description
EtherNet/IP Parallel Redundancy Protocol (PRP) Application Technique, publication ENET-AT006
EtherNet/IP Network Configuration User Manual, publication ENET-UM001 Describes how you can use EtherNet/IP communication modules with
EtherNet/IP Media Planning and Installation Manual This manual is available from the Open DeviceNet Vendor Association
(ODVA) at: http://www.odva.org.
Provides details about how to install, and configure a Parallel Redundancy Protocol (PRP) networks by using Rockwell Automation EtherNet/IP devices equipped with embedded switch technology.
your Logix5000 controller and communicate with various devices on the Ethernet network.
Provides details about how to install, configure, and maintain linear and Device Level Ring (DLR) networks by using Rockwell Automation® EtherNet/IP devices equipped with embedded switch technology.
You can view or download publications at
http:/www.rockwellautomation.com/literature/
. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
8 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 9
Notes:
Preface
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 9
Page 10
Preface
10 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 11
Chapter 1
Install a 1756 EtherNet/IP Communication Module
Top ic Pag e
Installation Summary 14
Install the Module 16
Determine Module Slot Location 15
Install the Module 16
Connect the Module 17
Connect to the Module Via the USB Port 19
Apply Chassis Power and Check Status Indicators 19
Install or Remove the Module Under Power (RIUP) 21
ATTENTION: Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication can contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
NEMA 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures
, for additional installation requirements
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 11
Page 12
Chapter 1 Install a 1756 EtherNet/IP Communication Module
North American Hazardous Location Approval
The following information applies when operating this equipment in hazardous locations.
Produc ts marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
WARNING: EXPLOSION HAZARD
Do not disconnect equipment unless power has
been removed or the area is known to be nonhazardous.
Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
Substitution of components may impair suitability for Class I, Division 2.
If this product contains batteries, they must only be changed in an area known to be nonhazardous.
Informations sur l’utilisation de cet équipement en environnements dangereux.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
AVERTISSEMENT: RISQUE D’EXPLOSION –
Couper le courant ou s'assurer que
l'environnement est classé non dangereux avant de débrancher l'équipement.
Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
S'assurer que l'environnement est classé non dangereux avant de changer les piles.
12 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 13
Install a 1756 EtherNet/IP Communication Module Chapter 1
European Hazardous Location Approval
The following applies when the product bears the Ex Marking.
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN 60079-0.
WARNING: Special Conditions for Safe Use
This equipment shall be mounted in an ATEX Zone 2 certified enclosure with a minimum ingress protection rating of at least
IP54 (as defined in EN 60529) and used in an environment of not more than Pollution Degree 2 (as defined in EN 60664-1) when applied in Zone 2 environments. The enclosure must be accessible only by the use of a tool.
This equipment shall be used within its specified ratings defined by Rockwell Automation.
Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other
means provided with this product.
Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
The USB port is intended for temporary local programming purposes only and not intended for permanent connection and do
not use the USB port in hazardous locations.
Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140% of the rated voltage when applied in Zone 2 environments.
This equipment must be used only with ATEX-certified Rockwell Automation backplanes.
The instructions in the user manual shall be observed.
ATTENTION: Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.
ATTENTION: This equipment is not resistant to sunlight or other sources of UV radiation.
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 13
Page 14
Chapter 1 Install a 1756 EtherNet/IP Communication Module

Installation Summary

Follow these steps to install a communication module in a 1756 ControlLogix® chassis.
1. Set the Network IP Address on a Module
2. Determine Module Slot Location
3. Install the Module
4. Connect the Module
5. Apply Chassis Power and Check Status Indicators
6. Install or Remove the Module Under Power (RIUP)
If needed, see Download the Add-on Profiles and Firmware on page 7
.
.
.
.
.
. - Optional
.

Grounding Considerations

The grounding and bonding must be of equal potential between all devices in the communication coverage area.
ATT EN TI ON : If this equipment is used in a manner that is not specified by the manufacturer, the protection that is provided by the equipment can be impaired.

Set the Network IP Address on a Module

To operate an EtherNet/IP communication module on an EtherNet/IP network, you must set a network IP address.
14 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 15
Install a 1756 EtherNet/IP Communication Module Chapter 1
Module Powerup
Module has an IP address.
Switches set from 001…254?
YesNo
Is DHCP or BOOTP enabled?
YesNo
Module requests address from DHCP/ BOOTP server.
Module uses IP address stored in nonvolatile memory.
20806
Slot 2Slot 0
Slot 1 Slot 3
ControlLogix Chassis ControlLogix-XT Chassis
31896
Slot 0 Slot 4Slot 1 Slot 2 Slot 3
Figure 1 - How the IP Address for the Module is Set
See Set the Network IP Address on page 45 to view all steps for setting the IP address.

Determine Module Slot Location

Install the communication module in any slot in a ControlLogix® or ControlLogix-XT™ chassis. You can install multiple communication modules in the same chassis.
This example shows the chassis slot numbering in a 4-slot ControlLogix chassis and a 5-slot ControlLogix-XT™ chassis. Slot 0 is the first slot and is always the leftmost slot in the chassis.
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 15
Page 16
Chapter 1 Install a 1756 EtherNet/IP Communication Module
IMPORTANT
32455

Install the Module

Follow these steps to install the module.
WARNING: When you insert or remove the module while backplane power is on, an electric arc can occur. An electrical arc can cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding. Rep eated ele ctric al arc s caus es exce ssive wear to contacts on both t he mod ule an d its mating connector. Worn contacts can create electrical resistance that can affect module operation.
ATTENTION: Use caution when handling the module. One side of the module is a heat sink and can be hot.
Your module resembles one of the modules that are shown in the illustrations. The extreme temperature (XT) versions of the modules are not shown in the illustrations.
1. Align the circuit board with top and bottom guides in the chassis.
2. Slide the module into the chassis.
16 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 17
Install a 1756 EtherNet/IP Communication Module Chapter 1
8 ------ NC 7 ------ NC 6 ------ RD­5 ------ NC 4 ------ NC 3 ------ RD+ 2 ------ TD­1 ------ TD+
Make sure that the module backplane connector properly connects to the chassis backplane. The module is properly installed when it is flush with the power supply or other installed modules.

Connect the Module

Use the following information to wire the module.

Connect the Module to an EtherNet/IP Network Via an RJ45 Connection

Wire the RJ45 connector as shown.
Follow these steps to connect the module to the network.
WARNING: If you connect or disconnect the communication cable with power that is applied to this module or any device on the network, an electric arc can occur. An electric arc can cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 17
Page 18
Chapter 1 Install a 1756 EtherNet/IP Communication Module
Dual-port Module (Single port not shown)
32457
Dual-port Module
Single-port Module
1. Attach the cable with the RJ45 connector to the Ethernet port on the module as shown.
2. Attach the other end of the cable to the devices in your network.

Connect the Module to an EtherNet/IP Network Via a Fiber Connector

Attach the LC2 multimode fiber cable to the Ethernet port on the bottom of the module as shown.
ATTENTION: Do not look directly into the optical port. When you view the optical port under certain conditions, can expose the eye to hazard. When viewed under some conditions, the optical port can expose the eye beyond the maximum permissible exposure recommendations.
Class 1 laser product. Laser radiation is present when the system is open and interlocks bypassed. Only trained and qualified personnel are allowed to install, replace, or service this equipment.
18 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 19

Connect to the Module Via the USB Port

Install a 1756 EtherNet/IP Communication Module Chapter 1
WARNING: Do not use the USB port in hazardous locations.
ATTENTION: The USB port is intended for temporary local programming
purposes only and not intended for permanent connection. The USB cable is not to exceed 3.0 m (9.84 ft) and must not contain hubs. The USB cable can be ordered from Rockwell Automation, catalog number 9300-USBCBL-ABHR.
If the module has a USB port, is it a Type B receptacle. To use the USB port, you must have RSLinx® Classic software, version 2.55 or later, installed on your computer.
Use a USB cable to connect your computer to the USB port. You can download programs to controllers and configure Ethernet modules directly from your computer over a USB connection.
For more information about USB setup and configuration, see Chapter 6, USB
Communication on page 59.

Apply Chassis Power and Check Status Indicators

Before you apply power, you must install and connect a ControlLogix chassis and power supply.
Follow these steps to apply power.
1. Flip the switch to the ON position.
32458
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 19
Page 20
LINK
LINK
NET
OK
32452
NET
OK
1
LNK1LNK1LNK2LNK2 NETNET
OKOK
LNK1LNK1
1
2
LNK2
LNK2
NETNET OKOK
3245332453
Single-port Module
Dual-port Module
LINKLINK
NETNET
OKOK
Single-port Module
Dual-port Module
32730
1756-EN2TP
Chapter 1 Install a 1756 EtherNet/IP Communication Module
2. To determine that the power supply and module are operating properly, check the power supply and Module Status indicators and alphanumeric display.
The alphanumeric display cycles through the following states: TEST ­PASS - OK - REV x.x, where x.x is the firmware revision of the module.
The display then alternates between OK and port link status for both ports.
This graphic shows the front of the module for these modules (extended­temperature versions [catalog numbers 1756-EN2TXT and 1756­EN2TRXT] not shown).
LINK
OK
NET
LINK
OK
NET
32452
20 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
32730
Page 21
Install a 1756 EtherNet/IP Communication Module Chapter 1
IMPORTANT
32460
32461

Install or Remove the Module Under Power (RIUP)

You can install or remove this module while chassis power is applied.
WARNING: When you insert or remove the module while backplane power is on, an electric arc can occur. An electric arc can cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcs can cause excessive wear to contacts on both the module and its mating connector. Worn contacts can create electrical resistance that can affect module operation.
ATT EN TI ON : Although the module is designed to support RIUP, when you remove or insert the module with field-side power applied, unintended machine motion or loss of process control can occur. Exercise extreme caution when using this feature.
Follow these steps to remove or replace the module.
1. Push the upper and lower module tabs to disengage them.
2. Slide the module out of the chassis.
If you want to replace an existing module with an identical one, and you want to resume identical system operation, you must install the new module in the same slot and assign the same network configuration.
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 21
Page 22
Chapter 1 Install a 1756 EtherNet/IP Communication Module
Notes:
22 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 23
Chapter 2
Install a 1768 EtherNet/IP Communication Module
Top ic Pag e
Installation Summary 25
Set the Network IP Address 26
Install the Module 27
Wire the Module 29
Apply Chassis Power and Check Status Indicators 30
Remove the Module 30
ATTENTION: Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the application if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
NEMA 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures
, for additional installation requirements
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 23
Page 24
Chapter 2 Install a 1768 EtherNet/IP Communication Module
North American Hazardous Location Approval
The following information applies when operating this equipment in hazardous locations.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
WARNING: EXPLOSION HAZARD
Do not disconnect equipment unless power has been
removed or the area is known to be nonhazardous.
Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
Substitution of components may impair suitability for Class I, Division 2.
If this product contains batteries, they must only be changed in an area known to be nonhazardous.
Informations sur l’utilisation de cet équipement en environnements dangereux.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
AVERTISSEMENT: RISQUE D’EXPLOSION
Couper le courant ou s'assurer que l'environnement
est classé non dangereux avant de débrancher l'équipement.
Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
S'assurer que l'environnement est classé non dangereux avant de changer les piles.
24 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 25
Install a 1768 EtherNet/IP Communication Module Chapter 2
European Hazardous Location Approval
The following applies when the product bears the Ex Marking.
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN 60079-0.
ATTENTION: This equipment is not resistant to sunlight or other sources of UV radiation.
WARNING:
This equipment shall be mounted in an ATEX certified enclosure with a minimum ingress protection rating of at least IP54 ( as
defined in IEC60529) and used in an environment of not more than Pollution Degree 2 (as defined in IEC 60664-1) when applied in Zone 2 environments. The enclosure must utilize a tool removable cover or door.
This equipment shall be used within its specified ratings defined by Rockwell Automation.
Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140% of the
rated voltage when applied in Zone 2 environments.
Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
ATTENTION: Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.

Installation Summary

Follow these steps to install a communication module in a 1768 CompactLogix™ system.
1. Set the Network IP Address
2. Install the Module
.
.
3. Connect the Module to an EtherNet/IP Network via an RJ45
Connection.
4. Apply Chassis Power and Check Status Indicators
.
5. Remove the Module
If needed, see Download the Add-on Profiles and Firmware on page 7
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 25
. - Optional
.
Page 26
Chapter 2 Install a 1768 EtherNet/IP Communication Module
Module Powerup
Module has an IP address.
Is DHCP or BOOTP enabled?
YesNo
Module requests address from DHCP/ BOOTP server.
Adapter uses IP address stored in nonvolatile memory.

Grounding Considerations

ATTENTION: This product is grounded through the DIN rail to chassis ground.
Use zinc-plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.87 in.) and use end-anchors appropriately.

Set the Network IP Address

To operate an EtherNet/IP communication module on an EtherNet/IP network, you must set a network IP address. This graphic shows the process that is used to set the IP address for the module.
Figure 2 - Set the IP Address for the Module
See Set the Network IP Address on page 45 to view all steps for setting the IP address.
26 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 27
Install a 1768 EtherNet/IP Communication Module Chapter 2
IMPORTANT

Install the Module

Follow these steps to install the module.

Mount the Module with Screws

Do not use screws and DIN rail to mount the modules. It is possible to break
off the mounting tabs if you screw the modules to the panel while they are on the DIN rail.
Complete these steps to install the module with screws.
1. Use the modules as a template and mark pilot holes on your panel.
2. Drill the pilot holes for M4 or #8 screws.
3. Use M4 or #8 screws to mount the modules to your panel, by using
1.16 N•m (10 lb•in) of torque.
4. Ground the module on a ground bus with a dedicated earth ground stake.
5. Connect the ground bus to a functional earth ground on the DIN rail
or panel.
See the Industrial Automation Wiring and Grounding Guidelines, publication
1770-4.1
, for additional information.

Mount on a DIN Rail

Follow these steps to install the module on a DIN rail.
1. Mount the DIN rail in a suitable location.
ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc-plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.87 in.) and use end-anchors appropriately.
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 27
Page 28
Chapter 2 Install a 1768 EtherNet/IP Communication Module
31597-M
2. Open the DIN rail latches on the module.
3. Align and press the module onto the DIN rail to the left of the controller.
4. Slide the module snugly against the controller.
5. Mount the 1768 power supply and additional 1768 modules to the left of
the controller.
6. Close the DIN rail latches.
31599-M
In this example, the 1768 EtherNet/IP communication module is installed in slot 1 and the 1768 CompactLogix controller is installed in slot 0.
28 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 29
Install a 1768 EtherNet/IP Communication Module Chapter 2
8 ------ NC 7 ------ NC 6 ------ RD­5 ------ NC 4 ------ NC 3 ------ RD+ 2 ------ TD­1 ------ TD+

Wire the Module

Use the following information to wire the module.

Connect the Module to an EtherNet/IP Network via an RJ45 Connection

Wire the RJ45 connector as shown.
Follow these steps to connect the module to the network.
WARNING: If you connect or disconnect the communication cable with power that is applied to this module or any device on the network, an electric arc can occur. An electric arc can cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
1. Attach the cable with the RJ45 connector to the Ethernet port on the bottom of the module as shown.
2. Attach the other end of the cable to the devices in your network.
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 29
Page 30
Chapter 2 Install a 1768 EtherNet/IP Communication Module
1
2
IMPORTANT

Apply Chassis Power and Check Status Indicators

Before you apply power, you must install and mount a CompactLogix controller and Compact I/O™ power supply on the DIN rail.
Follow these steps to apply power.
1. Flip the switch to the ON position.
2. Check the power supply (1) and module (2) status indicators.
3. Check the alphanumeric display to determine that the power supply and
module are operating properly.

Remove the Module

30 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Follow these steps to remove the communication module.
When you turn off the CompactLogix power supply, make sure that you wait for all status indicators on the power supply and controller to turn off before disconnecting any part from the system.
If you disconnect the CompactLogix system while the controller is still writing its program to memory, the program write is not completed and your program is lost.
Page 31
Install a 1768 EtherNet/IP Communication Module Chapter 2
1. Flip the switch to the OFF position.
2. Open the DIN rail latches of the communication module and the module
directly to the left of communication module.
3. Slide the communication module and other modules to the right.
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 31
Page 32
Chapter 2 Install a 1768 EtherNet/IP Communication Module
4. Open the DIN rail latches of the controller.
5. Slide the controller and other modules away from the communication
module.
6. Pull the communication module off the DIN rail.
32 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 33
Install a 1769 EtherNet/IP Adapter
Top ic Pa ge
System Configuration 35
Installation Summary 37
Set the Network IP Address 37
Install the Adapter in a 1769 System 39
Wire the Adapter 43
Remove or Replace the Adapter 43
Chapter 3
ATTENTION: Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
, for additional installation requirements.
NEMA 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 33
Page 34
Chapter 3 Install a 1769 EtherNet/IP Adapter
North American Hazardous Location Approval
The following information applies when operating this equipment in hazardous locations.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
WARNING: EXPLOSION HAZARD
Do not disconnect equipment unless power has been
removed or the area is known to be nonhazardous.
Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
Substitution of components may impair suitability for Class I, Division 2.
If this product contains batteries, they must only be changed in an area known to be nonhazardous.
Informations sur l’utilisation de cet équipement en environnements dangereux.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
WARNING: RISQUE D’EXPLOSION
Couper le courant ou s'assurer que l'environnement
est classé non dangereux avant de débrancher l'équipement.
Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
S'assurer que l'environnement est classé non dangereux avant de changer les piles.
ATTENTION: Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.
WARNING: When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with
proper wiring method that complies with the governing electrical codes.
34 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 35
Install a 1769 EtherNet/IP Adapter Chapter 3

System Configuration

Follow these rules when planning your system configuration.
The adapter must be the first and left-most module in the system (the first module of Bank 1). See page 36
The adapter can communicate with up to 30 modules in a system that is distributed across three I/O banks.
An end cap/terminator must be on the last I/O bank.
Each bank of I/O must have its own power supply.
A bank of I/O can have a maximum of 16 modules with a maximum of
eight on either side of the power supply, depending upon module loading on the supply.
A 1769 I/O power supply has limits in the amount of 5V DC and 24V DC current it can supply to the modules in its I/O bank. These limits depend on the catalog number (for example, 1769-PA2) of the supply. A bank of modules should not exceed the current limits of the I/O bank power supply. See the Compact 1769 Expansion I/O Power Supplies Installation Instructions, publication 1769-IN028
The maximum amount of current the system supports in one direction (either side of the power supply) is: 2 A @ 5V DC, 1 A @ 24V DC.
If another bank of I/O is required due to module requirements or I/O loading, you can use a cable to link them together. You can have a maximum of three banks of I/O connected with up to two communication cables.
Each module type has its own distance rating (the number of modules from the power supply). Each module must be within this rating for its type.
The adapter has a distance rating of five, therefore the adapter must be within five modules of the power supply.
for an example configuration.
.
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 35
Page 36
Chapter 3 Install a 1769 EtherNet/IP Adapter
TIP
Bank 1
Bank 2
Bank 3
Bank 3Bank 2Bank 1
Right-to-Right Cable
1769-AENTR
1769 I/O
1769 I/O
1769-CRRx
I/O Slot Number
12
I/O Slot Number
10 11 12
1769-CLLx
1769 I/O
1769 I/O
1769 I/O
1769-CRRx
1769 Power Supply
1769-CLLx
1769 I/O
1769 I/O
1769 I/O
1769 I/O
1769 Right End Cap
I/O Slot Number
20
1769 I/O
1769-CRLx
1769-CRLx
1769 I/O
1769 I/O
1769-CRLx
1769 Power Supply
1769-CRLx
1769 I/O
1769 Power Supply
1769 I/O
1769 Right End Cap
I/O Slot Number
12 3 4 5 6
Left-to -Left Cable
42131
1769 I/O
1769 I/O
1769 Power Supply
34 5
1769 I/O
1769 I/O
6
1769 I/O
1769 Power Supply
1769 I/O
1769 I/O
987
1769 I/O
1769 I/O
1769 I/O
1769 I/O
19181716151413
1769-AENTR
1769 I/O
1769 Power Supply
Right-to-Left Cable Right-to-Left Cable

Example Configurations

The following illustrations show examples of two valid system setups.
I/O modules are not required between either the adapter and an end cap or between the power supply and an end cap.
36 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 37
Install a 1769 EtherNet/IP Adapter Chapter 3

Installation Summary

Complete these steps to install an adapter in a 1769 CompactLogix™ system.
1. Set the Network IP Address
2. Install the Adapter in a 1769 System
3. Wire the Adapter
4. Remove or Replace the Adapter
If needed, see Download the Add-on Profiles and Firmware on page 7
.
.
.
. - Optional
.

Grounding Considerations

ATTENTION: This product is intended to be mounted to a well-grounded
mounting surface such as a metal panel. Additional grounding connections from the mounting tabs on the adapter or DIN rail (if used) are not required unless you cannot ground the mounting surface. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 additional information.
, for

Set the Network IP Address

To operate an EtherNet/IP adapter on an EtherNet/IP network, you must set a network IP address. 'The 1769 EtherNet/IP adapters are shipped with BOOTP/ DHCP enabled.
The IP address uniquely identifies the module. The IP address is in the form xxx.xxx.xxx.xxx where each xxx is a number from 000…254.
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 37
Page 38
Chapter 3 Install a 1769 EtherNet/IP Adapter
Module Powerup
Module has an IP address.
Switches set from 001…254?
YesNo
Is DHCP or BOOTP enabled?
YesNo
Module requests address from DHCP/ BOOTP server.
Module uses IP address stored in nonvolatile memory.
Figure 3 - Set the IP Address for the Module
See Set the Network IP Address on page 45 to view all steps for setting the IP address.
38 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 39
Install a 1769 EtherNet/IP Adapter Chapter 3
Comm Adapter
MOD
NET
LINK 1
LINK 2
X 100
X 10
X 1
LINK 1LINK 2
6a
1
2
3
4
6b
7a
5
7b
9
8
46269

Install the Adapter in a 1769 System

Use the following information to install the adapter with the 1769 system.

Adapter Description

Item Description
1 Status indicators
2 IP address rotary switches
3 Ethernet port
4 Ethernet port for use in a Device Level Ring network
5 Nameplate label
6 Upper panel mounting tab
Lower panel mounting tab
7Upper DIN rail latch
8Bus lever
9 Stationary bus connector with male pins
Lower DIN rail latch
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 39
Page 40
Chapter 3 Install a 1769 EtherNet/IP Adapter
IMPORTANT
a
a
a
a
1769-
b
c
e
d
42126

System Assembly

The adapter can be attached to adjacent 1769 modules before or after mounting.
The 1769-AENTR adapter must be used with one of the following Rockwell Automation® power supply models: 1769-PA2, 1769-PB2, 1769-PA4, or 1769-PB4.
For mounting instructions, see Mount the Adapter with Screws on page 41
Mount on a DIN Rail on page 42
.
Follow these steps to assemble the Compact I/O™ system.
1. Disconnect power.
WARNING: If you insert or remove the module while backplane power is on, an electric arc can occur. An electric arc can cause an explosion in hazardous location installations.
Be sure that power is removed before proceeding.
, or
2. Check that the bus lever of the module to the right of the adapter is in the unlocked (fully right) position.
3. Use the upper and lower tongue-and-groove slots (a) to secure the modules together.
4. Move the module back along the tongue-and-groove slots until the bus connectors align with each other.
5. Use your fingers or a small screwdriver to push the bus lever of the module to the right of the adapter back slightly to clear the positioning tab (b).
6. To allow communication between the adapter and I/O modules, move the bus lever of the module to the right of the adapter fully to the left (c) until it clicks. Make sure it is locked firmly into place.
ATT EN TI ON : When you attach the adapter, it is important that the bus connectors are securely locked together to create a proper electrical connection.
40 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 41
Install a 1769 EtherNet/IP Adapter Chapter 3
IMPORTANT
1769 I/O
1769 I/O
1769 I/O
End Cap or Cable
42124
1769 I/O
1769 Power Supply
Side Side
Bottom
Top
1769 I/O
1769 I/O
1769-AENTR
For more than 1 module: Number of modules x 35 mm (1.38 in.)
28.5 (1.12)
35
(1.38)
132
(5.197)
(4.826+
0.008)
122.6+
0.2 1769-AENTR
1769 Power Supply
1769 I/O
Right End Cap
mm (in.)
Hole spacing tolerance: ±0.4 mm (0.016 in.)
42121
(1.38)
35
70
(2.76)
(1.58)
40
35
(1.38)
1769 I/O
7. Attach an end cap terminator (d) to the last I/O module in the system by using the tongue-and-groove slots as before.
8. Lock the end-cap bus terminator (e).
A 1769-ECR or 1769-ECL right or left end cap must be used to terminate the end of the serial communication bus.

Mount the Adapter and I/O Modules

ATT EN TI ON : During panel or DIN rail mounting of all devices, be sure that all
debris (metal chips, wire strands) is kept from falling into the adapter or modules. Debris that falls into the adapter or modules can cause damage on power-up.
Minimum Spacing
Maintain spacing from enclosure walls, wireways, and adjacent equipment. Allow 50 mm (2 in.) of space on all sides for adequate ventilation, as shown.
Mount the Adapter with Screws
Mount the adapter or module to a panel by using two screws per adapter or module. Use M4 or #8 panhead screws. Mounting screws are required on every module. This figure illustrates panel mounting using the dimensional template.
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 41
Page 42
Chapter 3 Install a 1769 EtherNet/IP Adapter
TIP
Mount to Module with Screws by Using the Modules as a Template
The following procedure lets you use the assembled adapter and modules as a template for drilling holes in the panel. If you have sophisticated panel mounting equipment, you can use the dimensional template that is provided on page 41
Due to the module-mounting hole tolerance, it is important to follow this procedure.
1. On a clean work surface, assemble no more than three modules.
2. Using the assembled modules as a template, carefully mark the center of all
module-mounting holes on the panel.
3. Return the assembled modules to the clean work surface, including all previously mounted modules.
4. Drill and tap the mounting holes for the recommended M4 or #8 screw.
5. Place the modules back on the panel and check for proper hole alignment.
6. Attach the modules to the panel with the mounting screws.
.
If mounting more modules, mount only the last one of this group and put the others aside. This reduces remounting time during drilling and tapping of the next group.
7. Repeat steps 1...6 for any remaining modules.
Mount on a DIN Rail
The adapter can be mounted using the following DIN rails:
35 x 7.5 mm (EN50022 - 35 x 7.5)
35 x 15 mm (EN 50022 - 35 x 15)
Follow these steps to mount the module.
1. Verify that the DIN rail latches are closed.
2. Press the DIN rail mounting area of the module against the DIN rail.
The latches momentarily open, then lock into place.
ATT EN TI ON : This product is grounded through the DIN rail to chassis ground. Use zinc-plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials, for example, aluminum and plastic, that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding.
42 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 43
Install a 1769 EtherNet/IP Adapter Chapter 3
8 ------ NC 7 ------ NC 6 ------ RD­5 ------ NC 4 ------ NC 3 ------ RD+ 2 ------ TD­1 ------ TD+
8
1
TIP

Wire the Adapter

Use the following information to wire the adapter.
This product is intended to be mounted to a well-grounded mounting surface such as a metal panel. Additional grounding connections from the mounting tabs on the adapter or DIN rail (if used) are not required unless you cannot ground the mounting surface. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
, for additional information.
Connect the module to an EtherNet/IP network via an RJ45 cable.
WARNING: If you connect or disconnect the communication cable with power that is applied to this module or any device on the network, an electric arc can occur. An electric arc can cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Wire the RJ45 connector as shown.

Remove or Replace the Adapter

The adapter can be replaced while the system is mounted to a panel or DIN rail.
1. Remove power.
ATT EN TI ON : Do not remove or replace an adapter while power is applied. Interruption of the backplane can result in unintentional operation or machine motion.
2. Remove the EtherNet/IP cable from the module.
3. Remove the upper and lower mounting screws from the adapter or open
the DIN latches with a flat-blade or Phillips-style screwdriver.
4. On the right-side adjacent module, move its bus lever to the right (unlock) to disconnect it from the adapter being removed.
5. Gently slide the disconnected adapter forward.
If you feel excessive resistance, make sure that you disconnected the adapter from the bus and that you removed both mounting screws or opened the DIN latches.
Rock the module slightly from front to back, if necessary, to remove it, or, in a panel-mounted system, to loosen the screws of adjacent modules.
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 43
Page 44
Chapter 3 Install a 1769 EtherNet/IP Adapter
6. Before installing the replacement adapter, be sure that the bus lever on the right-side adjacent module is in the unlocked (fully right) position.
7. Slide the replacement adapter into the open slot.
8. Connect the adapter and modules together by locking (fully left) the bus
levers on the right-side adjacent module.
9. Replace the mounting screws or snap the adapter onto the DIN rail.
10. Insert the Ethernet cable into the module.
11. Set the network address switches to the same value as the removed adapter.
44 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 45
Chapter 4
Set the Network IP Address
Top ic Pag e
Set the Network IP Address with the BOOTP/DHCP Server 47
Set the Network IP Address with RSLinx Software or the Studio 5000™ Environment 50
The IP address uniquely identifies the module. The IP address is in the form xxx.xxx.xxx.xxx where each xxx is a number from 000…254.
There are some reserved values that you cannot use as the first octet in the address. These numbers are examples of values you cannot use:
001.xxx.xxx.xxx
127.xxx.xxx.xxx
223 to 255.xxx.xxx.xxx
The specific reserved values that cannot be used vary by application.
For more information about how to configure an EtherNet/IP network, see EtherNet/IP Network Configuration User Manual, publication ENET-UM001
Depending on the 1756 EtherNet/IP communication module, you can use some or all of these tools to set the network Internet Protocol (IP) address:
Rotary switches - The 1756-ENBT and 1756-EWEB modules do not offer rotary switches. If you are using either of these modules, skip Set the Network IP Address with the Rotary Switches on page 46 the Network IP Address with the BOOTP/DHCP Server on page 47
Bootstrap Protocol (BOOTP)/Dynamic Host Configuration Protocol (DHCP) server
RSLinx® Classic software
Studio 5000 environment
The module uses these tools sequentially to set the IP address.
and go to Set
.
.
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 45
Page 46
Chapter 4 Set the Network IP Address
32454
Rotary Switches
Front of Module
The 1756 EtherNet/IP communication modules are shipped with this configuration:
BOOTP/DHCP enabled
Rotary switches set to 999 - when applicable
To reset the module factory default settings during normal module operation, see
Reset the Module IP Address to a Factory Default Value on page 54
.
These tools are used in this sequence to set the network IP address.
1. Set the Network IP Address with the Rotary Switches
2. Set the Network IP Address with the BOOTP/DHCP Server
3. Set the Network IP Address with RSLinx Software or the Studio 5000™
Environment

Set the Network IP Address with the Rotary Switches

This graphic shows the rotary switches on a 1756 EtherNet/IP communication module. Depending on the module, the switches are on the top or the side of the module.
At power-up, the module reads the rotary switches to determine if they are set to a valid number for the last portion of the IP address. For example, if the numbers are in the range from 001…254.
If the settings are a valid number, these conditions result:
IP address = 192.168.1.xxx (where xxx represents the switch settings)
Subnet mask = 255.255.255.0
Gateway address
= 192.168.1.1 for firmware revision 5.008 or later
= 0.0.0.0 for firmware revision 5.007 or earlier
46 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 47
Set the Network IP Address Chapter 4
IMPORTANT
IMPORTANT
The gateway address of 192.168.1.1 applies only to the 1756-EN2T, 1756-EN2TR, 1756-EN2TRXT, 1756-EN2F, 1756-EN2TSC, and 1756-EN3TR modules with firmware revision 5.008 or later. Other modules use the gateway address of 0.0.0.0 with firmware revision
5.007 or earlier.
For more information, see the Ethernet Design Considerations Reference Manual, publication ENET-RM002
The module does not have a host name that is assigned and does not use any Domain Name System
We recommend that you set the rotary switches to a valid number before installing the module.
If either of these conditions exist, the module attempts to use the BOOTP/ DHCP server to set the IP address:
Rotary switches are not set to a valid number.
Module does not have rotary switches.
.

Set the Network IP Address with the BOOTP/DHCP Server

The BOOTP/DHCP server is a standalone server that you can use to set an IP address. When used, the BOOTP/DHCP server sets an IP address and other Transport Control Protocol (TCP) parameters.
You can use the BOOTP/DHCP server to set the IP address of the module if one of these conditions exists when you apply power:
The rotary switches on the module are not set to a valid number and the module is BOOTP/DHCP enabled.
The module does not have rotary switches and the module is BOOTP/DHCP enabled.
Access the BOOTP/DHCP server from one of these locations:
Programs > Rockwell Software > BOOTP-DHCP Server
If you have not installed the server, you can download and install it from
http://www.ab.com/networks/ethernet/bootp.html
Tools directory on the Studio 5000 environment installation CD
Before you start the BOOTP/DHCP server, make sure that you have the hardware (MAC) address for the module. The hardware address is on a sticker on the side of the communication module and uses an address in a format similar to the following:
.
00-00-BC-14-55-35
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 47
Page 48
Chapter 4 Set the Network IP Address
Follow these steps to set the IP address of the module with a BOOTP/DHCP server.
1. Start the BOOTP/DHCP software.
2. From the Tools menu, choose Network Settings.
3. Type the Subnet Mask of the network.
The Gateway address, Primary and/or Secondary DNS address, and Domain Name fields are optional.
4. Click OK.
The Request History panel appears with the hardware addresses of all modules that issue BOOTP requests.
5. Select the appropriate module.
6. Click Add to Relation List.
48 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 49
Set the Network IP Address Chapter 4
IMPORTANT
The New Entry dialog box appears.
7. Type an IP Address, Hostname, and Description for the module.
8. Click OK.
9. To assign this configuration permanently to the module, wait for the
module to appear in the Relation List panel and select it.
10. Click Disable BOOTP/DHCP.
When power is recycled, the module uses the assigned configuration and does not issue a BOOTP request.
If you do not click Disable BOOTP/DHCP, on a power cycle, the host controller clears the current IP configuration and begins sending BOOTP requests again.

Use DHCP Software

Dynamic Host Configuration Protocol (DHCP) software automatically assigns IP addresses to client stations logging on to a TCP/IP network. DHCP is based on BOOTP and maintains some backward compatibility. The main difference is that BOOTP allows for manual configuration (static), while DHCP allows for both static and dynamic allocation of network addresses and configurations to newly attached modules.
Be cautious when using DHCP software to configure a module. A BOOTP client, such as the EtherNet/IP communication modules, can start from a DHCP server only if the DHCP server is written to handle BOOTP queries. This is specific to the DHCP software package used. Consult your system administrator
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 49
Page 50
Chapter 4 Set the Network IP Address
to see if a DHCP package supports BOOTP commands and manual IP allocation.
AT TE NT IO N: The EtherNet/IP communication module must be assigned a fixed network address. The IP address of this module must not be dynamically provided.
Failure to observe this precaution can result in unintended machine motion or loss of process control.

Set the Network IP Address with RSLinx Software or the Studio 5000™ Environment

This table describes when to set the network IP address with RSLinx software or the Studio 5000 environment.
Conditions Software to Use Page
A BOOTP server is not available.
The EtherNet/IP communication module is connected to another
NetLinx network.
The Studio 5000® project is online with a controller that communicates to or through the EtherNet/IP communication module.
RSLinx 51
Studio 5000 environment 53
Consider these factors when you determine how to set the network IP address:
Network isolation from or integration into the plant/enterprise network
Network size - For large networks, isolated networks, it can be more
convenient to use a BOOTP/DHCP server rather than the Studio 5000 environment or RSLinx software. The BOOTP/DHCP server also limits the possibility of assigning duplicate IP addresses.
Company policies and procedures for plant-floor network installation and maintenance
Level of involvement by IT personnel in plant floor network installation and maintenance
Type of training that is offered to control engineers and maintenance personnel
If you use the Rockwell Automation® BOOTP or DHCP server in an uplinked subnet where an enterprise DHCP server exists, a module can get an address from the enterprise server before the Rockwell Automation utility even sees the module. You can disconnect from the uplink to set the address and configure the module to retain its static address before reconnecting to the uplink. This is not a problem if you have node names that are configured in the module and leave DHCP enabled.
50 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 51
Set the Network IP Address Chapter 4
IMPORTANT
Set the Network IP Address with RSLinx Software
Follow these steps to use RSLinx software to set the communication module’s IP address.
1. From the Communications menu, choose RSWho.
The RSWho dialog box appears.
2. Navigate to the Ethernet network.
3. Right-click the EtherNet/IP module and choose Module Configuration.
The Module Configuration dialog box appears.
4. Click the Port Configuration tab.
5. For Network Configuration Type, click Static to assign this configuration
permanently to the port.
If you select Dynamic, on a power cycle, the controller clears the current IP configuration and resumes sending BOOTP requests.
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 51
Page 52
Chapter 4 Set the Network IP Address
IMPORTANT
6. Type this information in the appropriate fields:
In the IP Address field, type the IP address.
In the Network Mask field, type the network mask address.
In the Gateway Address field, type the gateway address.
In the Primary Name Server field, type the IP address.
In the Secondary Name Server field, type the IP address.
In the Domain Name field, type the domain name.
In the Host Name field, type the host name.
7. Configure the port settings.
To Th en
Use the default port speed and duplex settings
Manually configure the port speed and duplex settings
Leave Auto-negotiate port speed and duplex checked. This setting determines the actual speed and duplex setting.
Follow these steps.
1. Clear the Auto-negotiate port speed and duplex checkbox.
2. From the Current Port Speed pull-down menu, choose a port speed.
3. From the Current Duplex pull-down menu, choose the appropriate Duplex value, that is, half-duplex or full-duplex.
Consider the following when you configure the port settings of the module:
The speed and duplex settings for the devices on the same Ethernet network must be the same to avoid transmission errors.
Fixed speed and full-duplex settings are more reliable than autonegotiate settings and are recommended for some applications.
If the module is connected to an unmanaged switch, leave Autonegotiate port speed and duplex that is checked or communication can be impaired.
If you force the port speed and duplex with a managed switch, the corresponding port of the managed switch must be forced to the same settings or the module fails.
If you connect a manually configured device to an autonegotiate device (duplex mismatch), a high rate of transmission errors can occur.
8. Click OK.
52 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 53
Set the Network IP Address Chapter 4
IMPORTANT
Set the Network IP Address with the Studio 5000 Environment
Follow these steps to use the Studio 5000 environment to set the IP address of the communication module.
1. In the Controller Organizer, right-click the EtherNet/IP module and choose Properties.
The Module Properties dialog box appears.
2. Click the Port Configuration tab.
3. In the IP Address field, type the IP address.
4. In the other fields, type the other network parameters, if needed.
The fields that appear vary from one EtherNet/IP module to another.
5. Click Set.
6. Click OK.
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 53
Page 54
Chapter 4 Set the Network IP Address

Reset the Module IP Address to a Factory Default Value

You can reset the IP address of the module to the factory default value by using the following methods:
If the module has rotary switches, set the switches to 888 and cycle power.
If the module does not have rotary switches, use an MSG instruction to the
reset the IP address.
For more information on how to reset the network IP address to its default value with an MSG instruction, see Knowledgebase Answer ID 55362, at
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/ 55362 (login required).
54 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 55
Chapter 5
Configure a Workstation to Operate on an EtherNet/IP Network
Top ic Pag e
Select the Driver 55
Configure the Ethernet Communication Driver 56
Before you begin, make sure that the workstation is ready to connect to the EtherNet/IP network:

Select the Driver

The Ethernet communication card is already installed in the workstation.
The IP address and other network parameters are correctly configured for
the workstation.
The workstation is properly connected to the EtherNet/IP network.
You can choose either of these Ethernet drivers:
AB_ETHIP
AB_ETH
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 55
Page 56
Chapter 5 Configure a Workstation to Operate on an EtherNet/IP Network
IMPORTANT

Configure the Ethernet Communication Driver

To configure the Ethernet communication driver in RSLinx® Classic software, follow these steps.
1. From the Communications pull-down menu, choose Configure Drivers.
The Configure Drivers dialog box appears.
2. From the Available Driver Types pull-down menu, choose EtherNet/IP Driver or Ethernet devices.
3. Click Add New.
The Add New RSLinx Classic Driver dialog box appears.
If you are using a Microsoft Windows 7 VPN client to connect to a secure communication module, such as the1756-EN2TSC module, we recommend using the RSlinx software Ethernet devices AB_ETH driver for the 1756-EN2TSC module.
If you do not choose this driver, the device is shown in RSLinx software, but you cannot right-click the device listing and request additional information.
56 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 57
Configure a Workstation to Operate on an EtherNet/IP Network Chapter 5
4. Type a name for the new driver and click OK.
The Configure driver dialog box appears.
5. Click Browse Local Subnet.
6. Click Apply.
7. Click OK.
This new driver is now available.
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 57
Page 58
Chapter 5 Configure a Workstation to Operate on an EtherNet/IP Network
Notes:
58 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 59
Chapter 6
Local C hassis
USB Connection
EtherNet/IP
Remote Chassis with Logix5000 ™Controllers
USB Communication
Top ic Pag e
Set Up the Hardware 59

Configure a Module Via the USB Port 59

Load Firmware Through a USB Por t 62
This chapter is intended to show only the steps that differ when using a USB device port. Use this chapter if your module has a USB port.

Set Up the Hardware

Configure a Module Via
Make sure that your USB cable is properly connected to the computer and the chassis to facilitate messaging with a remote chassis.
See Appendix A
Figure 4 - Sharing Data and Transferring Messages
You can configure some EtherNet/IP communication modules via the USB port.
and Appendix B to troubleshoot by using status indicators.
the USB Port
WARNING: Do not use the USB port in hazardous locations.
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 59
Page 60
Chapter 6 USB Communication
To use the USB port, you must have RSLinx® Classic software, version 2.51 or later, installed on your computer.
Use a USB cable to connect your computer to the USB port. You can download programs to controllers and configure other devices accessible via the communication module through this connection.
ATTENTION: The USB port is intended for temporary local programming purposes only and is not intended for permanent connection. The USB cable is not to exceed 3.0 m (9.84 ft) and must not contain hubs.

Set Up a USB Driver

To configure RSLinx Classic software to use a USB port, first configure a USB driver. To configure a USB driver, follow these steps.
1. With one end that is installed in the computer, plug in the USB cable into your communication module.
The RSLinx Found New Hardware Wizard dialog box appears.
2. Click Install the software automatically (recommended).
3. Click Next.
60 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 61
These RSLinx dialog boxes appear consecutively.
USB Communication Chapter 6
4. Click Finish to configure your USB driver.
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 61
Page 62
Chapter 6 USB Communication
Virtual Chassis Driver
USB Port Driver
IMPORTANT
5. In RSLinx Classic software, from the Communications menu, choose RSWho.
The RSLinx Workstation organizer appears.
Your 1756-EN2T module appears under two different drivers, a virtual chassis and the USB port.

Load Firmware Through a USB Port

Do not simultaneously load firmware for more than one module through a USB port. If you do, one or more of the firmware loads can fail in the middle of the loading process.
62 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 63
Appendix A
LINK
LINK
NET
OK
32452
NET
OK
1
LNK1
LNK2
NET
OK
LNK1
1
2
LNK2
NETOKOK
32453
Single-port Module
Dual-port Module
LINKLINK
NETNET
OKOK
Single-port Module
Dual-port Module
32730
1756-EN2TP
1756 EtherNet/IP Status Indicators
This graphic shows the front of the module for these modules (extended­temperature versions not shown).
LNK1
LNK2
NET
OK
LINK
NET
LINK
OK
NET
32452
OK
LNK1
LNK2
NET
32453
32730
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 63
Page 64
Appendix A 1756 EtherNet/IP Status Indicators
Table 1 - Single-port Module Status Indicators
Status Indicator Description Status State
Module Status Display Alphanumeric display that scrolls messages.
For example, when a module is operating normally, the display scrolls the IP address of the module.
Link Status (LINK) Indicates the current state of the module
about transmitting data on the EtherNet/IP network.
OK Status (OK) Indicates the current state of the module.
For example, this status indicator indicates if the module is executing power-up tests, in the process of a firmware update or operating normally.
Network Status (NET) Indicates if CIP™ connections are established. Off One of these conditions exists:
——
Off One of these conditions exists:
The module is not powered.Verify that there is chassis power.Verify that the module is inserted, snapped into the
chassis and backplane.
Make sure that the module has been configured.
No link exists on the port.
Flashing green Activity exists on the port.
Green Activity exists on the por t.
Off The module is not powered.
Verify that there is chassis power.
Verify that the module is inserted, snapped into the chassis
and backplane.
Make sure that the module has been configured.
Flashing green The module is not configured. The Module Status display scrolls:
BOOTP or DHCP<Mac_address_of_module> For example: BOOTP 00:0b:db:14:55:35 Configure the module.
Green The module is operating correctly. The IP address of the module
scrolls across the Module Status display.
Flashing red The module detected a recoverable minor fault. Check the
module configuration. If necessar y, reconfigure the module.
Red The m odule d etecte d an un recoverable major fault. Cycle power
to the module. If the power cycle does not clear the fault, replace the module.
The module is not powered.
Verify that there is chassis power.
Verify that the module is inserted, snapped into the
chassis and backplane.
Make sure that the module has been configured.
The module is powered but does not have an IP address.
Assign an IP address to the module.
Flashing green The controller has an IP address and one of these conditions
exists:
The module has not established any CIP™ connections. If connections are configured for this module, check the
connection originator for the connection error code.
One or more connections have timed out. For example, an HMI or I/O connection has timed out.
Re-establish the connection.
64 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 65
1756 EtherNet/IP Status Indicators Appendix A
Table 1 - Single-port Module Status Indicators
Status Indicator Description Status State
Network Status (NET) Indicates if CIP™ connections are established. Green The module has established at least one CIP™ connection and is
Red The module is in conflict mode. It shares an IP address with
Flashing green/flashing red The module is performing its power-up testing.
operating properly. The IP address of the module scrolls across the Module Status display.
another device on the network. The current IP address of the module scrolls across the Module Status display. The display scrolls: OK <IP_address_of_this_module> Duplicate IP <Mac_address_of_duplicate_node_detected>
For example: OK 10.88.60.196 Duplicate IP - 00:00:BC:02:34:B4 Change the IP address of the module.
Table 2 - Dual-port Module Status Indicators
Status Indicator Description Status State
Module Status Display Alphanumeric display that scrolls messages.
For example, when a module is operating normally, the display scrolls the IP address of the module.
OK Indicates the current state of the module.
For example, this status indicator indicates if the module is executing power-up tests, in the process of a firmware update or operating normally.
——
Off The module is not powered.
Verify that there is chassis power.
Verify that the module is inserted, snapped into the chassis
and backplane.
Make sure that the module has been configured.
Flashing green The module is not configured. The Module Status display scrolls:
Green The module is operating correctly. The Module Status display
Flashing red The module detected a recoverable minor fault. Check the
Red The module detected an unrecoverable major fault. Cycle power
Both of these conditions exist:
Status Indicator is Red
Module Status Display is scrolling: Image Update Needed
Flashing red and green The module is performing its power-up testing.
BOOTP or DHCP<Mac_address_of_module> For example: BOOTP 00:0b:db:14:55:35 Configure the module.
scrolls: OK <IP_address_of_this_module> For example: OK 10.88.60.160
module configuration. If necessary, reconfigure the module.
to the module. If this does not clear the fault, replace the module.
The module’s main firmware image needs to be updated. Follow these steps:
1. Update the firmware image.
2. Cycle power to the module.
3. If the status indicators remain the same, that is, red and scrolling Image Update Needed, replace the module.
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 65
Page 66
Appendix A 1756 EtherNet/IP Status Indicators
Table 2 - Dual-port Module Status Indicators
Status Indicator Description Status State
Network Status (NET) Indicates if CIP connections are established.
IMPORTANT: The new-series 1756-EN2TR and 1756-EN3TR modules have a NET status indicator. The older-series 1756-EN2TR and 1756-EN3TR modules do not have a NET status indicator.
LINK 1 (3) LINK 2 (4)
LAN A LAN B
When using the 1756-EN2TP module, the corresponding LAN A/B Parallel Redundancy Protocol (PRP) Warning bit is set.
Off One of these conditions exists:
The module is not powered.
The module is powered but does not have an IP address.
Flashing green The controller has an IP address and one of these conditions
Green The module has established at least one CIP™ connection and is
Red The module is in conflict mode. It shares an IP address with
Flashing green/ flashing red
Off One of these conditions exists:
Flashing green Activity exists on the port.
Green One of these conditions exists:
Flashing red 0 = Off
exists:
The module has not established any CIP™ connections.
One or more connections have timed out. For example, an
operating properly. The IP address of the module scrolls across the Module Status display.
another device on the network. The current IP address of the module scrolls across the Module Status display. The display scrolls: OK <IP_address_of_this_module> Duplicate IP <Mac_address_of_duplicate_node_detected>
For example: OK 10.88.60.196 Duplicate IP - 00:00:BC:02:34:B4 Change the IP address of the module.
The module is performing its power-up testing.
The module is not powered.
No link exists on the port.
The port is administratively disabled (LNK2).
The port is disabled due to rapid ring faults (LNK2).
A link exists on the port.
The ring network is operating normally on active ring
A ring partial network fault was detected on the active ring
1 = On
Verify that there is chassis power.
Verify that the module is inserted, snapped into the
chassis and backplane.
– Make sure that the module has been configured.
Assign an IP address to the module.
If connections are configured for this module, check the connection originator for the connection error code.
HMI or I/O connection has timed out. Re-establish the connection.
Verify that there is chassis power.
Verify that the module is inserted, snapped into the
chassis and backplane.
– Make sure the module has been configured.
supervisor (LNK2).
supervisor (LNK2).
66 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 67
Appendix B
LINK
NET
OK
LINK
NET
OK
1
4
2
3
1768 EtherNet/IP Module Status Indicators
The 1768 EtherNet/IP communication modules support these status indicators. This graphic shows the front of the module for the listed modules.
Table 3 - 1768 Module Status Indicators
Number Status Indicator Description Status State
1 Module Status Display Alphanumeric display that scrolls messages. For
example, when a module is operating normally, the display scrolls the IP address for the module.
2 Link Status (LINK) Indicates the module’s current state with respect to
transmitting data on the EtherNet/IP network.
3 OK Status (OK) Indicates the module’s current state. For example,
this status indicator indicates if the module is executing power-up testing, in the process of a firmware update or operating normally.
N/A N/A
Off One of these conditions exists:
The module is not powered.
No link exists on the port.
Flashing green Activity exists on the port.
Green Activity exist s on the port.
Off The module is not powered.
Verify there is chassis power.
Verify that the module is completely inserted
Flashing green The module is not configured. The Module Status
display scrolls: BOOTP or DHCP<Mac_address_of_module>
For example: BOOTP 00:0b:db:14:55:35
Verify there is chassis power.Verify that the module is completely
inserted into the chassis and backplane.
– Make sure the module has been
configured.
into the chassis and backplane.
Configure the module.
Green The module is operating correctly. The Module
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 67
Status display scrolls: OK <IP_address_of_this_module>
For example: OK 10.88.60.160
Page 68
Appendix B 1768 EtherNet/IP Module Status Indicators
Table 3 - 1768 Module Status Indicators
Number Status Indicator Description Status State
4 Network Status (NET) Indicates if CIP connections are established.
The 1756-EN2TR and 1756-EN3TR modules do not have a NET status indicator.
Flashing red The mo dule detected a recoverable minor fault.
Red The module detected an unrecoverable major
Off One of these conditions exists:
Flashing green The controller has an IP address and one of these
Green The module has established at least 1 CIP
Red The module is in conflict mode. It shares an IP
Check the module configuration. If necessary, reconfigure the module.
fault. Cycle power to the module. If this does not clear the fault, replace the module.
The module is not powered.
The module is powered but does not have an
conditions exists:
The module has not established any CIP
One or more connections have timed out. For
connection and is operating properly. The module’s IP address scrolls across the Module Status display.
address with another device on the network. The module’s current IP address scrolls across the Module Status display. The display scrolls: OK <IP_address_of_this_module> Duplicate IP <Mac_address_of_duplicate_node_detected>
Verify there is chassis power.
Verify that the module is completely
inserted into the chassis and backplane.
– Make sure the module has been
configured.
IP address. Assign an IP address to the module.
connections. If connections are configured for this module,
check the connection originator for a connection error code.
example, an HMI or I/O connection has timed out.
Reestablish the connection.
Flashing green/ flashing red
68 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
For example: OK 10.88.60.196 Duplicate IP ­00:00:BC:02:34:B4
Change the module’s IP address.
The module is performing its power-up testing.
Page 69

1769 EtherNet/IP Adapter Status Indicators

MOD
NET
LINK 1
LINK 2
The 1769 EtherNet/IP supports these status indicators.
Table 4 - 1769 Module Status Indicators
Status Indicator Description Status State
Module (MOD) Status
Network (NET) Status
Link (LNK1/LNK2) Status
Indicates the module’s current state. Off Module does not have 24V/5V DC power.
Flashing green Module has not been configured.
Green Module has 24V/5V DC power.
Flashing red Recoverable fault and/or duplicate IP address has been detected.
Red An unrecoverable fault has been detected.
Flashing red/green Module is performing power-up self-test.
Indicates the status of the module’s IP address and connection status.
Indicates the module’s current state with respect to transmitting data on the EtherNet/IP network.
Off Module is not powered, or does not have an IP address.
Flashing green The adapter has an IP address, but no CIP connections are established.
Green Module has an IP address and at least one established connection.
Flashing red One or more of the connec tions in which the module is the target has
timed out.
Red A duplicate IP address has been detected.
Off No data is being transmitted.
Green Link established at 100 Mbps. Module is ready to communicate.
Flashing green Data transmission in progress at 100 Mbps.
Flashing Yellow Link activity present on indicated port at 10 Mbps.
Yellow Link established on indicated port at 10 Mbps.
Appendix C
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 69
Page 70
Appendix C 1769 EtherNet/IP Adapter Status Indicators
Notes:
70 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 71
Appendix D
IMPORTANT
Fiber Cable and LC Connector
This appendix provides specifications for the fiber cable and LC connector used with the 1756-EN2F EtherNet/IP fiber module or the 1783-ETAP1F and 1783-ETAP2F EtherNet/IP fiber taps.
Figure 5 - Fiber Cable

Specifications

The 1756-EN2F EtherNet/IP fiber module and the 1783-ETAP1F and 1783-ETAP2F EtherNet/IP fiber taps use a fiber cable and LC connector. The fiber cable is typically used in 1 m (3 ft), 2 m, (6 ft), 3 m (9 ft), 5 m (15 ft), and 100 m (300 ft) lengths, but supports lengths up to 2 km (1.24 mi).
You can special order a fiber cable in any length up to 2 km (1.24 mi) from your fiber cable vendor.
The fiber cable and LC connector supports these specifications.
Table 5 - Fiber Cable and LC Connector Specifications
Attribute Value
Fiber transceiver type 100Base-FX IEEE802.3u
Optical wavelength 1310 nm no cap
Transmitter launch power at beginning of life (BOL), min Allow -1 dB at end of life (EOL)
Receiver sensitivity, min -31.8 dBm
Receiver sensitivity, max -14 dBm
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 71
-19 dBm into 62.5/125 μm fiber, N/A = 0.275
-22.5 dBm into 50/125 μm fiber, N/A = 0.20
Page 72
Appendix D Fiber Cable and LC Connector
IMPORTANT
EXAMPLE
Fiber 1 dB/km Fiber 1 dB/kmFiber 1 dB/km
0.75 dB0.75 dB
1km0.75km 0.25km
0.75 dB 0.75 dB 0.75dB 0.25 dB1 dB
++++
Total channel insertion loss = 3.5 db
Table 5 - Fiber Cable and LC Connector Specifications
Attribute Value
Fiber channel power budget at rated BER (Two connected modules or taps, either the 1756-EN2F
EtherNet/IP fiber module, or 1783-ETAP1F or 1783­ETAP2F EtherNet/IP fiber taps)
Fiber type Glass
Connector type IEC 61754-20 LC connector, max. insertion loss 0.75 dB per
Channel length, max 2 km (1.24 mi)
(1) The channel, that is, connectors and cable, must not exceed the allowable power budget.
12.8 dB for 62.5/125 μm multimode fiber
9.3 dB for 50/125 μm multimode fiber
62.5/125 μm and 50/125 μm multimode fiber Simplex or duplex Jacket type and jacket diameter is dependent on
connector selection Graded Index (GI) fiber Per IEC 60794-1-1, IEC 60793-2-10 category A1 fibers
connection
(1)
Allow at least 5.08 cm (2 in.) for the fiber cable bend radius. Contact the cable manufacturer for more information on the recommended cable bend radius.
In the example shown here, the channel insertion loss is calculated for an optical channel based on these factors:
1 dB/km fiber
0.75 dB per adapter
Note that in this example, the end connectors are not factored in the calculations.
ATTENTION: The maximum power budget for this example is 12.8 dB for 62.5/125 μm fiber. Therefore, the channel insertion loss for the example of 3.5 dB is less than the maximum power budget.
72 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 73

Index

Numerics
1756 module
apply power determine slot location grounding install install under power installation summary remove under power 21 status indicators USB port wire via fiber connector 18 wire via RJ45 connector
1768 module
add-on profile apply power 30 grounding install installation summary mount on a DIN rail mount with screws remove 30 status indicators wire via RJ45 connector
1769 adapter
description grounding install installation summary 37 minimum spacing mount on a DIN rail mount with screws 41 remove replace status indicators system assembly 40 system configuration example system configuration rules
19
14
16
21
63
19
7
26
27
27
27
67
39
37
39
41
42
43
43
69
A
additional resources 7 add-on profile, download
1768 module
apply power
1756 chassis 1768 chassis 30
assemble the 1769 system
7
19
B
BOOTP/DHCP server
set the network IP address
1756 module
47
C
chassis power, applying
1756 chassis 1768 chassis
19 30
14
25
15
17
29
40
35
36
configure
DHCP server
configure a module via USB configure a workstation configure the driver connector
fiber
RJ45
USB
49
56
1756 module
1756 module 1768 module 29
1756 module
18
17
19
59
55
D
DHCP server 49 download the add-on profile
1768 module
7
E
Ethernet/IP driver 56 EtherNet/IP modules in this publication
F
fiber cable
specifications
firmware
load over USB
71
62
G
grounding
1756 module 1768 module 1769 adapter
14 26 37
I
install the 1756 module 16 install the 1768 module install the 1769 adapter install under power
1756 module
installation summary
1756 module 1768 module 1769 adapter
IP address, reset
1756 module
IP addresses
DHCP server
27
39
21
14 25 37
54
49
L
LAN A 66
7
Rockwell Automation Publication ENET-IN002H-EN-P - August 2017 73
Page 74
Index
LAN B 66
M
minimum spacing
1769 module
module slot location
1756 module
mount the module
on a DIN rail
with screws
41
15
1768 module 1769 adapter 42
1768 module 1769 adapter 41
27
27
N
network IP address
set with rotary switches
1756 module
network IP address, setting
introduction
1768 module 1769 adapter 37
with BOOTP/DHCP server
1756 module
with RSLinx software
1756 module
with Studio 5000 environment
1756 module
46
26
47
50
50
1769 adapter
with BOOTP/DHCP server
1756 module
with rotary switches
1756 module
with RSLinx software
1756 module
with Studio 5000 environment
1756 module
set up USB driver set up USB hardware specifications
fiber cable
status indicators
1756 module 1768 module 67 1769 adapter
Studio 5000 environment
set the network IP address
1756 module
system configuration, 1769
example
36
rules
35
37
47
46
50
50
60
59
71
63
69
50
U
USB port
serial communication set up hardware
USB port connection
1756 module
59
59
19
P
PRP
module
20
status indicators 66
R
remove module
1768 module 1769 adapter
remove under power
1756 module
removing the module, under power reset IP address
1756 module
RIUP. See remove under power RSLinx software
set the network IP address
30 43
21
54
1756 module
50
S
serial communication
USB port
set the network IP address
59
introduction
1768 module
26
21
W
warning bit 66 wire the 1756 module
via fiber connector via RJ45 connector 17
wire the 1768 module
via RJ45 connector
18
29
74 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Page 75
Page 76
Rockwell Automation Support
Use the following resources to access support information.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf
.
Technical Support Center
Knowledgebase Articles, How-to Videos, FAQs, Chat, User Forums, and Product Notification Updates.
https://rockwellautomation.custhelp.com/
Local Technical Support Phone Numbers Locate the phone number for your country. http://www.rockwellautomation.com/global/support/get-suppor t-now.page
Direct Dial Codes
Find the Direct Dial Code for your product. Use the code to route your call directly to a technical support engineer.
http://www.rockwellautomation.com/global/support/direct-dial.page
Literature Library
Installation Instructions, Manuals, Brochures, and Technical Data.
http://www.rockwellautomation.com/global/literature-library/overview.page
Product Compatibility and Download Center (PCDC)
Get help determining how products interact, check features and capabilities, and find associated firmware.
http://www.rockwellautomation.com/global/support/pcdc.page
.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation maintains current product environmental information on its webs ite at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.
Allen- Bradley, Com pact I/O, Co mpactLog ix, Control Logix, Cont rolLogix-X T, Contro lFLASH, L ogix5000, Logix Des igner, Rock well Soft ware, Rockwell Automation, RSLinx, RSLogix, and Studio 5000 are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respec tive companies.
Publication ENET-IN002H-EN-P - August 2017
Supersedes Publication ENET-IN002G-EN-P - November 2014 Copyright © 2017 Roc kwell Automation, Inc. All rights rese rved. Printed in the U.S.A.
Loading...