
Series 61
Low Water Cut-Off
Typical Applications:
- Primary or secondary low water cut-off
for hot water and steam boilers.
- Low water cut-off
- High water cut-off
- Alarm actuator
OPERATION
INSTRUCTION MANUAL
MM-214E
CUT-OFF
LEVEL
Maximum Boiler Pressure: 20 psi (1.4 kg/cm2)
Electrical Ratings
Motor Switch Rating (Amperes)
Voltage Full Load Locked Rotor Pilot Duty
120 VAC
240 VAC
NOTE: 11 MV is rated at 24 VA @ 24VAC to 120 VAC
CAUTION
WARNING
7.4
3.7
• Before using this product read and understand instructions.
• Save these instructions for future reference.
• All work must be performed by qualified personnel trained in the proper application, installation, and maintenance of plumbing, steam, and electrical equipment and/or systems in
accordance with all applicable codes and ordinances.
• To prevent serious burns, the boiler must be cooled to 80˚F (27˚C) and the pressure must be
0 psi (0 bar) before servicing.
• To prevent electrical shock, turn off the electrical power before making electrical connections.
• This low water cut-off must be installed in series with all other limit and operating controls
installed on the boiler. After installation, check for proper operation of all of the limit and
operating controls, before leaving the site.
• We recommend that secondary (redundant) Low Water Cut-Off controls be installed on all
steam boilers with heat input greater than 400,000 BTU/hour or operating above 15 psi of
steam pressure. At least two controls should be connected in series with the burner
control circuit to provide safety redundancy protection should the boiler experience a
low-water condition. Moreover, at each annual outage, the low water cutoffs should be
dismantled, inspected, cleaned, and checked for proper calibration and performance.
• To prevent serious personal injury from steam blow down, connect a drain pipe to the control
opening to avoid exposure to steam discharge.
44.4
22.2
125 VA at
120 or 240 VAC
WARNING
!
Model 61
• To prevent a fire, do not use this low water cut-off to switch currents over 7.4A, 1/3 Hp at
120 VAC or 3.7A, 1/3 Hp at 240 VAC, unless a starter or relay is used in conjunction with it.

Gauge Glass Mounted
Directly into Boiler
CUT-OFF
LEVEL
1" BLOW DOWN
VALVE
For Boilers with
Independent Water Columns
1" STEAM
EQUALIZING PIPE
MODEL 61
LOW WATER
CUT-OFF
1" WATER
EQUALIZING PIPE
1" WATER
EQUALIZING PIPE
1" WATER
EQUALIZING PIPE
CUT-OFF
LEVEL
MODEL 61
LOW WATER
CUT-OFF
a. Whether the gauge glass is mounted directly into the boiler or on an independent water column, the
cut-off line on the 61 body casting should be mounted 1/2” (15mm) above the lowest visible point of the
gauge glass.
a. Locate the gauge glass and
determine the level that the 61
has to be mounted at in order
to achieve the criteria in Step 1.
b. Pipe the 61 following the
diagrams shown to the right.
Follow the diagram that
represents your boiler.
c. Crosses should be used at
each right angle connection for
inspection and cleaning.
d. Make sure the blow-down
valves are full port.
e. Test the Model 61 before
leaving the site
STEP 2 - Installation of the Model 61
Model 61 – For Steam Boilers with 1” (25mm) Equalizing Lines
INSTALLATION –
TOOLS NEEDED:
One (1) flathead screwdriver and two (2) pipe wrenches.
STEP 1 - Determine the Location of the Low Water Cut-Off
California Proposition 65 warning! This product contains chemicals known to the
•
!
state of California to cause cancer and birth defects or other reproductive harm.
Previous controls should never be installed on a new system. Always install new
•
controls on a new boiler or system.
Failure to follow this warning could cause property damage, personal inj ury or death.
CAUTION:
•
A more frequent replacement interval may be necessary based on the condition of
the unit at time of inspection. McDonnell & Miller s warranty is one (1) year from date
&
'
of installation or two (2) years from the date of manufacture.

3
a. The line on the casting of the model 61 must be installed above the lowest permissible water level
determined by the boiler manufacturer.
a. Study the figures to the right and determine which
figure shows how the 61 control will be attached to
the boiler.
Figure 1. Connect the upper equalizing pipe to
the riser going to the radiation or to the compression
tank. Connect the lower equalizing pipe to any
available opening in the side of the boiler. NOTE: If
no opening is available in the side of the boiler,
connect the lower equalizing pipe into the drain
connection.
Figure 2. If there is a tapping available on the
top of the boiler connect the upper equalizing pipe to
it. NOTE: During initial filling or after blow down the
upper equalizing pipe and possibly the 61 control will
have an air pocket. Connect a vent or bleed valve on
the top of the vertical equalizing pipe. If the Test-NCheck (TC-4) valve is used the vacuum breaker can
be used to bleed the air pocket.
CAUTION: When bleeding an air pocket manually,
protect yourself from being burned with hot water.
Figure 3. If there is no tapping available on the
boiler, connect both the upper and lower equalizing
pipe into the vertical riser going to the radiation or to
the
compression tank. IMPORTANT: The horizontal
equalizing
pipe should be below the horizontal
run going to the radiation. If it is not, an air pocket
will be created and a vent or bleed will have to
be installed.
b. Test the Model 61 before leaving the site.
NOTE: If no Test-N-Check (TC-4) valves were used,
do this test before filling the system completely.
STEP 2 - Installation of the Model 61
Model 61 – For Hot Water Boilers with 1” (25mm) Equalizing Lines
INSTALLATION –
TOOLS NEEDED:
One (1) flathead screwdriver and two (2) pipe wrenches.
For float type controls it is recommended that Test-N-Check
®
(TC-4) valves be used in the upper and
lower equalizing lines. They offer a functional means for testing the 61 control, and conform to the
ASME CSD-1 code.
STEP 1 - Determine the Location of the Low Water Cut-Off
VERTICAL RISER
TO RADIATION
HOT WATER
BOILER
MODEL
61
Figure 1
Figure 2
Figure 3
VERTICAL RISER TO RADIATION
OR COMPRESSION TANK
HOT WATER
BOILER
TC-4
MODEL
61
TC-4
AVAILABLE OPENING
IN TOP BOILER
HOT WATER
BOILER
AIR
VENT
MODEL
61

4
1. Assemble the TC-U (the upper Test-N-Check
valve, with the vacuum breaker) into the upper
equalizing line in place of the cross described
in the low water cut-off installation instructions.
NOTE: The vacuum breaker must be on the top
and the long leg must face the boiler. NOTE:
Make sure low water cut-off position is located
in accordance with the boiler manufacturer
recommended cut-off level.
2. Assemble the TC-L (the lower Test-N-Check
valve, without the vacuum breaker) into the
lower equalizing line in place of the cross
described in the low water cut-off installation
instructions. NOTE: The brass cap must be
located above the center of the lower equalizing
line, and the long leg must face the boiler.
3. Assemble the blow-off valve into the bottom
port of the TC-L.
4. Assemble 1” NPT pipe plugs into the remaining
open port in both the TC-U and TC-L.
5. Complete the installation as described in the
low water cut-off installation instructions.
6. After all piping assembly has been completed,
refill the system with water, turn on all electrical
supply and bring system to operating conditions. After system reaches operating pressure,
inspect to make sure no leaks exist at the
threaded connections. Test valves by opening
blow-off valve while burner is on, to make sure
valves operate correctly and low water cut-off
shuts burner off.
TEST-N-CHECK®VALVES
Installation of the TC-4 Test-N-Check Valve with a New Low Water Cut-off
IMPORTANT:
• Installation should be performed by qualified personnel only, in accordance with all applicable codes.
• If vacuum breaker stem is accidentally depressed, hot water could be discharged causing burns.
• Blow-off valve drain piping should be piped to a suitable drain to handle hot water and steam discharge,
and should be the same size as the equalizing pipe.
REMOVE CROSS
TC-U in Place
LWCO
LWCO
TC-L
in Place
Brass
Cap
Blow-off Valve

TOP LEFT BOTTOM RIGHT
TOP12
34
Electrical connector is movable into any one of four positions illustrated, by simply removing two black
headed screws and rotating housing.
NOTE: This control should be wired with materials suitable for use at 75˚C.
Switch Operation
The No. 11 switch can be identified by a black terminal panel. The switch contains two (2) single pole single throw switches to control the water feeder and the low water cut-off. The low water cut-off switch is
between terminals marked “1” and “2”. A second switch is located between terminals marked “3” and “4”.
This can be used to operate a low water alarm or a McDonnell & Miller electric water feeder.
NOTE: Connect hot wire to terminal marked (2) ahead of all controls. See diagram 1 on the following page
(page 6) for control operation. See diagrams 2-4 on the following page (page 6) for proper application
wiring.
Wiring Instructions
• To prevent electrical shock, turn off the electrical power before making electrical connections.
• This low water cut-off must be installed in series with all other limit and operating controls installed on the
boiler. After installation, check for proper operation of all of the limit and operating controls, before leaving
the site.
Failure to follow this warning could cause electrical shock, an explosion and/or a fire, which could result in
property damage, personal injury or death.
WARNING
Cover Removal and Installation Procedure
• Using a flathead screwdriver, remove the one
(1) screw that secures the switch cover.
• Place the cover on the switch housing and,
using a flathead screwdriver, tighten the one
(1) screw to approximately 2 ft•lb (2.6 N•m).

0
2
0
4
1
0
3
0
0
2
0
4
1
0
3
0
0
2
0
4
1
0
3
0
SCHEMATIC OF TWIN SWITCH
INTERNAL OPERATION
NORMAL WATER LEVEL
FEEDER OR ALARM
OPERATING LEVEL
LOW WATER CUT-OFF
OPERATING LEVEL
NEUTRAL WIRE
NEUTRAL WIRE
HOT WIRE
HOT WIRE
TO BURNER
TO ALARM
SAFETY
SWITCH
0
2
0
4
1
0
3
0
USED AS MAIN LINE SWITCH
TO LINE
TO BURNER
STARTER
NO. 11
SWITCH
L1
L2
L3
0
2
0
4
1
0
3
0
USED AS PILOT SWITCH IN SERIES WITH
HOLDING COIL OF AUTOMATIC STARTER
NEUTRAL WIRE
TO
TWO WIRES OF 101A
OR TO ALARM CIRCUIT
HOT WIRE
TO BURNER
JUMPER
NO. 11
SWITCH
0
2
0
4
1
0
3
0
USED WITH MODEL 101 ELECTRIC
WATER VALVE OR IN ALARM CIRCUIT
Diagram 3 Diagram 4
IMPORTANT: Low water cut-off circuit of the 61 series must be electrically wired in series with all other boiler
limit operating controls.
TROUBLESHOOTING
Problem:
1. Burner does not shut off on low water.
a. Cause: Float chamber is loaded with mud or
sediment.
Test: With water level below the control
check if terminals 1 and 2 are open. If
not, remove switch and manually test if
terminals 1 and 2 can be opened.
Solution: Open float chamber and clean. At this
time, check for a build-up of scale or
sediment between corrugations of the
bellows.
b. Cause: Contacts are fused together.
Test: Remove switch and operate manually to
verify proper switch operation.
Solution: Replace switch. Check electrical load
and make sure it is within the ratings of
the switch.
2. Electric water feeder does not shut off.
a. Cause: Build-up of scale or sediment between
corrugations of the bellows.
Test: With water level above the control,
check if terminals 3 and 4 are open. If
not, remove switch and manually test
to verify terminals 3 and 4 can be
opened.
Solution: Open float chamber and replace or
clean the bellows.
b. Cause: Contacts are fused together.
Test: Remove switch and operate manually
to verify proper switch operation.
Solution: Replace switch. Check electrical load
and make sure it is within the ratings of
the switch.

7
MAINTENANCE
SCHEDULE:
• Blow down control as follows when boiler is in
operation:
Steam
– Daily if operating pressure is above 15 psi.
– Weekly if operating pressure is below 15 psi.
Hot Water
– Quarterly
• Disassemble and inspect annually. Replace the
low water cut-off if it is worn, corroded, or if
components no longer operate properly.
• Inspect the float chamber and equalizing piping
annually. Remove all sediment and debris.
• Replace head mechanism every 5 years.
More frequent replacement may be required when
severe conditions exist such as rapid switch cycling,
surging water levels, and use of water treatment
chemicals.
• We recommend head mechanism replacement
when the switch(es) no longer operate properly.
If you choose to replace the switch(es), order the
proper McDonnell & Miller replacement switch or
switch assembly and follow the Repair Procedure
provided.
More frequent blow-down may be necessary due to dirty
water and/or local codes.
NOTE
PROCEDURE:
1. Blow down the low water cut-off when the water
level is at its normal level and the burner is on.
Slowly open the blow-down valve until it is fully
open and observe the water level fall in the gauge
glass. Close the valve after verifying that the pump
contacts have closed and the burner shuts off. If
this does not happen, immediately shut off the
boiler and correct the problem.
To prevent serious personal injury from steam
pipe blow down, connect a drain pipe to the
control opening to avoid exposure to steam
discharge.
Failure to follow this caution could cause
personal injury.

Xylem
1) The tissue in plants that brings water upward from the roots;
2) a leading global water technology company.
We’re 12,500 people unified in a common purpose: creating innovative solutions
to meet our world’s water needs. Developing new technologies that will improve
the way water is used, conserved, and re-used in the future is central to our work.
We move, treat, analyze, and return water to the environment, and we help people
use water efficiently, in their homes, buildings, factories and farms. In more than
150 countries, we have strong, long-standing relationships with customers who
know us for our powerful combination of leading product brands and applications
expertise, backed by a legacy of innovation.
For more information on how Xylem can help you, go to www.xyleminc.com
Xylem Inc.
8200 N. Austin Avenue
Morton Grove, Illinois 60053
Phone: (847) 966-3700
Fax: (847) 965-8379
www.xyleminc.com/brands/mcdonnellmiller
McDonnell & Miller is a trademark of Xylem Inc. or one of its subsidiaries.
© 2013 Xylem Inc. MM-214E July 2013 Part No. 246745