IEC Technical data
A/F145...AF300, 3-pole Utilization characteristics
Across |
|
Contactorsline |
|
|
the |
1
Main pole - Utilization characteristics according to IEC
Contactor types |
|
AC operated |
A145 |
A185 |
A210 |
A260 |
A300 |
||||
|
|
|
|
|
AC / DC operated |
AF145 |
AF185 |
AF210 |
AF260 |
AF300 |
|
Standards |
|
|
IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1 |
|
|
|
|||||
Rated operational voltage Ue max. |
|
1000 V |
|
690 V |
|
|
|
||||
Rated frequency (without derating) |
|
50/60 Hz |
|
|
|
|
|
||||
Conventional free-air thermal current Ith |
|
|
|
|
|
|
|
||||
acc. to IEC 60947-4-1, open contactors, θ ≤ 40 °C |
|
250 A |
275 A |
350 A |
400 A |
500 |
A (4) |
||||
With conductor cross-sectional area (3) |
|
120 mm² |
150 mm² |
185 mm² |
240 mm² |
300 mm² (4) |
|||||
AC-1 Utilization category |
|
|
|
|
|
|
|
||||
For air temperature close to contactor |
|
|
|
|
|
|
|
||||
Ie / Rated operational current AC-1 |
θ ≤ 40 °C |
250 A |
275 A |
350 A |
400 A |
500 |
A (4) |
||||
Ue max. ≤ 690 V, 50/60 Hz |
θ ≤ 55 °C |
230 A |
250 A |
300 A |
350 A |
400 |
A (4) |
||||
|
|
|
|
|
θ ≤ 70 °C |
180 A |
180 A |
240 A |
290 A |
325 |
A (4) |
Ie / Rated operational current AC-1 |
θ ≤ 40 °C |
180 A |
200 A |
– |
– |
– |
|
||||
Ue max. ≤ 1000 V, 50/60 Hz |
θ ≤ 55 °C |
180 A |
200 A |
– |
– |
– |
|
||||
|
|
|
|
|
θ ≤ 70 °C |
180 A |
180 A |
– |
– |
– |
|
With conductor cross-sectional area |
|
120 mm² |
150 mm² |
185 mm² |
240 mm² |
300 mm² (4) |
|||||
AC-3 Utilization category |
|
|
|
|
|
|
|
||||
For air temperature close to contactor θ ≤ 55 °C |
|
|
|
|
|
|
|||||
Ie / Max. rated operational current AC-3 (1) |
|
|
|
|
|
|
|
||||
|
|
|
|
|
220-230-240 V |
145 A |
185 A |
210 A |
260 A |
305 |
A |
|
|
|
|
|
380-400 V |
145 A |
185 A |
210 A |
260 A |
305 |
A |
|
|
|
|
|
415 V |
145 A |
185 A |
210 A |
260 A |
300 |
A |
|
|
|
|
|
|||||||
|
M |
|
|||||||||
|
3-phase motors |
440 V |
145 A |
185 A |
210 A |
240 A |
280 |
A |
|||
3 |
|
|
|||||||||
|
|
|
500 V |
145 A |
170 A |
210 A |
240 A |
280 |
A |
||
|
|
|
|
|
690 V |
120 A |
170 A |
210 A |
220 A |
280 |
A |
|
|
|
|
|
1000 V |
80 A |
95 A |
– |
– |
– |
|
Rated operational power AC-3 (1)
|
|
|
|
|
|
220-230-240 V |
45 kW |
55 kW |
59 kW |
80 kW |
90 kW |
|
|
|
|
|
|
380-400 V |
75 kW |
90 kW |
110 kW |
140 kW |
160 kW |
|
|
|
|
|
1500 r.p.m. 50 Hz |
415 V |
75 kW |
90 kW |
110 kW |
140 kW |
160 kW |
|
|
M |
|
||||||||
|
|
|
|||||||||
|
|
|
1800 r.p.m. 60 Hz |
440 V |
75 kW |
90 kW |
110 kW |
140 kW |
160 kW |
||
3 |
|
|
|
||||||||
|
|
|
3-phase motors |
500 V |
90 kW |
110 kW |
132 kW |
180 kW |
200 kW |
||
|
|
|
|
|
|
690 V |
110 kW |
132 kW |
160 kW |
200 kW |
250 kW |
|
|
|
|
|
|
1000 V |
110 kW |
132 kW |
– |
– |
– |
Rated making capacity AC-3 |
|
10 x Ie AC-3 acc. to IEC 60947-4-1 |
|
|
|
||||||
Rated breaking capacity AC-3 |
|
8 x Ie AC-3 acc. to IEC 60947-4-1 |
|
|
|
||||||
Short-circuit protection device for contactors |
|
|
|
|
|
|
without thermal overload relay - Motor protection excluded (2)
Ue ≤ 500 V AC - gG type fuse |
|
315 A |
355 A |
400 A |
500 A |
500 A |
Rated short-time withstand current Icw |
1 s |
1800 A |
2000 A |
2500 A |
3500 A |
3500 A |
at 40 °C ambient temperature, |
10 s |
1200 A |
1500 A |
1700 A |
2400 A |
2400 A |
in free air from a cold state |
30 s |
800 A |
1000 A |
1200 A |
1500 A |
1500 A |
|
||||||
|
1 min |
600 A |
800 A |
1000 A |
1100 A |
1100 A |
|
15 min |
280 A |
320 A |
400 A |
500 A |
500 A |
Maximum breaking capacity |
|
|
|
|
|
|
cos φ = 0.45 |
at 440 V |
1500 A |
2000 A |
2300 A |
2600 A |
3000 A |
(cos φ = 0.35 for Ie > 100 A) |
at 690 V |
1200 A |
1600 A |
2000 A |
2400 A |
2500 A |
Power dissipation per pole |
Ie / AC-1 |
13 W |
16 W |
18 W |
25 W |
32 W |
|
Ie / AC-3 |
5 W |
8 W |
9 W |
14 W |
18 W |
Max. electrical switching frequency |
AC-1 |
300 cycles/h |
|
300 cycles/h |
|
|
|
AC-3 |
300 cycles/h |
|
300 cycles/h |
|
|
|
AC-2, AC-4 |
150 cycles/h |
|
150 cycles/h |
|
|
(1)For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".
(2)For the protection of motor starters against short circuits, see "Coordination with short-circuit protection devices".
(3)Conductors with preparation.
(4)Use terminal extension / enlargement pieces (LX 300 / LW 300).
Low Voltage Products & Systems
1SXU000023C0202 Rev. A
UL/NEMA/CSA Technical data
A/F145...A/F300; A/F145N4...A/F260N5, 3-pole Utilization characteristics
Across |
|
Contactorsline |
|
|
the |
1
Main pole - Utilization characteristics according to UL / NEMA / CSA
|
Contactor types |
AC operated |
A145 |
|
A185 |
|
A210 |
|
A260 |
|
A300 |
|
|
AC / DC operated |
AF145 |
|
AF185 |
|
AF210 |
|
AF260 |
|
AF300 |
|
Standards |
|
UL 508, CSA C22. |
|
2 N°14 |
|
|
|
|
|
|
|
Max. operational voltage |
|
600 V |
|
|
|
|
|
|
|
|
|
NEMA size |
|
4 |
|
– |
|
– |
|
5 |
|
– |
|
|
|
|
|
|||||||
|
NEMA maximum horse power ratings 1-phase, 60 Hz |
|
|
|
|
|
|
|
|
|
|
|
|
115 V AC |
– |
|
– |
|
– |
|
– |
|
– |
|
|
230 V AC |
– |
|
– |
|
– |
|
– |
|
– |
|
NEMA maximum horse power ratings 3-phase, 60 Hz |
|
|
|
|
|
|
|
|
|
|
|
|
200 V AC |
40 hp |
|
|
|
|
|
75 hp |
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
230 V AC |
50 hp |
|
|
|
|
|
100 hp |
|
|
|
|
460 V AC |
100 hp |
|
|
|
|
|
200 hp |
|
|
|
|
575 V AC |
200 hp |
|
|
|
|
|
200 hp |
|
|
|
UL / CSA general use rating |
|
|
|
|
|
|
|
|
|
|
|
600 V AC |
|
230 A |
|
250 A |
|
300 A |
|
350 A |
|
400 A |
|
UL / CSA maximum 1-phase motor rating |
|
|
|
|
|
|
|
|
|
|
|
Full load current |
240 V AC |
– |
|
– |
|
– |
|
– |
|
– |
|
Horse power rating |
240 V AC |
– |
|
– |
|
– |
|
– |
|
– |
|
UL / CSA maximum 3-phase motor rating |
|
|
|
|
|
|
|
|
|
|
|
Full load current (1) |
200-208 V AC |
119.6 A |
|
149.5 A |
|
166.8 A |
|
220.8 A |
|
285.2 A |
|
|
220-240 V AC |
130 A |
|
145 A |
|
192 A |
|
248 A |
|
248 A |
|
|
440-480 V AC |
124 A |
|
156 A |
|
180 A |
|
240 A |
|
302 A |
|
|
550-600 V AC |
125 A |
|
144 A |
|
192 A |
|
242 A |
|
289 A |
|
Horse power rating (1) |
200-208 V AC |
40 hp |
|
50 hp |
|
60 hp |
|
75 hp |
|
100 hp |
|
|
220-240 V AC |
50 hp |
|
60 hp |
|
75 hp |
|
100 hp |
|
100 hp |
|
|
440-480 V AC |
100 hp |
|
125 hp |
|
150 hp |
|
200 hp |
|
250 hp |
|
|
550-600 V AC |
125 hp |
|
150 hp |
|
200 hp |
|
250 hp |
|
300 hp |
|
Max. electrical switching frequency |
|
|
|
|
|
|
|
|
|
|
|
For general use |
|
300 cycles/h |
|
|
|
|
|
|
|
|
|
For motor use |
|
300 cycles/h |
|
|
|
|
|
|
|
|
(1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see “Motor rated operational powers and currents”.
General technical data
Contactor types |
|
|
AC operated |
A145 |
A185 |
A210 |
A260 |
A300 |
|
|
|
|
|
AC / DC operated |
AF145 |
AF185 |
AF210 |
AF260 |
AF300 |
Rated insulation voltage Ui |
|
|
|
|
|
|
|||
|
acc. to IEC 60947-4-1 |
|
1000 V |
|
|
|
|
||
|
acc. to UL |
|
|
|
600 V |
|
|
|
|
Rated impulse withstand voltage Uimp. |
|
8 kV |
|
|
|
|
|||
Electromagnetic compatibility |
|
AF contactors complying with IEC 60947-1 / EN 60947-1 - Environment A |
|
||||||
Ambient air temperature close to contactor |
|
|
|
|
|
|
|||
|
Operation |
|
Fitted with thermal overload relay |
-25 to +55 °C |
|
|
|
|
|
|
|
|
Fitted with electronic overload relay |
-25 to +70 °C |
|
|
|
|
|
|
|
|
Without electronic overload relay |
|
-40 to +70 °C |
|
|
|
|
|
Storage |
|
|
|
-40 to +70 °C |
|
|
|
|
Climatic withstand |
|
|
acc. to IEC 60068-2-30 |
|
|
|
|||
Maximum operating altitude (without derating) |
|
3000 m |
|
|
|
|
|||
Mechanical durability |
|
|
|
|
|
|
|
||
|
Number of operating cycles |
|
5 millions operating cycles |
|
|
|
|||
|
Max. switching frequency |
|
3600 cycles/h (300 for AF… contactors) |
|
|
||||
Shock withstand acc. to IEC 60068-2-27 and EN 60068-2-27 |
|
|
|
|
|
|
|||
Mounting position 1 |
|
|
|
|
|
|
|
||
|
|
|
C1 |
Shock direction |
1/2 sinusoidal shock for 30 ms: no change in contact position, closed or open position |
||||
|
|
|
A |
5 g |
|
|
|
|
|
A |
A |
B1 |
B2 |
|
|
|
|
||
B1 |
5 g |
|
|
|
|
||||
|
ABB |
|
|
|
|
|
|
|
|
|
|
|
|
B2 |
5 g |
|
|
|
|
|
|
|
C2 |
C1 |
5 g |
|
|
|
|
|
|
|
C2 |
5 g |
|
|
|
|
|
|
|
|
|
|
|
|
|
Low Voltage Products & Systems
1SXU000023C0202 Rev. A