The Visual KV Series User’s Manual is composed of 3 separate
manuals; 1-Installation, 2-Support Software, 3-Programming.
Please read each manual relevant to your purpose.
Page 2
Safety Precautions
This instruction manual describes the operation and function of the KV Series PLC.
Read this manual carefully to ensure safe use and maximum performance from your
KV Series PLC.
Symbols
The following symbols alert you to important messages. Be sure to read these
messages carefully.
Note:
Conventions
This manual describes the operation/function of all Keyence KV Series PLC.
Note following conventions when you use.
•At startup and during operation, be sure to monitor the functions and performance of the KV Sereis PLC.
WARNING
CAUTION
Failure to follow instructions may lead to injury. (electric
shock, burn, etc.)
Failure to follow instructions may lead to product damage.
Provides additional information on proper operation.
KV-300
•We recommend that you take substantial safety measures to avoid any damage
in the event a problem occurs.
•Do not open or modify the KV Series PLC or use it in any way other than described in the specifications.
•When the KV Series PLC is used in combination with other instruments, functions and performance may be degraded, depending on operating conditions and
the surrounding environment.
•Do not use the KV Series PLC for the purpose of protecting the human body.
Note: The built-in display may show the error message "Error 40" blinking the very
first time you turn on the power supply to the Visual KV Series. Press any key
around the display to cancel this message.
The Visual KV Series shows this message when no program is loaded.
(1)
Page 3
Note to User
When using the Visual KV Series in the following conditions or environments, be
sure to use the Visual KV Series with sufficient margin regarding the rating and
functions, take appropriate safety precautions such as fail-safe, and contact our
sales personnel if any questions arise.
•Use in conditions or environments not described in this manual
•Use for nuclear power control, railway facilities, air service facilities, vehicles,
combustion devices, medical equipment, amusement machines, safety equipment, etc.
•Use for applications where large effects are predicted to be given on human lives
and properties and safety is especially requested.
Restriction on Acquiring the CE Marking
■ Restriction to be compatible with EMC directives
•When using a relay output type unit (whose model name ends with "R"), connect
spark killers having the appropriate withstand voltage against the load to the
output terminals in parallel to contacts (because the unit discharges when a relay
contact becomes open and noise is generated). In our experiments, we use the
following models of spark killers.
XEB0101 0.1 µF-10 Ω manufactured by OKAYA DENKI SANGYO
The following 1-turn ferrite core is added to the AC power input circuit of the KV-
40AR/T, the KV-24AR/T and to the DC power input circuit of the KV-40DR/T.
ZCAT3035-1330 manufactured by TDK
Note: The contents above do not by themselves ensure that the entire machine
manufactured in accordance with the above contents is compatible with EMC
directives.
You must judge by yourself whether or not the entire machine is compatible with
EMC directives because compatibility may change depending on the component
configuration, wiring and location inside of the machine.
■ Restriction on compatibility with low-voltage directives (IEC-1010-1)
•Use insulated type crimp-style terminals.
•For wiring materials, use lead wires whose sheath is 0.4 mm or more.
•The Visual KV Series is allowed to be installed in a vertical position only.
(Spacers for expansion units are not available.)
•Be sure to use the Visual KV Series inside the control panel.
(2)
Page 4
Features of the Visual KV Series
● Extremely small
The Visual KV Series is the smallest in the world among AC type PLCs equipped
with screw terminal blocks, and saves installation space.
● Extremely fast
The minimum scan time is 140 µs and minimum instruction execution time is 0.7
µs, which is the fastest control in its class.
● AC power built-in type newly added
AC power built-in type units are newly added. This type can be used in small
spaces where a switching power supply unit cannot be installed.
● Excellent Access Window
An Access Window with two-color backlight is adopted in all models to facilitate
changing and monitoring of device data. Changing between RUN mode and
PROGRAM mode, checking the error code when an error has occurred, etc. can
be performed in a Visual KV Series unit without the need for any handheld
programmer.
The analog trimmer, which has been popular in the conventional KV Series, is
digitized to enable more detail settings. [Digital trimmers]
● User message setting function
In the Access Window, 256 different user messages can be displayed. This
function can be used to give instructions on works on the production line, indicate
abnormalities in the units, etc.
● Program write in RUN mode
Ladder programs can be changed even while the system is running.
● Equipped with two serial ports
Visual KV Series basic units are equipped with two serial ports to connect peripheral units, improving the debug environment.
(The KV-10xx is equipped with only one serial port.)
● Easy Ramp-up/down control function
The one-axis motor control function is offered separately from high-speed
counters so that feedback control is enabled.
● Equipped with two 24-bit high-speed 30 kHz, two-phase counters
The Visual KV Series is equipped with two high-speed counters each with a twopoint comparator output function that enables high-speed encoder input.
● Specified frequency pulse output function
High-speed counters can function as pulse oscillators of 50 kHz maximum with
easy setting, without creating a complicated ladder program.
● Frequency counter function
High-speed counters can function as frequency counters with easy setting,
without creating complicated ladder programs.
(3)
● Cam switch function
High-speed counters can function as cam switches with easy setting, without
creating complicated ladder programs.
Page 5
● Interrupt function
The Visual KV Series is equipped with four high-speed interrupt inputs of
10 µs maximum.
● Input time constant change function
The time constant can be set in 7 steps from 10 µs to 10 ms.
● Double memory backup functions
In addition to a conventional SRAM battery backup function, the Visual KV Series
is also equipped with an EEPROM backup function.
Compatibility with Conventional KV Series Peripheral Units
The Visual KV Series functions as a high-end compatible model of the conventional
KV Series. Peripheral units of the conventional KV Series such as the ladder support
software "KV IncrediWare (DOS)" and "LADDER BUILDER for KV" and the
handheld programmer KV-P3E(01) can be used since they are part of the Visual KV
Series.
However, it should be noted that the contents have changed as follows.
•The internal clock cycle of high-speed counters consists of three types: 1 µs, 10
µs, and 100 µs.
•The time constant for an input relay specified by the HSP instruction is 10 µs.
•The analog trimmer function is set with the Access Window built into the basic
unit.
•The available device setting range of the TMIN instruction is from 0 to 65535.
[Handheld programmer KV-P3E(01) can display 0 to 9999 .]
•The RUN/PROGRAM LED is displayed in the Access Window provided on the
front face of the basic unit.
•Transistor output is not independent, but is common.
•With the transistor type, the output terminal layout is different.
•The specifications for output current of transistor outputs Nos. 500 to 502 is 100
mA.
•Conventional KV Series expansion units are not available as expansion units for
the Visual KV Series.
• The channel setting switch is not provided for expansion units. Channels are
determined in connection order.
•Scans in expansion I/O units are not synchronous with the scan time in Visual KV
Series basic units.
•Assignment of special utility relays has partially changed.
•Data memory device Nos. DM1000 to DM1999 are assigned as special data
memories.
(4)
Page 6
Cautions when using the previous version of ladder support software
Pay strict attention to the following items when using the ladder support software.
•When using the ladder support software "KV IncrediWare (DOS)" or "LADDER
BUILDER for KV Ver. 1.0x", set the model to "KV-300".
•DM0 to DM1999 are only available.
CAUTION
When the ladder support software "LADDER BUILDER for KV Ver. 1.0x" is
used, do not use the monitor’s Change All function. If the Change All function
is used, the basic unit may be damaged. Never use the Change All function.
Peripheral units and other units incompatible with the Visual KV Series
Peripheral units in the conventional KV Series and other units shown below are not
compatible with the Visual KV Series.
•Expansion I/O units for the conventional KV Series: KV-8ER/8ET/8EX/16EX/
8EYR/8EYT/16EYR/16EYT
•Analog I/O units for the conventional KV Series: KV-AD4/DA4
Cautions when Using the Serial Port
The KV-16xx/24xx/40xx units are equipped with two RJ-11 modular connectors for
serial communication.
When using them, pay strict attention to the following contents:
•Programs can be transferred and monitored using either communication port A or
B. However, never connect the ladder software and a handheld programmer to
the two ports at the same time.
•The KV-D20 operator interface panel can be connected to either communication
port A or B. However, only one KV-D20 unit can be connected to a single basic
unit.
•Never leave both the KV-D20 operator interface panel and KV-P3E(01) handheld
programmer on simultaneously for a long period of time.
(5)
Page 7
(6)
Page 8
How this manual is organized
The Visual KV Series User’s Manual is composed of 3 separate manuals;
1-Installation, 2-Support Software, 3-Programming. Please read each manual
relevant to your purpose.
1
Installation
Chapter 1Configuration and Specifications [Visual KV Series Only]
Describes the system configuration of the Visual KV Series, the names and functions of
each part, and the specifications.
Chapter 2System Installation [Visual KV Series Only]
Describes the installation and connection of each Visual KV Series unit as well as
system maintenance.
Chapter 3Access Window [Visual KV Series Only]
Describes the Access Window used for changing and monitoring data.
Chapter 4KV-D20 Operator Interface Panel [Visual KV Series Only]
Describes the KV-D20 Operator Interface Panel used for changing, monitoring, and
displaying the status of inside relays, timers, counters and data memories.
Chapter 5KV-300, KV-10/80 Hardware [KV-300, KV-10/80 Series Only]
Describes the hardware specifications and wirings for KV-300 and KV-10/80 Series.
Chapter 6Handheld Programmer
Describes how to use the handheld programmer and memory card.
Chapter 7KV-L2 Serial Interface Module [KV-300 Series Only]
Describes the serial interface modules for KV-300 Series.
Chapter 8KV-AN6 Analog I/O Module [KV-300 Series Only]
Describes the optional Analog I/O module for KV-300 Series
Chapter 9KV-AD4/DA4 Analog I/O Unit [KV-10/80 Series Only]
Describes the optional Analog I/O unit for KV-10/80 Series.
Chapter 10Troubleshooting
This chapter describes the error code list, countermeasures against problems, and error
indications for each unit.
2
Support Software
Chapter 1Introduction
(7)
Appendices
The appendix includes a list of ladder program applications and the index.
Describes the items included in the package, the product outline, the method to connect
a personal computer, the installation method, etc.
Page 9
Chapter 2Editor
Chapter 3Simulator
Chapter 4Monitor
3
Programming
Chapter 1Programming
Chapter 2Instructions
Describes the operating procedures in Editor mode.
Describes the operating procedures in Simulator mode.
Describes the operating procedures in Monitor mode.
Appendices
Includes instructions list, devices list, sample program list and quick reference for key
operation and shortcuts.
Describes basic knowledge including program creation procedures, device configuration,
relay assignments, special functions to set and confirm Visual KV Series operations, as
well as the extended ladder diagrams. Understand the contents described here completely at first before creating programs.
Describes the concrete usage of instructions in the KV Series.
Refer to "Chapter 3 Interrupts" on page 3-183 for details of interrupt instructions.
Refer to "Chapter 4 High-speed counters" on page 3-195 for details of the high-speed
counters used in the application instruction.
Chapter 3Interrupts [Visual KV Series Only]
The interrupt processing function executes an interrupt program when an external input
or request from the high-speed counter comparator (interrupt factor) is encountered
during KV operation.
This chapter describes the types of interrupt factors as well as inputs and outputs
encountered during interrupt processing.
Chapter 4High-speed Counters [Visual KV Series Only]
Describes high-speed counters and high-speed counter comparators, which allow highspeed pulse measurement and pulse output, independent of the scan time.
Chapter 5Positioning Control [Visual KV Series Only]
Describes ramp-up/down control of stepping motors and servo motors.
Chapter 6
Interrupts, High-speed Counters, Positioning Control [KV-300, KV-10/80 Series Only]
Describes ramp-up/down control of stepping motors and servo motors.
Chapter 7Serial Communication
The KV Series can be connected to an external device with an RS-232C interface to
establish communication.
This chapter describes communications specifications, how to connect the KV Series to
external devices, and how to perform communication.
Chapter 8Programming Examples
Describes the typical programming examples for KV-10/80 Series. These programs can
be used for Visual KV Series. However, pay attention to the I/O addressing compatibility
before use.
(8)
Page 10
Contents
1
Installation
Chapter 1Configuration and SpecificationsVisual KV
•No part of this manual may be reprinted or reproduced in any form or by any
means without the prior written permission of KEYENCE CORPORATION.
•The content of this manual is subject to change without notice.
•KEYENCE has thoroughly checked and reviewed this manual. Please contact
the sales office listed at the end of this manual if you have any questions or
comments regarding this manual or if you find an error.
•KEYENCE assumes no liability for damages resulting from the use of the information in this manual, item 3 above notwithstanding.
•KEYENCE will replace any incomplete or incorrectly collated manual.
All company names and product names in this manual are registered trademarks or
trademarks of their respective owners.
(23)
Page 25
Chapter 1
Configuration and Specifications
This chapter describes the system configuration of the Visual KV Series, the
names and functions of each part, and the specifications.
For more about expanding the system by connecting expansion units, refer to "Connecting Visual KV
Series Expansion Units" (p.1-71).
KV-E4XR/E4XT(P)
KV-E8X/
E8R/E8T(P)
KV-E16X
E16R/E16T(P)
■ Conventional KV Series peripheral units
Personal computer
IBM PC/AT or
compatible machine
KV-P3E(01) Handheld
programmer
Z-1 Card reader/writer
* Available for the
KV-H4E only
Programming support software
KV-H4E [KV IncrediWare (DOS)]
KV-H6WE2
(LADDER BUILDER for KV Ver.1.5)
M2/M3 Memory card
1-2
Chapter 1 Configuration and Specifications
Page 27
1.1 System Configuration
WARNING
Extension cable for
expansion unit (300 mm)
For all expansion units
OP-35361
Expansion unit spacer
For 4-I/O expansion unit
OP-35342
For 8-I/O expansion unit
OP-35343
For 16-I/O expansion unit
OP-35344
Metal fixture for screw tightening
For 10-I/O basic unit OP-35345
For 16-I/O basic unit OP-35346
For 24-I/O basic unit OP-35347
For 40-I/O basic unit OP-35348
For 4- to 16-I/O expansion units
OP-35349
When the ladder support software "KV IncrediWare (DOS)" or "LADDER
BUILDER for KV Ver. 1.0x" is used, the Change All function on the monitor is
not available. Using the Change All function may damage the basic unit. Never
use the Change All function.
Series
Visual KV
1
1
Chapter 1 Configuration and Specifications
1-3
Page 28
1.2 Specifications
1.2Specifications
This section describes the general specifications and performance specifications for
the Visual KV Series units.
1. Includes the internal current consumption and current consumption of expansion units.
Note: The maximum output capacity available with the AC type service power
output is the output capacity of each basic unit subtracted by the internal current
consumption of the basic unit, connected expansion units, and connected peripheral
units.
Visual KV Series operation at power interruption
CDV42± %01
1.2 Specifications
A5.0:xA61-VKA4.0:xA01-VK
A7.0:xA04-VKA6.0:xA42-VK
A6.0:xA61-VKA4.0:xA01-VK
A7.0:xA04-VKA6.0:xA42-VK
W12:xA61-VKW41:xA01-VK
W42:xA04-VKW12:xA42-VK
,A51.3:tnerrucdetar,CAV042:egatlovdetaR
epytgnitlem-tsaF:scitsiretcarahC
Series
Visual KV
1
1
■ Drop in supply voltage
When the supply voltage drops, the Visual KV Series stops operating and the
output turns off.
■ Detection of instantaneous power interruption
•An AC type basic unit continues operating against instantaneous power interruption of less than 40 ms. A DC type basic unit continues operating against
instantaneous power interruption of less than 2 ms.
•An AC type basic unit may or may not accept instantaneous power interruption of
40 ms or more. A DC type basic unit may or may not accept instantaneous power
interruption of 2 ms or more.
•When accepting instantaneous power interruption, a basic unit stops operating
and the output turns off.
■ Automatic recovery
•Once the supply voltage recovers, the Visual KV Series restarts operation automatically.
Rated voltage
Rated voltage
Instantaneous power interruption:
Less than 40 ms
▲
Instantaneous power interruption:
40 ms or more
▲
▲
▲
Rated voltage
Rated voltage
Note: If the supply voltage increases gradually or drops, the Visual KV Series may
repeat operation and then stop. If problems continue to occur with equipment and
other operations from repetitive starts and stops, provide a protection circuit so that
the output shuts down until the voltage reaches the rated value.
■ Time until start of operation
•The time period from when the power is turned on until operation starts varies
depending on the conditions, including the supply voltage, system configuration,
and operating environment. The minimum time is approximately 1.2 ms.
•When a user program is changed, it will be saved in the EEPROM when the
power is next turned on. Therefore, in such a case, the time period from when the
power is turned on until operation starts is longer than usual.
1. When high-speed counters are set using the MEMSW instruction, 24-bit data can be
counted.
2. Comments cannot be handled in the handheld programmer KV-P3E(01).
3. The card reader/writer Z-1 can be used with the programming support software "KV
IncrediWare (DOS)".
4. When the programming support software "LADDER BUILDER for KV Ver. 1.0x" is used,
the Change All function on the monitor is not available. Using the Change All function may
damage the basic unit. Never use the Change All function.
Chapter 1 Configuration and Specifications
Page 31
Data backup function against instantaneous power interruption
■ Electrical double-layer capacitor built into the basic unit
Contents of data memories, current values of counters, and the contents of internal
utility relays in a Visual KV Series basic unit are saved in RAM backed up with an
electrical double-layer capacitor built into the Visual KV Series basic unit by the Data
backup function against instantaneous power interruption.
1.2 Specifications
The backup time varies depending on the ambient temperature.
If power to the Visual KV Series basic unit remains OFF for more than the holding
time by the RAM, the data may be cleared or become corrupted.
To avoid the data being cleared, save the data in the EEPROM using the backup
function to the EEPROM.
➮
For writing to and reading from the EEPROM, refer to "LOAD mode and SAVE mode" (p.1-96).
When a user program is written, it is saved in RAM. The next time the power is
turned on, the user program is automatically transferred from RAM to the EEPROM
and is also saved in the EEPROM. If power to the Visual KV Series basic unit will
remain OFF for more than the backup time by the RAM, turn the power off immediately after writing a user program, and then turn the power on again so that the user
program is transferred to the EEPROM.
•Data backup function by electrical double-layer capacitor built into the
basic unit
Visual KV Series: 2 months or more at 25°C (77°F)
(20 days or more at 25°C (77°F) in KV-10xx)
■ EEPROM
The Visual KV Series basic unit is equipped with a backup function to save programs, contents of data memories, current values of counters, etc. in the EEPROM.
Series
Visual KV
1
1
Even if the power is interrupted or power to the Visual KV Series basic unit remains
OFF, the data is still saved. When the power turns ON again, the contents of the
EEPROM is automatically read. (The contents of data memories and current values
of counters should be read by manipulating the Access Window.)
When data is changed and the power is turned off without saving the changed data,
the changes are saved only in the built-in electrical double-layer capacitor and are
not saved in the EEPROM.
If the Visual KV Series basic unit remains OFF for 2 months or more at 25°C (77°F)
(20 days or more at 25°C (77°F) in KV-10xx) while the data is backed up only with
the built-in electrical double-layer capacitor, the saved contents may be cleared or
become corrupted.
If the Visual KV Series basic unit will remain OFF for a long period of time, save the
data in the EEPROM.
➮
Refer to "LOAD mode and SAVE mode" (p.1-96).
•Data backup function with the EEPROM
Visual KV Series: 10 years or more at 25°C (77°F)
(available number of overwrites: 100,000 times or more)
Chapter 1 Configuration and Specifications
1-7
Page 32
1.3 Common I/O Specifications of Basic Units
1.3Common I/O Specifications of Basic
Units
This section describes the common I/O specifications of Visual KV Series basic
units. There are two types of basic units, AC power type and DC power type. Two
types of output types are offered: relay output and transistor output.
Series
Visual KV
1.3.1Model of a Basic Unit
■ Basic unit model designation
The model of a Visual KV Series basic unit is indicated as follows:
KV-10AR
Output type: R = relay output, T = transistor output
Power supply type: A = AC power type, D = DC power type
Number of I/O points: 10 = 10 points, 16 = 16 points,
■ Unit type
The following four types of Visual KV Series basic units are offered:
24 = 24 points, 40 = 40 points
1
AC power/relay output type: KV-10AR/16AR/24AR/40AR
AC power/transistor output type: KV-10AT(P)/16AT(P)/24AT(P)/40AT(P)
DC power/relay output type: KV-10DR/16DR/24DR/40DR
DC power/transistor output type: KV-10DT(P)/16DT(P)/24DT(P)/40DT(P)
1.3.2Common I/O Specifications
■ Input specifications
metIedomV42
gnitartupnimumixaMCDV4.62
egatlovtupnIAm3.5,CDV42Am0.1,CDV5
egatlovNOmuminiMV91V5.4
tnerrucFFOmuminiM
)egatlov(
dohtemnommoC.edisniderahssiMOC
tnatsnocemittupnI
esnopsertupnitpurretnI01 µ)evitatneserper(s
retnuocdeeps-hgiH
esnopsertupni
edomV5
ebnac700ot000stupnI(
).tupniV5otdegnahc
Am2V5.2
lacipytsm01
01 µdesusinoitcurtsniPSHnehws
01morfspets7nielbairaVµ ots
NOsi3182yalerytilitulaicepselihwsm01
)0491MDybteS(
V42(zHk03±)%05:ytud()%01
1-8
*For 5V±10%, refer to the 5 V mode response frequency characteristic chart (representa-
tive example).
5 V mode response frequency characteristic chart
Response
frequency
(kHz)
(representative example)
40
35
30
25
20
15
10
5
0
Chapter 1 Configuration and Specifications
5.55.45.35.25.154.94.84.74.6
Input voltage (V)
Page 33
1.3 Common I/O Specifications of Basic Units
■ Output specifications (relay output):
KV-10AR/DR, KV-16AR/DR, KV-24AR/DR, and KV-40AR/DR
This section describes the name and function of each part, the I/O specifications, the
terminal layout, circuit diagrams, and dimensions of the KV-10xx.
1.4.1Part Names and Functions
Series
Visual KV
1
1. Input terminal block
9. Input voltage
selector switch
Provided on side
24V
INPUT
001002 003004 005
000
C2
VOLT
5V
10. Communication
port A
3. Power input terminal
(Power input terminals for AC
power types are provided on
the lower side.)
For more about the Access Window, refer to "Chapter 3. Access Window" (p.1-79).
Chapter 1 Configuration and Specifications
Page 35
1.4 KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit)
1.4.2Terminal Layout Drawings and I/O Circuit Diagrams
KV-10AR/DR (Relay output type)
■ Terminal layout drawing
000 001 002 003 004 005
C1 C2
501 502
Series
Visual KV
■ Input circuit diagram
Internal circuit
005
Blue
004
Blue
002003
Blue
24V 0V 500 C3 C4 503
C1
C2
001
000
Blue
Blue
Blue
000 to 005
C1
C2
4.3KΩ
24V/5V
selector
circuit
Photocoupler
insulation
1
1
Internal circuit
Black
type
Three-wire
Brown
Black
Brown
type
Three-wire
Brown
Black
type
Three-wire
Sensor
Brown
Brown
Black
type
Three-wire
Black
type
Three-wire
Black
type
Three-wire
Brown
Chapter 1 Configuration and Specifications
1-11
Page 36
1.4 KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit)
■ Output circuit diagram
Series
Visual KV
1
Internal circuit
501
C35000V24V
C4
502
503
Internal circuit
• C3 and C4 are each independent.
500
501 to 503
C3
C4
1-12
Chapter 1 Configuration and Specifications
Page 37
KV-10AT(P)/DT(P) (Transistor output type)
■ Terminal layout drawing
000 001 002 003 004 005
C1 C2
24V 0V 500 C3 C4 503
1.4 KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit)
Series
Visual KV
501 502
■ Input circuit diagram
Internal circuit
005
Black
Three-wire
Blue
type
004
Brown
Black
Blue
Brown
type
Three-wire
Blue
Black
type
Three-wire
002003
Brown
C2
Blue
Black
type
Three-wire
001
Brown
Black
C1
000
Blue
Brown
Black
type
Three-wire
Blue
Brown
type
Three-wire
000 to 005
1
1
4.3KΩ
24V/5V
selector
circuit
C1
C2
Photocoupler
insulation
Internal circuit
Sensor
Chapter 1 Configuration and Specifications
1-13
Page 38
1.4 KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit)
■ Output circuit diagram
Internal circuit
Series
Visual KV
501
502
500
0V24V
R502
C3
*
* For KV-10ATP/DTP
NPN
Insulating
power
1
supply
Internal
circuit
• 1.6 kΩ current limiting resistor is built in R502
(to connect a motor driver).
1
1.6kΩW
2
1.4.3AC Power Input (KV-10AR/AT(P))
503
R502
500 to 503
C3
PNP
C3
Internal circuit
Insultating
power
supply
• 1.6 kΩ current limiting resistor is built in R502
(to connect a motor driver).
1.6 kΩW
500 to 503
R502
1
2
L
L
~
N
N
AC100V-240V 0.4A
50/60Hz
FG
1-14
Chapter 1 Configuration and Specifications
Page 39
110
100
90
80
70
60
50
40
30
20
10
0
86%
79%
64%
L=Max.
L=0,1/2Max.
L=Max.
47 48
(116.0)(118.4)
45 (113)
30 35 40 45 50
(86)
(95) (104) (113) (122)
1.4 KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit)
1.4.4Relationship between Continuous Simultaneous ON
Ratio and Ambient Temperature
CAUTION
If the number of I/O points which turn ON at the same time exceeds the
specifications range, the unit may be damaged.
The graphs below show the relationship between the ambient temperature and
the continuous simultaneous ON ratio.
Load current L:
(AC power output
capacity at 400 mA)
(Individual current consumption
–
when KV-D20 is connected)
Derating when KV-10AR is mounted upward
110
100
90
80
70
60
50
40
30
ON ratio (%)
20
Individual unit
10
Continuous simultaneous
With expansion unit
0
30 35 40 45 50
(86) (95) (104) (113) (122)
Ambient temperature [°C]
[°F] for figure in ( ).
39
(102.2)41(105.8)42(107.6)
L=0
L=1/2Max.
L=Max.
L=1/2Max.
L=Max.
L=0
44 (111.2)
46 (114.8)
(120.2)
63%
38%
25%
49
Derating when KV-10AT(P) is mounted upward
110
100
90
80
70
60
50
40
30
ON ratio (%)
20
Individual unit
With expansion unit
10
Continuous simultaneous
0
30 35 40 45 50
(86)
Ambient temperature [°C]
[°F] for figure in ( ).
Derating when KV-10DR is mounted upward
110
100
90
80
70
60
50
40
30
ON ratio (%)
20
Individual unit
10
With expansion unit
0
Continuous simultaneous
Derating when KV-10DT(P) is mounted upward
110
100
ON ratio (%)
Continuous simultaneous
30 35 40 45 50
(86)
Ambient temperature [°C]
[°F] for figure in ( ).
90
80
70
60
50
40
30
20
Individual unit
With expansion unit
10
0
30 35 40 45 50
(86)
Ambient temperature [°C]
[°F] for figure in ( ).
41 43 46 47
(105.8)(109.4)(114.8)(116.6)
L=0
L=1/2Max.
L=Max.
L=0
(95) (104) (113) (122)
45 (113)
(95) (104) (113) (122)
49 (120.2)
(95) (104) (113) (122)
86%
68%
60%
30%
58%
88%
Chapter 1 Configuration and Specifications
Derating when KV-10AR is mounted in front
ON ratio (%)
Continuous simultaneous
Derating when KV-10AT(P) is mounted in front
ON ratio (%)
Continuous simultaneous
Derating when KV-10DR is mounted in front
110
100
ON ratio (%)
Continuous simultaneous
Derating when KV-10DT(P) is mounted in front
ON ratio (%)
Continuous simultaneous
(Service power
=
output current)
Individual unit
With expansion unit
Ambient temperature [°C]
[°F] for figure in ( ).
110
100
90
80
70
60
50
40
30
20
Individual unit
10
With expansion unit
0
30 35 40 45 50
(86) (95) (104) (113) (122)
Ambient temperature [°C]
[°F] for figure in ( ).
90
80
70
60
50
40
30
20
Individual unit
10
With expansion unit
0
30 35 40 45 50
(86)
Ambient temperature [°C]
[°F] for figure in ( ).
110
100
90
80
70
60
50
40
30
20
Individual unit
10
With expansion unit
0
30 35 40 45 50
(86)
Ambient temperature [°C]
[°F] for figure in ( ).
(Expansion
+
unit current
consumption)
48 (118.4)
(95) (104) (113) (122)
(95) (104) (113) (122)
1-15
80%
Series
Visual KV
1
1
Page 40
1.4 KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit)
1.4.5Dimensions
■ Main unit
Front viewSide view (KV-10AR/AT(P))Side view (KV-10DR/DT(P))
24.5
9.9
Series
Visual KV
4.1
17
35.490
35.490
55
Bottom view (KV-10AR/AT(P))
17.5
2270
43.8
2243
43.8
1
20.5
■ Metal fixture for screw tightening
4-ø5.0
(Mounting hole)
Main unit
mounting hole*
(2 positions)
11199
1-16
40
54
* Two M3.5 countersunk-head screws are
included for mounting the main unit.
Chapter 1 Configuration and Specifications
t=2
Page 41
1.5 KV-16AR/AT(P)/DR/DT(P) (16-I/O Basic Unit)
1.5KV -16AR/AT(P)/DR/DT(P) (16-I/O Basic Unit)
This section describes the name and function of each part, the I/O specifications, the
terminal layout, circuit diagrams, and dimensions of the KV-16xx.
1.5.1Part Names and Functions
1. Input terminal block
9. Input voltage selector switch
Provided on side
24V
INPUT
VOLT
5V
10.Communication
port A
C1001003 005 007 009
000
0ch
0123456789
IN
008006004002
4. Input indicator lamps
5. Output indicator lamps
6. Connector
(provided on side)
7. Access Window
Series
Visual KV
11. Communication
port B
3. Power input terminal
(Power input terminals for
AC power type are provided
on the lower side.)
1.5.2Terminal Layout Drawings and I/O Circuit Diagrams
KV-16AR/DR (Relay output type)
■ Terminal layout drawing
C1 001 003 005 007 009
Series
Visual KV
1
000 002 004 006 008
500 501 502 504
24V 0V C3 C4 503 505
■ Input circuit diagram
Internal circuit
008
Black
Brown
007
Blue
Black
Brown
type
Three-wire
Blue
type
Three-wire
009
Blue
Black
type
Three-wire
Circuit configuration of inputs 000 to 007
000 to 007
4.3KΩ
selector
C1
Photocoupler
insulation
24V/5V
circuit
006
Black
Brown
005
Blue
Black
Brown
type
Three-wire
Sensor
004002000
003
Blue
Blue
Blue
Blue
Black
Black
Brown
type
Three-wire
Brown
type
Three-wire
Black
Brown
type
Three-wire
type
Three-wire
Circuit configuration of inputs 008 to 009
008 to 009
C1
Internal circuit
001
Black
Brown
Blue
Black
Brown
type
Three-wire
4.3KΩ
510Ω
C1
Blue
Brown
type
Three-wire
Photocoupler
insulation
Internal circuit
1-18
Chapter 1 Configuration and Specifications
Page 43
■ Output circuit diagram
1.5 KV-16AR/AT(P)/DR/DT(P) (16-I/O Basic Unit)
Internal circuit
Internal circuit
501
500502504
• C3 and C4 are each independent.
0V
24V
C4
C3503505
500 to 501
502 to 505
C3
C4
Series
Visual KV
1
1
Chapter 1 Configuration and Specifications
1-19
Page 44
1.5 KV-16AR/AT(P)/DR/DT(P) (16-I/O Basic Unit)
KV-16AT(P)/DT(P) (Transistor output type)
■ Terminal layout drawing
Series
Visual KV
C1 001 003 005 007 009
000 002 004 006 008
24V 500 501 502 504
24V 0V C3
1
■ Input circuit diagram
R502
503 505
Internal circuit
009
Black
Blue
008
Brown
Black
Blue
007
Black
Brown
Blue
006
Black
Brown
Blue
004002000
005
Black
Brown
Blue
Black
Brown
Blue
003
Black
Brown
Blue
Brown
Black
Blue
001
Black
Brown
Blue
Black
Brown
C1
Blue
Brown
1-20
type
type
Three-wire
Three-wire
type
Three-wire
Three-wire
Circuit configuration of inputs 000 to 007
24 V/5 V
selector
circuit
Photocoupler
insulation
000 to 007
4.3KΩ
C1
Chapter 1 Configuration and Specifications
type
type
Three-wire
Sensor
Internal circuit
type
type
type
type
Three-wire
Three-wire
Three-wire
Three-wire
type
Three-wire
Circuit configuration of inputs 008 to 009
008 to 009
4.3 kΩ
510 Ω
C1
Photocoupler
insulation
Internal circuit
Page 45
■ Output circuit diagram
Insultating
power
supply
Internal circuit
500 to 505
C3
R502
1.6 kΩW
1
2
24V
500502
1.5 KV-16AR/AT(P)/DR/DT(P) (16-I/O Basic Unit)
Internal circuit
501
504
Series
Visual KV
R502
C3
503
*
* For KV-16ATP/DTP
NPN
Insulating
power
supply
Internal
circuit
• A current limiting resistor 1.6 kΩ is built in R502
(to connect a motor driver).
1
1.6kΩW
2
R502
500 to 505
C3
• A current limiting resistor 1.6 kΩ is built in R502
1.5.3AC Power Input (KV-16AR/AT(P))
5050V24V
PNP
(to connect a motor driver).
1
1
L
L
~
N
N
AC100V-240V
0.5A 50/60Hz
FG
Chapter 1 Configuration and Specifications
1-21
Page 46
1.5 KV-16AR/AT(P)/DR/DT(P) (16-I/O Basic Unit)
1.5.4Relationship between Continuous Simultaneous ON
Ratio and Ambient Temperature
Series
Visual KV
1
CAUTION
If the number of I/O points which turn ON at the same time exceeds the specifications range, the unit may be damaged.
The graphs below show the relationship between the ambient temperature and the
continuous simultaneous ON ratio.
Load current L:
(AC power output
capacity at 600 mA)
(Individual current consumption
–
when KV-D20 is connected)
Derating when KV-16AR is mounted upward
Supply voltage: 100 to 240 V
110
100
90
80
70
60
50
40
30
ON ratio (%)
20
10
0
Continuous simultaneous
Ambient temperature [°C]
[°F] for figure in ( ).
36 37
(96.8)(98.6)
40 (104)
35 (95)
L=1/2Max.
L=Max.
Individual unit
With expansion unit
30 35 40 45 50
(86)
(95) (104) (113) (122)
39
(102.2)
L=0
L=1/2Max.
L=Max.
41 (105.8)
L=0
49
(120.2)
50%
44%
38%
18%
13%
Derating when KV-16AT(P) is mounted upward
Supply voltage: 100 to 240 V
110
100
90
80
70
60
50
40
ON ratio (%)
30
20
Continuous simultaneous
Derating when KV-16DR is mounted upward
ON ratio (%)
Continuous simultaneous
Derating when KV-16DT(P) is mounted upward
ON ratio (%)
Continuous simultaneous
Individual unit
With expansion unit
10
0
Ambient temperature [°C]
[°F] for figure in ( ).
110
100
90
80
70
60
50
40
30
20
Individual unit
10
With expansion unit
0
110
100
90
80
70
60
50
40
30
20
Individual unit
With expansion unit
10
0
36 37
(96.8)(98.6)
40 (104)
41(105.8)
35 (95)
L=1/2Max.
L=Max.
30 35 40 45 50
(86)
30 35 40 45 50
(86)
Ambient temperature [°C]
[°F] for figure in ( ).
30 35 40 45 50
(86)
Ambient temperature [°C]
[°F] for figure in ( ).
39
(102.2)
L=0
L=1/2Max.
L=Max.
(95) (104) (113) (122)
43 (109.4) 47 (116.6)
(95) (104) (113) (122)
43 (109.4) 47 (116.6)
(95) (104) (113) (122)
L=0
49
(120.2)
50%
44%
38%
18%
13%
75%
50%
75%
50%
Derating when KV-16AR is mounted in front
Continuous simultaneous
Derating when KV-16AT(P) is mounted in front
Continuous simultaneous
Derating when KV-16DR is mounted in front
Continuous simultaneous
Derating when KV-16DT(P) is mounted in front
Continuous simultaneous
(Service power
=
output current)
110
100
90
80
70
60
50
40
ON ratio (%)
30
20
10
0
110
100
90
80
70
60
50
40
ON ratio (%)
30
20
10
0
110
100
90
80
70
60
50
40
30
ON ratio (%)
20
10
0
110
100
90
80
70
60
50
40
ON ratio (%)
30
20
10
0
(Expansion
+
unit current
consumption)
Supply voltage: 100 to 240 V
L=0, 1/2Max.
Individual unit
With expansion unit
30 35 40 45 50
(86)
(95) (104) (113) (122)
Ambient temperature [°C]
[°F] for figure in ( ).
L=0, 1/2Max.
Individual unit
With expansion unit
30 35 40 45 50
(86)
(95) (104) (113) (122)
Ambient temperature [°C]
[°F] for figure in ( ).
Individual unit
With expansion unit
30 35 40 45 50
(86)
(95) (104) (113) (122)
Ambient temperature [°C]
[°F] for figure in ( ).
Individual unit
With expansion unit
30 35 40 45 50
(86)
(95) (104) (113) (122)
Ambient temperature [°C]
[°F] for figure in ( ).
44
(111.2)47(116.6)49(120.2)
L=0, 1/2Max.
L=Max.
L=Max.
Supply voltage: 100 to 240 V
L=0, 1/2Max.
L=Max.
L=Max.
46 (114.8)
47
44
(116.6)
(111.2)
46 (114.8)
44 (111.2) 49 (120.2)
44 (111.2) 49 (120.2)
49
(120.2)
91%
75%
66%
50%
91%
75%
66%
50%
93%
58%
93%
58%
1-22
Chapter 1 Configuration and Specifications
Page 47
1.5.5Dimensions
2243
35.490
43.8
2270
35.490
43.8
20.5
17.5
65
4.1
17
13.3
24.5
■ Main unit
1.5 KV-16AR/AT(P)/DR/DT(P) (16-I/O Basic Unit)
Front view
Bottom view of AC type
Side view (KV-16AR/AT(P))Side view (KV-16DR/DT(P))
Series
Visual KV
1
1
■ Metal fixture for screw tightening
Main unit
mounting hole
(2 positions)
31
50
64
* Two M3.5 countersunk-head screws are
included for mounting the main unit.
6-ø5.0
(Mounting
hole)
11199
t=2
Chapter 1 Configuration and Specifications
1-23
Page 48
1.6 KV-24AR/AT(P)/DR/DT(P) (24-I/O Basic Unit)
1.6KV -24AR/AT(P)/DR/DT(P) (24-I/O Basic Unit)
This section describes the name and function of each part, the I/O specifications, the
terminal layout, circuit diagrams, and dimensions of the KV-24xx.
1.6.1Part Names and Functions
1. Input terminal block
Series
Visual KV
1
9. Input voltage
selector switch
Provided on side
24V
INPUT
VOLT
5V
10.Communication
port A
11.Communication
port B
3. Power input terminal
(Power input terminals for AC
power type are provided on
the lower side.)
1.6.2Terminal Layout Drawings and I/O Circuit Diagrams
KV-24AR/DR (Relay output type)
■ Terminal layout drawing
C1 001 003 005 007 009 011 013 015
000 002 004 006 008 010 012 014
24V 0VC3 C4 C5 C6 505 507
■ Input circuit diagram
500 501 502 503 504 506
Internal circuit
Series
Visual KV
1
1
Blue
Black
type
Three-wire
Black
Brown
013
Blue
Black
Brown
type
Three-wire
000 to 007
008
009011015
Blue
Blue
Blue
Blue
Blue
Black
Black
Black
Black
Brown
type
Three-wire
Brown
type
Three-wire
Brown
type
Three-wire
type
Three-wire
Brown
Black
Brown
type
Three-wire
Three-wire
Sensor
Circuit configuration of inputs 000 to 007
24V/5V
selector
circuit
Photocoupler
insulation
4.3KΩ
C1
007
Blue
Blue
Black
Brown
type
Three-wire
Internal circuit
type
006
Black
Brown
005
Blue
Black
Brown
type
Three-wire
004002000010012014
Black
Brown
001
Blue
Black
Brown
type
Three-wire
Blue
Black
Brown
type
Three-wire
Blue
Black
Brown
type
Three-wire
003
Blue
Black
Brown
type
Three-wire
Blue
type
Three-wire
Circuit configuration of inputs 008 to 015
008 to 015
4.3KΩ
510Ω
C1
Photocoupler
insulation
C1
Blue
Brown
type
Three-wire
Internal circuit
Chapter 1 Configuration and Specifications
1-25
Page 50
1.6 KV-24AR/AT(P)/DR/DT(P) (24-I/O Basic Unit)
■ Output circuit diagram
Series
Visual KV
Internal circuit
503
502504506
501500
0V
24V
C4C3
C6
C5505507
1
500
501
502 to 503
504 to 507
C3
C4
C5
C6
• C3 to C6 are each independent.
1-26
Chapter 1 Configuration and Specifications
Page 51
KV-24AT(P)/DT(P) (Transistor output type)
■ Terminal layout drawing
C1 001 003 005 007 009 011 013 015
000 002 004 006 008 010 012 014
V1 V2 500 501 502 503 504 506
1.6 KV-24AR/AT(P)/DR/DT(P) (24-I/O Basic Unit)
Series
Visual KV
Blue
■ Input circuit diagram
013
Blue
Blue
Blue
Blue
24V 0V C3
Internal circuit
009011015
Blue
Blue
008
Blue
R500 R501 R502
006
007
Blue
Blue
V3 505 507
004002000010012014
005
Blue
Blue
003
Blue
Blue
001
Blue
Blue
1
1
C1
Black
type
Three-wire
Black
Brown
Black
Brown
type
Three-wire
000 to 007
Black
Black
Black
Black
Brown
type
Three-wire
Brown
type
Three-wire
Brown
type
Three-wire
type
Three-wire
Brown
Black
Brown
type
Three-wire
Three-wire
Circuit configuration of inputs 000 to 007
Photocoupler
4.3 kΩ
24V/5V
selector
circuit
C1
insulation
Chapter 1 Configuration and Specifications
Black
Brown
type
Three-wire
Sensor
Internal circuit
type
Black
Brown
Black
Brown
type
Three-wire
Black
Black
Black
Black
Brown
type
Three-wire
Brown
type
Three-wire
Brown
type
Three-wire
Brown
type
Three-wire
Black
Brown
type
Three-wire
Circuit configuration of inputs 008 to 015
008 to 015
4.3 kΩ
510Ω
C1
Photocoupler
insulation
Brown
type
Three-wire
Internal circuit
1-27
Page 52
1.6 KV-24AR/AT(P)/DR/DT(P) (24-I/O Basic Unit)
■ Output circuit diagram
Series
Visual KV
V1
Internal circuit
V2
500
501
502
503
504
506
R500
C30V24V
*
* For KV-24ATP/DTP
1
Insulating
power
supply
1
1.6 kΩW
2
Internal
circuit
• A 1.6 kΩ current limiting resistor is built in each of
R500 to R502 (to connect a motor driver).
• V1 to V3 are short-circuited inside (so they can
be used as a relay terminal block).
1.6.3AC Power Input (KV-24AR/AT(P))
R5O1
R500
to R502
500
to 507
C3
R502
V3
505
507
PNPNPN
C3
Internal circuit
Insultating
power
supply
1.6 kΩW
• A 1.6 kΩ current limiting resistor is built in each of
R500 to R502 (to connect a motor driver).
• V1 to V3 are short-circuited inside (so they can
be used as a relay terminal block).
1
2
500 to 507
R500 to R502
1-28
L
~
L
AC100V-240V
0.6A 50/60Hz
Chapter 1 Configuration and Specifications
N
N
FG
Page 53
1.6 KV-24AR/AT(P)/DR/DT(P) (24-I/O Basic Unit)
1.6.4Relationship between Continuous Simultaneous ON
Ratio and Ambient Temperature
CAUTION
If the number of I/O points which turn ON at the same time exceeds the specifications range, the unit may be damaged.
The graphs below show the relationship between the ambient temperature and the
continuous simultaneous ON ratio.
Load current L:
(AC power output
capacity at 600 mA)
(Individual current consumption
–
when KV-D20 is connected)
Derating when KV-24AR is mounted upward
110
29°C
100
90
80
70
60
50
40
ON ratio (%)
30
20
Continuous simultaneous
10
0
32°C 33°C
31°C
Individual unit
With expansion unit
30 35 40 45 50
34°C
L=0
L=1/2Max.
L=Max.
L=0
L=1/2Max.
L=Max.
11%
6%
Ambient temperature (°C)
Derating when KV-24AT(P) is mounted upward
110
29°C 31°C
100
90
80
70
60
50
40
ON ratio (%)
30
20
Individual unit
10
Continuous simultaneous
With expansion unit
0
36°C 37°C
L=0
L=1/2Max.
L=Max.
38°C
L=0
L=1/2Max.
L=Max.
35°C
30 35 40 45 50
Ambient temperature (°C)
45%
38%
19%
6%
Derating when KV-24AR is mounted in front
ON ratio (%)
Continuous simultaneous
Derating when KV-24AT(P) is mounted in front
ON ratio (%)
Continuous simultaneous
(Service power
=
output current)
110
100
90
80
70
60
50
40
30
20
Individual unit
10
With expansion unit
0
30 35 40 45 50
Ambient temperature (°C)
110
100
90
80
70
60
50
40
30
20
10
0
L=0, 1/2Max.
Individual unit
With expansion unit
30 35 40 45 50
Ambient temperature (°C)
37°C40°C
L=0 to Max.
40°C
L=Max.
L=0, 1/2Max.
L=Max.
(Expansion
+
unit current
consumption)
L=0 to Max.
43°C 44°C
48°C
56%
44%
88%
72%
63%
50%
Series
Visual KV
1
1
Derating when KV-24DR is mounted upward
110
100
90
80
70
60
50
40
ON ratio (%)
30
20
10
Continuous simultaneous
30°C35°C
Individual unit
With expansion unit
0
30 35 40 45 50
Ambient temperature (°C)
42%
16%
Derating when KV-24DT(P) is mounted upward
110
100
90
80
70
60
50
40
ON ratio (%)
30
20
Individual unit
10
Continuous simultaneous
With expansion unit
0
30 35 40 45 50
Ambient temperature (°C)
47°C
91%
79%
Derating when KV-24DR is mounted in front
110
100
90
80
70
60
50
40
ON ratio (%)
30
20
Individual unit
10
Continuous simultaneous
With expansion unit
0
30 35 40 45 50
Ambient temperature (°C)
37°C43°C
Derating when KV-24DT(P) is mounted in front
110
100
90
80
70
60
50
40
ON ratio (%)
30
20
Individual unit
10
Continuous simultaneous
With expansion unit
0
30 35 40 45 50
Ambient temperature (°C)
47°C
67%
44%
91%
79%
Chapter 1 Configuration and Specifications
1-29
Page 54
1.6 KV-24AR/AT(P)/DR/DT(P) (24-I/O Basic Unit)
1.6.5Dimensions
■ Main unit
Front viewSide view (KV-24AR/AT(P))Side view (KV-24DR/DT(P))
31
5.2
Series
Visual KV
20.5
35.490
35.490
80
Bottom view (KV-24AR/AT(P))
17.5
2270
43.8
2243
43.8
1
20.5
■ Metal fixture for screw tightening
6-ø0.5
(Mounting
hole)
Main unit
mounting hole*
(2 positions)
11199
1-30
48
66
79
* Two M3.5 countersunk-head screws are
included for mounting the main unit.
Chapter 1 Configuration and Specifications
t = 2
Page 55
1.7 KV-40AR/AT(P)/DR/DT(P) (40-I/O Basic Unit)
01234567
0123456789
10 11 12 13 14 15
5ch
8 9 10 11 12 13 14 15
0ch
01234567
1ch
C1001003 005 007 009
008006004002
KV-40AR
24V-OUT-OV
000
C3C4C5C6
500501 502 503504
505 507509511513C8515
506508 510512514
013011015
014012010
103101105 107
104 106102100
IN
OUT
C7
24V
5V
INPUT
VOLT
AC100V-240V
0.7A 50/60Hz
L
~
N
1.7KV-40AR/AT(P)/DR/DT(P) (40-I/O Basic Unit)
This section describes the name and function of each part, the I/O specifications, the
terminal layout, circuit diagrams, and dimensions of the KV-40xx.
1.7.1Part Names and Functions
1. Input
terminal
block
4. Input
indicator
lamps
5. Output
indicator
lamps
6. Connector
(provided
on side)
Series
Visual KV
9. Input voltage selector
switch
Provided on side
10.Communication
port A
11.Communication
port B
3. Power input terminal
(Power input terminals for
AC power type are provided
on the lower side.)
• A 1.6 kΩ current limiting resistor is built in each
of R500 to R502 (to connect a motor driver).
• V1 to V3 are short-circuited inside (so they can
be used as a relay terminal block).
1
1.6 kΩW
2
R500
to R502
500
to 515
C3
506
508
507
510
509
512
511
PNP
Internal circuit
Insultating
power
supply
• A 1.6 kΩ current limiting resistor is built in each
of R500 to R502 (to connect a motor driver).
• V1 to V3 are short-circuited inside (so they can
be used as a relay terminal block).
1.6 kΩW
513
1
2
514
515
C3
500 to 515
R500 to R502
Series
Visual KV
1
1
1.7.3AC Power Input (KV-40AR/AT(P))
L
L
AC100V-240V
0.7A 50/60Hz
~
N
N
FG
Chapter 1 Configuration and Specifications
1-35
Page 60
1.7 KV-40AR/AT(P)/DR/DT(P) (40-I/O Basic Unit)
1.7.4Relationship between Continuous Simultaneous ON
Ratio and Ambient Temperature
Series
Visual KV
1
CAUTION
If the number of I/O points which turn ON at the same time exceeds the specifications range, the unit may be damaged.
The graphs below show the relationship between the ambient temperature and the
continuous simultaneous ON ratio.
Load current L:
(AC power output
capacity at 700 mA)
(Individual current consumption
–
when KV-D20 is connected)
Derating when KV-40AR is mounted upward
Supply voltage: 100 to 240 V
110
100
90
80
70
60
50
40
30
ON ratio (%)
20
10
Continuous simultaneous
0
33 34
(91.4)(93.2)
32 (89.6)
Individual unit
With expansion unit
30 35 40 45
(86)
Ambient temperature [°C]
[°F] for figure in ( ).
35 (95)
L=1/2Max. Max
L=0
L=1/2Max.
L=Max.
(95) (104) (113)
L=0
48
(118.4)
49
(120.2)
Derating when KV-40AT(P) is mounted upward
Supply voltage: 100 to 240 V
110
100
90
80
70
60
50
40
ON ratio (%)
30
20
10
Continuous simultaneous
0
Derating when KV-40DR is mounted upward
110
100
90
80
70
60
50
40
ON ratio (%)
30
20
Continuous simultaneous
10
0
33 34
(91.4)(93.2)
27 (80.6)
31
(87.8)
Individual unit
With expansion unit
30 35 40 45 50
(86)
Ambient temperature [°C]
[°F] for figure in ( ).
33 (91.4) 36 (96.8)
Individual unit
With expansion unit
30 35 40 45 50
(86)
Ambient temperature [°C]
[°F] for figure in ( ).
35 (95)
L=0
L=1/2Max.
L=Max.
(95) (104) (113) (122)
(95) (104) (113) (122)
L=0
L=1/2Max.
L=Max.
49
(120.2)
Derating when KV-40DT(P) is mounted upward
110
100
90
80
70
60
50
40
ON ratio (%)
30
20
Continuous simultaneous
Individual unit
10
With expansion unit
0
30 35 40 45 50
(86)
Ambient temperature [°C]
[°F] for figure in ( ).
40 (104)36 (96.8)
49
(95) (104) (113) (122)
(120.2)
33%
27%
6%
38%
27%
53%
34%
54%
30%
Derating when KV-40AR is mounted in front
ON ratio (%)
Continuous simultaneous
Derating when KV-40AT(P) is mounted in front
ON ratio (%)
Continuous simultaneous
Derating when KV-40DR is mounted in front
ON ratio (%)
Continuous simultaneous
Derating when KV-40DT(P) is mounted in front
ON ratio (%)
Continuous simultaneous
=
110
100
90
80
70
60
50
40
30
20
10
0
110
100
90
80
70
60
50
40
30
20
10
0
110
100
90
80
70
60
50
40
30
20
10
0
110
100
90
80
70
60
50
40
30
20
10
0
(Service power
output current)
(Expansion
+
unit current
consumption)
39 40
(102.2)(104)
37 (98.6)
L=1/2Max.
L=Max.
Individual unit
With expansion unit
30 35 40 45 50
(86)
(95) (104) (113) (122)
Ambient temperature [°C]
[°F] for figure in ( ).
L=1/2Max.
Individual unit
With expansion unit
30 35 40 45 50
(86)
(95) (104) (113) (122)
Ambient temperature [°C]
[°F] for figure in ( ).
Individual unit
With expansion unit
30 35 40 45 50
(86)
(95) (104) (113) (122)
Ambient temperature [°C]
[°F] for figure in ( ).
Individual unit
With expansion unit
30 35 40 45 50
(95) (104) (113) (122)
(86)
Ambient temperature [°C]
[°F] for figure in ( ).
44 45
(111.2) (113)
41
(105.8)
L=0
L=1/2Max.
L=Max.
45
43
41
(113)
(109.4)
(105.8)
44
(111.2)
L=0
L=Max.
L=0
L=1/2Max.
L=Max.
42 (107.6) 46 (114.8)
(120.2)
48 (118.4)44 (111.2)
L=0
75%
70%
55%
16%
8%
4846
(118.4)(114.8)
90%
83%
75%
50%
41%
49
80%
60%
87%
62.5%
1-36
Chapter 1 Configuration and Specifications
Page 61
1.7.5Dimensions
2243
35.490
43.8
2270
35.490
43.8
20.5
17.5
110
20.5
20.2
31
■ Main unit
Bottom view (KV-40AR/AT(P))
1.7 KV-40AR/AT(P)/DR/DT(P) (40-I/O Basic Unit)
Front viewSide view (KV-40AR/AT(P))Side view (KV-40DR/DT(P))
Series
Visual KV
■ Metal fixture for screw tightening
Main unit
mounting hole*
(2 positions)
* Two M3.5 countersunk-head screws
are included for mounting the main unit.
78
109
4-ø5.0
(Mounting
hole)
11199
t=2
1
1
Chapter 1 Configuration and Specifications
1-37
Page 62
1.8 KV-E4X/E8X/E16X (Expansion Input Unit)
1.8
KV-E4X/E8X/E16X (Expansion Input Unit)
This section describes the name and function of each part, the input specifications,
the terminal layout, circuit diagrams, and dimensions of three types of expansion
input units.
This section describes the name and function of each part, the output specifications,
the terminal layout, circuit diagrams, and dimensions of three types of expansion
input units.
This section describes the name and function of each part, the I/O specifications, the
terminal layout, circuit diagrams, and dimensions of two types of expansion I/O
units.
For more about the general specifications, refer to "General Specifications" (p.1-4).
)PNP/NPN(rotsisnarT
kcolblanimreT
CDV03
)PNP(tniop/A3.0,)NPN(tniop/A5.0
001µsselroA
sselroV8.0
nommoc/stniop4
05 µsselros
052µsselros
Chapter 1 Configuration and Specifications
1-53
Page 78
1.10 KV-E4XR/E4XT(P) (Expansion I/O Unit)
1.10.4 Terminal Layout Drawings and Input Circuit Diagrams
KV-E4XR (Relay output type)
■ Terminal layout drawing
C1 X1 X3 V2
Series
Visual KV
X0 X2 V1
Y0 Y2 V3
C2 Y1 Y3 V4
1
■ Input circuit diagram
Internal circuit
X3
Black
Three-wire
Brown
Blue
type
X2
Black
Three-wire
Brown
Blue
type
V1
V2
X1
Brown
Black
Three-wire
type
Blue
X0
Black
Three-wire
C1
Brown
type
Blue
1-54
X0 to X3
4.3KΩ
510Ω
C1
• V1 to V2 and V3 to V4 are short-circuited inside
(so they can be used as relay terminal blocks).
Chapter 1 Configuration and Specifications
Sensor
Photocoupler
insulation
Internal circuit
Page 79
■ Output circuit diagram
Internal circuit
Y0
1.10 KV-E4XR/E4XT(P) (Expansion I/O Unit)
Y2
V3
Series
Visual KV
C2
• V1 to V2 and V3 to V4 are short-circuited inside
(so they can be used as relay terminal blocks).
Y1
Internal circuit
Y3
V4
Y0 to Y3
C2
1
1
Chapter 1 Configuration and Specifications
1-55
Page 80
1.10 KV-E4XR/E4XT(P) (Expansion I/O Unit)
KV-E4XT(P) (Transistor output type)
■ Terminal layout drawing
Series
Visual KV
C1 X1 X3 V2
X0 X2 V1
Y0 Y2 V3
C2 Y1 Y3 V4
1
■ Input circuit diagram
Internal circuit
X3
Black
Three-wire
Brown
Blue
type
X2
Black
Three-wire
Brown
Blue
type
V1
V2
X1
Brown
Black
type
Three-wire
Blue
X0
Black
Three-wire
C1
Brown
Blue
type
Sensor
1-56
X0 to X3
4.3KΩ
510Ω
C1
Photocoupler
insulation
Chapter 1 Configuration and Specifications
Internal circuit
• V1 to V2 and V3 to V4 are short-circuited inside
(so they can be used as relay terminal blocks).
Page 81
■ Output circuit diagram
Internal circuit
Y0
1.10 KV-E4XR/E4XT(P) (Expansion I/O Unit)
Y2
V3
Series
Visual KV
C2
Y1
Y3
V4
*
* For KV-E4XTP
NPN
Insulating
power
supply
Internal
circuit
• V1 to V2 and V3 to V4 are short-circuited inside (so they can be used as relay terminal blocks).
Y0 to Y3
C2
PNP
Internal circuit
Insultating
power
supply
C2
Y0 to Y3
1
1
Chapter 1 Configuration and Specifications
1-57
Page 82
1.10 KV-E4XR/E4XT(P) (Expansion I/O Unit)
1.10.5 Dimensions
■ Main unit
Series
Visual KV
1
Front view
45
■ Metal fixture for screw tightening
Main unit
mounting hole*
(2 positions)
Side view
35.4 90
44
43.5
4-ø5.0
(Mounting
hole)
11199
25
38
* Two M3.5 countersunk-head screws are
included for mounting the main unit.
t = 2
1-58
Chapter 1 Configuration and Specifications
Page 83
1.11 KV-D20 (Operator interface panel)
1.11 KV-D20 (Operator Interface Panel)
This section describes the name and function of each part, the general specifications, the functional specifications, and dimensions of the operator interface panel.
This section describes cautions with the environment in which each unit is installed
and the installation position inside the panel.
2.1.1Installation Environment
Series
Visual KV
2
CAUTION
Never install a unit in the following locations:
•Locations exposed to direct sunlight
•Locations whose ambient temperature is outside the allowable range of 0 to
+50°C
•Locations whose ambient humidity is outside the allowable range of 35 to 85%
RH
•Locations subject to drastic temperature change where condensation may occur
•Locations with corrosive or flammable gases
•Locations with excessive dust, salt, iron powder, or soot
•Locations subject to direct vibrations and impacts
•Locations subject to splashes of water, oil, chemicals, etc.
•Locations where a strong magnetic or electrical field is generated
Units are made of synthetic resin. If the unit surface touches a solvent with a
strong dissolving force, it could melt. Keep such solvents away from the units.
1-64
Chapter 2 System Installation
Page 89
2.1.2Installation Position
■ Installation direction
When attaching a unit inside a panel, install the unit so that the front face (equipped
with the Access Window, communication ports, etc.) faces front or upwards.
2.1 Installation Environment
Front installation
Correct
Upward installation *
Correct
* Upward installation does not
comply with CE marking.
■ Distance between adjacent panels/equipment
When installing a unit, keep the distances shown below between the panel or
equipment so that the power supply can release heat.
Installation on ceiling
Incorrect
Vertical installation
Incorrect
Series
Visual KV
1
2
20 mm
10 mm
Unit
20 mm
Note 1: If the temperature inside the panel exceeds 50°C, which is specified as the
maximum ambient operating temperature, then install heat exchangers, etc. to
reduce the temperature.
Note 2: Ensure sufficient ventilation space so that the power supply can release
heat.
Note 3: Never install a unit just above any equipment which generates a lot of heat.
Chapter 2 System Installation
1-65
Page 90
2.1 Installation Environment
2.1.3Installation Procedure
This section describes how to attach a connected unit directly to a panel, to a DIN
rail, or to a DIN rail with an expansion unit spacer.
■ Attaching a unit directly to a panel
Attach the metal fixture for screw tightening to each
Series
Visual KV
KV Series unit using the countersunk-head screws
through the countersunk holes. Mount the fixture
directly to the panel.
■ Attaching a unit to a DIN rail
Hang an upper claw of a Visual KV Series basic unit
to the upper side of the DIN rail, and press the basic
unit onto the DIN rain until a click sound is heard.
2
Expansion unit spacer
■ Removing a unit from a DIN rail
Pull a lower claw of a Visual KV Series basic unit
downward from the front direction using a screwdriver, and then remove the basic unit from the DIN
rail.
When an expansion unit spacer is attached to a Visual KV Series expansion unit, its
height becomes flush with an AC power type Visual KV Series basic unit.
The procedure to attach a Visual KV Series expansion unit to an expansion unit
spacer is the same as the procedure to attach a Visual KV Series unit to a DIN rail.
Refer to the instruction manual supplied with the Visual KV Series for DIN rail
mounting.
■ Dimensions for expansion unit spacers
OP-35342
Spacer for 4-I/O
expansion unit
OP-35343
Spacer for 8-I/O
expansion unit
OP-35344
Spacer for 16-I/O
expansion unit
1-66
ø4.0
42.8
28
38
Chapter 2 System Installation
35
45
ø4.0
42.8
55
65
ø4.0
42.8
25.34
66
Page 91
2.1.4Cautions on Wiring for Each Unit
CAUTION
This section describes cautions to keep in mind when wiring is performed for I/O
units.
Be sure to read this section before starting wiring.
Wiring procedures for basic units
2.1 Installation Environment
The wiring procedures for basic units are described below.
•Turn off the power before starting wiring.
•For the installation position, select a location whose ambient temperature
is 0 to +50°C, whose ambient humidity is 35 to 85% RH, and one which is
not subject to drastic temperature changes.
•If the 24 VDC + output terminal and the 24 VDC - output terminal are
switched, the power supply unit and connected units may be damaged.
Never switch them.
•Be sure that the sum of the current consumption of all connected units
does not exceed the output capacity of the service power supply. If the
system is operating in an overload status, the internal circuits may generate heat or be damaged. To recover from an overload status, disconnect
some of the connected units.
•Never connect the DC output of any other power supply, either in serial or
parallel, to the 24 VDC output terminals. If the DC output is connected, the
power supply unit may be damaged.
■ Wiring for an AC type basic unit
For an AC type basic unit, perform the wiring as shown in the figure below.
KV-16AR
Series
Visual KV
1
2
100 to
240 VAC
±10%
Breaker
Insulating transformer,
noise filter, etc.
Bottom
Grounding
C1 001 003 005 007 009
000
0ch
EYENCE
0123456789
012345
KV-16AR
5ch
500
C324V-OUT-OVC4 503 505
501 502 504
IN
008006004002
OUT
24 VDC service
power supply
(supplied from
outside)
Note 1: Connect an insulating transformer (1:1) or noise filter to reduce line noise.
Note 2: Use twisted cables to reduce induction effects.
Note 3: When using a basic unit in a location with a lot of noise, the noise may be reduced
by completely grounding the basic unit.
Chapter 2 System Installation
1-67
Page 92
2.1 Installation Environment
Series
Visual KV
■ Wiring for a DC type basic unit
For a DC type basic unit, perform the wiring as shown in the figure below.
KV-10DR
001 002 003 004 005
24 VDC
external power
supply
Breaker
000
C1
EYENCE
KV-10DR
C2
0ch
012345
0123
5ch
50024V-IN-OVC3 C4 503
501 502
IN
OUT
Note: Connect the power supply to the power supply input terminals with 24 VDC
output, which offers a sufficient margin of power capacity. Usually, the sum of the
current consumption of all connected units multiplied by 1.5 or more is required for
the power capacity.
Cautions on wiring for I/O units
2
When performing wiring for an I/O unit, pay strict attention to the following contents.
•Separate input lines from output lines in wiring.
•If the wiring for power is located near I/O signal lines, a malfunction may occur
caused by the effects of a high voltage and large current.
•Keep I/O signal lines away from the power wiring by at least 100 mm.
•Separate 24 VDC I/O lines from 100 VAC and 200 VAC lines.
•When using pipes for wiring, make sure that the pipes are securely grounded.
■ When I/O signal lines cannot be separated from the wiring for power
In such a case, perform grounding on the KV side using batch-shielded cables.
(In some environments, grounding should be performed on the reverse side of the
KV.)
Input
Output
KV
24 VDC
Shielded cable
Sensor
RL
Ground
Terminal
1-68
The terminal screws used are M3. When performing wiring with crimp-style terminals, use the following ones.
6.0 maximum
Chapter 2 System Installation
Unit: mm
6.0 maximum
M3
Page 93
Cautions on grounding
Because the Visual KV Series is constructed to be sufficiently resistant to noise, it
can usually be used without being grounded. However, when the Visual KV Series is
used in an environment with a lot of noise, grounding is required. In such a case,
pay strict attention to the following contents.
•Perform complete grounding for each individual unit. In this case, the ground
resistance should be 100 Ω or less.
•If individual grounding is not possible, perform common grounding. In this case,
the length of each grounding cable should be equal.
2.1 Installation Environment
Series
Visual KV
Recommended
KV
Complete grounding
Other deviceOther deviceOther device
2.1.5Contact Protection
If inductive loads such as clutches, motors, and solenoids are used, a rush current
may flow when the load power supply is turned on, or a counter electromotive
voltage may be generated when the load power supply is shut down. The rush
current and the counter electromotive voltage can contribute considerably to
shortening the service life of the contacts. To prevent this from happening, provide a
contact protection circuit.
■ Contact protection circuit examples
For AC load 1
Acceptable
KV
A
A = BA > B
B
For DC load 1
Unacceptable
KV
A
A < B
B
1
2
Contact
Contact
Load
For AC load 2
ab
Varistor
CR circuit
Contact
Contact
Load
For DC load 2
Zener diode
Diode
When the supply voltage is 24 to 48 V, provide a protection circuit in position "b".
When the supply voltage is 100 to 200 V, provide a protection circuit in position "a".
Note 1: Use a load coil whose rating is less than the contact capacity.
Note 2: Use a diode whose peak inverse voltage is 10 times or more the circuit
voltage and whose forward current is not less than the load current.
Note 3: Individually attach diodes, varistors, and CR circuits directly to the relay coil
terminal.
Chapter 2 System Installation
1-69
Page 94
2.2 Connecting Visual KV Series Expansion Units
2.2Connecting Visual KV Series
Expansion Units
This section describes the method to connect Visual KV Series expansion units to a
Visual KV Series basic unit and the various functions of expansion units.
Series
2.2.1Visual KV Series Expansion Units
Visual KV
Visual KV Series expansion input units
KV-E4XKV-E8XKV-E16X
Visual KV Series expansion output units
2
KV-E4R
Visual KV Series expansion I/O units
KV-E4XR
KV-E4XT(P)
KV-E8RKV-E16RKV-E4TKV-E8T(P)KV-E16T(P)
1-70
Chapter 2 System Installation
Page 95
2.2 Connecting Visual KV Series Expansion Units
2.2.2Connecting Visual KV Series Expansion Units
•Connect a basic unit and an expansion unit with an expansion cable.
•An expansion cable approximately 60 mm long is provided as standard.
•When extending the expansion cable, use long expansion cables (300 mm)
(OP-35361).
•Up to two expansion cables (300 mm) can be connected to one basic unit.
•The READY/ERROR LED is lit during normal communication, flashes when an
abnormality occurs, and is not lit when the power is not supplied correctly. If this
LED is not lit, check whether the expansion cables are correctly connected.
Standard cable (approx. 60 mm)
Basic unit
Expansion cable
(60 mm)
Long cable (approx. 300 mm)
Basic unit
Expansion unit
Expansion unit
Expansion unit
Series
Visual KV
1
2
CAUTION
Expansion cable
(300 mm)
Standard cable (approx. 60) + Long cable (approx. 300 mm)
Basic unit
Expansion cable
Expansion unit
(60 mm)
Expansion cable
(300 mm)
Expansion unit
Expansion cable
(300 mm)
Be sure to turn off the power before connecting or disconnecting expansion
cables. If they are connected or disconnected while the power is on, the units
may be damaged or fail.
Note: Keep noise sources such as power cables and electromagnetic switches away
from expansion cables (300 mm) as much as possible.
Chapter 2 System Installation
1-71
Page 96
2.2 Connecting Visual KV Series Expansion Units
Connection methods
1. Peel off the tape stuck to the right side of the basic unit.
Series
Visual KV
2. Connect an expansion cable to the connector.
2
■ When extending a cable
Replace a standard expansion cable (60 mm) with an optional expansion cable (300
mm) (OP-35361).
1. Disconnect the standard expansion cable from the expansion unit connector.
2. Connect an optional expansion cable (300 mm) to the expansion unit connector.
3. Connect the optional expansion cable (300 mm) to the basic unit connector.
1-72
Chapter 2 System Installation
Page 97
Number of connectable units
● When the basic unit is a KV-10xx/16xx/24xx
Up to four input units and four output units (that is, up to 8 total expansion units)
can be connected to one basic unit.
Basic unit
● When the basic unit is a KV-40xx
Up to three input units and four output units (that is, up to 7 total expansion units)
can be connected to one basic unit.
Basic unit
2.2 Connecting Visual KV Series Expansion Units
Expansion units
Input OutputInput
OutputOutputInputOutputInput
InputOutput
Up to 8 units
Expansion units
Output Output
Output
Input
Series
Visual KV
Input
Up to 7 units
● When KV-E4XT/KV-E4XR expansion I/O units are connected
One I/O unit is regarded as two units (that is, one input and one output unit). For
example, when only expansion I/O units are connected to one basic unit, up to
four expansion I/O units can be connected. Up to three expansion I/O units can
be connected to a KV-40xx basic unit.
When two expansion I/O units are connected
Expansion units
Basic unit
Input
Output
InputI/OI/O
1
0
1
1
Output
6 units
1
1
Output
0
1
Input
0
1
10= 4
= 4
Note 1: There are no restrictions about the order of connected expansion units.
Note 2: When connecting expansion units to an AC power type basic unit, be sure
that the total current consumption of all connected units does not exceed the output
capacity of the Visual KV Series basic unit. Otherwise, consider to use a DC power
type basic unit in conbination with an external DC power supply having enough
capacity.
1
2
Chapter 2 System Installation
1-73
Page 98
2.2 Connecting Visual KV Series Expansion Units
2.2.3Confirming the Connection Settings of Expansion Units
Relay No. (unit No., address No., contact No.)
The relay No. of each expansion unit is automatically assigned in the order of connection.
Expansion unit relay list
Series
Visual KV
2
■ Input units
noitcennoC
redro
tupnits1
tinu
tupnidn2
tinu
tupnidr3
tinu
tupniht4
tinu
■ Output units
noitcennoC
redro
tuptuots1
tinu
tuptuodn2
tinu
tuptuodr3
tinu
tuptuoht4
tinu
X4E-VKX8E-VKX61E-VK
/01-VK
42/61
301ot001302ot002701ot001702ot002511ot001511ot002
302ot002303ot003702ot002703ot003512ot002513ot003
303ot003304ot004703ot003704ot004513ot003514ot004
304ot004–704ot004–514ot004–
04-VK
R/T4E-VKR/)P(T8E-VKR/)P(T61E-VK
306ot006706ot006516ot006
307ot007707ot007517ot007
308ot008708ot008518ot008
309ot009709ot009519ot009
/01-VK
42/61
04-VK
/01-VK
42/61
04-VK
■ I/O units
redro
tupnits1
tinu
tupnidn2
tinu
tupnidr3
tinu
tupniht4
tinu
tuptuots1
tinu
tinu
tuptuodr3
tinu
tuptuoht4
tinu
noitcennoC
42/61/01-VK04-VK42/61/01-VK04-VK
301ot001302ot002——
302ot002303ot003——
303ot003304ot004——
304ot004———
——306ot006306ot006
tuptuodn2
——307ot007307ot007
——308ot008308ot008
——309ot009309ot009
yalertupnIyalertuptuO
)P(T/RX4E-VK
1-74
Chapter 2 System Installation
Page 99
2.2 Connecting Visual KV Series Expansion Units
Connection information for expansion units
The connection status (connected or unconnected) of a connected expansion unit
can be confirmed using the Access Window, the ladder support software "KV
IncrediWare (DOS)" and "LADDER BUILDER for KV", or the KV-P3E(01) handheld
programmer.
➮
Refer to "Chapter 3. Access Window" (p.1-79), "Chapter 6. Handheld Programmer" (p.1-195), and the
"6.2.9. Displaying the Use Status" (p. 2-70).
The connection information is written to data memory DM1937 as shown in the table
below.
In the case of connection above, DM1937 is set as follows.
DM1937 (binary)
Normal status:
KV-E16T
When KV-E8X has failed:
When KV-E4XT has failed:
900 800 700 600 400 300 200 100
0
1110110
KV-E4XT
KV-E8R
DM1937 (binary)
0
1110100
DM1937 (binary)
0
1100010
Decimal (Hexadecimal)
= #118($0076)
* Always set to "0" when the KV-40xx is used.
KV-E8X
Decimal (Hexadecimal)
= #116($0074)
Decimal (Hexadecimal)
= #98($0062)
Chapter 2 System Installation
1-75
Page 100
2.2 Connecting Visual KV Series Expansion Units
Input time constant for expansion units
The initial setting of the time constant is "10 ms" for each expansion unit.
The input time constant can be set to "10 µs" using the Access Window, the ladder
support software "KV IncrediWare (DOS)" and "LADDER BUILDER for KV", or the
KV-P3E(01) handheld programmer.
Change the value of special utility relays 2609 to 2612.
Series
Visual KV
*9062
0162
1162
2162
*Not used for the KV-40xx.
.oNyalerytilitulaicepSnoitcnuF
Clearing the input value when disconnecting
The system can be set so that the input value is cleared when disconnection has
occurred for some reason.
This setting can be performed using the Access Window, the ladder support software "KV IncrediWare (DOS)" and "LADDER BUILDER for KV", or the KV-P3E(01)
2
handheld programmer.
Change the value of special utility relay 2613. Enter "0" or "1".
.oNyalerytilitulaicepSnoitcnuF
3162
.detcennocsidsinoisnapxenehwtupnisraelC
.tupnisraelC:NO.eulavsuoiverpsdloH:FFO
1-76
Chapter 2 System Installation
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.