ABB A145, A185, A210, A260, A300 Technical Data

...
0 (0)

IEC Technical data

A/F145...AF300, 3-pole Utilization characteristics

Across

 

Contactorsline

 

the

1

Main pole - Utilization characteristics according to IEC

Contactor types

 

AC operated

A145

A185

A210

A260

A300

 

 

 

 

 

AC / DC operated

AF145

AF185

AF210

AF260

AF300

Standards

 

 

IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1

 

 

 

Rated operational voltage Ue max.

 

1000 V

 

690 V

 

 

 

Rated frequency (without derating)

 

50/60 Hz

 

 

 

 

 

Conventional free-air thermal current Ith

 

 

 

 

 

 

 

acc. to IEC 60947-4-1, open contactors, θ ≤ 40 °C

 

250 A

275 A

350 A

400 A

500

A (4)

With conductor cross-sectional area (3)

 

120 mm²

150 mm²

185 mm²

240 mm²

300 mm² (4)

AC-1 Utilization category

 

 

 

 

 

 

 

For air temperature close to contactor

 

 

 

 

 

 

 

Ie / Rated operational current AC-1

θ ≤ 40 °C

250 A

275 A

350 A

400 A

500

A (4)

Ue max. ≤ 690 V, 50/60 Hz

θ ≤ 55 °C

230 A

250 A

300 A

350 A

400

A (4)

 

 

 

 

 

θ ≤ 70 °C

180 A

180 A

240 A

290 A

325

A (4)

Ie / Rated operational current AC-1

θ ≤ 40 °C

180 A

200 A

 

Ue max. ≤ 1000 V, 50/60 Hz

θ ≤ 55 °C

180 A

200 A

 

 

 

 

 

 

θ ≤ 70 °C

180 A

180 A

 

With conductor cross-sectional area

 

120 mm²

150 mm²

185 mm²

240 mm²

300 mm² (4)

AC-3 Utilization category

 

 

 

 

 

 

 

For air temperature close to contactor θ 55 °C

 

 

 

 

 

 

Ie / Max. rated operational current AC-3 (1)

 

 

 

 

 

 

 

 

 

 

 

 

220-230-240 V

145 A

185 A

210 A

260 A

305

A

 

 

 

 

 

380-400 V

145 A

185 A

210 A

260 A

305

A

 

 

 

 

 

415 V

145 A

185 A

210 A

260 A

300

A

 

 

 

 

 

 

M

 

 

3-phase motors

440 V

145 A

185 A

210 A

240 A

280

A

3

 

 

 

 

 

500 V

145 A

170 A

210 A

240 A

280

A

 

 

 

 

 

690 V

120 A

170 A

210 A

220 A

280

A

 

 

 

 

 

1000 V

80 A

95 A

 

Rated operational power AC-3 (1)

 

 

 

 

 

 

220-230-240 V

45 kW

55 kW

59 kW

80 kW

90 kW

 

 

 

 

 

 

380-400 V

75 kW

90 kW

110 kW

140 kW

160 kW

 

 

 

 

 

1500 r.p.m. 50 Hz

415 V

75 kW

90 kW

110 kW

140 kW

160 kW

 

 

M

 

 

 

 

 

 

 

1800 r.p.m. 60 Hz

440 V

75 kW

90 kW

110 kW

140 kW

160 kW

3

 

 

 

 

 

 

3-phase motors

500 V

90 kW

110 kW

132 kW

180 kW

200 kW

 

 

 

 

 

 

690 V

110 kW

132 kW

160 kW

200 kW

250 kW

 

 

 

 

 

 

1000 V

110 kW

132 kW

Rated making capacity AC-3

 

10 x Ie AC-3 acc. to IEC 60947-4-1

 

 

 

Rated breaking capacity AC-3

 

8 x Ie AC-3 acc. to IEC 60947-4-1

 

 

 

Short-circuit protection device for contactors

 

 

 

 

 

 

without thermal overload relay - Motor protection excluded (2)

Ue ≤ 500 V AC - gG type fuse

 

315 A

355 A

400 A

500 A

500 A

Rated short-time withstand current Icw

1 s

1800 A

2000 A

2500 A

3500 A

3500 A

at 40 °C ambient temperature,

10 s

1200 A

1500 A

1700 A

2400 A

2400 A

in free air from a cold state

30 s

800 A

1000 A

1200 A

1500 A

1500 A

 

 

1 min

600 A

800 A

1000 A

1100 A

1100 A

 

15 min

280 A

320 A

400 A

500 A

500 A

Maximum breaking capacity

 

 

 

 

 

 

cos φ = 0.45

at 440 V

1500 A

2000 A

2300 A

2600 A

3000 A

(cos φ = 0.35 for Ie > 100 A)

at 690 V

1200 A

1600 A

2000 A

2400 A

2500 A

Power dissipation per pole

Ie / AC-1

13 W

16 W

18 W

25 W

32 W

 

Ie / AC-3

5 W

8 W

9 W

14 W

18 W

Max. electrical switching frequency

AC-1

300 cycles/h

 

300 cycles/h

 

 

 

AC-3

300 cycles/h

 

300 cycles/h

 

 

 

AC-2, AC-4

150 cycles/h

 

150 cycles/h

 

 

(1)For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".

(2)For the protection of motor starters against short circuits, see "Coordination with short-circuit protection devices".

(3)Conductors with preparation.

(4)Use terminal extension / enlargement pieces (LX 300 / LW 300).

Low Voltage Products & Systems

1SXU000023C0202 Rev. A

ABB A145, A185, A210, A260, A300 Technical Data

UL/NEMA/CSA Technical data

A/F145...A/F300; A/F145N4...A/F260N5, 3-pole Utilization characteristics

Across

 

Contactorsline

 

the

1

Main pole - Utilization characteristics according to UL / NEMA / CSA

 

Contactor types

AC operated

A145

 

A185

 

A210

 

A260

 

A300

 

 

AC / DC operated

AF145

 

AF185

 

AF210

 

AF260

 

AF300

 

Standards

 

UL 508, CSA C22.

 

2 N°14

 

 

 

 

 

 

 

Max. operational voltage

 

600 V

 

 

 

 

 

 

 

 

 

NEMA size

 

4

 

 

 

5

 

 

 

 

 

 

 

NEMA maximum horse power ratings 1-phase, 60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

115 V AC

 

 

 

 

 

 

230 V AC

 

 

 

 

 

NEMA maximum horse power ratings 3-phase, 60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

200 V AC

40 hp

 

 

 

 

 

75 hp

 

 

 

 

 

 

 

 

 

 

 

 

 

230 V AC

50 hp

 

 

 

 

 

100 hp

 

 

 

 

460 V AC

100 hp

 

 

 

 

 

200 hp

 

 

 

 

575 V AC

200 hp

 

 

 

 

 

200 hp

 

 

 

UL / CSA general use rating

 

 

 

 

 

 

 

 

 

 

 

600 V AC

 

230 A

 

250 A

 

300 A

 

350 A

 

400 A

 

UL / CSA maximum 1-phase motor rating

 

 

 

 

 

 

 

 

 

 

 

Full load current

240 V AC

 

 

 

 

 

Horse power rating

240 V AC

 

 

 

 

 

UL / CSA maximum 3-phase motor rating

 

 

 

 

 

 

 

 

 

 

 

Full load current (1)

200-208 V AC

119.6 A

 

149.5 A

 

166.8 A

 

220.8 A

 

285.2 A

 

 

220-240 V AC

130 A

 

145 A

 

192 A

 

248 A

 

248 A

 

 

440-480 V AC

124 A

 

156 A

 

180 A

 

240 A

 

302 A

 

 

550-600 V AC

125 A

 

144 A

 

192 A

 

242 A

 

289 A

 

Horse power rating (1)

200-208 V AC

40 hp

 

50 hp

 

60 hp

 

75 hp

 

100 hp

 

 

220-240 V AC

50 hp

 

60 hp

 

75 hp

 

100 hp

 

100 hp

 

 

440-480 V AC

100 hp

 

125 hp

 

150 hp

 

200 hp

 

250 hp

 

 

550-600 V AC

125 hp

 

150 hp

 

200 hp

 

250 hp

 

300 hp

 

Max. electrical switching frequency

 

 

 

 

 

 

 

 

 

 

 

For general use

 

300 cycles/h

 

 

 

 

 

 

 

 

 

For motor use

 

300 cycles/h

 

 

 

 

 

 

 

 

(1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see “Motor rated operational powers and currents”.

General technical data

Contactor types

 

 

AC operated

A145

A185

A210

A260

A300

 

 

 

 

AC / DC operated

AF145

AF185

AF210

AF260

AF300

Rated insulation voltage Ui

 

 

 

 

 

 

 

acc. to IEC 60947-4-1

 

1000 V

 

 

 

 

 

acc. to UL

 

 

 

600 V

 

 

 

 

Rated impulse withstand voltage Uimp.

 

8 kV

 

 

 

 

Electromagnetic compatibility

 

AF contactors complying with IEC 60947-1 / EN 60947-1 - Environment A

 

Ambient air temperature close to contactor

 

 

 

 

 

 

 

Operation

 

Fitted with thermal overload relay

-25 to +55 °C

 

 

 

 

 

 

 

Fitted with electronic overload relay

-25 to +70 °C

 

 

 

 

 

 

 

Without electronic overload relay

 

-40 to +70 °C

 

 

 

 

 

Storage

 

 

 

-40 to +70 °C

 

 

 

 

Climatic withstand

 

 

acc. to IEC 60068-2-30

 

 

 

Maximum operating altitude (without derating)

 

3000 m

 

 

 

 

Mechanical durability

 

 

 

 

 

 

 

 

Number of operating cycles

 

5 millions operating cycles

 

 

 

 

Max. switching frequency

 

3600 cycles/h (300 for AF… contactors)

 

 

Shock withstand acc. to IEC 60068-2-27 and EN 60068-2-27

 

 

 

 

 

 

Mounting position 1

 

 

 

 

 

 

 

 

 

 

C1

Shock direction

1/2 sinusoidal shock for 30 ms: no change in contact position, closed or open position

 

 

 

A

5 g

 

 

 

 

A

A

B1

B2

 

 

 

 

B1

5 g

 

 

 

 

 

ABB

 

 

 

 

 

 

 

 

 

 

 

 

B2

5 g

 

 

 

 

 

 

 

C2

C1

5 g

 

 

 

 

 

 

 

C2

5 g

 

 

 

 

 

 

 

 

 

 

 

 