QUICKSTART GUIDE
IM247R02
SPD PLUS
Centrifugal Pump Controller
Quick Start Guide
Overview
The installation of the SPD PLUS adjust-able
speed drive follows the outline below.
Task
PREPARE for installation
UNPACK the drive
PREPARE mounting location
REMOVE the front cover
MOUNT the drive
INSTALL wiring
CHECK installation
REINSTALL the cover
APPLY power
START-UP Assistant
Application
This guide provides a quick reference for
installing SPD PLUS drives having a standard
enclosure (NEMA 1).
NOTE: This guide does not provide detailed
installation, safety or operational instructions. See the Installation Operation Manual
for complete information.
Prepare for Installation
WARNING! The Aquavar should ONLY
be installed by a qualified electrician.
Check
• Motor Compatibility – Motor type, nominal current,
frequency and voltage range must match drive
specifications (3 phase motor only).
• Suitable Environment – Drive requires heated,
indoor controlled environment that is suitable for
the selected enclosure below 122º F (50º C).
• Wiring – Follow local codes for wiring and fusing
requirements. Refer to NEC, Local, State or Municipal codes.
Refer to the Installation Operation Manual and
confirm that all preparations are complete.
Tools Required
Screwdrivers, wire stripper, tape measure, mounting screws or bolts, and drill.
Use the following chart to interpret the type code
found on the drive label.
SPD 4 0600 N1
Single Pump Drive
Voltage
2 – 230 Volt 4 – 460 Volt 5 – 575 Volt
Nominal Horsepower
0400 = 40 HP 0500 = 50 HP 0600 = 60 HP
0750 = 75 HP 1000 = 100 HP
Enclosure and Filter Options
Blank = NEMA 3R, no lter N1 = NEMA 1, no lter
F = NEMA 3R, with lter
NOTE: HP rating is for reference only, and is based on 3Ø input power.
Collect Motor Data
Collect the following data from the motor nameplate
for later use in the Aquavar startup:
______________________________
• Voltage
• Nominal Motor Current
• Nominal Frequency
• Nominal Speed
• Nominal Power
_______________
___________________
______________________
_______________________
Unpack the Drive
NOTE: Lift the SPD PLUS by its chassis and not
by its cover.
1. Unpack the drive.
2. Check for any damage and notify the
shipper immediately if damaged components are found.
3. Check the contents against the order
and the shipping label to verify that all
parts have been received.
Prepare the Mounting Location
The drive requires a smooth,
vertical, solid surface, free from
heat and moisture, with free
space for air ow – 200 mm (8
in.) above and below, and 25
mm (1 in.) around the sides of
the drive.
1. Mark the mounting
points.
2. Drill the mounting holes.
1
Remove the Front Cover
1. Remove the control panel
(display), if attached.
2. Loosen the
captive screw
at
the top.
3. Pull near the
top to remove
the cover.
Mount the Drive
1. Position the
SPD PLUS and use
screws or bolts to
securely tighten all
four corners.
2. Attach a warning
sticker in the
appropriate language on the inside
plastic shell.
Install the Wiring (copper only)
1. Install thin-wall conduit clamps (not
supplied) in the conduit/gland box.
2. Install conduit/gland box.
Wiring Power
1. Connect conduit runs to box.
2. Route input power and motor
wiring through conduits.
3. Strip wires.
4. Connect power, motor and
ground wires to the drive terminals.
See “Power Supply and Wiring”
in the instruction manual.
Frame Sizes R1…R4
X0002
* Single phase input power must use U1, W1
and PE for wiring.
WARNING! For floating networks
remove screws at EM1 and EM3 on
Frame Sizes R1…R4.
Frame Size R5
Frame Size R6
WARNING!
For floating networks remove
screws at
F1 and F2
on Frame
Sizes R5 or R6.
Wiring the Transducer
1. Route the
transducer
cable
through
the conduit.
3
5
2. Strip the
transducer
cable
sheathing
and twist
1
the screen
wire.
3. Connect the screen
wire of the
transducer to
terminal X1-1.
4. Connect the power supply wire of the
transducer (red or brown) to terminal
X1-10.
5. Connect analog output wire from the
transducer (white or black) to X1-5. See
chart in next column.
6. Install the conduit/gland box cover (1
screw).
1
Digital input impedance 1.5 kΩ. Maximum voltage
for digital inputs is 30 V.
Check Installation
Before applying power, perform the following checks.
√ Check
Environment conforms to specifications.
The drive is mounted securely.
Proper cooling space around the drive.
Motor and driven equipment are ready for start.
Floating networks: Internal RFI filter disconnected.
Drive is properly grounded, with pump/motor.
Input power (mains) voltage matches the drive
nominal input voltage.
The input power (mains) terminals, U1, V1, W1,
are connected and tightened as specified.
The input power (mains) fuses / mains switch installed.
The motor terminals, U2, V2, W2, are connected
and tightened as specified.
Motor cable is routed away from other cables.
NO power factor compensation capacitors are
connected to the motor cable.
Control terminals are wired and tightened as specified.
NO tools or foreign objects (such as drill shavings) are
inside the drive.
NO alternate power source for the motor is connected
– no input voltage is applied to the output of the drive.
Reinstall the Cover
1. Align the cover
and slide
it on.
2. Tighten
the captive
screw.
3. Reinstall the
control panel.
Apply Power
Always reinstall the front cover before turning power on.
WARNING! The SPD PLUS will start
up automatically at power up, if the
external run command is on.
1. Apply input power.
When power is applied to the SPD PLUS,
the green LED comes on.
NOTE! Before increasing motor speed,
check that the motor is running in the
desired direction.
Start-Up
Run the Start-Up Assistant
to configure the motor and
system parameters. If this is
the first time the drive has
been powered, the display
will prompt the user if they
would like to run the StartUp Assistant. Select Yes to
run the Start-Up Assistant.
If this is not the first time the drive has been
powered, follow the steps below:
1. From the Main Screen press MENU to
enter the MENU screen.
2. Select QUICKSTART
3. Select Start-Up
4. Follow the menu prompts to congure
the drive.
NOTE! For common parameters and
menu items, use the Help Key to
display descriptions. If you encounter
Alarms or Faults, use the Help Key or
refer to the Diagnostic section of the
instruction manual.
REM
DIR MENU
LOC
REM
40.2 PSI sp
0.0 PSI ac
0.0 HZ
11.1%
Xylem, Inc.
2881 East Bayard Street Ext., Suite A, Seneca Falls, NY 13148
Phone: (800) 453-6777 • Fax: (888) 322-5877 • www.centripro.com
CentriPro and Aquavar are trademarks of Xylem, Inc. or one of its subsidiaries.
© 2012 Xylem Inc. IM247 Rev. 2 March 2013