ABB AC500-eCo Technical Data

03
72 MAIN CATALOG PLC AUTOMATION
AC500-eCo
Technical data
AC500-eCo CPUs
Typ e PM564-TP-ETH PM566-TP-ETH PM564-RP-ETH PM564-RP-ETH-AC
Supply voltage 24 V DC 100-240 V AC Current consumption on 24 V DC 100 V AC 240 V AC
Min. (module alone) 0.10 A 0.10 A 0.12 A 0.023 A 0.014 A
Max. (I/Os) 0.22 A 0.22 A 0.25 A 0.22 A 0.13 A Program memory 128 kB 512 kB 128 kB Integrated data memory 14 kB thereof 2 kB saved 130 kB thereof 2 kB saved 14 kB thereof 2 kB saved Web server's data for user R AM disk 512 kB 1024 kB 512 kB Data buffering (of saved data) flash memory Real-time clock (option with battery back-up) (1)
Program execution
Cyclical Time controlled Multi tasking no, 1 task + 1 interrupt task max. Interruption User program protection by password
Cycle time for 1 instruction (minimum)
Binary 0.08 µs Word 0.1 µs Floating 1.2 µs
Onboard digital inputs
Channels 6 (including 2 counter inputs, or up to 4 interrupt inputs) Signal voltage 24 V DC
Onboard digital outputs
Channels 6 (including 2 PWM outputs for types w ith transistor outputs) Relay / Transistor Transistor Transistor Relay Relay Rated voltage 24 V DC 24 V DC 240 V AC 240 V AC Nominal current per channel 0.5 A 0.5 A 2 A resistive 2 A resistive
Onboard analog inputs
Channels 2 signal ranges 0...10 V / can be configured as digital input 24 V DC
Onboard analog outputs
Channels 1 signal ranges 0...10 V / 0...20 mA / 4...20 mA
Max. number of centralized inputs/outputs
Max. number of extension modules on I/O bus Digital inputs 320 + 8
Analog inputs 160 + 2
Max. number of decentralized inputs/outputs
On CS31 bus up to 31 stations with up to 120 DI / 120 DO each or up to 32 AI/32 AO per station
Internal interfaces
COM1
RS485
Sub-D connection
Programming, Modbus-RTU, ASCII,
CS31 COM2 (option) (2)
RS485 / RS485 isolated
Terminal block
Programming, Modbus-RTU, ASCII Ethernet
RJ45
Ethernet functions: Programming,
Modbus TCP/IP, UDP/IP, integrated
Web server, DHCP, FTP server, SNTP
client
SMTP – RUN/STOP switch LED for power, status and error Approvals see detailed over view page 238 or ww w.abb.com/plc
(1) Real‑time clock requires optional TA561‑RTC or TA562‑RS‑RTC. (2) COM2 requires TA5 62‑RS‑ RTC, TA562‑ RS or new TA569 ‑RS‑I SO.
outputs 320 + 6
outputs 160 + 1
up to max. 10 (S500 and/or S50 0-eCo modules allowed)
/
Loading...