Yaskawa 120 User Manual

0 (0)
Yaskawa 120 User Manual

MEMOCON GL120, GL130

120-SERIES I/O MODULES

USER'S MANUAL

MANUAL NO. SIE-C825-20.22C

Manual Contents

This manual describes specifications, connections, and precautions for 120-series I/O Modules. The 120-series I/O Modules are used with the MEMOCON GL120, GL130 Programmable Controllers (PLCs).

Read this manual carefully and be sure to understand the information provided before attempting to install or use 120-series I/O Modules.

Also, keep this manual in a safe place so that it can be used whenever necessary.

Visual Aids

IMPORTANT

EXAMPLE

INFO

SUMMARY

Note

TERMS

The following aids are used to indicate certain types of information for easier reference.

Indicates references for additional information.

Indicates important information that should be memorized.

Indicates application examples.

Indicates supplemental information.

Indicates a summary of the important points of explanations.

Indicates inputs, operations, and other information required for correct operation but that will not cause damage to the device.

Indicates definitions of terms used in the manual.

Notice

The following conventions are used to indicate precautions in this manual. Failure to heed precautions provided in this manual can result in injury to people or damage to the products.

WARNING Indicates precautions that, if not heeded, could possibly result in loss of life or serious injury.

CAUTION Indicates precautions that, if not heeded, could result in relatively serious or minor injury, damage to the product, or faulty operation.

© Yaskawa, 1998

All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of Yaskawa. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because Yaskawa is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, Yaskawa assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.

iii

CONTENTS

Manual Contents - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - iii Visual Aids- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - iii Notice - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - iii

1 Introduction and Precautions

1.1 Overview of Manual - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-2

1.2 Precautions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-3

1.2.1 Safety Precautions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1-3

1.2.2 Installation Precautions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1-4

1.2.3 Removal Precautions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1-5

1.2.4 Wiring Precautions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1-6

1.2.5 Application Precautions- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-11

1.2.6 Maintenance - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-14

1.3 Using This Manual - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-15

2 Models and General Specifications of I/O Modules

2.1 General Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - 2-2

2.2 I/O Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2-3

2.2.1 Models of I/O Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2-3

2.2.2 Overview of I/O Module Specifications - - - - - - - - - - - - - - - - - - - - - - -2-5

2.2.3 Using I/O Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2-10

3 Digital I/O Specifications

3.1 Digital Input Module specifications - - - - - - - - - - - - - - - - - - 3-2

3.1.1 100-VAC 16-point Input Module - - - - - - - - - - - - - - - - - - - - - - - - - - - -3-2 3.1.2 200-VAC 16-point Input Module - - - - - - - - - - - - - - - - - - - - - - - - - - - -3-6 3.1.3 12/24-VDC 16-point Input Module - - - - - - - - - - - - - - - - - - - - - - - - - 3-10 3.1.4 12/24-VDC 32-point Input Module - - - - - - - - - - - - - - - - - - - - - - - - - 3-14 3.1.5 12/24-VDC 64-point Input Module - - - - - - - - - - - - - - - - - - - - - - - - - 3-18

3.2 Digital Output Module Specifications - - - - - - - - - - - - - - - - 3-24

3.2.1 100/200-VAC 8-point Output Module - - - - - - - - - - - - - - - - - - - - - - - 3-24 3.2.2 100/200-VAC 16-point Output Module - - - - - - - - - - - - - - - - - - - - - - 3-28 3.2.3 12/24-VDC 8-point Output Module - - - - - - - - - - - - - - - - - - - - - - - - - 3-32 3.2.4 12/24-VDC 16-point Output Module (Sinking) - - - - - - - - - - - - - - - - - 3-36 3.2.5 12/24-VDC 16-point Output Module (Sourcing) - - - - - - - - - - - - - - - - 3-40 3.2.6 12/24-VDC 32-point Output Module - - - - - - - - - - - - - - - - - - - - - - - - 3-44 3.2.7 12/24-VDC 64-point Output Module - - - - - - - - - - - - - - - - - - - - - - - - 3-49 3.2.8 Relay Contact 16-point Output Module - - - - - - - - - - - - - - - - - - - - - - 3-55

3.3 I/O Module Cables - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-60

3.3.1 I/O Module Cable Types - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-60 3.3.2 W0300 Cables (Model No. JZMSZ-120W0300- ) - - - - - - - - - - - - 3-62 3.3.3 W0302 Cables (Model No. JZMSZ-120W0302- ) - - - - - - - - - - - - 3-65 3.3.4 W0301 Cables (Model No. JZMSZ-120W0301- ) - - - - - - - - - - - - 3-68 3.3.5 32-point I/O Connector Terminal Block - - - - - - - - - - - - - - - - - - - - - - 3-71 3.3.6 W5410 Cables (Model No. JEPMC-W5410- ) - - - - - - - - - - - - - - - 3-74

v

3.4 I/O Allocation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-81

3.4.1 16-point Input Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-81

3.4.2 32-point Input Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-84

3.4.3 64-point Input Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-87

3.4.4 8-point Output Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-92

3.4.5 16-point Output Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-94

3.4.6 32-point Output Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-97

3.4.7 64-point Output Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-101

3.5 Operations Using MEMOSOFT - - - - - - - - - - - - - - - - - - - 3-106

3.5.1 MEMOSOFT Versions Supporting 64-point I/O Modules - - - - - - - - 3-106 3.5.2 Digital Input Module I/O Allocation Screen - - - - - - - - - - - - - - - - - - 3-107 3.5.3 Digital Output Module I/O Allocation Screen - - - - - - - - - - - - - - - - - 3-108 3.5.4 I/O Allocations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-109

4 Analog I/O Specifications

4.1 Analog Input Specifications - - - - - - - - - - - - - - - - - - - - - - - - 4-2

4.1.1 Analog Input Modules (±10 V, 4 channels) - - - - - - - - - - - - - - - - - - - - 4-2 4.1.2 Analog Input Modules (0 to 10 V, 4 channels) - - - - - - - - - - - - - - - - - - 4-8 4.1.3 Analog Input Modules (4 to 20-mA, 4 channels) - - - - - - - - - - - - - - - 4-14

4.2 Analog Output Specifications- - - - - - - - - - - - - - - - - - - - - - 4-20

4.2.1 Analog Output Modules (±10 V, 2 channels) - - - - - - - - - - - - - - - - - - 4-20 4.2.2 Analog Output Modules (0 to 10 V, 2 channels) (0 to 5 V, 2 channels) 4-25 4.2.3 Analog Output Modules (4 to 20-mA, 2 channels) - - - - - - - - - - - - - - 4-30

4.3 I/O Allocation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-35

4.3.1 Analog Input Modules- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-35

4.3.2 Analog Output Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-39

4.4 Operations Using MEMOSOFT - - - - - - - - - - - - - - - - - - - - 4-41

4.4.1 Analog Input Module I/O Allocation Screen- - - - - - - - - - - - - - - - - - - 4-41 4.4.2 Analog Output Module I/O Allocation Screen - - - - - - - - - - - - - - - - - 4-42 4.4.3 I/O Allocations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-43

5 Register I/O Specifications

5.1 Register Input Specifications - - - - - - - - - - - - - - - - - - - - - - - 5-2

5.1.1 Register Input Modules- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-2

5.2 Register Output Specifications- - - - - - - - - - - - - - - - - - - - - - 5-6

5.2.1 Register Output Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-6

5.3 I/O Allocation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-10

5.3.1 Register Input Modules- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-10

5.3.2 Register Output Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-13

5.4 Operations Using MEMOSOFT - - - - - - - - - - - - - - - - - - - - 5-17

5.4.1 Register Input Module I/O Allocation Screen- - - - - - - - - - - - - - - - - - 5-17 5.4.2 Register Output Module I/O Allocation Screen - - - - - - - - - - - - - - - - 5-18 5.4.3 I/O Allocations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-20

vi

6 Installation and Wiring

6.1 Installing Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6-2

6.1.1 Module Installation Location - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -6-2 6.1.2 Installing I/O Modules with Terminal Blocks - - - - - - - - - - - - - - - - - - - -6-4 6.1.3 Installing I/O Modules with Connectors - - - - - - - - - - - - - - - - - - - - - - 6-10

6.2 Panel Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6-13

6.2.1 Separation of Power Supply Systems - - - - - - - - - - - - - - - - - - - - - - - 6-13

6.2.2 Wiring AC I/O Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6-14

6.2.3 Wiring DC I/O Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6-17

6.2.4 Wiring Analog I/O Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6-25

6.2.5 Grounding - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6-28

6.3 External Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6-31

6.3.1 External Wiring for Digital I/O Modules - - - - - - - - - - - - - - - - - - - - - - 6-31

6.4 Precautions on Wiring - - - - - - - - - - - - - - - - - - - - - - - - - -

6-32

6.4.1 AC Input Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

- 6-32

6.4.2 AC Output Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

6-35

6.4.3 DC Input Modules- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

6-40

6.4.4 DC Output Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

6-45

6.4.5 Connections between AC I/O Modules - - - - - - - - - - - - - - - - - - - - -

6-49

6.4.6 Connections between DC I/O Modules - - - - - - - - - - - - - - - - - - - - -

6-50

6.4.7 Analog Input Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

6-50

6.4.8 Analog Output Modules- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

6-51

6.4.9 External Power Supplies - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

6-52

7 Maintenance

7.1 Built-in Fuses - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 7-2

7.1.1 I/O Modules with Built-in Fuses - - - - - - - - - - - - - - - - - - - - - - - - - - - -7-2

7.1.2 Built-in Fuses - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -7-3

7.1.3 Replacement of Built-in Fuses - - - - - - - - - - - - - - - - - - - - - - - - - - - - -7-5

7.2 Hot Swapping - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 7-6

7.2.1 Hot Swapping- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -7-6

8 EN Standard Low voltage Directive Compliant I/O Modules

8.1 EN Standard Compliant I/O Modules - - - - - - - - - - - - - - - - - 8-2

8.1.1 Low Voltage Directive Compliant I/O Modules - - - - - - - - - - - - - - - - - -8-2

8.1.2 External Appearances- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -8-3

8.1.3 EN Standards- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -8-5

8.1.4 Specifications of the I/O Modules - - - - - - - - - - - - - - - - - - - - - - - - - - -8-7

Appendix A External Dimensions

A.1 I/O Module Types- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A-2 A.2 I/O Modules with Terminal Blocks - - - - - - - - - - - - - - - - - - - A-3 A.3 DC 32-point I/O Modules - - - - - - - - - - - - - - - - - - - - - - - - - A-3 A.4 DC 64-point I/O Modules - - - - - - - - - - - - - - - - - - - - - - - - - A-4 A.5 Register I/O Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - A-4

INDEX

vii

Introduction and Precautions

1

 

1

This chapter introduces the features of 120-series I/O Modules and provides precautions for the use of this manual and the product.

Read this chapter before attempting to read the rest of the manual or use the product.

1.1 Overview of Manual - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-2

1.2 Precautions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-3

1.2.1 Safety Precautions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-3

1.2.2 Installation Precautions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-4

1.2.3 Removal Precautions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-5

1.2.4 Wiring Precautions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-6

1.2.5 Application Precautions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-11

1.2.6 Maintenance - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-14

1.3 Using This Manual - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-15

1-1

1Introduction and Precautions

1.1Overview of Manual

This manual describes the functional specifications of the 120-series I/O Modules used for the MEMOCON GL120 and GL130 Programmable Controllers. Read this manual carefully in order to use the 120-series I/O Modules properly. Also, keep this manual in a safe place so that it can be used whenever necessary.

Refer to the following manuals for related Peripheral Devices and Modules.

Product

Manual Name

Manual No.

 

Contents

 

 

 

 

CPU Module

MEMOCON GL120, GL130

SIEZ-C825-20.1

Gives information on the GL120 and GL130 hard-

 

Hardware User’s Manual

 

ware, including explanations on the following items.

 

 

 

1)

System configuration

 

 

 

2)

System components

 

 

 

3)

Function and specifications of system compo-

 

 

 

 

nents

 

 

 

4)

Installation and wiring

 

 

 

5)

Examples of panel-layout and hole dimensions

 

 

 

6)

External Dimensions

 

 

 

 

 

MEMOCON GL120, GL130

SIEZ-C825-20.11

Describes the following items for the GL120 and

 

Software User’s Manual Vol. 1

 

GL130.

 

 

 

1)

Operating principles

 

 

 

2)

I/O allocation

 

 

 

3)

Overview of instructions

 

 

 

4)

Instruction processing times

 

 

 

 

 

MEMOCON GL120, GL130

SIEZ-C825-20.12

Describes the programming instructions used to

 

Software User’s Manual Vol.2

 

create ladder programs for the GL120 and GL130.

 

 

 

The following items are explained in other manuals.

 

 

 

1)

Expansion Math instructions

 

 

 

2)

Process control instructions

 

 

 

3)

Communications instructions

 

 

 

4)

Motions control instructions (ladder motion

 

 

 

 

instructions)

 

 

 

5)

Motion language

 

 

 

 

Human-

MEMOCON GL120, GL130

SIEZ-C825-60.7

Describes the functions, specifications, and opera-

Machine

MEMOSOFT for P120

 

tional methods of the Programming Panel P120 with

Interface

Programming Panel

 

built-in MEMOSOFT.

 

User’s Manual

 

 

 

 

 

 

 

 

MEMOCON GL120, GL130

SIEZ-C825-60.10

Describes the functions and operational methods of

 

MEMOSOFT

 

MEMOSOFT for DOS.

 

User’s Manual

 

 

 

 

 

 

 

 

MEMOCON GL120, GL130

SIEZ-C825-60.25

Describes the functions and operational methods of

 

MEMOSOFT for Windows

 

MEMOSOFT for Windows.

 

User’s Manual

 

 

 

 

 

 

 

 

Thoroughly check the specifications and conditions or restrictions of the product before use.

1-2

1.2 Precautions

1.2Precautions

This section outlines general precautions that apply to using this manual and the product. Read this section first before reading the remainder of the manual.

1.2.1

Safety Precautions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

- 1-3

 

1.2.2

Installation Precautions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

- 1-4

 

1

1.2.3

Removal Precautions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

1-5

1.2.4

Wiring Precautions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

1-6

1.2.5

Application Precautions

1-11

 

 

1.2.6

Maintenance - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

1-14

 

1.2.1Safety Precautions

The GL120 and GL130 were not designed or manufactured for use in devices or systems directly related to human life. Users who intend to use the product described in this manual for special purposes such as devices or systems relating to transportation, medical, space aviation, atomic power control, or underwater use must contact Yaskawa Electric Corporation beforehand.

This product has been manufactured under strict quality control guidelines. However, if this product is to be installed in any location in which a failure of GL120 and GL130 involves a life and death situation or in a facility where failure may cause a serious accident, safety devices MUST be installed to minimize the likelihood of any accident.

Any illustrations, photographs, or examples used in this manual are provided as examples only and may not apply to all products to which this manual is applicable.

The products and specifications described in this manual or the content and presentation of the manual may be changed without notice to improve the product and/or the manual. A new version of the manual will be released under a revised manual number when any changes are made.

Contact your Yaskawa representative or a Yaskawa office listed on the back of this manual to order a new manual whenever this manual is damaged or lost. Please provide the manual number listed on the front cover or this manual when ordering.

Contact your Yaskawa representative or a Yaskawa office listed on the back of this manual to order new nameplates whenever a nameplate becomes worn or damaged.

Yaskawa cannot guarantee the quality of any products that have been modified. Yaskawa assumes no responsibility for any injury or damage caused by a modified product.

1-3

1 Introduction and Precautions

1.2.2Installation Precautions

1.2.2Installation Precautions

 

Abide by the following precautions when installing MEMOCON systems.

CAUTION

• The installation environment must meet the environmental conditions given in prod-

 

uct catalogs and manuals. Using the GL120 and GL130 in environments subject to

 

high temperatures, high humidity, excessive dust, corrosive gases, vibration, or

 

shock can lead to electrical shock, fire, or faulty operation. Do not use the GL120

 

and GL130 in the following locations.

 

• Locations subject to direct sunlight or ambient temperatures not between 0 °C

 

and 60 °C.

 

• Locations subject to relative humidity in excess of 95%, or condensation

 

because of rapid changes in humidity.

 

• Locations subject to corrosive or flammable gas.

 

• Locations that would subject the GL120 and GL130 to direct vibration or

 

shock.

 

• Locations subject to contact with water, oil, chemicals, and so on.

CAUTION

• Install Modules as described in the user’s manuals.

 

Faulty or inappropriate installation may result in detachment or malfunction.

CAUTION

• Do not remove the connector covers from the Module connectors on the Mounting

 

Base slots where no Modules are installed.

 

The presence of any foreign matter in a Module connector may cause the

 

GL120 and GL130 to malfunction.

CAUTION

• Make sure that all mounting screws for the Modules are securely tightened.

 

Loose screws may cause malfunction of the GL120 and GL130.

CAUTION

• Make sure that all mounting screws for the terminal block are securely tightened.

 

Loose screws may cause a malfunction of the GL120 and GL130.

CAUTION

CAUTION

CAUTION

When installing the terminal block for the AC I/O Modules, turn OFF the AC power supply to the I/O Modules for inputting signals and for driving load.

Installing a terminal block with the AC power being supplied to the terminal of the external power supply for the AC I/O Modules may cause an electric shock if the power supply terminals are touched.

When using a single-phase AC power supply (100/200 VAC) for driving loads of the Relay Contact Output Module, turn OFF the AC power to the Modules for driving loads before installing the terminal block for the Modules.

Installing a terminal block with the AC power being supplied to the external power supply terminal of the Relay Contact Output Module may cause an electric shock if the power supply terminals are touched.

Make sure that all cable connectors for the Module are securely inserted and tightened.

Incorrect connections may cause malfunction of the GL120 or GL130.

1-4

1.2 Precautions

1.2.3Removal Precautions

CAUTION

CAUTION

CAUTION

CAUTION

Always turn OFF the AC power supply to the AC I/O Modules that are used for inputting signals and driving loads before removing the terminal block from the AC I/ O Modules.

Removing a terminal block with AC power to the external power supply terminal of the AC I/O Modules may cause an electric shock at touching the power sup-

ply terminals.

1

 

When using a single-phase AC power supply (100/200 VAC) for driving loads of the Relay Contact Output Module, turn OFF the AC power to the Modules for driving loads before removing the terminal block for the Modules.

Removing a terminal block with the AC power being supplied to the external power supply terminal of the Relay Contact Output Module may cause an electric shock if the power supply terminals are touched.

When inserting or removing an AC I/O Module while the AC power supply is turned ON, install a safety switch for each Module and always turn this safety switch OFF to turn OFF the AC power supply to the Module.

Inserting or removing an AC I/O Module while AC power is being supplied may result in an electric shock at touching the power supply terminals.

When using a single-phase AC power supply (100/200 VAC) for driving the loads of the Relay Contact Output Module, install a safety switch for each Module. Before inserting or removing the Relay Contact Output Module, always turn this safety switch OFF to turn OFF the AC power supply to the Module.

Inserting or removing a Relay Contact Output Module while AC power is being supplied may result in an electric shock at touching the power supply terminals.

1-5

1 Introduction and Precautions

1.2.4 Wiring Precautions

1.2.4Wiring Precautions

CAUTION • Wiring must be performed by qualified personnel.

Wrong or inappropriate wiring may result in fire, product failure, or electric shock.

CAUTION • Connect the correct power supply for the required ratings.

Connecting unsuitable power supplies may result in fires.

CAUTION

• Do not allow foreign matter such as cable chips in the Modules or Mounting Bases.

 

Foreign matter in the Modules or Mounting Bases may cause fire, failures and/

 

or malfunctions.

CAUTION

• Connect power supplies of the same phases to the common 1 and common 2 of the

 

AC I/O Module.

 

If power supplies of different phases are connected, overheating or fire may

 

occur.

CAUTION

• If using a single-phase AC power supply (100/200 VAC) for driving the loads of the

 

Relay Contact Output Module, connect power supplies with the same phases to the

 

common 1 and common 2 of the Module.

 

If power supplies of different phases are connected, overheating or fire may

 

occur.

CAUTION

• If using an Output Module, connect a fuse that complies with the load specifications

 

in series with the load.

A protective fuse is not built into the following Output Modules. If a fuse is not connected, a fire or damage to the device or output circuits may occur if the load is short-circuited or the circuit overloaded.

100/200-VAC 8-point Output Module: Model No. JAMSC-120DAO083000

Relay contact 16-point Output Module: Model No. JAMSC-120DRA84300

CAUTION

• If using an Output Module, connect a fuse that complies with the load specifications

 

in series with the load.

A protective fuse built into the following Output Modules does not protect the output element. If a fuse is not connected, a fire or damage to the device or output circuits may occur if the load is short-circuited or the circuit overloaded.

100/200-VAC 16-point Output Module: Model No. JAMSC-120DAO84300

12/24-VDC 8-point Output Module: Model No. JAMSC-120DDO33000

12/24-VDC 16-point Output Module: Model No. JAMSC-120DAO34310

12/24-VDC 16-point Output Module: Model No. JAMSC-120DAO34320

12/24-VDC 32-point Output Module: Model No. JAMSC-120DAO35410

12/24-VDC 64-point Output Module: Model No. JAMSC-120DAO36410

1-6

1.2 Precautions

CAUTION

CAUTION

Connect an AC power supply (100/200 VAC) or a DC power supply (12/24 VDC) to the Power Supply for driving loads of the Relay Contact Output Module.

Do not connect both an AC power supply and a DC power supply to one Module at the same time. If unsuitable power supplies are connected, in overheating or fire may result.

• Although a 0.6-A load can be connected to each output point for the AC 16-point

 

Output Module, the total load must be 2.4A or less for each common. Keep the

1

maximum load at 2.4A for each common.

If this limit is exceeded, damage may occur to the output circuit.

CAUTION

• Although a 0.5-A load can be connected to each output point for the DC 16-point

 

Output Module, the total load must be 1.0 A or less for each of the four output

 

points. Keep the load distribution within the 1.0 A limit.

 

If this limit is exceeded, damage may occur to the output circuit.

CAUTION

• Although a 0.3-A load can be connected to each output point of the DC 32-point

 

Output Module, the total load must be 0.4 A or less for each of the four output

 

points. Keep the load distribution within the 0.4 A limit.

 

If this limit is exceeded, damage may occur to the output circuit.

CAUTION

• If using an Output Module, connect a fuse that complies with the load specifications

 

in series with the load.

100/200-VAC 8-point Output Module: Model No. JAMSC-120DAO83000

100/200-VAC 16-point Output Module: Model No. JAMSC-120DAO84300

12/24-VDC 16-point Output Module (sinking output): Model No. JAMSC-120DDO33000

12/24-VDC 16-point Output Module (sourcing output): Model No. JAMSC-120DAO34320

12/24-VDC 32-point Output Module (sinking output): Model No. JAMSC-120DAO35410

12/24 VDC 64-point Output Module (sinking output): Model No. JAMSC-120DAO36410

Relay Contact 16-point Output Module: Model No. JAMSC-120DAO84300

 

If a fuse is not connected, a fire or damage to the device or output circuit may

 

occur if the load is short-circuited or the circuit overloaded.

CAUTION

• If connecting an inductive load in parallel with AC Input Module, connect the surge

 

absorber in parallel with the inductive load to prevent surge voltage.

 

Failure to connect a surge absorber may result in damage to the AC Input Mod-

 

ule.

CAUTION

• If connecting an inductive load to the AC Output Module, connect the surge

 

absorber in parallel with the inductive load to prevent surge voltage.

 

Failure to connect a surge absorber may result in damage to the AC Output

 

Module.

1-7

1 Introduction and Precautions

1.2.4 Wiring Precautions

CAUTION

• If connecting an inductive load in parallel with DC Input Module, connect the fly-

wheel diode in parallel with the inductive load to prevent surge voltage.

 

 

Failure to connect a flywheel diode may result in damage to the DC Input Mod-

 

ule.

CAUTION

• If connecting an inductive load to the DC Output Module, connect the flywheel

 

diode in parallel with the inductive load to prevent surge voltage.

 

Failure to connect a flywheel diode may result in damage to the DC Output

 

Module.

CAUTION

• If connecting a contact to an inductive load of the DC Output Module, connect the

 

flywheel diode in parallel with the inductive load to prevent surge voltage.

 

Failure to connect a flywheel diode may result in damage to the DC Output

 

Module.

CAUTION

• Insulation is not provided between the channels of the Analog Input Module.

 

To insulate all the analog signals connected to the Analog Input Module, use a com-

 

mercial isolation amplifier for each channel.

 

Incorrect connections may cause damages and malfunctions of the Analog

 

Input Modules.

CAUTION

• The maximum allowable load current for Analog Output Modules (±10V, 2 chan-

 

nels) is ±5 mA (2 kΩ). The load resistance must be 2 kΩ or more.

Incorrect connection may cause the output signal to be overloaded, and result in damages or malfunction of the Analog Output Module.

CAUTION

• The maximum allowable load current for Analog Output Modules (0 to10V, 2 chan-

 

nels) is 5 mA (2 kΩ). The load resistance must be 2 kΩ or more.

Incorrect connection may cause the output signal to be overloaded, and result in damages or malfunction of the Analog Output Module.

CAUTION

• The maximum allowable load current for Analog Output Modules (0 to 5V, 2 chan-

 

nels) is 2.5 mA (2 kΩ). The load resistance must be 2 kΩ or more.

Incorrect connection may cause the output signal to be overloaded, and result in damages or malfunction of the Analog Output Module.

CAUTION

• The maximum allowable load resistance for Analog Output Modules (4 mA to 20

 

mA, 2 channels) is 550 kΩ). The load resistance must be 550 kΩ or more.

Incorrect connection may cause the output signal to be overloaded, and result in damages or malfunction of the Analog Output Module.

CAUTION

• If using Low Voltage Directive compliant products, always use round crimp termi-

 

nals for M3 screws and mount insulation cover at each crimp when connecting

 

wires to wiring terminals.

 

If bare wires are used, an electric shock or a short-circuit may result if the wires

 

become loose.

1-8

1.2 Precautions

CAUTION

CAUTION

Ground the shield of the shielded twisted-pair wire that connects to the Analog I/O Module to one point (a resistance of 100 Ω max.).

Not grounding the shield of the shielded twisted-pair wire may result in malfunction of the GL120 and GL130.

Ground the ground terminal of the Analog Input Module to a resistance of 100 Ω max.

Not grounding the ground terminal may result in malfunction of the GL120 and

1

GL130.

 

 

Power Supply Noise Reduction

Prevent noise from penetrating into the product by installing an isolation transformer or a noise filter for the external power supply.

Noise from power supply may result in malfunction of the GL120 and GL130.

Do not install the GL120 and GL130 system components in the same control panel as high-voltage or high-current circuits.

Here, high-voltage circuits are those with voltages of 600 VAC or 750 VDC min. and high-current circuits are those with amperages of 800 A min.

When installing the GL120 and GL130 system components in the same control panel as low-voltage main circuits, separate the low-voltage circuits and related devices as far as possible from the GL120 and GL130 system components and wiring.

The recommended separation is 200 mm min. Here. low-voltage main circuits are those with voltages up to 600 VAC or 750 VDC and amperages of 20 A min.

Do not bundle GL120 and GL130 wiring together with wiring for normal control circuits.

Here, normal control circuits are those with voltages up to 600 VAC or 750 VDC and amperages up to 20 A.

Insert the Interface Cables Properly

Insert the connectors of the various interface cables that are to be connected to the GL120 and GL130 into the communication ports and secure them properly.

Improper insertion of interface cables may cause operational errors in the GL120 and GL130.

1-9

1 Introduction and Precautions

1.2.4 Wiring Precautions

Select, Separate, and Lay External Wiring Correctly

I/O lines connecting external devices to the 120-series I/O Modules must be selected based on the following considerations: mechanical strength, resistance to noise, wiring distance, signal voltage, and so on.

I/O lines must be separated from power lines both inside and outside the control panel to minimize the affects of noise. Faulty operation may result if I/O lines are not sufficiently separated from power lines.

Steel-plate separator

Example of external wiring separation

Power lines

General control

Digital I/O

Analog I/O

Pulse input

 

circuit cables

signal cables

signal cables

signal cables

1-10

1.2 Precautions

1.2.5Application Precautions

WARNING • Do not touch the Module terminals while the power is ON.

Touching live terminals may cause electric shock.

WARNING

• Construct an emergency stop circuit and an interlock circuit outside of the GL120

 

 

and GL130.

 

 

1

 

The absence of emergency stop and interlock circuits may result in machine

 

damage or accidents should the GL120 or GL130 fail.

 

 

 

 

Install an Emergency Stop Circuit Outside the GL120 and GL130.

 

WARNING

An emergency stop circuit for the control system should not be constructed

 

using the ladder programming in the GL120 and GL130. Always construct the emergency stop circuit externally using a relay circuit, as shown in the figure below.

Use an N.C. contact (mechanical contact) in the emergency stop switch. The main power supply to the servo must be cut off by pressing the switch.

Failure to provide an emergency stop circuit as described above, may result in failure of the emergency stop when input circuits fail or cables break, and may cause machine damage or injury.

Control power Control power supply ON

 

MC1

supply OFF

 

 

 

 

MC1

 

 

Z

Emergency stop

MC1

Servo OFF Servo ON

MC2

ESP-TBOX

ALM

MC2

Z

 

 

 

Surge absorber

Noise filter

MEMOCON GL120, GL130

MC1

Noise filter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

r SERVOPACK

Control signal to MC Module

t

 

 

 

MC2

 

Encoder

r

 

s

U

 

t

Servomotor

V

 

 

W

 

1-11

1 Introduction and Precautions

1.2.5 Application Precautions

 

External Interlocks for the GL120 and GL130

WARNING

Externally connect an interlock to the GL120 and GL130 if there is any chance

 

that GL120 and GL130 failure could result in bodily harm or equipment damage.

Always use an external interlock system as shown in the following example when reciprocal operations (e.g., forward and reverse directions) are being performed with a motor.

An interlock is generally programmed in the GL120 and GL130 ladder program to ensure that forward and reverse signals are not simultaneously output. An external interlock circuit must also be provided using the auxiliary contacts of electromagnetic contactors.

CPU Module

Output Module

Ladder logic program

Output program with an interlock which prohibit simultaneous forward and reverse runs

R

F

OL

 

 

Contact of over-

F

R

current protection

device.

 

 

Electric interlock using the auxiliary contacts of electromagnetic contactors

F (Forward run)

Induction motor

 

R (Reverse run)

CAUTION

• When inserting or removing an AC I/O Module while the AC power supply is turned

 

ON, install a safety switch for each Module and always turn this safety switch OFF

 

to turn OFF the AC power supply to the Module.

Inserting or removing an AC I/O Module while AC power is being supplied may result in an electric shock at touching the power supply terminals.

CAUTION

• When using a single-phase AC power supply (100/200 VAC) for driving the loads of

 

the Relay Contact Output Module, install a safety switch for each Module. Before

 

inserting or removing the Relay Contact Output Module, always turn this safety

 

switch OFF to turn OFF the AC power supply to the Module.

Inserting or removing a Relay Contact Output Module while AC power is being supplied may result in an electric shock at touching the power supply terminals.

1-12

1.2 Precautions

CAUTION

• The following CPU Modules, Remote I/O Receiver Modules, and MEMOSOFT ver-

 

sions are required to use DC 64-point I/O Modules.

 

 

 

 

 

 

 

 

 

Using a version that is not recommended may result in failure or malfunction.

 

 

 

 

 

 

 

 

 

 

 

 

Name

Model

Model No.

Version Number

Location of

 

 

 

 

 

Name

 

 

Version Number

 

 

 

 

CPU Module

CPU10

DDSCR-

A01 and later

Module nameplate

 

 

 

 

(8 kW)

 

120CPU14200

 

 

 

1

 

 

 

 

 

 

 

 

 

 

CPU Module

CPU20

DDSCR-

B05 and later

Module nameplate

 

 

 

(16 kW)

 

120CPU34100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPU Module

CPU21

DDSCR-

A01 and later

Module nameplate

 

 

 

 

(16 kW)

 

120CPU34110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPU Module

CPU30

DDSCR-

B05 and later

Module nameplate

 

 

 

 

(32 kW)

 

120CPU54100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPU Module

CPU35

DDSCR-

A01 and later

Module nameplate

 

 

 

 

(40 kW)

 

120CPU154110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote I/O

RIOR-

JAMSC-

A10 and later

Module nameplate

 

 

 

 

Receiver

COAX

120CRR13100

 

 

 

 

 

 

Module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MEMOSOFT

 

FMSGL-AT3

1.21 and later

In the middle at the

 

 

 

 

 

 

(for English

 

bottom of the

 

 

 

 

 

 

DOS)

 

MEMOSOFT

 

 

 

 

 

 

 

 

startup screen.

 

 

 

 

 

 

FMSGL-PP3E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(for P120

 

 

 

 

 

 

 

 

English version)

 

 

 

 

 

 

 

 

 

 

 

 

 

* The nameplate is on the right side of the Module.

1-13

1 Introduction and Precautions

1.2.6 Maintenance

1.2.6Maintenance

CAUTION • Do not disassemble or modify Modules and Mounting Bases.

Failure to observe this caution may result in fire, product failure, or malfunction.

CAUTION • Do not replace the built-in fuses of the AC 16-point Output Modules.

If the built-in fuses are replaced by anyone other than a Yaskawa-approved technician, a failure or a malfunction may occur in the AC 16-point Output Modules, and the guarantee is void.

CAUTION • Do not replace the built-in fuses of the DC 8-point Output Modules.

If the built-in fuses are replaced by anyone other than a Yaskawa-approved technician, a failure or malfunction may occur in the DC 8-point Output Modules, and the guarantee is void.

CAUTION • Do not replace the built-in fuses of the DC 32-point Output Modules.

If the built-in fuses are replaced by anyone other than a Yaskawa-approved technician, a failure or malfunction may occur in the DC 32-point Output Modules, and the guarantee is void.

CAUTION • Do not replace the built-in fuses of the DC 64-point Output Modules.

If the built-in fuses are replaced by anyone other than a Yaskawa-approved technician, a failure or malfunction may occur in the DC 64-point Output Modules, and the guarantee is void.

CAUTION • Do not replace the built-in fuses of the Register I/O Modules.

If the built-in fuses are replaced by anyone other than a Yaskawa-approved technician, a failure or malfunction may occur in the Register I/O Modules, and the guarantee is void.

1-14

1.3 Using This Manual

1.3Using This Manual

This manual is written for those who already have a basic knowledge of MEMOCON

PLCs. We recommended reading the MEMOCON GL120, GL130 Hardware User’s

Manual (manual No. SIEZ-C825-20.1) before attempting to read this manual.

• Meaning of Basic Terms

 

In this manual, the following terms indicate the meanings as described below,

1

 

unless otherwise specified.

 

 

Terms

Meaning

Remarks

 

 

 

 

PLC

 

Programmable (Logic) Controller

Does not mean “personal

 

 

 

computer.”

 

 

 

 

PP

 

Programming Panel

 

 

 

GL120, GL130

MEMOCON GL120 and MEMOCON GL130

 

 

Programmable Controllers

 

 

 

 

 

AC I/O

AC input

100-VAC 16-point Input Module

Module

Module

200-VAC 16-point Input Module

 

 

 

 

 

 

AC output

100/200-VAC 8-point Output Module

*1 When the AC load is

 

Module

100/200-VAC 16-point Output Module

applied.

 

 

Relay Contact 16-point Output Module*1

 

DC I/O

DC input

12/24-VDC 16-point Input Module

Module

Module

12/24-VDC 32-point Input Module

 

 

 

12/24-VDC 64-point Input Module

 

 

 

 

 

 

DC output

12/24-VDC 8-point Output Module

*2 When the DC load is

 

Module

12/24-VDC 16-point Output Module

applied.

 

 

12/24-VDC 32-point Output Module

 

 

 

12/24-VDC 64-point Output Module

 

 

 

Relay contact 16-point Output Module*2

 

Analog

Analog

Analog Input Module (±10V, 4CH)

I/O

input Module

Analog Input Module (0 to 10V, 4CH)

 

Module

 

Analog Input Module (4 to 20mA, 4CH)

 

 

 

 

 

 

Analog

Analog Output Module (±10V, 2CH)

 

output Module

Analog Output Module (0 to 10V, 2CH)

 

 

 

Analog Output Module (0 to 5V, 2CH)

 

 

 

Analog Output Module (4 to 20mA, 2CH)

 

 

 

 

 

Register I/O Module

Register Input Module

 

 

 

 

 

 

Register Output Module

 

 

 

 

 

• Description of Technical Terms

The bold technical terms in this manual are briefly explained in the Glossary provided at the bottom of the page. An example is shown below.

Glossary

TERMS

The following types of terms are described.

 

 

Specific sequence control terms required for explanation of functions.

 

Terms that are specific to programmable controllers and electronic devices.

1-15

Models and General Specifications

of I/O Modules

2

2

This chapter describes the models and general specifications of I/O

Modules.

2.1 General Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - 2-2

2.2 I/O Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2-3

2.2.1 Models of I/O Modules - - - - - - - - - - - - - - - - - - - - - - - 2-3

2.2.2 Overview of I/O Module Specifications - - - - - - - - - - - - 2-5

2.2.3 Using I/O Modules - - - - - - - - - - - - - - - - - - - - - - - - - 2-10

2-1

2Models and General Specifications of I/O Modules

2.1General Specifications

This section gives the general specifications of I/O Modules.

Table 2.1 General Specifications

 

Item

Specification

 

 

 

Environmental

Ambient Operating Temperature

0 °C to 60 °C

Conditions

 

 

Ambient Storage Temperature

-25 C° to 85 °C (excluding battery)

 

 

 

 

 

Ambient Operating Humidity

30 % to 95 % RH (with no condensation)

 

 

 

 

Ambient Storage Humidity

5 % to 95 % RH (with no condensation)

 

 

 

 

Pollution Level

Pollution level 1 (according to JIS B3502)

 

 

 

 

Corrosive Gas

No corrosive gas

 

 

 

 

Operating Altitude

Less than 2,000 m above sea level

 

 

 

Mechanical

Vibration Shock

10 to 57 Hz with half-amplitude of 0.075mm

Operating

 

57 to 150 Hz with fixed acceleration of 9.8 m/s2

Conditions

 

10 sweep times each in X, Y, and Z directions

 

 

 

 

(sweep time: 1 octave/min) (according to JIS B3502)

 

 

 

 

Shock Resistance

Peak acceleration of 147 m/s2 twice for 11 ms in X, Y,

 

 

and Z directions (according to JIS B3502)

 

 

 

Electrical

Noise Resistance

1,500 V in either normal or common mode with pulse

Operating

 

widths of 100 ns and 1 µs and rise time of 1 ns (with

Conditions

 

impulse noise simulator) (according to JIS B3502)

 

 

 

Installation

Ground

Ground to 100 Ω or less

Requirements

 

 

Configuration

Building-block, wall-mounted, or DIN track mounted

 

 

 

 

 

Cooling Method

Natural cooling

 

 

 

 

Mass

See specifications for individual I/O Modules.

 

 

 

 

External Dimensions

See specifications for individual I/O Modules.

 

 

 

2-2

2.2 I/O Modules

2.2I/O Modules

This section describes various input modules and output modules.

2.2.1 Models of I/O Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2-3

2.2.2 Overview of I/O Module Specifications - - - - - - - - - - - - - - - - - - - - - - -2-5

2.2.3 Using I/O Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2-10

2.2.1Models of I/O Modules

Twenty models of I/O Modules are available.

2

Table 2.2 I/O Modules

 

Product

Name

Model Name

Model No.

 

Features

Number

 

 

 

 

 

 

of slots

 

 

 

 

 

 

required

Digital

100-VAC

AC100IN-16P

JAMSC-

1)

Used to input digital signals.

1

Input

16-point Input

 

120DAI54300

2)

100VAC, 16 points, 7mA (50Hz)

 

Modules

Module

 

 

 

 

 

 

200-VAC

AC200IN-16P

JAMSC-

1)

Used to input digital signals.

1

 

16-point Input

 

120DAI74300

2)

200VAC, 16 points, 7mA (50Hz)

 

 

Module

 

 

 

 

 

 

 

 

 

 

 

 

 

12/24-VDC

DC24IN-16P

JAMSC-

1)

Used to input digital signals.

1

 

16-point Input

 

120DDI34300

2)

12/24VDC, 16 points, 4mA (12VDC), 8mA

 

 

Module

 

 

 

(24VDC)

 

 

 

 

 

 

 

 

 

12/24-VDC

DC24IN-32P

JAMSC-

1)

Used to input digital signals.

1

 

32-point Input

 

120DDI35400

2)

12/24VDC, 32 points, 2mA (12VDC), 4mA

 

 

Module

 

 

 

(24VDC)

 

 

12/24-VDC

DC24IN-64P

JAMSC-

1)

Used to input digital signals.

1

 

64-point Input

 

120DDI36400

2)

12/24VDC, 64 points, 2mA (12VDC), 4mA

 

 

Module

 

 

 

(24VDC)

 

 

 

 

 

 

 

 

Analog

Analog Input

A/D-VOL-

JAMSC-

1)

Used to input analog signals.

1

Input

Module (±10V,

4CH

120AVI02000

2)

-10 to 10V, 4 channels

 

Modules

4 channels)

 

 

 

 

 

 

Analog Input

A/D 0-10V

JAMSC-

1)

Used to input analog signals.

1

 

Module (0 to

4CH

120AVI02100

2)

0 to 10V, 4 channels

 

 

10V, 4 chan-

 

 

 

 

 

 

nels)

 

 

 

 

 

 

Analog Input

A/D-CUR-

JAMSC-

1)

Used to input analog signals.

1

 

Module (4 to

4CH

120ACI02000

2)

4 to 20mA/1 to 5V, 4 channels

 

 

20mA, 4 chan-

 

 

 

 

 

 

nels)

 

 

 

 

 

Digital

100/200-VAC

ACOUT-8P

JAMSC-

1)

Used to output digital signals.

1

Output

8-point

 

120DAO83000

2)

100/200VAC, 8 points, 1.0 A/point

 

Modules

Output Module

 

 

 

 

 

 

100/200-VAC

ACOUT-16P

JAMSC-

1)

Used to output digital signals.

1

 

16-point

 

120DAO84300

2)

100/200VAC, 16 points, 0.3 A/point

 

 

Output Module

 

 

 

 

 

 

 

 

 

 

 

 

 

12/24-VDC 8-

DC24OUT-8P

JAMSC-

1)

Used to output digital signals.

1

 

point Output

 

120DDO33000

2)

12/24VDC, 8 points, sourcing/sinking

 

 

Module

 

 

 

outputs, 2.0 A/point

 

 

12/24-VDC

DC24OUT-

JAMSC-

1)

Used to output digital signals.

1

 

16-point Out-

16PSN

120DDO34310

2)

12/24VDC, 16 points, sinking outputs, 0.5

 

 

put Module

 

 

 

A/point, 1.0 A/4points

 

 

(sinking)

 

 

 

 

 

2-3

2 Models and General Specifications of I/O Modules

2.2.1 Models of I/O Modules

Table 2.2 I/O Modules

Product

Name

Model Name

Model No.

 

Features

Number

 

 

 

 

 

 

of slots

 

 

 

 

 

 

required

Digital

12/24-VDC

DC24OUT-

JAMSC-

1)

Used to output digital signals.

1

Output

16-point Out-

16PSR

120DDO34320

2)

12/24VDC, 16 points, sourcing outputs,

 

Modules

put Module

 

 

 

0.5 A/point, 1.0 A/4points

 

 

(sourcing)

 

 

 

 

 

 

12/24-VDC

DC24OUT-

JAMSC-

1)

Used to output digital signals.

1

 

32-point Out-

32PSN

120DDO35410

2)

12/24VDC, 32 points, sinking outputs, 0.3

 

 

put Module

 

 

 

A/point, 0.4 A/4points

 

 

(sinking)

 

 

 

 

 

 

12/24-VDC

DC24OUT-

JAMSC-

1)

Used to output digital signals.

1

 

64-point Out-

64PSN

120DDO36410

2)

12/24VDC, 64 points, sinking outputs, 0.1

 

 

put Module

 

 

 

A/point

 

 

(sinking)

 

 

 

 

 

 

Relay Contact

RELAY-16P

JAMSC-

1)

Used to output digital signals.

1

 

16-point Out-

 

120DRA84300

2)

Relay contacts, 16 points, 1.0 A/point

 

 

put Module

 

 

 

 

 

Analog

Analog Out-

D/A-VOL-2CH

JAMSC-

1)

Used to output analog signals.

1

Output

put Module

 

120AVO01000

2)

-10 to 10V, 2 channels

 

Modules

(±10V, 2 chan-

 

 

 

 

 

 

nels)

 

 

 

 

 

 

Analog Out-

D/A 0-10V 2CH

JAMSC-

1)

Used to output analog signals.

1

 

put Module

 

120AVO01100

2)

0 to 10V, 2 channels

 

 

(0 to 10V, 2

 

 

 

 

 

 

channels)

 

 

 

 

 

 

Analog Out-

D/A 0-5V 2CH

JAMSC-

1)

Used to output analog signals.

1

 

put Module

 

120AVO01200

2)

0 to 5V, 2 channels

 

 

(0 to 5V, 2

 

 

 

 

 

 

channels)

 

 

 

 

 

 

Analog Out-

D/A-CUR- 2CH

JAMSC-

1)

Used to output analog signals.

1

 

put Module

 

120ACO01000

2)

4 to 20mA, 2 channels

 

 

(4 to 20mA, 2

 

 

 

 

 

 

channels)

 

 

 

 

 

Special

Register Input

REGISTER-IN

JAMSC-

1)

Used to input a maximum of 8 sets (8

1

Purpose

Module

 

120RDI34410

 

channel) or 16 sets (16 channel) of 16-bit

 

Modules

 

 

 

 

or BCD 4-digit values.

 

 

 

 

 

2)

The data input cycle can be selected:

 

 

 

 

 

 

For 8 channels: 10/32/64/192/320 ms

 

 

 

 

 

 

For 16 channels: 20/64/128/384/640 ms

 

 

Register Out-

REGISTER-

JAMSC-

1)

Used to output a maximum of 8 sets (8

1

 

put Module

OUT

120RDO34410

 

channel) or 16 sets (16 channel) of 16-bit

 

 

 

 

 

 

or BCD 4-digit values.

 

 

 

 

 

2)

Select the data output cycle.

 

 

 

 

 

 

For 8-channel: 32/64/192/320 ms

 

 

 

 

 

 

For 16-channel: 64/128/640 ms

 

Note: The 64-point I/O Modules are limited to versions for the CPU Module, remote I/O

Receiver Module and MEMOSOFT. Refer to 2.2.3 Using I/O Modules for details.

2-4

2.2 I/O Modules

2.2.2

Overview of I/O Module Specifications

 

 

1) Digital Input Modules

 

 

a) Function

 

 

A Digital Input Module converts the digital signals coming from pushbutton switches,

 

 

limit switches, and digital switches into signals of appropriate voltage for PLC inter-

 

 

nal processing. The converted digital signals are stored by the CPU Module as input

 

 

relays and input registers in state memory.

 

 

b) Specifications

 

 

The following table shows the main specifications of Digital Input Modules.

2

 

 

 

Table 2.3 Main Specifications of Digital Input Modules

 

 

 

Name

Model

Model No.

Rated

Rated

Input

Input

Num-

Internal

Maxi-

Hot

 

Name

 

Volt-

Current

Imped-

Delay

ber of

Current Con-

mum

Swap-

 

 

 

age

 

ance

Times

inputs

sumption

Heat-

ping

 

 

 

 

 

 

 

 

 

ing

 

 

 

 

 

 

 

 

 

 

Value

 

100-VAC

AC100IN-

JAMSC-

100

7 mA

14.3 kΩ

OFF→ON:

16

With all points

2.0 W

Per-

16-point

16P

120DAI54

VAC

(50Hz)

(50 Hz)

Max. 20 ms

 

ON: 90 mA

 

mitted

Input

 

300

 

 

12.5 kΩ

ON→OFF:

 

 

 

 

Module

 

 

 

 

(60 Hz)

Max. 35 ms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200-VAC

AC200IN-

JAMSC-

200

7 mA

28.6 kΩ

OFF→ON:

16

With all points

3.5 W

Per-

16-point

16P

120DAI74

VAC

(50Hz)

(50 Hz)

Max. 20 ms

 

ON: 90 mA

 

mitted

Input

 

300

 

 

23.1 kΩ

ON→OFF:

 

 

 

 

Module

 

 

 

 

(60 Hz)

Max. 35 ms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12/24-

DC24IN-

JAMSC-

12/24

4 mA

3.0 kΩ

OFF→ON:

16

With all points

3.7 W

Per-

VDC 16-

16P

120DDI34

VDC

(12 VDC)

 

Max. 5 ms

 

ON: 100 mA

 

mitted

point Input

 

300

 

8 mA

 

ON→OFF:

 

 

 

 

Module

 

 

 

(24 VDC)

 

Max. 5 ms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12/24-

DC24IN-

JAMSC-

12/24

2 mA

5.6 kΩ

OFF→ON:

32

With all points

3.6 W

Per-

VDC 32-

32P

120DDI35

VDC

(12 VDC)

 

Max. 5 ms

 

ON: 80 mA

 

mitted

point Input

 

400

 

4 mA

 

ON→OFF:

 

 

 

 

Module

 

 

 

(24 VDC)

 

Max. 5 ms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12/24-

DC24IN-

JAMSC-

12/24

2 mA

5.6 kΩ

OFF→ON:

64

With all points

7.0 W

Per-

VDC 64-

64P

120DDI36

VDC

(12 VDC)

 

Max. 5 ms

 

ON: 100 mA

 

mitted

point Input

 

400

 

4 mA

 

ON→OFF:

 

 

 

 

Module

 

 

 

(24 VDC)

 

Max. 5 ms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Other Specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1) Slots required: 1

 

 

 

 

 

 

 

 

 

2) Width: 40.3 mm

Height: 130 mm

Depth: 103.9 mm

 

 

 

 

 

3)Approx. mass

16-point Input Module: 250 g

32-point Input Module: 250 g

64-point Input Module: 300 g

4)Field connections

16-point Input Module: terminal block

32-point Input Module: connector

64-point Input Module: connector

5)Number of points per common

16-point Input Module: 8 points per common

32-point Input Module: 16 points per common

64-point Input Module: 16 points per common

2-5

2 Models and General Specifications of I/O Modules

2.2.2Overview of I/O Module Specifications

2)Analog Input Modules

a)Function

An Analog Input Module converts the analog signals coming from weight sensors, temperature sensors, etc., into numeric data appropriate for PLC internal processing. The converted numeric data is stored by the CPU Module as the input registers in state memory.

b)Specifications

The following table shows the main specifications of the Analog Input Modules.

Table 2.4 Main Specifications of Analog Input Modules

Name

Model

Model

Input

Overall

Resolution

Input

Num-

Internal

Maxi-

Hot

 

Name

No.

Signal

Accuracy

and Data

Impedance

ber of

Current

mum

Swap-

 

 

 

Range

 

Types

 

Chan-

Con-

Heat-

ping

 

 

 

 

 

 

 

nels

sump-

ing

 

 

 

 

 

 

 

 

 

tion

Value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog

A/D-

JAMSC-

-10 to

±0.5% F.S.

0 to 4000

1 MΩ min.

4

450

2.3 W

Per-

Input

VOL-

120AVI

+10 V

(25°C)

mode: 12 bits,

 

 

mA

 

mitted

Module

4CH

02000

 

 

binary between

 

 

 

 

 

(±10 V, 4

 

 

 

 

0 and 4000

 

 

 

 

 

channels)

 

 

 

±1.0% F.S.

± 2000 mode:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(0 to 60°C)

12 bits, 2’s

 

 

 

 

 

 

 

 

 

 

complement

 

 

 

 

 

 

 

 

 

 

between -2000

 

 

 

 

 

 

 

 

 

 

and +2000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog

A/D

JAMSC-

0 to

±0.5% F.S.

12 bits, binary

1 MΩ min.

4

450

2.3 W

Per-

Input

0-10V

120AVI

+10 V

(25°C)

between 0 and

 

 

mA

 

mitted

Module

4CH

02100

 

±1.0% F.S.

4000

 

 

 

 

 

(0 to

 

 

 

(0 to 60°C)

 

 

 

 

 

 

10 V,

 

 

 

 

 

 

 

 

 

 

4 chan-

 

 

 

 

 

 

 

 

 

 

nels)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog

A/D-

JAMSC-

Current

±0.5% F.S.

12 bits, binary

Current

4

450

2.3 W

Per-

Input

CUR-

120ACI

input:

(25 °C)

between 0 and

input: 250 Ω

 

mA

 

mitted

Module (4

4CH

02000

4 to 20

±1.0% F.S.

4000

voltage

 

 

 

 

to 20 mA,

 

 

mA

(0 to 60°C)

 

input: 1 MΩ

 

 

 

 

4 chan-

 

 

Voltage

 

 

min.

 

 

 

 

nels)

 

 

input:

 

 

 

 

 

 

 

 

 

 

1 to 5 V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Other Specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1)Slots required: 1

2)Approx. mass: 300 g

3)

Width: 40.3 mm

Height: 130 mm

Depth: 103.9 mm

4)

Field connections: Terminal block

 

2-6

2.2 I/O Modules

3) Digital Output Modules a) Function

A Digital Output Module converts the numeric data stored in output registers or the ON/OFF state of the output coil in the state memory of the CPU Module into digital signals for control of indicators, electromagnetic switches, relays, solenoid valves, numeric indicators, etc.

b)Specifications

The following table shows the main specifications of Digital Output Modules.

 

 

Table 2.5 Main Specifications of Digital Output Modules

 

 

 

 

2

Name

Model

Model No.

Rated

Load

Remarks

Output

Num

 

Internal

Maxi-

Hot

 

 

 

 

Name

 

Volt-

Current

 

Delay

ber

 

Current Con-

mum

Swap

 

 

 

 

age

 

 

Times

of

 

sumption

Heat-

ping

 

 

 

 

 

 

 

 

Out-

 

 

ing

 

 

 

 

 

 

 

 

 

 

puts

 

 

Value

 

 

 

100/200-

ACOUT

JAMSC-

100/

1.0 A/

Unpro-

OFF→ON:

8

 

With all

9.0 W

Per-

 

 

VAC

-8P

120DAO83

200

point

tected

Max. 5 ms

 

 

points ON:

 

mit-

 

8-point

 

000

VAC

 

outputs

ON→OFF:

 

 

150 mA

 

ted

 

Output

 

 

 

 

 

1/2 cycle +

 

 

 

 

 

 

 

Module

 

 

 

 

 

5 ms max.

 

 

 

 

 

 

 

100/200-

ACOUT

JAMSC-

100/

0.6 A/

Unpro-

OFF→ON:

16

 

With all

5.5 W

Per-

 

 

VAC

-16P

120DAO84

200

point

tected

Max. 5 ms

 

 

points ON:

 

mit-

 

16-point

 

300

VAC

 

outputs

ON→OFF:

 

 

300 mA

 

ted

 

Output

 

 

 

 

 

1/2 cycle +

 

 

 

 

 

 

 

Module

 

 

 

 

 

5 ms max.

 

 

 

 

 

 

 

12/24-VDC

DC24O

JAMSC-

12/24

2.0 A/

Short-cir-

OFF→ON:

8

 

With all

1.6 W

Per-

 

 

8-point

UT-8P

120DDO33

VDC

point

cuit pro-

Max. 3 ms

 

 

points ON:

 

mit-

 

Output

 

000

 

 

tection

ON→OFF:

 

 

220 mA

 

ted

 

Module

 

 

 

 

Sourcing/

Max. 5 ms

 

 

 

 

 

 

 

 

 

 

 

 

sinking

 

 

 

 

 

 

 

 

 

 

 

 

 

outputs

 

 

 

 

 

 

 

 

12/24-VDC

DC24O

JAMSC-

12/24

0.5 A/

Unpro-

OFF→ON:

16

 

With all

7.1 W

Per-

 

 

16-point

UT-

120DDO34

VDC

point,

tected

Max. 1 ms

 

 

points ON:

 

mit-

 

Output

16PSN

310

 

1.0 A/

outputs

ON→OFF:

 

 

220 mA

 

ted

 

Module

 

 

 

4 points

Sinking

Max. 1 ms

 

 

 

 

 

 

 

(sinking)

 

 

 

 

outputs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12/24-VDC

DC24O

JAMSC-

12/24

0.5 A/

Unpro-

OFF→ON:

16

 

With all

7.5 W

Per-

 

 

16-point

UT-

120DDO34

VDC

point,

tected

Max. 1 ms

 

 

points ON:

 

mit-

 

Output

16PSR

320

 

1.0 A/

outputs

ON→OFF:

 

 

300 mA

 

ted

 

Module

 

 

 

4 points

Sourcing

Max. 1 ms

 

 

 

 

 

 

 

(sourcing)

 

 

 

 

outputs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12/24-VDC

DC24O

JAMSC-

12/24

0.3 A/

Unpro-

OFF→ON:

32

 

With all

6.5 W

Per-

 

 

32-point

UT-

120DDO35

VDC

point,

tected

Max. 1 ms

 

 

points ON:

 

mit-

 

Output

32PSN

410

 

0.4 A/

outputs

ON→OFF:

 

 

330 mA

 

ted

 

Module

 

 

 

4 points

Sinking

Max. 1 ms

 

 

 

 

 

 

 

(sinking)

 

 

 

 

outputs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12/24-VDC

DC24O

JAMSC-

12/24

0.1 A/

Unpro-

OFF→ON:

64

 

With all

13.0 W

Per-

 

 

64-point

UT-

120DDO36

VDC

point

tected

Max. 1 ms

 

 

points ON:

 

mit-

 

Output

64PSN

410

 

 

output

ON→OFF:

 

 

650 mA

 

ted

 

Module

 

 

 

 

Sinking

Max. 1 ms

 

 

 

 

 

 

 

(sinking)

 

 

 

 

outputs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Relay con-

RELAY-

JAMSC-

Relay

1.0 A/

Unpro-

OFF→ON:

16

 

With all

3.1 W

Per-

 

 

tact

16P

120DRA84

contact

point

tected

Max. 10 ms

 

 

points ON:

 

mit-

 

16-point

 

300

 

 

outputs

ON→OFF:

 

 

610 mA

 

ted

 

Output

 

 

 

 

 

Max. 15 ms

 

 

 

 

 

 

 

Module

 

 

 

 

 

 

 

 

 

 

 

 

 

2-7

2 Models and General Specifications of I/O Modules

2.2.2 Overview of I/O Module Specifications

Table 2.5 Main Specifications of Digital Output Modules

 

Name

Model

Model No.

Rated

Load

Remarks

Output

Num

Internal

Maxi-

Hot

 

 

Name

 

Volt-

Current

 

Delay

ber

Current Con-

mum

Swap

 

 

 

 

age

 

 

Times

of

sumption

Heat-

ping

 

 

 

 

 

 

 

 

Out-

 

ing

 

 

 

 

 

 

 

 

 

puts

 

Value

 

Other Specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1)

Slots required: 1

 

 

 

 

 

 

 

 

 

2)

Width: 40.3 mm

Height: 130 mm

Depth: 103.9 mm

 

 

 

 

 

3)

Approx. mass

 

 

 

 

 

 

 

 

 

 

AC Output Module: 300 g

 

 

 

 

 

 

 

 

DC Output Module (8-point, 16-point, 32-point): 250 g

 

 

 

 

 

 

DC Output Module (64-point): 300 g

 

 

 

 

 

 

 

 

Relay Contact Output Module: 300 g

 

 

 

 

 

 

 

4)

Field connections

 

 

 

 

 

 

 

 

 

 

8-point Output Module: terminal block

 

 

 

 

 

 

 

16-point Output Module: terminal block

32-point Output Module: connector

64-point Output Module: connector

Relay Contact Output Module: terminal block 5) Number of points per common

8-point Output Module: Independent outputs

16-point Output Module: 8 points per common

32-point Output Module: 16 points per common

64-point Output Module: 16 points per common Relay Contact Output Module: 8 points per common

2-8

2.2 I/O Modules

4) Analog Output Module a) Function

An Analog Output Module converts the numeric data stored in output registers in the state memory of the CPU Module into analog signals for control of heaters, pumps, PID adjusters, inverters, etc.

b)Specifications

The following table shows the main specifications of the Analog Output Modules.

 

 

 

Table 2.6 Main Specifications of Analog Output Modules

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

Name

Model

Model

 

Output

Overall

Resolution and

Maxi-

Num-

Inter-

Maxi-

Hot

 

Name

No.

 

Signal

Accuracy

Data Types

mum

ber of

nal Cur-

mum

Swap-

 

 

 

 

Range

 

 

Permis-

Chan-

rent

Heat-

ping

 

 

 

 

 

 

 

 

 

 

 

 

 

 

sible

nels

Con-

ing

 

 

 

 

 

 

 

 

 

 

Load

 

sump-

Value

 

 

 

 

 

 

 

 

 

 

 

tion

 

 

 

 

 

 

 

 

 

 

Current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog

D/A-

JAMSC-

 

-10 to

±0.2% F.S.

0 to 4000 mode:

±5 mA,

2

400

2.0 W

Permit-

 

Output

VOL-

120AVO

 

+10 V

(25 °C)

12 bits, binary

2 kΩ

 

mA

 

ted

 

Module

2CH

01000

 

 

 

between 0 and

min.

 

 

 

 

 

 

(±10 V, 2

 

 

 

 

 

4000

 

 

 

 

 

 

 

channels)

 

 

 

 

±0.5% F.S.

±2000 mode: 12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(0 to

bits, 2’s comple-

 

 

 

 

 

 

 

 

 

 

 

 

60 °C)

ments between

 

 

 

 

 

 

 

 

 

 

 

 

 

-2000 and

 

 

 

 

 

 

 

 

 

 

 

 

 

+2000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog

D/A

JAMSC-

 

0 to +10

±0.2% F.S.

12 bits, binary

5 mA,

2

400

2.0 W

Permit-

 

Output

0-10V

120AVO

 

V

(25 °C)

between 0 and

2 kΩ

 

mA

 

ted

 

Module (0

2CH

01100

 

 

±0.5% F.S.

4000

min.

 

 

 

 

 

 

to 10 V, 2

 

 

 

 

(0 to 60 °C)

 

 

 

 

 

 

 

 

channels)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog

D/A

JAMSC-

 

0 to +5

±0.2% F.S.

12 bits, binary

2.5 mA,

2

400

2.0 W

Permit-

 

Output

0-5V

120AVO

 

V

(25 °C)

between 0 and

2 kΩ

 

mA

 

ted

 

Module (0

2CH

01200

 

 

±0.5% F.S.

4000

min.

 

 

 

 

 

 

to 5 V, 2

 

 

 

 

(0 to 60 °C)

 

 

 

 

 

 

 

 

channels)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog

D/A-

JAMSC-

 

4 to 20

±0.2% F.S.

12 bits, binary

550 Ω

2

500

2.5 W

Permit-

 

Output

CUR-

120AC

 

mA

(25 °C)

between 0 and

max.

 

mA

 

ted

 

Module (4

2CH

O01000

 

 

±0.5% F.S.

4000

 

 

 

 

 

 

 

to 20 mA,

 

 

 

 

(0 to 60 °C)

 

 

 

 

 

 

 

 

2 chan-

 

 

 

 

 

 

 

 

 

 

 

 

 

nels)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Other Specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1)Slots required: 1

2)Approx. mass : 350 g

3)

Width: 40.3 mm

Height: 130 mm

Depth: 103.9 mm

4)

Field connection: Terminal block

 

2-9

2 Models and General Specifications of I/O Modules

2.2.3Using I/O Modules

2.2.3Using I/O Modules

1)Installation Location of I/O Modules

(1)I/O Modules can be mounted to any slot of the Mounting Base of any Rack. Each I/O Module occupies one slot.

(2)The following diagram shows an example on where to mount I/O Modules.

EXAMPLE

1

2

 

3

 

4

 

5

 

 

6

 

7

8

 

9

 

10

11

12

 

 

 

Slot No.

 

 

 

 

 

 

 

 

 

 

 

PS10

 

 

 

 

 

 

 

 

DI

 

DI

 

DO

 

MC20

 

 

 

 

 

 

 

 

 

 

 

 

Rack 1 (CPU Rack)

 

 

CPU30

 

 

 

 

 

MC20

 

EXP

 

 

 

 

 

 

 

 

 

P

 

M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MB12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W0100-02

1

2

3

4

5

 

6

 

7

8

 

9

 

10

 

11

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rack 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PS

 

DI

 

DI

 

DI

 

DI

 

DI

 

DI

 

DO

 

DO

 

 

DO

 

 

DO

 

EXP

 

 

 

05

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MB12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PS10:

Power Supply Module (7 A)

 

 

 

MC20:

 

4-axis Motion Module

PS05:

Power Supply Module (3 A)

 

 

 

EXP:

 

Expander Module

CPU30: CPU Module (32 kW)

 

 

 

 

 

 

 

MB12:

 

12 slot Mounting Base

 

 

 

 

 

W0100-02: Rack-to-rack I/O Cable (0.2 m)

DI:

 

 

 

12/24-VDC 16-point Input Module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DO:

 

 

 

12/24-VDC 16-point Output Module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 2.1 Example of Mounting I/O Modules

2) Versions Supporting 64-point I/O Modules

The following CPU Modules, Remote I/O Receiver Modules, and MEMOSOFT versions are required to user 64-point I/O Modules.

Table 2.7 Versions Supporting 64-point I/O Modules

Name

Model

Model No.

Version Number

Location of Ver-

 

Name

 

 

sion Number

 

 

 

 

 

CPU Module

CPU10

DDSCR-120CPU14200

A01 and later

Module nameplate

(8 kw)

 

 

 

 

 

 

 

 

 

CPU Module

CPU20

DDSCR-120CPU34100

B05 and later

Module nameplate

(16 kw)

 

 

 

 

 

 

 

 

 

CPU Module

CPU21

DDSCR-120CPU34110

A01 and later

Module nameplate

(16 kw)

 

 

 

 

 

 

 

 

 

CPU Module

CPU30

DDSCR-120CPU54100

B05 and later

Module nameplate

(32 kw)

 

 

 

 

 

 

 

 

 

CPU Module

CPU35

DDSCR-120CPU54110

A01 and later

Module nameplate

(40 kw)

 

 

 

 

 

 

 

 

 

Remote I/O

RIOR-

DDSCR-120CRR13100

A10 and later

Module nameplate

Receiver

COAX

 

 

 

Module

 

 

 

 

 

 

 

 

 

MEMOSOFT

 

FMSGL-AT3

1.21 and later

In the middle at the

 

 

(for English DOS)

 

bottom of the

 

 

 

 

MEMOSOFT

 

 

FMSGL-PP3E

 

 

 

 

startup screen

 

 

(for P120 English version)

 

 

 

 

 

 

 

 

 

Note: The nameplate is on the right side of the Module.

 

2-10

Loading...
+ 278 hidden pages