Xylem IM247 User Manual

QUICKSTART GUIDE
IM247R02
SPD PLUS
Centrifugal Pump Controller
Quick Start Guide
Overview
The installation of the SPD PLUS adjust-able speed drive follows the outline below.
Task
PREPARE for installation
PREPARE mounting location
REMOVE the front cover
MOUNT the drive
INSTALL wiring
CHECK installation
REINSTALL the cover
APPLY power
START-UP Assistant
Application
This guide provides a quick reference for installing SPD PLUS drives having a standard enclosure (NEMA 1).
NOTE: This guide does not provide detailed installation, safety or operational instruc­tions. See the Installation Operation Manual for complete information.
Prepare for Installation
WARNING! The Aquavar should ONLY
be installed by a qualified electrician.
Check
• Motor Compatibility – Motor type, nominal current,
frequency and voltage range must match drive specifications (3 phase motor only).
• Suitable Environment – Drive requires heated,
indoor controlled environment that is suitable for the selected enclosure below 122º F (50º C).
• Wiring – Follow local codes for wiring and fusing
requirements. Refer to NEC, Local, State or Munici­pal codes.
Refer to the Installation Operation Manual and confirm that all preparations are complete.
Tools Required
Screwdrivers, wire stripper, tape measure, mount­ing screws or bolts, and drill.
Use the following chart to interpret the type code found on the drive label.
SPD 4 0600 N1
Single Pump Drive
Voltage
2 – 230 Volt 4 – 460 Volt 5 – 575 Volt
Nominal Horsepower
0400 = 40 HP 0500 = 50 HP 0600 = 60 HP 0750 = 75 HP 1000 = 100 HP
Enclosure and Filter Options
Blank = NEMA 3R, no lter N1 = NEMA 1, no lter F = NEMA 3R, with lter
NOTE: HP rating is for reference only, and is based on 3Ø input power.
Collect Motor Data
Collect the following data from the motor nameplate for later use in the Aquavar startup:
______________________________
• Voltage
• Nominal Motor Current
• Nominal Frequency
• Nominal Speed
• Nominal Power
_______________
___________________
______________________
_______________________
Unpack the Drive
NOTE: Lift the SPD PLUS by its chassis and not
by its cover.
1. Unpack the drive.
2. Check for any damage and notify the shipper immediately if damaged com­ponents are found.
3. Check the contents against the order and the shipping label to verify that all parts have been received.
Prepare the Mounting Location
The drive requires a smooth, vertical, solid surface, free from heat and moisture, with free
space for air ow – 200 mm (8
in.) above and below, and 25 mm (1 in.) around the sides of the drive.
1. Mark the mounting
points.
2. Drill the mounting holes.
1
Remove the Front Cover
1. Remove the control panel (display), if attached.
2. Loosen the captive screw at the top.
3. Pull near the top to remove the cover.
Mount the Drive
1. Position the SPD PLUS and use screws or bolts to securely tighten all four corners.
2. Attach a warning sticker in the appropriate lan­guage on the inside plastic shell.
Install the Wiring (copper only)
1. Install thin-wall conduit clamps (not
supplied) in the conduit/gland box.
2. Install conduit/gland box.
Wiring Power
1. Connect conduit runs to box.
2. Route input power and motor
wiring through conduits.
3. Strip wires.
4. Connect power, motor and ground wires to the drive terminals. See “Power Supply and Wiring” in the instruction manual.
Frame Sizes R1…R4
X0002
* Single phase input power must use U1, W1
and PE for wiring.
WARNING! For floating networks remove screws at EM1 and EM3 on
Frame Sizes R1…R4.
Frame Size R5
Frame Size R6
WARNING!
For floating net­works remove screws at
F1 and F2 on Frame
Sizes R5 or R6.
Wiring the Transducer
1. Route the transducer cable through the conduit.
3
5
2. Strip the transducer cable sheathing and twist
1
the screen wire.
3. Connect the screen wire of the transducer to terminal X1-1.
4. Connect the power supply wire of the
transducer (red or brown) to terminal X1-10.
5. Connect analog output wire from the transducer (white or black) to X1-5. See chart in next column.
6. Install the conduit/gland box cover (1
screw).
1
Digital input impedance 1.5 kΩ. Maximum voltage
for digital inputs is 30 V.
Check Installation
Before applying power, perform the follow­ing checks.
Check
Environment conforms to specifications. The drive is mounted securely. Proper cooling space around the drive. Motor and driven equipment are ready for start. Floating networks: Internal RFI filter disconnected. Drive is properly grounded, with pump/motor. Input power (mains) voltage matches the drive
nominal input voltage. The input power (mains) terminals, U1, V1, W1,
are connected and tightened as specified. The input power (mains) fuses / mains switch installed. The motor terminals, U2, V2, W2, are connected
and tightened as specified. Motor cable is routed away from other cables. NO power factor compensation capacitors are
connected to the motor cable. Control terminals are wired and tightened as specified. NO tools or foreign objects (such as drill shavings) are
inside the drive. NO alternate power source for the motor is connected
– no input voltage is applied to the output of the drive.
Reinstall the Cover
1. Align the cover and slide it on.
2. Tighten the captive screw.
3. Reinstall the control panel.
Apply Power
Always reinstall the front cover before turn­ing power on.
WARNING! The SPD PLUS will start up automatically at power up, if the external run command is on.
1. Apply input power.
When power is applied to the SPD PLUS,
the green LED comes on.
NOTE! Before increasing motor speed, check that the motor is running in the desired direction.
Start-Up
Run the Start-Up Assistant to configure the motor and system parameters. If this is the first time the drive has been powered, the display will prompt the user if they would like to run the Start­Up Assistant. Select Yes to run the Start-Up Assistant. If this is not the first time the drive has been powered, follow the steps below:
1. From the Main Screen press MENU to enter the MENU screen.
2. Select QUICKSTART
3. Select Start-Up
4. Follow the menu prompts to congure the drive.
NOTE! For common parameters and menu items, use the Help Key to display descriptions. If you encounter Alarms or Faults, use the Help Key or refer to the Diagnostic section of the instruction manual.
REM
DIR MENU
LOC REM
40.2 PSI sp
0.0 PSI ac
0.0 HZ
11.1%
Xylem, Inc.
2881 East Bayard Street Ext., Suite A, Seneca Falls, NY 13148
Phone: (800) 453-6777 • Fax: (888) 322-5877 • www.centripro.com
CentriPro and Aquavar are trademarks of Xylem, Inc. or one of its subsidiaries.
© 2012 Xylem Inc. IM247 Rev. 2 March 2013
Loading...