ABB A40, A50, A63, A75, A95 Technical Data

...
0 (0)

 

 

line

 

 

the

 

Contactors

1

Across

 

IEC Technical data

A/E/L40, A/E/F50...A/F110, 3-pole Utilization characteristics

Main pole - Utilization characteristics according to IEC

Contactor types

 

AC operated

A40

 

A50

A63

A75

A95

A110

 

 

 

 

 

DC operated

AL40

 

AE50

AE63

AE75

 

 

 

 

 

 

TAL40

 

TAE50

 

TAE75

 

 

 

 

 

AC / DC operated

 

 

AF50

AF63

AF75

AF95

AF110

Standards

 

 

IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1

 

 

 

Rated operational voltage Ue max.

 

690 V

 

1000 V (690 V for AF.. contactors)

 

 

1000 V

 

 

 

 

 

 

Rated frequency (without derating)

 

50/60 Hz

 

 

 

 

 

 

 

 

 

Conventional free-air thermal current Ith

 

 

 

 

 

 

 

 

 

 

 

 

acc. to IEC 60947-4-1, open contactors, θ ≤ 40 °C

 

65

A

 

100 A

125 A

125 A

145 A

160 A

With conductor cross-sectional area

 

16 mm²

 

35 mm²

50 mm²

50 mm²

50 mm²

70 mm²

AC-1 Utilization category

 

 

 

 

 

 

 

 

 

 

 

 

For air temperature close to contactor

 

 

 

 

 

 

 

 

 

 

 

 

Ie / Rated operational current AC-1

θ ≤ 40 °C

60

A

 

100 A

115 A

125 A

145 A

160 A

Ue max. ≤ 690 V, 50/60 Hz

θ ≤ 55 °C

60

A

 

85

A

95

A

105 A

135 A

145 A

 

 

 

 

 

θ ≤ 70 °C (3)

42

A

 

70

A

80

A

85

A

115 A

130 A

With conductor cross-sectional area

 

16 mm²

 

35 mm²

50 mm²

50 mm²

50 mm²

70 mm²

AC-3 Utilization category

 

 

 

 

 

 

 

 

 

 

 

 

For air temperature close to contactor θ 55 °C

 

 

 

 

 

 

 

 

 

 

 

Ie / Max. rated operational current AC-3 (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

220-230-240 V

40

A

53

A

65

A

75

A

96 A

110 A

 

 

 

 

 

380-400 V

37

A

50

A

65

A

75

A

96 A

110 A

 

 

 

 

 

415 V

37

A

50

A

65

A

75

A

96 A

110 A

 

 

 

 

 

 

M

 

 

3-phase motors

440 V

37

A

45

A

65

A

70

A

93 A

100 A

3

 

 

 

 

 

500 V

33

A

45

A

55 A

65

A

80 A

100 A

 

 

 

 

 

690 V

25

A (4)

35

A

43

A

46

A

65 A

82 A

 

 

 

 

 

1000 V

 

23

A (6)

25

A (6)

28

A (6)

30 A

30 A

Rated operational power AC-3 (1)

 

 

 

 

 

220-230-240 V

11 kW

15 kW

18.5 kW

22 kW

25 kW

30 kW

 

 

 

 

 

380-400 V

18.5 kW

22 kW

30 kW

37 kW

45 kW

55 kW

 

 

 

 

1500 r.p.m. 50 Hz

415 V

18.5 kW

25 kW

37 kW

40 kW

55 kW

59 kW

 

 

 

 

 

M

 

1800 r.p.m. 60 Hz

440 V

22 kW

25 kW

37 kW

40 kW

55 kW

59 kW

3

 

 

 

 

3-phase motors

500 V

22 kW

30 kW

37 kW

45 kW

55 kW

59 kW

 

 

 

 

 

690 V

22 kW (4)

30 kW

37 kW

40 kW

55 kW

75 kW

 

 

 

 

 

1000 V

30 kW (6)

33 kW (6)

37 kW (6)

40 kW

40 kW

Rated making capacity AC-3

 

10 x Ie AC-3 acc. to IEC 60947-4-1

 

 

 

 

Rated breaking capacity AC-3

 

8 x Ie AC-3 acc. to IEC 60947-4-1

 

 

 

 

AC-8a Utilization category (without thermal overload relay - Ue 400 V 50/60 Hz - θ ≤ 40 °C)

 

 

 

 

 

 

Ie / Rated operational current AC-8a

 

50 A

63 A

 

85 A

95 A

120 A

140 A

Rated operational power AC-8a

 

22 kW

30 kW

 

45 kW

45 kW

55 kW

75 kW

Short-circuit protection device for contactors

 

 

 

 

 

 

 

 

without thermal overload relay - Motor protection excluded (2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ue ≤ 500 V AC - gG type fuse

 

63 A

100 A

 

125 A

160 A

160 A

200 A

Rated short-time withstand current Icw

1 s

600 A

1000 A

 

 

1320 A

 

at 40 °C ambient temperature,

10 s

400 A

650 A

 

 

800 A

 

in free air from a cold state

30 s

225 A

370 A

 

 

500 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 min

150 A

250 A

 

 

350 A

 

 

 

 

 

 

15 min

65 A

110 A

 

135 A

135 A

160 A

175 A

Maximum breaking capacity

 

 

 

 

 

 

 

 

cos φ = 0.45

 

at 440 V

820 A (5)

1300 A

 

 

1160 A

 

(cos φ = 0.35 for Ie > 100 A)

at 690 V

340 A (5)

630 A

 

 

800 A

 

Power dissipation per pole

Ie / AC-1

3 W

5 W

 

6.5 W

7 W

6.5 W

7.5 W

 

 

 

 

 

Ie / AC-3

1.3 W

1.3 W

 

1.5 W

2 W

2.7 W

3.6 W

Max. electrical switching frequency

AC-1

600 cycles/h

600 cycles/h (300 for AF.., AE.., TAE..)

300 cycles/h

 

 

 

 

 

 

AC-3

1200 cycles/h

600 cycles/h (300 for AF.., AE.., TAE..)

300 cycles/h

 

 

 

 

 

 

AC-2, AC-4

300 cycles/h

150 cycles/h

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1)For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".

(2)For the protection of motor starters against short circuits, see "Coordination with short-circuit protection devices".

(3)Unauthorized for TAL.., TAE.. contactors.

(4)AC-3, 690 V values for AL40 and TAL40 contactors: 18.5 kW, Ie = 21 A.

(5)Max. breaking capacity for AL40 and TAL40 contactors: 470 A at 440 V, 175 A at 690 V.

(6)AF contactors excluded.

1.84

Low Voltage Products & Systems

1SXU000023C0202 Rev. A

ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

ABB A40, A50, A63, A75, A95 Technical Data

 

 

line

 

 

the

 

Contactors

1

Across

 

UL/NEMA/CSA Technical data

A/E/L40; A/E/F50...A/F110, A/E/F50N2...A/E/F75N3, 3-pole Utilization characteristics

Main pole - Utilization characteristics according to UL / NEMA / CSA

Contactor types

AC operated

A40

A50

A63

 

A75

A95

A110

 

DC operated

AL40, TAL40

AE50, TAE50

AE63

 

AE75, TAE75

 

AC / DC operated

AF50

AF63

 

AF75

AF95

AF110

Standards

 

UL 508, CSA C

22.2 N°14

 

 

 

 

 

Max. operational voltage

 

600 V

 

 

 

 

 

 

NEMA size

 

2

 

3

NEMA continuous amp rating

Thermal current

45 A

 

90 A

NEMA maximum horse power ratings 1-phase, 60 Hz

 

 

 

 

 

 

 

 

 

115 V AC

3 hp

 

 

230 V AC

7-1/2

 

NEMA maximum horse power ratings 3-phase, 60 Hz

 

 

 

 

 

 

 

 

 

200 V AC

10 hp

 

25 hp

 

230 V AC

15 hp

 

30 hp

 

460 V AC

25 hp

 

50 hp

 

575 V AC

25 hp

 

50 hp

UL / CSA general use rating

 

 

 

 

 

 

 

 

600 V AC

 

60 A

80 A

90 A

 

105 A

125 A

150 A

With conductor cross-sectional area

 

AWG 6

AWG 4

AWG 3

 

AWG 2

AWG 1

AWG 1/0

UL / CSA maximum 1-phase motor rating

 

 

 

 

 

 

 

 

Full load current

120 V AC

34 A

34 A

56 A

 

80 A

80 A

100 A

 

240 V AC

40 A

40 A

50 A

 

68 A

88 A

110 A

Horse power rating

120 V AC

3 hp

3 hp

5 hp

 

7.5 hp

7.5 hp

10 hp

 

240 V AC

7.5 hp

7.5 hp

10 hp

 

15 hp

20 hp

25 hp

UL / CSA maximum 3-phase motor rating

 

 

 

 

 

 

 

 

Full load current (1)

200-208 V AC

32.2 A

48.3 A

62.1 A

 

78.2 A

92 A

92 A

 

220-240 V AC

42 A

54 A

68 A

 

80 A

80 A

104 A

 

440-480 V AC

40 A

52 A

77 A

 

77 A

77 A

96 A

 

550-600 V AC

41 A

52 A

77 A

 

77 A

77 A

99 A

Horse power rating (1)

200-208 V AC

10 hp

15 hp

20 hp

 

25 hp

30 hp

30 hp

 

220-240 V AC

15 hp

20 hp

25 hp

 

30 hp

30 hp

40 hp

 

440-480 V AC

30 hp

40 hp

60 hp

 

60 hp

60 hp

75 hp

 

550-600 V AC

40 hp

50 hp

75 hp

 

75 hp

75 hp

100 hp

Max. electrical switching frequency

 

 

 

 

 

 

 

 

For general use

 

600 cycles/h

600 cycles/h (300 for AF.., AE..)

 

300 cycles/h

 

For motor use

 

1200 cycles/h

600 cycles/h (300 for AF.., AE..)

 

300 cycles/h

 

(1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see “Motor rated operational powers and currents”.

General technical data

Contactor types

 

AC operated

A40

A50

A63

A75

A95

A110

 

 

 

DC operated

AL40, TAL40

AE50, TAE50

AE63

AE75, TAE75

 

 

 

AC / DC operated

AF50

AF63

AF75

AF95

AF110

Rated insulation voltage Ui

 

 

 

 

 

 

 

 

acc. to IEC 60947-4-1

 

1000 V

 

 

 

 

 

 

acc. to UL

 

 

600 V

 

 

 

 

 

Rated impulse withstand voltage Uimp.

 

8 kV

 

 

 

 

 

Electromagnetic compatibility

 

AF contactors complying with IEC 60947-1 / EN 60947-1 - Environment A

 

Ambient air temperature close to contactor

 

 

 

 

 

 

 

 

Operation

Fitted with thermal overload relay

-25...+55 °C

 

 

 

 

 

 

 

Without thermal overload relay

 

-40…+70 °C (55 °C max. for TAL.., and TAE.. contactor)

 

 

 

Storage

 

 

-60...+80 °C

 

 

 

-40...+70 °C

 

Climatic withstand

 

 

acc. to IEC 60068-2-30 and 60068-2-11

 

acc. to IEC 60068-2-30

 

 

 

 

UTE C 63-100 specification II

 

 

 

 

Maximum operating altitude (without derating)

 

3000 m

 

 

 

 

 

Mechanical durability

 

 

 

 

 

 

 

 

 

Number of operating cycles

 

10 millions operating cycles (5 millions for AE.. and TAE..)

 

 

 

Max. switching frequency

 

3600 cycles/h (300 for AF contactors)

 

 

 

Shock withstand acc. to IEC 60068-2-27 and EN 60068-2-27

 

 

 

 

 

 

 

Mounting position 1

 

 

 

 

 

 

 

 

 

 

C1

Shock direction

1/2 sinusoidal shock for 11 ms: no change in contact position, closed or open position (2)

 

 

 

A

20 g

 

 

For AL40, TAL40

 

A

A B1

B2

B1

10 g closed position / 5 g open position

A : 20 g closed position / 10 g open position

 

 

 

B2

15 g

 

 

B1 : 15 g closed position / 5 g open position

 

 

 

 

 

B2 : 10 g closed position / 10 g open position

 

 

 

C1

20 g

 

 

 

 

 

 

 

C1 : 20 g closed position / 8 g open position

 

 

C2

C2

20 g

 

 

C2 : 14 g closed position / 8 g open position

(2) These values are not valid for rail mounting with contactors A95 ... A110 and AF95 ... AF110.

1.88

Low Voltage Products & Systems

1SXU000023C0202 Rev. A

ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

 

 

line

 

 

the

 

Contactors

1

Across

 

General technical data

AF50...AF110, 3-pole

Coil & mounting characteristics

Magnet system characteristics

Contactor types

 

AC / DC operated

AF50

AF63

AF75

AF95

AF110

Coil operating limits

 

AC or DC supply

At θ ≤ 70 °C 0.85 x Uc min...1.1 x Uc max.

 

 

acc. to IEC 60947-4-1

 

 

Please also refer to "Mounting characteristics and conditions for use"

 

AC control voltage

Rated control circuit voltage Uc

48…250 V 50/60 Hz

 

 

 

50/60 Hz

Coil consumption

Average pull-in value

210 VA

 

 

350 VA

 

 

 

 

 

 

Average holding value

7 VA / 2.8 W

 

 

7 VA / 3.5 W

 

DC control voltage

Rated control circuit voltage Uc

20…250 V DC

 

 

 

 

 

Coil consumption

Average pull-in value

190 W

 

 

400 W

 

 

 

Average holding value

2.8 W

 

 

2 W

 

Drop-out voltage

 

 

55 % of Uc min.

 

 

 

 

Voltage sag immunity

 

 

Conditions of use on request

 

 

 

acc. to SEMI F47

 

 

 

 

 

 

 

Dips withstand

 

 

≥ 20 ms

 

 

 

 

Operating time

 

 

 

 

 

 

 

Between coil energization and:

N.O. contact closing

30…100 ms

 

 

30…80 ms

 

 

 

N.C. contact opening

27…95 ms

 

 

27…77 ms

 

Between coil de-energization and:

N.O. contact opening

30…110 ms

 

 

55…125 ms

 

 

 

N.C. contact closing

35…115 ms

 

 

60…130 ms

 

Mounting characteristics and conditions for use

Contactor types

 

AC / DC operated

AF50

AF63

AF75

AF95

AF110

Mounting positions

 

 

 

Pos. 2

+30° -30°

 

 

 

 

 

 

Pos. 4

 

 

 

 

 

 

 

 

 

Pos. 3

 

 

 

 

 

 

 

 

Pos. 1

Pos. 1 ± 30°

Pos. 5

Pos. 6

 

 

 

 

Max. built-in and add-on N.O. or N.C. auxiliary contacts:

 

 

 

 

 

 

see accessory fitting details for 3-pole contactor AF50 ... AF110

 

Control voltage / Ambient temperature

 

 

 

 

 

 

Mounting

 

1, 1±30°, 2, 3, 4, 5

at θ ≤ 70 °C

0.85 x Uc min…1.1 x Uc max.

 

 

 

positions

 

6

 

Unauthorized

 

 

 

 

Mounting distances

 

 

The contactors can be assembled side by side

 

 

Fixing

On rail according to IEC 60715, EN 60715

35 x 15 mm or 75 x 25 mm

 

 

 

By screws (not supplied)

 

2 x M6 screws placed diagonally

 

 

 

1.94

Low Voltage Products & Systems

1SXU000023C0202 Rev. A

ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage