Yaskawa GPD 506-P5 User Manual

0 (0)

Yaskawa Electric

America

Unit Troubleshooting Manual

Section Three:

Fault Codes & Appendix

GPD 506/P5 and GPD 515/G5

(0.4 ~ 160kW)

PP.P5G5.03.Troubleshoot

Page 1

Rev. 06/11/2003

Yaskawa GPD 506-P5 User Manual

Section Three:

Fault Codes

 

 

REMOTE

 

 

SEQ

REF

 

 

OC

FREF

FOUT

IOUT

kWout

F/R

MONTR

ACCEL

DECEL

VMTR

V/F

FGAIN

FBIAS

FLA

PID

kWsav

PRGM

DIGITAL OPERATOR JVOP-131U

 

DSPL

ENTER

LOCAL

 

 

REMOTE

 

 

RUN

STOP

RESET

GPD 515/G5

GPD 505/P5

GPD 506/P5

PP.P5G5.03.Troubleshoot

Page 2

Rev. 06/11/2003

Fault Codes

The GPD 506/P5 and GPD 515/G5 inverters can store up to (4) faults.

The GPD 515/G5 inverter has a fault trace that saves the drive status at the time of the fault, and a fault history indicating elapsed time of the stored faults.

The fault codes can be grouped into (3) categories:

Major Fault - Motor coasts to a stop, the fault is displayed on the digital operator, and the fault relay is activated.

Minor Fault - Operation continues and the fault flashes on the digital operator. The fault relay does not activate.

Parameter Setting Error - Inverter can’t run. The fault is displayed on the digital operator, and the fault relay is not activated.

A complete list of fault codes may be found in the appendix.

PP.P5G5.03.Troubleshoot

Page 3

Rev. 06/11/2003

Fault Codes

Major Fault - Motor coasts to a stop, the fault is displayed on the digital operator, and the fault relay is activated.

506 515

505

Undervoltage of the main circuit when running.

 

 

 

UV1

 

 

230V Units - trip point 190V DC or less.

 

Uu1

DC Bus Undervolt

 

460V Units - trip point 380V DC or less.

 

 

 

 

 

600V Units - trip point 546V DC or less.

Possible Cause(s): Single phase condition on the input, low input voltage at L1, L2, and L3. Corrective Action: Check the three phase input voltage, verify L2-05 for 515/G5 units.

UV2

 

 

Undervoltage of the control circuit when running.

 

Uu2

CTL PS Undervolt

 

230V Units - 30kW ~ 75kW, monitors the (-15V)

 

 

 

power supply.

460V Units - 55kW ~ 160kW, monitors the (-15V) power supply.

Possible Cause(s): External load connected pulling down the inverter power supplies.

Corrective Action: Repair or replace the power/gate drive board.

PP.P5G5.03.Troubleshoot

Page 4

Rev. 06/11/2003

Fault Codes

Major Fault - Motor coasts to a stop, the fault is displayed on the digital operator, and the fault relay is activated.

506 515

505

 

 

 

 

 

UV3

 

 

 

 

Uu3

The pre-charge contactor opened while the inverter is

MC Answerback

 

 

 

running.

 

 

 

This fault only applies to 230V units 18kW ~ 75kW , 460V units 22kW ~ 160kW and 600V units 30kW ~ 160kW .

Possible Cause(s): Contacts on contactor are dirty, contactor does not function mechanically.

Corrective Action: Check the contactor, check the ribbon cable from the control board to the gate drive board.

 

 

 

Overvoltage of the main circuit when running.

OV

 

 

 

ou

230V

Units - trip point 400V DC or more.

DC Bus Overvolt

 

 

 

 

460V

Units - trip point 800V DC or more.

 

 

 

600V

Units - trip point 1050V DC or more.

Possible Cause(s): High input voltage at L1, L2, and L3. The deceleration time is set too short. Power factor correction capacitors are being used on the input to the inverter.

Corrective Action: Check the input circuit, verify the program parameters, add a braking resistor, remove the power factor correction capacitors.

PP.P5G5.03.Troubleshoot

Page 5

Rev. 06/11/2003

Fault Codes

Major Fault - Motor coasts to a stop, the fault is displayed on the digital operator, and the fault relay is activated.

506 515

505

 

 

 

OC

 

 

 

oc

Over current

 

 

 

Designed to protect the inverter.

Output current has exceeded OC level of the inverter rated value instantaneously.

OC – 200%

OC – 180%

20P4 – 2015

2018 – 2075

40P4 – 4015

4018 – 4160

51P5 - 5160

 

Possible Cause(s): Shorted inverter output phase to phase, shorted motor, locked rotor.

Corrective Action: Remove the motor and run the inverter without the motor. Check the motor for a phase to phase short. Check the inverter for a phase to phase short at the output.

GF

Ground Fault

gf

Designed to protect the inverter.

Inverter output grounding current has exceeded 50% of the inverter rated current.

Possible Cause(s): Motor lead shorted to ground, DCCT defective.

Corrective Action: Remove the motor and run the inverter without the motor. Check the motor for a phase to ground short. Check the output current with a clamp on meter to verify the DCCT reading.

PP.P5G5.03.Troubleshoot

Page 6

Rev. 06/11/2003

Fault Codes

Major Fault - Motor coasts to a stop, the fault is displayed on the digital operator, and the fault relay is activated.

506 515

505

 

 

 

 

 

SC

 

 

 

 

sc

The inverter output is short-circuited.

Short Circuit

 

 

 

 

Possible Cause(s): Shorted inverter output phase to phase, shorted motor, locked rotor.

Corrective Action: Remove the motor and run the inverter without the motor. Check the motor for a phase to phase short. Check the inverter for a phase to phase short at the output.

PUF

DC Bus Fuse Open

PUf

Detects if the DC bus fuse has opened.

Possible Cause(s): Shorted output transistor, shorted main circuit component.

Corrective Action: Remove power from the inverter and disconnect the motor. Perform the checks without/with power starting on page 10. Replace the shorted component(s), then replace the defective fuse.

PP.P5G5.03.Troubleshoot

Page 7

Rev. 06/11/2003

Fault Codes

Major Fault - Motor coasts to a stop, the fault is displayed on the digital operator, and the fault relay is activated.

506

515

505

 

 

 

 

 

Motor overload, designed to protect the motor.

OL1

 

 

ol1

 

 

Fully adjustable from parameter setting (n033 and

Motor Overloaded

 

 

 

 

 

n034 for 506/P5 and E1-02 and E2-01 for 515/G5)

 

 

 

 

A pre-alarm can be selected as a minor fault by using

the multi-function outputs. Possible Cause(s): Motor is overloaded.

Corrective Action: Verify the program settings, reduce the load on the motor.

 

 

 

Inverter overload, designed to protect the inverter.

OL2

 

ol2

 

120 or150% of inverter rated current for 1 minute.

Inv Overloaded

 

 

 

 

 

515 - 150% for 1 minute

 

 

 

 

 

 

505 and 506 - 120% or 150% depending on drive

 

 

 

capacity and setting parameter n116

Possible Cause(s): Motor is overloaded.

Corrective Action: Verify the program settings, reduce the load on the motor.

PP.P5G5.03.Troubleshoot

Page 8

Rev. 06/11/2003

Fault Codes

Major Fault - Motor coasts to a stop, the fault is displayed on the digital operator, and the fault relay is activated.

506

515

505

 

 

 

 

 

OL3

 

Over torque detection function.

ol3

Overtorque Det 1

 

A customer programmable current detection. Response

 

 

 

 

 

 

 

 

may be selected. A minor fault contact output can be

 

 

 

 

programmed by using the multi-function outputs.

Possible Cause(s): Motor is overloaded.

Corrective Action: Verify the program settings, reduce the load on the motor.

506

515

505

 

 

OL4

N/A

Over torque detection function (2).

Overtorque Det 2

 

A customer programmable current detection. Response may be selected. A minor fault contact output can be programmed by using the multi-function outputs.

Possible Cause(s): Motor is overloaded.

Corrective Action: Verify the program settings, reduce the load on the motor.

PP.P5G5.03.Troubleshoot

Page 9

Rev. 06/11/2003

Fault Codes

Major Fault - Motor coasts to a stop, the fault is displayed on the digital

506

515

 

operator, and the fault relay is activated.

505

 

 

 

 

 

 

 

PF

 

 

Inverter input power supply has an open phase.

 

 

sp1

Input Pha Loss

 

Large imbalance of input voltage.

 

 

 

 

Possible Cause(s): Open phase on the input of the inverter. Loose terminal screws at terminals L1, L2, or L3. Program parameters set incorrectly (n083 for 506/P5, L8-05 for 515/G5)

Corrective Action: Tighten the terminal screws, check the input voltage, verify the program settings.

506

515

505

 

 

LF

 

 

 

 

 

spo

Inverter output has an open phase.

Output Pha Loss

 

 

 

 

 

 

 

 

 

Possible Cause(s): Open phase on the output of the inverter. Loose terminal screws at terminals T1, T2, or T3. Program parameters set incorrectly.

Corrective Action: Tighten the terminal screws, check the output voltage, verify the program settings.

PP.P5G5.03.Troubleshoot

Page 10

Rev. 06/11/2003

Fault Codes

Major Fault - Motor coasts to a stop, the fault is displayed on the digital operator, and the fault relay is activated.

506

515

505

The motor speed has exceeded the overspeed level

 

 

 

 

OS

 

 

N/A

when operating in the Closed Loop V/f or Closed

Overspeed Det

Loop Flux Vector modes.

 

Possible Cause(s): The load has changed considerably, the program settings may not be set correctly.

Corrective Action: Check the load on the motor, verify the program settings (F1-08 PG Overspeed Level, and F1-09 PG Overspeed Time).

506

515

505

 

 

PGO

N/A

Feedback pulses are not received by the PG option

PG open

 

board.

Possible Cause(s): The Pulse Generator feedback wires may be broken or not properly connected to the PG feedback option board.

Corrective Action: Check for a broken wire or a loose connection from the Pulse Generator, verify the program settings.

PP.P5G5.03.Troubleshoot

Page 11

Rev. 06/11/2003

Fault Codes

Major Fault - Motor coasts to a stop, the fault is displayed on the digital operator, and the fault relay is activated.

506 515

505

 

 

 

 

The braking transistor has failed.

RR

N/A

DynBrk Transistr

230V

Units - 0.4kW ~ 7.5kW

 

 

 

 

 

460V

Units - 0.4kW ~ 15kW

Possible Cause(s): Shorted braking transistor, high DC bus voltage, defective braking resistor.

Corrective Action: Replace defective transistor or resistor, monitor DC bus level.

RH

N/A

The braking resistor temperature has exceeded the

DynBrk Resistor

allowable value.

 

(Protects Yaskawa 3% duty cycle resistors only)

Can be selected as a minor fault by using the multifunction outputs.

Possible Cause(s): Overhauling load, extended braking duty cycle, defective braking resistor.

Corrective Action: Verify braking duty cycle, monitor DC bus voltage, replace resistor.

PP.P5G5.03.Troubleshoot

Page 12

Rev. 06/11/2003

Fault Codes

Major Fault - Motor coasts to a stop, the fault is displayed on the digital operator, and the fault relay is activated.

506

515

505

 

 

CF

N/A

The actual torque during deceleration has reached

Out of Control

 

 

 

the regen torque limit for more than 3 seconds.

 

 

 

(Open Loop Flux Vector mode only)

Possible Cause(s): The regen torque limit value is set too low, load torque is excessively large.

Corrective Action: Verify the program setting, L7-03 forward regen torque limit and L7-04 reverse regen torque limit, extend the deceleration time.

SVE

N/A

In the zero servo mode, the motor shaft has

Zero Servo Fault

rotated 10,000 non-quadrature PG pulses from the

 

 

 

home position.

Possible Cause(s): Torque limit or zero servo gain set too low, load torque excessively large, PG signal noise.

Corrective Action: Verify the program parameters B9-01 zero servo gain and torque limit settings L7-01 ~ L7-02, check for noise on the PG signals.

PP.P5G5.03.Troubleshoot

Page 13

Rev. 06/11/2003

Fault Codes

Major Fault - Motor coasts to a stop, the fault is displayed on the digital operator, and the fault relay is activated.

506 515

505

 

 

 

The transistor cooling fin temperature exceeded the

OH1

 

 

oh2

Heatsnk MAX Temp

 

allowable value. 506/P5 (105 ° C), 515/G5 (105 ° C)

 

 

 

 

Possible Cause(s): Cooling fan(s) are not working, high ambient temperature.

Corrective Action: Check for dirt build-up on the fans, reduce the ambient temperature around the inverter.

OPR

 

 

 

Oper Disconnect

 

op

The inverter will stop if the digital operator is removed

 

 

 

when the inverter is commanded to run through the

 

 

 

digital operator.

Possible Cause(s): The operator is not attached, broken operator cable.

Corrective Action: Attach the digital operator, check the cable connected to the digital operator, verify the program setting of parameter O2-06 for 515/G5 models and n112 for 506/P5 models.

PP.P5G5.03.Troubleshoot

Page 14

Rev. 06/11/2003

Corrective Action:
Possible Cause(s):

Fault Codes

Major Fault - Motor coasts to a stop, the fault is displayed on the digital operator, and the fault relay is activated.

506

515

505

 

 

 

 

 

 

E-10

N/A

The CPU on the SI-F/G option board has stopped

SI-F/G CPU down

operating.

 

Defective option board, electrical noise effecting operation.

Cycle power, replace the option board.

E-15

N/A

After initial communication has been established, the

SI-F/G Com Err

connection was then lost.

 

 

Response may be selected.

Possible Cause(s): Connection is broken, master has stopped communicating. Corrective Action: Check all connections, verify all user side software configurations.

E-10 and E-15 fault codes may only appear when using the OMRON specification (O2-09=3).

PP.P5G5.03.Troubleshoot

Page 15

Rev. 06/11/2003

Fault Codes

Major Fault - Motor coasts to a stop, the fault is displayed on the digital operator, and the fault relay is activated.

506

515

505

 

 

BUS

N/A

After initial communication has been established, the

SI-B Com Err

connection was then lost.

 

Response may be selected.

Possible Cause(s): Connection is broken, master has stopped communicating.

Corrective Action: Check all connections, verify all user side software configurations.

506 515

505

Transmission error. Control data was not received

CE

 

 

 

ce

Memobus Com Err

 

normally when the power supply is turned on.

 

 

 

 

 

Response may be selected.

Possible Cause(s): Connection is broken, master has stopped communicating.

Corrective Action: Check all connections, verify all user side software configurations.

PP.P5G5.03.Troubleshoot

Page 16

Rev. 06/11/2003

Fault Codes

Major Fault - Motor coasts to a stop, the fault is displayed on the digital operator, and the fault relay is activated.

506 515

505

 

 

 

 

 

EF3

 

 

 

 

ef3

External fault at terminal number 3.

External Fault3

 

 

 

 

Possible Cause(s): An external fault condition exists connected to terminal number 3.

Corrective Action: Check for an external condition, verify the program parameters.

EF4~8

External Fault

ef4

~6

External fault at the multi-function inputs terminal number 4 ~ 8. 506 is the same as 505 and only has EF 4-6.

Possible Cause(s): An external fault condition exists connected to one of the terminals 4, 5, 6, 7, or 8.

Corrective Action: Check for an external condition, verify the program parameters.

PP.P5G5.03.Troubleshoot

Page 17

Rev. 06/11/2003

Fault Codes

Major Fault - Motor coasts to a stop, the fault is displayed on the digital operator, and the fault relay is activated.

506 515

505

 

EF0

 

 

External fault from serial communication.

ef0

External Fault

 

 

 

 

 

 

 

Possible Cause(s): An external fault condition exists.

Corrective Action: Check for an external condition, verify the program parameters.

506 515

505

 

EF2

 

 

External fault at the multi-function input terminal

 

ef2

 

number S2.

External Fault

 

 

Possible Cause(s): An external fault condition exists at terminal S2.

Corrective Action: Check for an external condition at terminal S2, verify the program parameters.

PP.P5G5.03.Troubleshoot

Page 18

Rev. 06/11/2003

Fault Codes

Major Fault - Motor coasts to a stop, the fault is displayed on the digital operator, and the fault relay is activated.

506 515 505

DEV

N/A

Speed Deviation

 

The deviation of the speed reference and speed feedback has exceeded the regulation level.

A minor fault contact output can be programmed by using the multi-function outputs.

Possible Cause(s): The load has changed considerably.

Corrective Action: Check the load on the motor, verify the program settings (F1-10 PG Deviate Level, F1-11 PG Deviate Time. F1-04 PG Deviation Select.

ERR

N/A

EEPROM internal data does not match the value in

EEPROM R/W Err

 

RAM when setting a parameter.

 

 

Possible Cause(s): Control board hardware failure.

Corrective Action: Cycle power, replace the control board.

PP.P5G5.03.Troubleshoot

Page 19

Rev. 06/11/2003

Fault Codes

Major Fault - Motor coasts to a stop, the fault is displayed on the digital operator, and the fault relay is activated.

506 515

505

 

CPF00

 

 

Transmission between the inverter and the operator

Com-Err(OP&INV)

 

cpf0

 

cannot be established 5 seconds after supplying

 

 

 

power.

Possible Cause(s): Digital operator cable not securely connected, digital operator defective, control board defective.

Corrective Action: control board.

CPF01

Com-Err(OP&INV)

Check the operator cable, replace the digital operator, replace the

cpf1

Communication fault between the inverter and the

operator has occurred for more than 2 seconds.

 

Possible Cause(s): Digital operator cable not securely connected, digital operator defective, control board defective.

Corrective Action: Check the digital operator cable, replace the digital operator, replace the control board.

PP.P5G5.03.Troubleshoot

Page 20

Rev. 06/11/2003

Corrective Action:
Possible Cause(s):
Corrective Action:
Possible Cause(s):

Fault Codes

Major Fault - Motor coasts to a stop, the fault is displayed on the digital operator, and the fault relay is activated.

506

515

505

 

 

 

 

 

CPF02

 

N/A

Baseblock circuit fault at power up.

BB Circuit Err

 

 

Gate array hardware failure during power up.

Perform a factory initialization, cycle power, replace the control board.

506 515

505

 

CPF03

 

 

 

 

cpf4

EEPROM fault, check sum not valid. 506 digital

EEPROM Error

 

 

 

operator will display CPF04.

 

 

 

Noise or spike on the control input terminals.

Perform a factory initialization , cycle power, replace the control board.

PP.P5G5.03.Troubleshoot

Page 21

Rev. 06/11/2003

Loading...
+ 46 hidden pages