38QP024/40RR024 Heat Pump System 50/60 Hz

Installation, Start-Up and Service Instructions

Piping Package No. 40RR900271

NOTE: Read and become familiar with these instructions before beginning installation.

SAFETY CONSIDERATIONS

Installing and servicing air-conditioning equipment can be hazardous due to system pressures and electrical com­ ponents. Only trained and qualified service personnel should install or service air-conditioning equipment. When work­ ing on air-conditioning equipment, observe the precautions provided in literature, and on tags and labels attached to the unit.

A WARNING

Electrical shock can cause personal injury or death. Before beginning any modification or installation of this package, be sure the main electrical disconnect is in the off position. Ensure power is disconnected to the fan coil unit. On some systems both the fan coil and the outdoor unit may be on the same disconnect. Tag the disconnect switch with a suitable warning label.

GENERAL

The accessory heat pump piping package is designed for use with the Carrier 38QP024 heat pump (outdoor section) in combination with the 40RR024 fan coil unit (indoor section) (see Fig. 1).

Special accessories are available for electrical control of this system. Electric heaters for the 40RR024 are a fieldinstalled accessory. Ensure that all material required for installation is available at the jobsite, including the 38QP024 outdoor section, the 40RR024 indoor section, piping pack­ age, electrical control package, and 40RT electric heater packages. The Sporlan part no. G8 nozzle is used for both the upper (circuit no. 2) and lower (circuit no. 1) coil sec­ tions of the indoor unit. Nozzles are shipped as standard parts of the factory-installed 40RR distributor. Distributor sizes are as follows:

COIL SECTION

DISTRIBUTOR SIZE

(in. OD)

 

Upper (Ckt 2)

7/8

Lower (Ckt 1)

7/8

OUTDOOR SECTION

38QP024

INDOOR SECTION 40RR024

Fig. 1 — 38QP024/40RR024 Heat Pump System

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without Incurring obligations.

Book 11

PC 111

Catalog No 563-710

Printed in U.S. A

Form 38QP-5SI

Pg 1

11-92

Repiaces: New

Tab 5a

 

 

 

 

 

 

 

Accessories

PIPING PACKAGE — Contains check valves, thermo­ static expansion valves (TXV’s), receiver, filter driers, and tubing to connect the indoor coils for heat pump service.

THERMOSTAT HH07AT172 (HH07AT162 For Use on Celsius Scale) — Used with subbase HH93AZ174, is a 2-stage cool/2-stage heat thermostat with automatic changeover and a lockout light. There is no provision for emergency heat.

THERMOSTAT HH07AT172 (HH07AT162 For Use on Celsius Scale) — Used with subbase HH93AZ177, is a 2-stage cool/2-stage heat thermostat. This combination has all the features of HH07AT172 (HH07AT162)/HH93AZ174 plus a provision for emergency heat.

SEQUENCER PACKAGE — Can be used with this system when unloaders are added to the compressor(s). (Unloading can be applied in the cooling cycle only. Unloading can never be applied in the heating cycle.) The sequencer has 4-stage cooling capability.

ELECTRIC HEATERS — May be used with the 40RR in­ door unit (see Table 1). Use a maximum of four 20-kW (at 240 v) or 21.8-kW (at 480 v) electric heater assemblies.

ELECTRIC HEATER CONTROL PACKAGE 40RT900081

— Provides control for up to 3 stages of electric heat when used with outdoor-air thermostat(s). Package must be used whenever 40RT electric heaters are utilized. If a fourth stage of electric heat is used, an additional field-supplied heater control relay is necessary. This relay must have a 24-V coil with 230-v contacts. Outdoor thermostats (part no. HH22QA040) are recommended for staging elec­ tric heaters.

Table 1 — Unit 40RR Accessory Electric Heaters

PART NO.

 

ELECTRIC HEATER (3 PHASE 50/60 Hz)

 

Rated

kW

FLA

 

 

Voltage

 

 

 

 

40RT-900-101

 

240

20.0

48 0

40RT-900-111

 

480

21.8

26.0

LEGEND

 

 

 

FLA — Full Load Amps

NOTES;

1. A maximum of 4 electric heaters can be used with the 40RR024 unit.

2Electric heaters are not UL (Underwriters’ Laboratories) listed for the 38QP/40RR heat pump.

WATTAGE MULTIPLICATION FACTORS

Heater Voltage

Actual Heater

Multiplication

Voltage

Rating

Factor

(3 Phase, 50/60 Hz)

 

 

 

200

0.69

240

208

0.75

220

0.84

 

230

0.92

 

240

1.00

 

380

0.63

 

400

0 69

480

415

0.75

440

0.84

 

460

0.92

 

480

1.00

Example: 20.0 kW (at 240 v) heater on 230 v

=20.0 (0.92 multiplication factor)

=18.4 kW capacity at 230 v

INSTALLATION

Step 1 — Perform Outdoor and Indoor Unit Installation — Follow the installation instructions pro­ vided with each outdoor and indoor unit. See Table 2 for maximum vertical elevation between the indoor and out­ door sections.

Table 2 - Maximum Vertical Separation

 

 

HEIGHT OF INDOOR UNIT

SYSTEM

Above Outdoor

Below Outdoor

 

Unit

 

Unit

 

 

 

 

ft

 

m

ft

 

m

40RR024/38QP024,

59

 

180

59

 

18.0

60 Hz, Ckt 1 and 2

 

 

 

 

 

 

 

 

40RR024/38QP024,

58

 

17.7

58

 

17.7

50 Hz, Ckt 1 and 2

 

 

 

 

 

 

 

 

Step 2 Size Piping Lines — Employ one of the following methods to size interconnecting refrigerant pip­ ing between the 38QP and the 40RR:

1. Use the pipe sizes shown in Refrigerant (R-22) Charge and Piping Selection table in the 38QP installation in­ structions (when not using field-installed accessory un­ loaders).

2. Use the Carrier System Design Manual, Part 3, Piping Design (when using field-installed accessory unloaders).

3. Use the piping sizing portion of the Carrier E20-II com­ puter program (when using field-installed accessory unloaders).

NOTE: Liquid line solenoid valves are not required; they are factory-installed on the 38QP.

Step 3 - Check Contents of Piping Package

— Install heat pump piping package to convert indoor coil for heat pump service. Table 3 lists the contents of the pip­ ing package. Figure 2 shows the contents of the piping pack­ age in the approximate order in which they are installed.

Table 3 — Heat Pump Piping Package Contents

DESCRIPTION

QUANTITY

Receiver, Piping Assy (Ckt 1)

1

Piping Assy (Ckt 2)

1

Filter Drier (Ckt 1 and 2)

2

Receiver, Piping Assy Support Bracket

1

(Cktl)

 

Filter Drier Support Bracket (Ckt 2)

1

TXV (Thermostatic Expansion Valve)

2

(Ckt 1 and 2)

 

Screw, Receiver Strap*

1

Screws, No. 10 for Filter Drier Strap (4)

8

5/8" Tube Clamp (2), Filter Drier Support

Bracket (2)*

 

Tube, Filter Drier to TXV (Ckt 1)

1

Tube, Filter Drier to TXV (Ckt 2)

1

Strapping, 11" Long for Filter Driers

2

(Ckt 1 and 2)

 

Strapping, 10" Long for Receiver (Ckt 1)

1

Clamp for 5/8" OD Tube (Ckt 1)

1

Installation Instructions*

1

Strap for TXV Sensort

2

Screw and Nut for TXV Strapt

2

‘Items are included in a packet which accompanies piping package, titems are packed together with TXV.