Xylem MM 200G User Manual

Series 64 Low Water Cut-Off
INSTRUCTION MANUAL
MM-200G
Typical Applications:
- Primary or secondary low water cut-off for hot water and steam boilers.
-Low water cut-off
- High water cut-off
-Alarm actuator
OPERATION
Maximum Boiler Pressure: 50 psi (3.5 kg/cm2)
Electrical Ratings
Motor Switch Rating (Amperes)
Voltage Full Load Locked Rotor Pilot Duty
120 VAC 240 VAC
7.4
3.7
NOTE: 11MV is rated 24VA @ 24VAC to 120VAC.
ION
T
U
A
C
ING
N
AR
W
Before using this product read and understand instructions.
•Save these instructions for future reference.
All work must be performed by qualified personnel trained in the proper application, instal-
•To prevent serious burns, the boiler must be cooled to 80˚F (27˚C) and the pressure must be 0 psi (0 bar) before servicing.
•To prevent electrical shock, turn off the electrical power before making electrical connections.
• This low water cut-off must be installed in series with all other limit and operating controls
installed on the boiler. After installation, check for proper operation of all of the limit and operating controls, before leaving the site.
•We recommend that secondary (redundant) Low Water Cut-Off controls be installed on all steam boilers with heat input greater than 400,000 BTU/hour or operating above 15 psi of steam pressure.At least two controls should be connected in series with the burner control circuit to provide safety redundancy protection should the boiler experience a low water condition. Moreover, at each annual outage, the low water cut-offs should be dismantled, inspected,cleaned, and checked for proper calibration and performance.
•To prevent serious personal injury from steam blow down, connect a drain pipe to the control opening to avoid exposure to steam discharge.
•To prevent a fire, do not use this low water cut-off to switch currents over 7.4A, 1/3 Hp at 120 VAC or 3.7A, 1/3 Hp at 240 VAC, unless a starter or relay is used in conjunction with it.
California Proposition 65 warning! This product contains chemicals known to the
state of California to cause cancer and birth defects or other reproductive harm. Previous controls should never be installed on a new system. Always install new
controls on a new boiler or system.
Failure to follow this warning could cause property damage, personal inj ury or death.
CAUTION:
A more frequent replacement interval may be necessary based on the condition of the unit at time of inspection. McDonnell Miller s warranty is one (1) year from date of installation or two (2) years from the date of manufacture.
44.4
22.2
120 VA at
120 or 240 VAC
CUT-OFF
LEVEL
Model 64
CUT-OFF
LEVEL
Model 64-CB
WARNING
!
&
CUT-OFF
LEVEL
Model 64-A
Model 764
'
INSTALLATION –
Model 64 – For Steam Boilers with 1” (25mm) Equalizing Lines
TOOLS NEEDED:
One (1) flathead screwdriver and two (2) pipe wrenches.
STEP 1 - Determine the Location of the Low Water Cut-Off
a. Whether the gauge glass is mounted directly into the boiler or on an independent water column, the
cut-off line on the 64 body casting should be mounted 1/2" (15mm) above the lowest visible point of the gauge glass.
STEP 2 - Installation of the Model 64
a. Locate the gauge glass and
determine the level that the 64 has to be mounted at in order to achieve the criteria in Step 1.
b. Pipe the 64 following the
diagrams shown to the right. Follow the diagram that represents your boiler.
Gauge Glass Mounted
Directly into Boiler
1" STEAM
EQUALIZING PIPE
For Boilers with
Independent Water Columns
1" WATER
EQUALIZING PIPE
c. Crosses should be used at
each right angle connection for inspection and cleaning.
d. Make sure the blow-down
CUT-OFF LEVEL
MODEL 64 LOW WATER CUT-OFF
CUT-OFF LEVEL
MODEL 64 LOW WATER CUT-OFF
valves are full port.
1" WATER
EQUALIZING PIPE
1" BLOW DOWN
VALVE
1" WATER
EQUALIZING PIPE
Test the Model 64 Before Leaving the Site
Open the blow-down valve, causing the water level to drop in the float chamber while burner is operating. As the float drops the alarm circuit (if used) closes first; then on further drop the cut-off circuit will open, shut­ting the burner off.
IMPORTANT: Instruct boiler attendant to blow down the float chamber at least once a week during the heating
2
season, if operating pressure is below 15 psi (1 kg/cm
). If above 15 psi blow down once a day.
NOTE: On new boiler installations, leaky systems, or where the quality of the water is poor, blow down the control more frequently.
CAUTION
Protect yourself when blowing down controls, hot water and steam will flow out of the drain pipe attached to the blow-down valve.Failure to follow this caution may result in serious burns.
2
INSTALLATION –
VERTICAL RISER TO RADIAT ION
HOT WATER
BOILER
MODEL
64
Model 64 – For Hot Water Boilers with 1" (25mm) Equalizing Lines
TOOLS NEEDED:
One (1) flathead screwdriver and two (2) pipe wrenches.
STEP 1 - Determine the Location of the Low Water Cut-Off
a. The line on the casting of the model 64 must be installed above the lowest permissible water level
determined by the boiler manufacturer.
STEP 2 - Installation of the Model 64
For float type controls
it is recommended that Test-N-Check®(TC-4) valves be used in the upper and lower equalizing lines. They offer a functional means for testing the 64 control, and conform to the ASME CSD-1 code.
a. Study the figures to the right and determine which
figure shows how the 64 control will be attached to the boiler.
Figure 1. Connect the upper equalizing pipe to
VERTICAL RISER TO RADIATION OR COMPRESSION TANK
TC-4
AVAILABLE OPENING IN TOP BOILER
AIR VENT
the riser going to the radiation or to the compression tank. Connect the lower equalizing pipe to any available opening in the side of the boiler. NOTE: If
HOT WATER BOILER
MODEL
64
HOT WATER BOILER
MODEL
no opening is available in the side of the boiler, connect the lower equalizing pipe into the drain connection.
TC-4
Figure 2. If there is a tapping available on the top of the boiler connect the upper equalizing pipe to
Figure 1
Figure 2
it. NOTE: During initial filling or after blow down the upper equalizing pipe and possibly the 64 control will have an air pocket. Connect a vent or bleed valve on the top of the vertical equalizing pipe. If the Test-N­Check (TC-4) valve is used the vacuum breaker can be used to bleed the air pocket. CAUTION: When bleeding an air pocket manually, protect yourself from being burned with hot water.
Figure 3. If there is no tapping available on the boiler, connect both the upper and lower equalizing pipe into the vertical riser going to the radiation or to
compression tank. IMPORTANT: The horizontal
the equalizing run going to the radiation. If it is, an air pocket will be
pipe should not be above the horizontal
Figure 3
created and a vent or bleed will have to be installed.
64
Test the Model 64 Before Leaving the Site
While the burner is operating open the blow-down valve, causing the water level to drop in the float chamber.As the float drops the alarm circuit (if used) closes first; then on further drop the cut-off circuit will open, shutting the burner off. NOTE: If no Test-N-Checks (TC-4) valves were used, do this test before filling the system completely.
IMPORTANT: Instruct boiler attendant to blow down the float chamber at least once a week during the heating
2
season, if operating pressure is below 15 psi (1 kg/cm
). If above 15 psi blow down once a day.
NOTE: On a new boiler installation, leaky system, or where the quality of the water is poor, blow down the control more frequently.
CAUTION
Protect yourself when blowing down controls, hot water will flow out of the drain pipe attached to the blow-down valve. Failure to follow this caution may result in serious burns.
3
HOT WATER BOILER
DO NOT REDUCE THIS 2 1/2" DIMENSION
BLOWDOWN VALV E
MODEL 764 LOW WATER CUT OFF
INSTALLATION –
HOT WATER BOILER
DO NOT REDUCE THIS 2 1/2" DIMENSION
MODEL 764 LOW WATER CUT OFF
BLOWDOWN VALV E
SUPPLY LINE
Model 764 – For Steam or Hot Water Boilers
TOOLS NEEDED:
One (1) flathead screwdriver and two (2) pipe wrenches.
STEP 1 - For Steam or Hot Water Boilers where 2 1/2” (65mm) Tapping is Provided
a. See figure 1. The 2 1/2" (65mm) tapping on
the boiler has to be above the minimum safe operating level, as determined by the boiler manufacturer. On steam boilers, make sure the line on the casting is above the lower gauge glass nut. NOTE: Do not reduce the 2 1/2" (65mm) tapping, as this would compro­mise low water protection.
Figure 1
STEP 2 - For Hot Water Boilers where 2 1/2” (65mm) Tapping is not Provided
a. See figure 2. If there are no 2 1/2" (65mm)
tappings on a hot water boiler, the 764 control can be mounted on a 2 1/2" (65mm) tee on the riser going to the radiation or compression tank. NOTE: Do not reduce the 2 1/2" (65mm) tapping, as this would compro­mise low water protection.
Figure 2
Test the Model 764 Before Leaving the Site
While the burner is operating open the blow-down valve, causing the water level to drop in the float chamber. As the float drops the alarm circuit (if used) closes first; then on further drop the cut-off circuit will open, shutting the burner off. NOTE: If no Test-N-Checks (TC-4) valves were used, do this test before filling the system completely.
IMPORTANT: Instruct boiler attendant to blow down the float chamber at least once a week during the heat-
2
ing season, if operating pressure is below 15 psi (1 kg/cm
). If above 15 psi blow down once a day.
NOTE: On a new boiler installation, leaky system, or where the quality of the water is poor, blow down the control more frequently.
CAUTION
Protect yourself when blowing down controls, hot water will flow out of the drain pipe attached to the blow-down valve. Failure to follow this caution may result in serious burns.
4
INSTALLATION –
Model 64-A – For Steam Boilers Using Quick Hook-up Fittings
TOOLS NEEDED:
One (1) flathead screwdriver, two (2) pipe wrenches, and an adjustable wrench.
STEP 1 - Preparing the Boiler
a. Remove gauge glass and its trim from the boiler.
STEP 2 - Installation of the Model 64-A
a. See figures 1 and 2. Install both brass Y fittings
(A) into the boiler gauge glass tappings. NOTE: If gauge glass tappings are spaced more than 10 1/8" (270mm) apart, invert the Black Y (B). See figure 2. If spaced greater than 13 3/8" (339mm), substitute a longer 1/2" (15mm) nipple for original (C).
A
INVERTED
B
C
b. See figure 3. Install reducing bushing (D) and
Figure 2
nipple (C) into top 1" (25mm) NPT tapping (E). Install reducing bushing (F), nipple (G), and
Figure 1
blow down valve (H) into 1" (25mm) NPT (J).
B
S
c. See figure 3. Slip union nut (K) over lower tail
P
O
R
piece (L) and screw it into either 1/2" (15mm) tapping (M) or (N). Use the 1/2" (15mm) pipe plug to close unused tapping. Slip union nut (O) over union piece (P) and nipple (R) and install into black Y (B). Slide black Y (B) over nipple
C
K
L
D
E
(C). Connect upper (O) and lower (K) unions to brass Y fitting (A, figure 1) and tighten. NOTE: the black Y (B) will have to be moved up or down to mate the union halves.Tighten
N
M
J
F
G
compression nut (S).
H
Figure 3
Test the Model 64-A Before Leaving the Site
While the burner is operating open the blow-down valve, causing the water level to drop in the float chamber. As the float drops the alarm circuit (if used) closes first; then on further drop the cut-off circuit will open,
shutting the burner off. NOTE: If no Test-N-Checks (TC-4) valves were used, do this test before filling the system completely.
IMPORTANT: Instruct boiler attendant to blow down the float chamber at least once a week during the heat-
2
ing season, if operating pressure is below 15 psi (1 kg/cm NOTE: On a new boiler installation, leaky system, or where the quality of the w
). If above 15 psi blow down once a day.
ater is poor, blow down the
control more frequently.
CAUTION
Protect yourself when blowing down controls, hot water will flow out of the drain pipe attached to the blow-down valve. Failure to follow this caution may result in serious burns.
5
TOP LEFT BOTTOM RIGHT
TOP12
34
Wiring Instructions
Cover
•To prevent electrical shock, turn off the electrical power before making electrical connections.
This low water cut-off must be installed in series with all other limit and operating controls installed on the
boiler.After installation, check for proper operation of all of the limit and operating controls, before leaving the site.
Failure to follow this warning could cause electrical shock, an explosion and/or a fire, which could result in property damage, personal injury or death.
Using a flathead screwdriver, remove the one (1) screw that secures the switch cover.
WARNING
Electrical connector is movable into any one of four positions illustrated, by simply removing two black headed screws and rotating housing.
NOTE: This control should be wired with materials suitable for use at 75˚C.
Switch Operation
The No. 11 switch can be identified by a black terminal panel. The switch contains two (2) single pole sin­gle throw switches to control the water feeder and the low water cut-off. The low water cut-off switch is between terminals marked “1” and “2”. A second switch is located between terminals marked “3” and “4”. This can be used to operate a low water alarm or a McDonnell & Miller electric water feeder.
NOTE: Connect hot wire to terminal marked (2) ahead of all controls.See diagram 1 on the following page (page 7) for control operation. See diagrams 2-4 on the following page (page 7) for proper application wiring.
6
0
2
0
4
1
0
3
0
0
2
0
4
1
0
3
0
0
2
0
4
1
0
3
0
SCHEMATIC OF TWIN SWITCH
INTERNAL OPERATION
NORMAL WATER LEVEL
FEEDER OR ALARM OPERATING LEVEL
LOW WATER CUT-OFF OPERATING LEVEL
NEUTRAL WIRE
NEUTRAL WIRE
HOT WIRE
HOT WIRE
TO BURNER
TO ALARM
SAFETY SWITCH
0
2
0
4
1
0
3
0
USED AS MAIN LINE SWITCH
Diagram 1 Diagram 2
NEUTRAL WIRE
TO
TWO WIRES OF 101A
OR TO ALARM CIRCUIT
HOT WIRE
TO BURNER
JUMPER
SAFETY SWITCH
0
2
0
4
1
0
3
0
USED WITH MODEL 101 ELECTRIC
WATER VALVE OR IN ALARM CIRCUIT
Cover
Switch
Housing
12
34
NEUTRAL
HOT
ALARM
RESET
BUTTON
BURNER
TRANSFORMER
(OPTIONAL)
NORMAL WATER LEVEL
12
34
RESET
BUTTON
12
34
RESET
BUTTON
LOW WATER CUT-OFF ALARM LEVEL
Diagram 3
IMPORTANT: Low water cut-off circuit of the 64 series must be electrically wired in series with all other boiler
limit operating controls.
Model 64A-M For use on 24 or 120 VAC systems requiring manual reset on low water cut-off.
CAUTION
Do not electrically connect water feeder to Model 64A-M. This model includes a manual reset feature, failure to follow this caution could result in boiler flooding and property damage.
WIRING SCHEMATIC
Place the cover on the switch housing and, using a flathead screwdriver, tighten the one (1) screw to approximately 2 ft•lb (2.6 N•m).
SWITCH SCHEMATIC
7
MAINTENANCE
SCHEDULE:
Blow down weekly during heating season.
•Open up float chamber and clean annually.
More frequent cleaning may be necessary if there are high make-up water requirements or poor local water quality.
Replace control every 10 years.
TROUBLESHOOTING
Problem:
1. Burner does not shut off on low water.
a. Cause: Float chamber is loaded with mud or
sediment.
Test: With water level below the control
check if terminals 1 and 2 are open. If not, remove switch and manually test if terminals 1 and 2 can be opened.
Solution: Open float chamber and clean. At this
time, check for a build-up of scale or sediment between corrugations of the bellows.
b. Cause: Contacts are fused together.
Test: Remove switch and operate manually to
verify proper switch operation.
Solution: Replace switch. Check electrical load
and make sure it is within the ratings of the switch.
2. Electric water feeder does not shut off.
a. Cause: Build-up of scale or sediment between
corrugations of the bellows.
Test: With water level above the control,
check if terminals 3 and 4 are open. If not, remove switch and manually test to verify terminals 3 and 4 can be opened.
Solution: Open float chamber and replace or
clean the bellows.
b. Cause: Contacts are fused together.
Test: Remove switch and operate manually
to verify proper switch operation.
Solution: Replace switch. Check electrical load
and make sure it is within the ratings of the switch.
Xylem Inc.
8200 N. Austin Avenue Morton Grove, Illinois 60053 Phone: (847) 966-3700 Fax: (847) 965-8379 www.xyleminc.com/brands/mcdonnellmiller
McDonnell & Miller is a trademark of Xylem Inc. or one of its subsidiaries.
© 2013 Xylem Inc. MM-200G July 2013 Part No. 245632
Loading...