Fluke i410, i1010 Operating Manual

0 (0)

®

i410/i1010

AC/DC Current Clamp

Instruction Sheet

Safety Information

XW Read First: Safety Information

To ensure safe operation and service of the current clamp, follow these instructions:

Read all operating instructions before use and follow all safety instructions.

Use the Current Clamp only as specified in the operating instructions, otherwise the clamp’s safety features may not protect you.

Adhere to local and national safety codes. Individual protective equipment must be used to prevent shock and arc blast injury where hazardous live conductors are exposed.

Do not hold the Current Clamp anywhere beyond the tactile barrier. See Features and Connections.

Before each use, inspect the Current Clamp. Look for cracks or missing portions of the clamp housing or output cable insulation. Also look for loose or weakened components. Pay particular attention to the insulation surrounding the jaws.

Never use the clamp on a circuit with voltages higher than 600 V (CAT. III) or a frequency higher than 400 Hz (i410) or 2 kHz (i1010).

CAT III equipment is designed to protect against transients in equipment in fixed equipment installations, such as distribution panels, feeders and short branch circuits, and lighting systems in large buildings.

Use extreme caution when working around bare conductors or bus bars. Contact with the conductor could result in electric shock.

Use caution when working with voltages above 60 V dc, 30 V ac rms or 42 V ac peak. Such voltages pose a shock hazard.

PN 617677 September 1996, Rev.2, 6/05

1996-2005 Fluke Corporation. All rights reserved. Printed in Thailand.

Features and Connections

 

8

CAT

600V

 

600A

A ZERO

i410 CLAMP METER

600V

76 TRUE RMS MULTIMETER

V

ar001i.eps

A Jaw Lever

B Jaw Centering Marks

C ON Indicator

D ON/OFF Switch

E Zero Adjust

F Battery Access

G Output Cable

H Tactile Barrier

Minimum voltmeter requirements:

Accepts safetyshrouded banana plugs.

Can display 1 mV (0.1 mV preferred)

Accuracy 0.75 %

Input impedance 1 M, 100 pF.

Fluke i410, i1010 Operating Manual

Measuring DC Current

Maximum: 400 A dc (i410) or 1000 A dc (i1010)

i410

600V

 

76 TRUE RMS MULTIMETER

CAT

600V

 

600A

 

mV

A ZERO

i410 CLAMP METER

600V

ar002i.eps

A Connect to voltmeter.

B Select mV dc.

C Set ON.

D Adjust ZERO (jaws

empty.)

A ZERO

ar006i.eps

E Clamp and center around conductor.

F Read voltmeter (1 mV = 1 A.)