Rockwell Automation 1768-L45S User Manual

User Manual
Compact GuardLogix Controllers
Catalog Numbers 1768-L43S, 1768-L45S

Important User Information

IMPORTANT
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 your local Rockwell Automation
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
Rockwell Automation, Allen-Bradley, TechConnect, ControlLogix, GuardLogix, CompactBlock Guard I/O, ControlFLASH, Log ix5000, RSLogix, RSNetWorx, CompactLogix, Compact I/O, DriveLogix, Integrated Architecture, KwikLink, MicroLogix, PanelView, PhaseManager, POINT Guard I/O, POINT I/O, PowerFlex, Rockwell Software, SLC, and RSLinx are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Summary of Changes

The information below summarizes the changes to this manual since the last publication.
To help you find new and updated information in this release of the manual, we included change bars as shown to the right of this paragraph.
Top ic Pa ge
Specifications and certifications are in the CompactLogix Controller Specifications Technical Data, publication 1769-TD005
Added information on using unicast connections for I/O modules on EtherNet/IP networks 16, 57 Added installation information Chapter 2 Added information on Run mode protection for the safety task signature 36, 90, 91 Updated I/O replacement procedures to include various replacement scenarios 65…71 Updated Requested Packet Interval maximum value 75 Added DCA_INPUT and DCAF_INPUT data types to list of valid types for safety tags 78 Restructured information on produced and consumed safety tags and configuring peer
safety controllers so that all information is together in Chapter 6 Moved status indicator description tables to an appendix and added troubleshooting
information Added information on changing to a 1756-L7xS controller 125 Added History of Changes appendix 127
.
81
Appendix B
Rockwell Automation Publication 1768-UM002C-EN-P - April 2012 3
Summary of Changes
Notes:
4 Rockwell Automation Publication 1768-UM002C-EN-P - April 2012
System Overview
Install the Controller

Table of Contents

Preface
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Understanding Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Chapter 1
Safety Application Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Safety Network Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Safety Task Signature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Distinguishing Between Standard and Safety Components . . . . . . . . . . 12
HMI Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Controller Data Flow Capabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Selecting System Hardware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Selecting Safety I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Selecting Communication Networks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Programming Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Chapter 2
Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Environment and Enclosure Information. . . . . . . . . . . . . . . . . . . . . . . 17
Programmable Electronic Systems (PES) . . . . . . . . . . . . . . . . . . . . . . . 18
North American Hazardous Location Approval. . . . . . . . . . . . . . . . . 18
European Hazardous Location Approval . . . . . . . . . . . . . . . . . . . . . . . 19
Prevent Electrostatic Discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Required System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Clearance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Module Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Mount the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Panel Mount the Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Mount the Controller on a DIN Rail. . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Confirm the Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Insert or Remove a Memory Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Make Communication Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Update the Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Install Firmware via ControlFlash Software. . . . . . . . . . . . . . . . . . . . . 28
Install Firmware via AutoFlash Software. . . . . . . . . . . . . . . . . . . . . . . . 29
Install Firmware via a CompactFlash Card. . . . . . . . . . . . . . . . . . . . . . 29
Remove a 1768 or 1769 Module from the DIN Rail . . . . . . . . . . . . . . . . . 30
Rockwell Automation Publication 1768-UM002C-EN-P - April 2012 5
Table of Contents
Chapter 3
Configure the Controller
Communicate over Networks
Create a Controller Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Set Passwords for Safety-locking and -unlocking . . . . . . . . . . . . . . . . . . . . 35
Protecting the Safety Task Signature in Run Mode. . . . . . . . . . . . . . . . . . 36
Handling I/O Module Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Enable Time Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Configure a Peer Safety Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Chapter 4
The Safety Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Managing the Safety Network Number (SNN). . . . . . . . . . . . . . . . . . 39
Assigning the Safety Network Number (SNN). . . . . . . . . . . . . . . . . . 41
Changing the Safety Network Number (SNN). . . . . . . . . . . . . . . . . . 41
EtherNet/IP Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Producing and Consuming Data via an EtherNet/IP Network . . . 45
Connections over the EtherNet/IP Network . . . . . . . . . . . . . . . . . . . 45
EtherNet/IP Communication Example . . . . . . . . . . . . . . . . . . . . . . . . 46
EtherNet/IP Connections for CIP Safety I/O Modules. . . . . . . . . . 47
Standard EtherNet/IP Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
ControlNet Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Producing and Consuming Data via a ControlNet Network . . . . . 48
Connections over the ControlNet Network . . . . . . . . . . . . . . . . . . . . 48
ControlNet Communication Example . . . . . . . . . . . . . . . . . . . . . . . . . 49
ControlNet Connections for Distributed I/O . . . . . . . . . . . . . . . . . . 50
Standard DeviceNet Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Serial Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Chapter 5
Add, Configure, Monitor, and Replace CIP Safety I/O
6 Rockwell Automation Publication 1768-UM002C-EN-P - April 2012
Adding CIP Safety I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Configure CIP Safety I/O Modules via RSLogix 5000 Software . . . . . . 56
Setting the Safety Network Number (SNN) . . . . . . . . . . . . . . . . . . . . . . . . 57
Using Unicast Connections on EtherNet/IP Networks. . . . . . . . . . . . . . 57
Setting the Connection Reaction Time Limit. . . . . . . . . . . . . . . . . . . . . . . 57
Specify the Requested Packet Interval (RPI) . . . . . . . . . . . . . . . . . . . . 58
View the Maximum Observed Network Delay . . . . . . . . . . . . . . . . . . 58
Setting the Advanced Connection Reaction Time Limit
Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Understanding the Configuration Signature. . . . . . . . . . . . . . . . . . . . . . . . 61
Configuration via RSLogix 5000 Software . . . . . . . . . . . . . . . . . . . . . . 61
Different Configuration Owner (listen only connection) . . . . . . . . 62
Reset Safety I/O Module Ownership. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Addressing Safety I/O Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Monitor Safety I/O Module Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Resetting a Module to Out-of-box Condition. . . . . . . . . . . . . . . . . . . . . . . 65
Replacing a Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Develop Safety Applications
Table of Contents
Replacement with ‘Configure Only When No Safety Signature
Exists’ Enabled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Replacement with ‘Configure Always’ Enabled. . . . . . . . . . . . . . . . . . 70
Chapter 6
The Safety Task . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Safety Task Period Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Safety Task Execution. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Safety Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Safety Routines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Safety Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Tag Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Data Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Scope. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Constant Value. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
External Access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Produced/Consumed Safety Tags. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Configure the Peer Safety Controllers’ Safety Network Numbers . 81
Produce a Safety Tag. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Consume Safety Tag Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Safety Tag Mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Restrictions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Create Tag Mapping Pairs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Monitor Tag Mapping Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Safety Application Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Safety-lock the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Generate a Safety Task Signature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Software Restrictions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Go Online with the Controller
Chapter 7
Connecting the Controller to the Network. . . . . . . . . . . . . . . . . . . . . . . . . 93
Connect the Controller via a Serial Network. . . . . . . . . . . . . . . . . . . . 93
Connect Your EtherNet/IP Device and Computer. . . . . . . . . . . . . . 94
Connect Your ControlNet Communication Module and Your
Computer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Configuring the Network Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Configure a Serial Communication Driver. . . . . . . . . . . . . . . . . . . . . . 95
Configuring an EtherNet/IP or ControlNet Driver . . . . . . . . . . . . . 95
Understanding the Factors that Affect Going Online. . . . . . . . . . . . . . . . 95
Project to Controller Matching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Firmware Revision Matching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Safety Status/Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Safety Task Signature and Safety-locked and -unlocked Status . . . . 97
Download . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Upload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Go Online . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Rockwell Automation Publication 1768-UM002C-EN-P - April 2012 7
Table of Contents
Chapter 8
Monitor Status and Handle Faults
Store and Load Projects Using Nonvolatile Memory
Viewing Status via the Online Bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Monitoring Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
All Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Safety Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Monitoring Status Flags. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Monitoring Safety Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Controller Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Nonrecoverable Controller Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Nonrecoverable Safety Faults in the Safety Application . . . . . . . . . 106
Recoverable Faults in the Safety Application . . . . . . . . . . . . . . . . . . . 107
Viewing Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Developing a Fault Routine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Program Fault Routine. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Controller Fault Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Use GSV/SSV Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Chapter 9
Using Memory Cards for Nonvolatile Memory . . . . . . . . . . . . . . . . . . . . 113
Storing a Safety Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Loading a Safety Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Manage Firmware with Firmware Supervisor . . . . . . . . . . . . . . . . . . . . . . 116
Status Indicators
Change Controller Type in RSLogix 5000 Projects
History of Changes
Appendix A
Compact GuardLogix Controller Status Indicators . . . . . . . . . . . . . . . . 117
Clear a Major Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Clear a Nonrecoverable Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Troubleshoot a Nonresponsive Module . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Troubleshoot System Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Examine the Power Supply PWR Status Indicator. . . . . . . . . . . . . . 120
Examine the Controller PWR Indicator . . . . . . . . . . . . . . . . . . . . . . . 121
Examine the I/O PWR Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Appendix B
Changing from a Standard to a Safety Controller . . . . . . . . . . . . . . . . . . 123
Changing from a Safety to a Standard Controller . . . . . . . . . . . . . . . . . . 124
Changing from a 1756 GuardLogix Controller to a 1768 Compact
GuardLogix Controller or Vice Versa . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Changing from a 1756-L7xS Controller to a 1756-L6xS or 1768-L4xS
Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Appendix C
Index
8 Rockwell Automation Publication 1768-UM002C-EN-P - April 2012

Preface

Top ic Pa ge
Additional Resources 9 Understanding Terminology 10
This manual is a guide for using Compact GuardLogix controllers. It describes the Compact GuardLogix-specific procedures you use to configure, operate, and troubleshoot your controller.
Use this manual if you are responsible for designing, installing, programming, or troubleshooting control systems that use Compact GuardLogix controllers.
You must have a basic understanding of electrical circuitry and familiarity with relay logic. You must also be trained and experienced in the creation, operation, and maintenance of safety systems.
For detailed information on related topics like programming your Compact GuardLogix controller, SIL 3/PLe requirements, or information on standard Logix components, see the list of Additional Resources

Additional Resources

These documents contain additional information concerning related products from Rockwell Automation.
Resource Description
CompactLogix Controllers Specifications Technical Data, publication
1769-TD005
GuardLogix Controller Systems Safety Reference Manual, publication
1756-RM093
GuardLogix Safety Application Instruction Set Reference Manual, publication 1756-RM095
CompactBlock Guard I/O EtherNet/IP Safety Modules Installation Instructions, publication 1791ES-IN001
Guard I/O EtherNet/IP Safety Modules User Manual, publication
1791ES-UM001
CompactLogix Controllers User Manual, publication 1768-UM001 Logix5000 Controllers General Instruction Set Reference Manual,
publication 1756-RM003 Logix5000 Controllers Common Procedures Programming Manual,
publication 1756-PM001
EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication ENET-UM001
ControlNet Modules in Logix5000 Control Systems User Manual, publication CNET-UM001
Provides specifications, dimensions, and certification information for Compact GuardLogix controllers
Contains detailed requirements for achieving and maintaining SIL 3/PLe with the GuardLogix controller system
Provides information on the GuardLogix Safety ap plication instruction set
Provides information on installing CompactBlock Guard I/O EtherNet/IP Safety modules
Provides information on using Guard I/O EtherNet/IP Safety modules
Provides information on using CompactLogix controllers in standard applications Provides information on the Logix5000 instruction set
Provides access to the Logix5000 Controllers set of programming manuals, which covers managing project files, organizing tags, ladder logic programming, testing routines, creating Add-On Instructions, controller status data, handling faults, importing and exporting project components and more
Provides information on using EtherNet/IP communication modules in a Logix5000 control system
Provides information on using the 1756-CNB module in Logix5000 control systems
on page 9.
Rockwell Automation Publication 1768-UM002C-EN-P - April 2012 9
Preface
Resource Description
Logix5000 Controllers Execution Time and Memory Use Reference Manual, publication 1756-RM087
Logix5000 Controllers Import Export Reference Manual, publication
1756-RM084
PhaseManager User Manual, publication LOGI X-U M001 SERCOS and Analog Motion Configuration and Startup Manual,
publication MOTION-UM001 Industrial Automation Wiring and Grounding Guidelines, publication
1770-4.1
Provides information on estimating the execution time and memor y use for instructions
Provides information on using RSLogix 5000 Import/Export utility
Provides information on programming the controller to use equipment phases in a standard application Provides information on configuring the controller for motion axes, coordinate system, and motion modules in
standard applications Provides in-depth information on grounding and wiring programmable controllers
You can view or download publications at
http://www.rockwellautomation.com/literature
technical documentation, contact your local Allen-Bradley® distributor or Rockwell Automation sales representative.
. To order paper copies of

Understanding Terminology

This table defines terms used in this manual.
Table 1 - Terms and Definitions
Abbreviation Full Term Definition
1oo2 One Out of Two Refers to the behavioral design of a multi-processor safety system. CIP Common Industrial Protocol A communication protocol designed for industrial automation applications. CIP Safety Common Industrial Protocol – Safety Certified SIL 3/PLe rated version of CIP. DC Diagnostic Coverage The ratio of the detected failure rate to the total failure rate. EN European Norm. The official European standard. GSV Get System Value An instruction that retrieves specified controller-status information and places it in a destination tag. — Multicast The transmission of information from one sender to multiple receivers. PFD Probability of Failure on Demand The average probability of a system to fail to perform its design function on demand. PFH Probability of Failure per Hour The probability of a system to have a dangerous failure occur per hour. PL Performance Level ISO 13849-1 safety rating. RPI Requested Packet Interval The expected rate in time for production of data when communicating over a network. SNN Safety Network Number A unique number that identifies a section of a safety network. SSV Set System Value An instruction that sets controller system data. — Standard An object, task, tag, program, or component in your project that is not a safety-related item. — Unicast The transmission of information from one sender to one receiver.
10 Rockwell Automation Publication 1768-UM002C-EN-P - April 2012
System Overview
Top ic Pag e
Safety Application Requirements 11 Distinguishing Between Standard and Safety Components 12 Controller Data Flow Capabilities 13 Selecting System Hardware 14 Selecting Safety I/O Modules 14 Selecting Communication Networks 14 Programming Requirements 15
Chapter 1

Safety Application Requirements

The Compact GuardLogix controller system is certified for use in safety applications up to and including Safety Integrity Level (SIL) 3 and Performance Level (e) in which the de-energized state is the safe state. Safety application requirements include evaluating probability of failure rates (PFD and PFH), system reaction-time settings, and functional-verification tests that fulfill SIL 3/PLe criteria.
For SIL 3 and PLe safety system requirements, including functional validation test intervals, system reaction time, and PFD/PFH calculations, refer to the GuardLogix Controller Systems Safety Reference Manual, publication
1756-RM093
operating a Compact GuardLogix SIL 3, PLe safety system.
Compact GuardLogix-based SIL 3/PLe safety applications require the use of at least one safety network number (SNN) and a safety task signature. Both affect controller and I/O configuration and network communication.
Refer to the GuardLogix Controller Systems Safety Reference Manual, publication 1756-RM093
. You must read, understand, and fulfill these requirements prior to
, for details.

Safety Network Number

The safety network number (SNN) must be a unique number that identifies safety subnets. Each safety subnet that the controller uses for safety communication must have a unique SNN. Each CIP Safety device must also be configured with the safety subnet’s SNN. The SNN can be assigned automatically or manually.
Rockwell Automation Publication 1768-UM002C-EN-P - April 2012 11
Chapter 1 System Overview
For information on assigning the SNN, see Managing the Safety Network
Number (SNN) on page 39.

Safety Task Signature

The safety task signature consists of an ID number, date, and time that uniquely identifies the safety portion of a project. This includes safety logic, data, and configuration. The Compact GuardLogix system uses the safety task signature to determine the project’s integrity and to let you verify that the correct project is downloaded to the target controller. Creating, recording, and verifying the safety task signature is a mandatory part of the safety-application development process.

Distinguishing Between Standard and Safety Components

See Generate a Safety Task Signature
Slots in the Compact GuardLogix backplane may be populated with other CompactLogix I/O modules that are certified to the Low Voltage and EMC Directives. Refer to http://www.ab.com/certification/ce certificate for the Programmable Control – CompactLogix Product Family and determine which modules are certified.
You must create and document a clear, logical, and visible distinction between the safety and standard portions of the application. To aid in creating this distinction, RSLogix 5000 programming software features safety identification icons to identify the safety task, safety programs, safety routines, and safety components. In addition, the RSLogix 5000 software uses a safety class attribute that is visible whenever safety task, safety programs, safety routine, safety tag, or safety Add-On Instruction properties are displayed.
The controller does not allow writes to safety tag data from external HMI devices or via message instructions from peer controllers. RSLogix 5000 software can write safety tags when the Compact GuardLogix controller is safety-unlocked, does not have a safety task signature, and is operating without safety faults.
on page 90 for more information.
to find the CE
The 1768 CompactLogix Controllers User Manual, publication 1768-UM001 provides information on using 1768 CompactLogix controllers in standard (non-safety) applications.

HMI Devices

HMI devices can be used with Compact GuardLogix controllers. HMI devices can access standard tags just as with a standard controller. However, HMI devices cannot write to safety tags; safety tags are read-only for HMI devices.
12 Rockwell Automation Publication 1768-UM002C-EN-P - April 2012
,
System Overview Chapter 1
IMPORTANT
Compact GuardLogix Controller

Controller Data Flow Capabilities

This illustration explains the standard and safety data-flow capabilities of the Compact GuardLogix controller.
Figure 1 - Data Flow Capabilities
Standard Safety
Standard Tasks
Standard Programs
Standard Routines
Program Data
Controller Standard Tags
Safety Task
Safety Programs
Safety Routines
Program Safety Data
Controller Safety Tags
No. Description 1 Standard tags and logic behave the same way they do in the standard Logix platform. 2 Standard tag data, program- or controller-scoped, can be exchanged with external HMI devices, personal
3 Compact GuardLogix controllers are integrated controllers with the ability to move (map) standard tag data
4 Controller-scoped safety tags can be read directly by standa rd logic. 5 Safety tags can be read or written by safety logic. 6 Safety tags can be exchanged between safety controllers over Ethernet or ControlNet networks, including 1756
7 Safety tag data, program- or controller-scoped, can be read by external devices, such as HMI devices, personal
computers, and other controllers.
into safety tags for use within the safety task.
ATT EN TI ON : This data must not be used to directly control a SIL 3/PLe output.
and 1768 GuardLogix controllers.
computers, or other standard controllers.
Once this data is read, it is considered standard data, not SIL 3/PLe data.
Rockwell Automation Publication 1768-UM002C-EN-P - April 2012 13
Chapter 1 System Overview

Selecting System Hardware

The Compact GuardLogix system supports SIL 3 and PLe safety applications.

Controller

1768-L43S and 1768-L45S controllers feature one built-in serial port. A keyswitch on the front panel lets you change controller modes: RUN, PROGram and REMote. The 1768 Compact GuardLogix controllers combine a 1768 backplane with a 1769 backplane. This combination includes all the advantages of the 1768 architecture for safety applications while retaining the 1769 I/O support for standard applications.
Controller Available 1768
Slots
1768-L43S 2 2 16 Modules in 3 Banks 250 0.5 MB 2 MB 1768-L45S 4 2 30 Modules in 3 Banks 1 MB 3 MB
Number of 1768 Communication Modules
Maximum Local 1769 I/O Modules Supported
Number of Connections Supported
Safety Task Memory
In addition, Compact GuardLogix controllers support 1768-M04SE SERCOS modules for motion control in standard (non-safety) applications. For information on developing motion applications, refer to the SERCOS and Analog Motion Configuration and Startup Manual, publication
MOTION-UM001
.
Standard Memory

Selecting Safety I/O Modules

Selecting Communication Networks

Safety input and output devices can be connected to CIP Safety I/O on EtherNet/IP networks, allowing output devices to be controlled by a Compact GuardLogix controller system via EtherNet/IP communication.
For the most up-to-date information on available CIP Safety I/O catalog numbers, certified series, and firmware revisions, see
http://www.ab.com/certification/safety
.
The Compact GuardLogix controller supports communication that lets it do the following:
Distribute and control Safety I/O on EtherNet/IP networks.
Produce and consume safety tag data between 1756 and 1768 GuardLogix
controllers across EtherNet/IP or ControlNet networks.
Distribute and control standard I/O on EtherNet, ControlNet, or
DeviceNet networks.
14 Rockwell Automation Publication 1768-UM002C-EN-P - April 2012
System Overview Chapter 1
Use these communication modules to provide an interface between Compact GuardLogix controllers and network devices.
Use this module To interface between
1768-ENBT, series A, revision 3 1768-CNB, series A, revision 3
(1) This or later.
(1)
(1)
The Compact GuardLogix controller and EtherNet/IP devices Controllers on the ControlNet network
The Compact GuardLogix controller can connect to RSLogix 5000 programming software via a serial connection, an 1768-ENBT EtherNet module, or a 1768-CNB ControlNet module.

Programming Requirements

See the Additional Resources
on page 9 for more information on using network
communication modules.
RSLogix 5000 software is the programming tool for Compact GuardLogix controller applications.
Use Ta bl e 2
to identify the minimum software versions for use with your
Compact GuardLogix controllers.
Table 2 - Software Versi ons
Cat. No. RSLogix 5000 Software
1756-L43S, 1756-L45S 18 Any version
(1) This version or later. (2) RSLinx Classic version 2.59 or later is required with RSLogix 5000 software version 20 or later.
Versi on
(1)
RSLinx® Classic Software
(1)
Vers ion
(2)
Safety routines include safety instructions, which are a subset of the standard ladder logic instruction set, and safety application instructions. Programs scheduled under the safety task support only ladder logic.
Rockwell Automation Publication 1768-UM002C-EN-P - April 2012 15
Chapter 1 System Overview
Table 3 - Supported Features by RSLogix 5000 Software Version
Featu re
Safety Task Standard Task Safety Task Standard Task Safety Task Standard Task
Add-On instructions XXXXXX Alarms and events X X X Constant value tags XXXXXX Equipment phase routines X X X External Access XXXXXX Event tasks X X X Firmware Supervisor XXXXXX Function block diagrams (FBD) X X X Integrated motion X X X Ladder logic XXXXXX Language switching XXXXXX Online import and export of program components X X X Sequential function char t (SFC) routines X X X Structured text XXX Unicast connections for produced and consumed safety tags XXXX Unicast connections for safety I/O modules XX
Version 18 Version 19 Version 20
Compact GuardLogix controllers support 1768-M04SE SERCOS modules for motion control in standard (non-safety) applications. For information on developing motion applications, refer to the SERCOS and Analog Motion Configuration and Startup Manual, publication MOTION-UM001
.
Compact GuardLogix controllers also support PhaseManager™ programs, which let you add equipment phases to standard controller applications. Refer to the PhaseManager User Manual, publication LOGIX-UM001
, for more
information.
For information on using these features, refer to the Logix5000 Controllers Common Procedures Programming Manual, publication 1756-PM001 publications listed in the Additional Resources
on page 9, and RSLogix 5000
, the
software online help.
16 Rockwell Automation Publication 1768-UM002C-EN-P - April 2012
Install the Controller
Top ic Pag e
Precautions 17 Required System Components 20 Clearance Requirements 20 Module Placement 20 Mount the Controller 22 Insert or Remove a Memory Card 26 Make Communication Connections 26 Update the Controller 28 Remove a 1768 or 1769 Module from the DIN Rail 30
Chapter 2

Precautions

Read and follow these precautions for use.

Environment and Enclosure Information

ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II
applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted as well as radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the application if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures
, for additional installation requirements
Rockwell Automation Publication 1768-UM002C-EN-P - April 2012 17
Chapter 2 Install the Controller

Programmable Electronic Systems (PES)

AT TE NT IO N: Personnel responsible for the application of safety-related
Programmable Electronic Systems (PES) shall be aware of the safety requirements in the application of the system and shall be trained in using the system.

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous locations:
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
WARNING: EXPLOSION HAZARD
Do not disconnect equipment unless power has
been removed or the area is known to be nonhazardous.
Do not disconnect connections to this equipment
unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
Substitution of components may impair suitability
for Class I, Division 2.
If this product contains batteries, they must only be
changed in an area known to be nonhazardous.
Informations sur l'utilisation de cet équipement en environnements dangereux:
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
AVERTISSEMENT: RISQUE D’EXPLOSION
Couper le courant ou s'assurer que l'environnement
est classé non dangereux avant de débrancher l'équipement.
Couper le courant ou s'assurer que l'environnement
est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
La substitution de composants peut rendre cet
équipement inadapté à une utilisation en environnement de Classe I, Division 2.
S'assurer que l'environnement est classé non
dangereux avant de changer les piles.
18 Rockwell Automation Publication 1768-UM002C-EN-P - April 2012
Install the Controller Chapter 2

European Hazardous Location Approval

The following applies when the product bears the Ex Marking.
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN 60079-0.
ATTENTION: This equipment is not resistant to sunlight or other sources of UV radiation.
WARNING:
This equipment must be installed in an enclosure providing at least IP54
protection when applied in Zone 2 environments.
This equipment shall be used within its specified ratings defined by
Rockwell Automation.
Provision shall be made to prevent the rated voltage from being exceeded by
transient disturbances of more than 40% when applied in Zone 2 environments.
Secure any external connections that mate to this equipment by using
screws, sliding latches, threaded connectors, or other means provided with this product.
Do not disconnect equipment unless power has been removed or the area is
known to be nonhazardous.

Prevent Electrostatic Discharge

ATT EN TI ON : This equipment is sensitive to electrostatic discharge, which
can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in
use.
Rockwell Automation Publication 1768-UM002C-EN-P - April 2012 19
Chapter 2 Install the Controller
IMPORTANT
31609-M
Power
OUT
L1
L2/N
90 mm (3.54 in.)
105 mm (4.13 in.)
90 mm (3.54 in.)
105 mm (4.13 in.)
1768 Backplane (local)
1768 Controller, Power Supply, and I/O Modules
Remote Bank
1769 Power Supply and
I/O Modules
1769 Backplane

Required System Components

Clearance Requirements

You need these parts when installing your controller:
1768-L43S or 1768-L45S Compact GuardLogix controller
1768-PA3 or 1768-PB3 power supply
1769-ECR end cap
Mounting screws (M4 or #8 panhead) or one of these
EN 50 022 DIN rails:
35 x 7.5 mm (1.38 x 0.30 in.)35 x 15 mm (1.38 x 0.59 in.)
1756-CP3 serial cable (or make your own)
Allow for the minimum clearance from enclosure walls, wireways, and other equipment.

Module Placement

20 Rockwell Automation Publication 1768-UM002C-EN-P - April 2012
These minimum clearances keep the modules cool enough in most situations. The operating temperature range is 0…60 °C (32…140 °F).
Install the Controller Chapter 2
IMPORTANT
1768 Backplane
1768 Modules
1768-L43S
Slot 2 Slot 1 Slot 0
1769 Backplane
1769 Modules
1768-L43S
Slot 2Slot 1Slot 0
CompactLogix System Distance Ratings
Because the 1768 CompactLogix power supply works with the controller to power a 1768 system, the distance rating in a 1768 CompactLogix system differs from that in a 1769 CompactLogix system.
In the 1768 system, the distance rating is the distance between 1769 I/O modules and the controller. In the 1769 system, the distance rating is the distance between 1769 I/O modules and the power supply.
Follow these requirements to determine proper placement of your 1768 controller, power supply, 1768 I/O modules, and 1769 I/O modules:
Place the 1768-L4xx controller so that it is the last module (furthest away
from the power supply) in the 1768 backplane.
The 1768 CompactLogix power supply distributes power from the right
side of the supply and must be the leftmost module in the system.
The local bank is powered by a 1768 power supply.
Up to eight 1769 I/O modules can reside in the local bank.
1768 slots are numbered right to left, starting with the controller as slot 0.
Up to two remote banks of 1769 I/O modules may be connected by using
1769-CRLx extension cables.
Remote banks are powered by a standard 1769 power supply.
Each I/O bank must have its own 1769 power supply.
1769 slots are numbered from left to right, starting with the controller as
slot 0.
Rockwell Automation Publication 1768-UM002C-EN-P - April 2012 21
Chapter 2 Install the Controller
IMPORTANT
IMPORTANT
Up to eight 1769 Compact I/O modules can reside on each side of a 1769
power supply in a remote bank. Consult the module’s specifications for its distance rating.
1769 power supplies must be separated from the 1768 series processor by a bus extension cable. Never put a 1769 power supply in the 1768 backplane or the controller will generate a major fault that cannot be cleared until you remove the 1769 power supply.
The type of controller determines the maximum number of 1768 modules
that can reside in the local bank and the maximum number of 1769 I/O modules that can reside in one local and up to two remote banks.
Controller Max Local 1768 Modules Max 1769 I/O Modules (local and remote)
1768-L43S 2 16 1768-L45S 4 30

Mount the Controller

You can mount the controller to a panel or on a DIN rail.
Do not use screws if using a DIN rail to mount the controller. You can break the mounting tabs if you screw the controller to a panel while it is on a DIN rail.

Panel Mount the Controller

Follow these steps to mount your controller by using the panhead screws.
1. Connect the CompactLogix modules together as shown in Mount the
Controller on a DIN Rail on page 23.
2. Use the controller as a template and mark pilot holes on your panel.
3. Drill the pilot holes for M4 or #8 screws.
ATTENTION: During mounting of all devices, be sure that all debris (such as metal chips or wire strands) is kept from falling into the controller or I/O modules. Debris that falls into the controller or modules could cause damage while the controller is energized.
4. Use M4 or #8 screws to mount the controller to your panel with 1.16 N•m
(10 lb•in) of torque.
5. Ground the module on a ground bus with a dedicated earth ground stake.
6. Connect the ground bus to a functional earth ground on the panel or a
DIN rail.
22 Rockwell Automation Publication 1768-UM002C-EN-P - April 2012

Mount the Controller on a DIN Rail

31595-M
a.
b.
b.
c.
a.
a.
c.
AT TE NT IO N: This product is grounded through the DIN rail to chassis ground.
Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum and plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to the mounting surface approximately every 200 mm (7.87 in.) and use end anchors appropriately.
Mount 1768 Components
Follow these steps to mount the controller.
1. Mount the controller on the DIN rail.
Install the Controller Chapter 2
31596 -M
2. Mount additional 1768 modules to the left of the controller.
31597-M
Rockwell Automation Publication 1768-UM002C-EN-P - April 2012 23
Chapter 2 Install the Controller
31599-M
3. Mount the 1768 power supply and other 1768 modules.
Mount 1769 I/O Modules
Follow these steps to mount 1769 I/O modules to the right of the controller.
1. Align the upper and lower tongue-and-groove slots and slide the module
back toward the DIN rail until the bus levers line up.
2. Close the DIN rail latches.
24 Rockwell Automation Publication 1768-UM002C-EN-P - April 2012
Install the Controller Chapter 2
a.
b.
a.
Power
OUT
L1
L2/N
3. Slide the bus lever to the left to lock the modules together.
ATTENTION: When attaching I/O modules, it is very important that the bus connectors are securely locked together for proper electrical connection.
4. Attach the end cap by using the tongue and groove slots (a) and locking the
bus lever (b).

Confirm the Installation

After you have installed the controller and applied power, check that the PWR and I/O PWR status indicators are solid green.
If the indicators are in any other state, see Troubleshoot System Power
page 120.
Rockwell Automation Publication 1768-UM002C-EN-P - April 2012 25
on
Chapter 2 Install the Controller
Workstation Controller
1 DCD 2 RDX 3 TXD 4 DTR
COMMO N
6 DSR 7 RTS 8 CTS 9
1 DCD 2 RDX 3 TXD 4 DTR
COMMO N
6 DSR 7 RTS 8 CTS 9

Insert or Remove a Memory Card

Make Communication Connections

WARNING: When you insert or remove the memory card when power is
on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Follow these steps to insert or remove a CompactFlash card.
1. Press the memory-card door latch on the
controller front panel and pivot the door down toward you.
2. Insert or remove the card from the slot.
3. Close the memory card door.
WARNING: If you connect or disconnect the serial cable with power applied to this module or the serial device on the other end of the cable, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Make sure that power is removed or the area is nonhazardous before proceeding.
Connect the 1756-CP3 serial cable to the controller’s serial port and to your workstation.
If you make your own cable, follow these guidelines.
Wire the connectors as shown.
Limit the cable length to 15.2 m (50 ft).
Attach the shield to both connectors.
26 Rockwell Automation Publication 1768-UM002C-EN-P - April 2012
Install the Controller Chapter 2
Use RSLinx software to configure the driver for serial communication.
1. From the Communications menu, choose Configure Drivers.
2. From the Available Driver Types pull-down menu, choose the RS-232
DF1 devices driver.
3. Click Add New.
4. Type a name for the driver and click OK.
5. From the Comm Port pull-down menu on the Configure Devices dialog
box, choose the serial port on the workstation to which your cable is connected.
6. From the Device pull-down menu, choose Logix5550/CompactLogix.
7. Click Auto-Configure.
a. Click OK if the Auto Configuration Successful dialog box appears. b. If the dialog box does not appear, go back to step 5
and verify that you
selected the correct comm port.
8. Click Close.
Rockwell Automation Publication 1768-UM002C-EN-P - April 2012 27
Chapter 2 Install the Controller
IMPORTANT
TIP

Update the Controller

The controllers ship without firmware. Controller firmware is packaged with RSLogix 5000 programming software. In addition, controller firmware is also available for download from the Rockwell Automation Technical Support website at: http://www.rockwellautomation.com/support/
.
When installing or updating controller firmware, do not interrupt the update process in any way. Interrupting the firmware update may result in an inoperable controller. Inoperable controllers must be returned to Rockwell Automation.
To install firmware, you can use any of the following.
Method Page
ControlFlash, version 8 or later, software that ships with RSLogix 5000 software 28 AutoFlash software that runs within RSLogix 5000 software 29 A 1784-CF64 or 1784-CF128 CompactFlash card with valid firmware already loaded 29
Updating your controller firmware via ControlFlash or AutoFlash software requires either a serial or other network connection to the controller.
Updating via an Ethernet connection is faster, but you must first install a 1768­ENBT Ethernet module to connect to the controller via the Ethernet network.
For information on installing, configuring, and operating a 1768-ENBT module, refer to the EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication ENET-UM001
.

Install Firmware via ControlFlash Software

1. Make sure the network is connected.
2. Start ControlFlash software.
3. When the Welcome dialog box appears, click Next.
4. Select the catalog number of the controller and click Next.
5. Expand the network until you see the controller.
If the required network is not shown, first configure a driver for that network in RSLinx software.
6. Select the controller and click OK.
7. Select the desired revision level and click Next.
8. To start the update, click Finish and then Yes.
9. The OK status indicator flashes red to show that the update is in progress.
The status box indicates when the update is complete and the OK status indicator is solid green.
10. Click OK.
11. Click Cancel and then Yes to close ControlFlash software.
28 Rockwell Automation Publication 1768-UM002C-EN-P - April 2012
Install the Controller Chapter 2
TIP

Install Firmware via AutoFlash Software

1. Make sure the network is connected.
2. Using RSLogix 5000 software, attempt a download to a controller project.
3. AutoFlash software launches if the required firmware is not loaded on the
controller.
4. Select the catalog number of the controller and click Next.
5. Expand the network until you see the controller.
If the required network is not shown, first configure a driver for that network in RSLinx software.
6. Select the controller and click OK.
7. Select the desired revision level and click Next.
8. To start the update, click Finish and then Yes.
9. The OK status indicator flashes red to show that the update is in progress.
The status box indicates when the update is complete and the OK status indicator is solid green.
10. Click OK.
11. Click Cancel and then Yes to close AutoFlash software.

Install Firmware via a CompactFlash Card

Follow these steps to use RSLogix 5000 software to store the controller program and firmware of an already-configured controller to the CompactFlash card. The firmware is automatically stored on your CompactFlash card when you store the program.
1. With the CompactFlash card installed on the configured controller, on the
Controller Properties dialog box, click the Nonvolatile Memory tab.
2. Click Load Image On Powerup to save to the card.
3. Remove the card and insert it into the controller onto which you want to
load the firmware and user program.
4. Start the new controller and the image stored on the CompactFlash card
loads.
Rockwell Automation Publication 1768-UM002C-EN-P - April 2012 29
Chapter 2 Install the Controller
IMPORTANT
Power
OUT
L1
L2/N
Off
Power
OUT
L1
L2/N
a.
b.
31607-M
Powe r
OUT
L1
L2/N
c.
d.
c.
a.

Remove a 1768 or 1769 Module from the DIN Rail

If you need to remove a module from the DIN rail, follow these steps.
1. Remove power from the controller and wait for all status indicators on the
power supply and controller to turn off.
If you disconnect any part of the system while the controller is still writing its program to memory, you will lose your program.
2. Remove the 1768 module.
30 Rockwell Automation Publication 1768-UM002C-EN-P - April 2012
Loading...
+ 106 hidden pages