Across |
|
IEC/UL/CSA Technical data
A/E/F45...A/E/F75, 4-pole Utilization characteristics
Main pole - Utilization characteristics according to IEC
Contactor types |
AC operated |
A45 |
|
A50 |
|
A75 |
|
DC operated |
AE45 |
|
AE50 |
|
AE75 |
|
|
TAE45 |
|
TAE50 |
|
TAE75 |
|
AC / DC operated |
AF45 |
|
AF50 |
|
AF75 |
Standards |
|
IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1 |
|
|
||
Rated operational voltage Ue max. |
|
1000 V (690 V for AF.. contactors) |
|
|
|
|
Rated frequency (without derating) |
|
50 / 60 Hz |
|
|
|
|
Conventional free-air thermal current Ith |
|
|
|
|
|
|
acc. to IEC 60947-4-1, open contactors, θ ≤ 40 °C |
|
100 A |
|
100 A |
|
125 A |
With conductor cross-sectional area |
|
35 mm² |
|
35 mm² |
|
50 mm² |
AC-1 Utilization category |
|
|
|
|
|
|
For air temperature close to contactor |
|
|
|
|
|
|
Ie / Rated operational current AC-1 |
θ ≤ 40 °C |
70 A |
|
100 A |
|
125 A |
Ue max. ≤ 690 V, 50/60 Hz |
θ ≤ 55 °C |
60 A |
|
85 A |
|
105 A |
|
θ ≤ 70 °C (1) |
50 A |
|
70 A |
|
85 A |
With conductor cross-sectional area |
|
25 mm² |
|
35 mm² |
|
50 mm² |
Short-circuit protection device for contactors |
|
|
|
|
|
|
without thermal overload relay - Motor protection excluded |
|
|
|
|
|
|
Ue ≤ 500 V AC - gG type fuse |
|
80 A |
|
100 A |
|
160 A |
|
|
|
||||
Rated short-time withstand current Icw |
1 s |
1000 A |
|
|
|
|
At 40 °C ambient temperature, |
10 s |
650 A |
|
|
|
|
in free air from a cold state |
30 s |
370 A |
|
|
|
|
|
|
|
|
|
||
|
1 min |
250 A |
|
|
|
|
|
15 min |
110 A |
|
110 A |
|
135 A |
Power dissipation per pole |
Ie / AC-1 |
2.5 W |
|
5 W |
|
7 W |
Max. electrical switching frequency |
AC-1 |
600 cycles/h (300 for AF.., AE.., TAE..) |
|
|
||
|
|
|
|
|
|
|
(1) Unauthorized for TAE.. contactors |
|
|
|
|
|
|
Main pole - Utilization characteristics according to UL / CSA
Contactor types |
|
|
|
|
|
|
|
|
AC operated |
A45 |
A50 |
|
|
|
|
|
|
|
A75 |
|||||||
|
|
|
|
|
|
|
|
|
|
|
DC operated |
AE45 |
AE50 |
|
|
|
|
|
|
|
AE75 |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TAE45 |
TAE50 |
|
|
|
|
|
|
|
TAE75 |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
AC / DC operated |
AF45 |
AF50 |
|
|
|
|
|
|
|
AF75 |
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||
Standards |
|
|
|
|
|
|
|
|
|
|
|
|
|
UL 508, CSA C22.2 N°14 |
|
|
|
|
|
|
|
|
|
|
|
|
Max. operational voltage |
|
|
|
|
|
|
|
|
|
|
|
600 V |
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
UL / CSA general use rating |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
600 V AC |
|
|
|
|
|
|
|
|
|
|
|
|
|
65 A |
80 A |
|
|
|
|
|
|
|
105 A |
||
|
With conductor cross-sectional area |
|
|
|
|
|
|
|
AWG 6 |
AWG 4 |
|
|
|
|
|
|
|
AWG 2 |
||||||||
Max. electrical switching frequency |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
For general use |
|
|
|
|
|
|
|
|
|
|
|
|
600 cycles/h (300 for AF.., AE.. TAE..) |
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
Remark for 4-pole contactors fitted with 2 N.O. + 2 N.C. main poles |
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||
1 |
R3 |
R5 |
7 |
These contactors are suitable for controlling 2 separate circuits, i.e. 2 loads with 2 separate supplies, or 1 circuit comprising |
||||||||||||||||||||||
|
|
|
|
2 separate loads with a single supply (see diagrams below). When the contactor operates there is no mechanical overlapping |
||||||||||||||||||||||
|
|
|
|
between the N.O. poles and the N.C. poles: BREAK before MAKE. |
|
|
|
|
|
|
|
|
||||||||||||||
2 |
R4 |
R6 |
8 |
! |
|
|
These contactors are not suitable for a reversing starter or for controlling a single load from 2 separate supplies. |
|||||||||||||||||||
|
|
|
|
|
|
|||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
Block diagrams |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
– Single supply and 2 separate loads |
– 2 separate supplies and 2 separate loads |
||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
Supply |
|
|
|
|
|
|
|
|
|
|
Main |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
supply |
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Back-up |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
supply |
|
|
|
|
|
|
|
|
|
A1 |
1 |
|
R3 |
|
R5 |
7 |
|
|
|
A1 |
1 |
R3 |
|
R5 |
7 |
|
|
||||
|
|
|
|
|
|
|
|
|
R4 |
|
R6 |
8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
A2 |
2 |
|
|
|
|
|
A2 |
2 |
R4 |
|
R6 |
8 |
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
Load |
|
|
|
|
|
|
|
|
|
|
Load |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Load |
|
|
|
|
|
|
|
|
|
|
Load |
|
|
|
|
1.124 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Low Voltage Products & Systems |
1SXU000023C0202 Rev. A |
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage |
General technical data
AF45...AF75
Coil & mounting characteristics
Across |
|
Contactorsline |
|
|
the |
1
Magnet system characteristics
Contactor types |
|
AC / DC operated |
AF45 |
AF50 |
AF75 |
Coil operating limits |
|
AC or DC supply |
At θ ≤ 70 °C 0.85 x Uc min...1.1 x Uc max. |
|
|
acc. to IEC 60947-4-1 |
|
|
Please also refer to "Mounting characteristics and conditions for use" |
||
AC control voltage |
Rated control circuit voltage Uc |
48…250 V |
|
|
|
|
|
||||
50/60 Hz |
Coil consumption |
Average pull-in value |
210 VA |
|
|
|
|
Average holding value |
7 VA / 2.8 W |
|
|
DC control voltage |
Rated control circuit voltage Uc |
20…250 V DC |
|
|
|
|
Coil consumption |
Average pull-in value |
190 W |
|
|
|
|
Average holding value |
2.8 W |
|
|
Drop-out voltage |
|
|
55 % of Uc min. |
|
|
Voltage sag immunity |
|
|
Conditions of use on request |
|
|
acc. to SEMI F47 |
|
|
|
|
|
Dips withstand |
|
|
≥ 20 ms |
|
|
|
|
|
|
||
Operating time |
|
|
|
|
|
Between coil energization and: |
N.O. contact closing |
30…100 ms |
|
|
|
|
|
N.C. contact opening |
27…95 ms |
|
|
Between coil de-energization and: |
N.O. contact opening |
30…110 ms |
|
|
|
|
|
N.C. contact closing |
35…115 ms |
|
|
Mounting characteristics and conditions for use
Contactor types |
AC / DC operated AF45 |
AF50 |
|
AF75 |
Mounting positions |
Pos. 2 |
+30° -30° |
|
|
|
|
|
||
|
Pos. 4 |
|
|
|
|
Pos. 3 |
|
|
|
|
Pos. 1 |
Pos. 1 ± 30° |
Pos. 5 |
Pos. 6 |
|
|
|
|
Pos. 5 unauthorized for AF45-22-00, AF75-22-00 contactors |
|
|
|
|
Max. and add-on N.O. or N.C. auxiliary contacts: see accessory fitting details for 4-pole con- |
|
|
|
|
tactor AF45 ... AF110 |
Control voltage / Ambient temperature |
|
|
||
|
Mounting |
1, 1±30°, 2, 3, 4, 5 |
at θ ≤ 70 °C 0.85 x Uc min…1.1 x Uc max. |
|
|
positions |
6 |
|
Unauthorized |
Mounting distances |
|
|
The contactors can be assembled side by side |
|
Fixing |
On rail according to IEC 60715, EN 60715 |
|
35 x 15 mm or 75 x 25 mm |
|
|
By screws (not supplied) |
|
2 x M6 screws placed diagonally |
Low Voltage Products & Systems |
1.129 |
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage |
1SXU000023C0202 Rev. A |