INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
SUBJECT PAGE
e-SV Product Line Numbering System ...........................................................................................................................3
Transportation and Storage ............................................................................................................................................9
Mechanical Seal Replacement (Sizes 1SV-125SV) ........................................................................................................14
Mechanical Seal Replacement (Sizes 33SV-125SV) Fitted with Cartridge Seals ............................................................14
Motor Replacement .....................................................................................................................................................15
Engineering Data .........................................................................................................................................................16
Typical Plumbing and Installation ................................................................................................................................16
e-SV Major Components ........................................................................................................................................17-19
Pump Model Number:
Pump Serial Number:
Control Model Number:
Dealer:
Dealer Phone No.:
Date of Purchase: Installation:
Current Readings at Startup:
1 Ø 3 Ø L1-2 L2-3 L3-1
Amps: Amps:
Volts: Volts:
2
e-SV Product Line
Numbering System for 1 – 22SV Liquid End Only
The various versions of the e-SV line are identified by a product code number on the pump label. This number is also
the catalog number for the pump. The meaning of each digit in the product code number is shown below.
Note: Not all combinations are possible.
Example Product Code
22 SV 0 2 F E 3 0
Special Configurations (optional Characters)A = Jacketed Seal only
B = Jacketed Seal + Passivation
C = Jacketed Seal + Low NPSH
E = Electro-Polished
F = Destaged - 1 stage
G = Destaged - 2 stage
H = Horizontal mount only
J = Horizontal mount + Passivation
K = Horizontal mount + Low NPSH
L = Horizontal mount + High Pressure
M = i-Alert (standard for 10 HP units and greater)
N = Low NPSH only
P = Passivation only
Z = High pressure only
Motor Frame (NEMA)A = 56C E = 280TC
B = 180TC F = 320TSC
C = 210TC G = 360TSC
D = 250TC H = 140TC
ConfigurationC = Clamp-316 P = Victaulic-316 R = (SVC) 12Suct-12Disch
F = Round-304 (SVB) T = Oval-304 (SVA) W = (SVC) 12Suct-03Disch
G = CI-304 X = (SVC) 12Suct-06Disch
N = Round-316 (SVD) Y = (SVC) 12Suct-09Disch
Total Number of Impeller Stages (may be 1 or 2 characters)
Product Line:
SV – Stainless Vertical
Nominal Flow:
1 = 5 GPM 10 = 53 GPM
3 = 16 GPM 15 = 80 GPM
5 = 26 GPM 22 = 116 GPM
Top / Bottom
Suction
discharge
location
3
e-SV Product Line
Numbering System for 33 – 125SV Liquid End Only
The various versions of the e-SV line are identified by a product code number on the pump label. This number is also
the catalog number for the pump. The meaning of each digit in the product code number is shown below.
Note: Not all combinations are possible.
Example Product Code
125 SV 8 1 2 B F E 2 0
Special Configurations (optional Characters)E = Electro-Polished
F = Destaged - 1 stage
G = Destaged - 2 stage
H = Horizontal mount only
J = Horizontal mount + Passivation
K = Horizontal mount + Low NPSH (33, 46, and 66 only)
L = Horizontal mount + High Pressure
M = i-Alert (standard for 10 HP units and greater)
N = Low NPSH only (33, 46, and 66 only) P = Passivation only
Z = High pressure (250/300# pump body)
e-SV Product Line
Numbering System for 1 – 22SV Pump & Motor Combination
The various versions of the e-SV line are identified by a product code number on the pump label. This number is also
the catalog number for the pump. The meaning of each digit in the product code number is shown below.
Note: Not all combinations are possible.
Example Product Code
2 SV 2 2 F A 2 F 5 1 A H
Special Configurations (1 or 2 Characters)A = Jacketed Seal only J = Horizontal mount + Passivation
B = Jacketed Seal + Passivation K = Horizontal mount + Low NPSH
C = Jacketed Seal + Low NPSH L = Horizontal mount + High Pressure
E = Electro-Polished M = i-Alert (standard for 10 HP units and greater)
F = Destaged - 1 stage N = Low NPSH only
G = Destaged - 2 stage P = Passivation only
H = Horizontal mount only Z = High Press (250/300# pump body)
A = 115-230 H = 190/380 R = 220
B = 230 J = 115/208-230 S = 415
C = 230-460 K = 208 T = 220/380 WYE
D = 460 L = 208-230 U = 380-660 WYE
E = 575 M = 190/380/415 V = 208-230/460 WYE
F = 208-230/460 N = 380
G = 200 P = 110/220
HP RatingA = 0.50 H = 7.5
B = 0.75 J = 10
C = 1.00 K = 15
D = 1.50 L = 20
E = 2 M = 25
F = 3 N = 30
G = 5 P = 40
Configuration OPTIONC = Clamp-316
F = Round-304 (SVB) R = (SVC) 12Suct-12Disch
G = CI-304 W = (SVC) 12Suct-03Disch
N = Round-316 (SVD) X = (SVC) 12Suct-06Disch
P = Victaulic-316 Y = (SVC) 12Suct-09Disch
T = Oval-304 (SVA)
Total Number of Impeller Stages (may be 1 or 2 characters)
Product Line:
SV – Stainless Vertical
Nominal Flow:
1 = 5 GPM 10 = 53 GPM
3 = 16 GPM 15 = 80 GPM
5 = 26 GPM 22 = 116 GPM
Top / Bottom
Suction
discharge
location
5
e-SV Product Line
Numbering System for 33 – 125SV Pump & Motor Combination
The various versions of the e-SV line are identified by a product code number on the pump label. This number is also
the catalog number for the pump. The meaning of each digit in the product code number is shown below.
Note: Not all combinations are possible.
Example Product Code
125 SV 8 2 A G K 3 F 2 0
Special Configurations (1 or 2 Characters)E = Electro-Polished L = Horizontal mount + High Pressure
F = Destaged - 1 stage M = i-Alert (standard for 10 HP units and greater)
G = Destaged - 2 stage N = Low NPSH only (33, 46 and 66 only)
H = Horizontal mount only P = Passivation only
J = Horizontal mount + Passivation Z = High Press (250/300# pump body/Casing)
K = Horizontal mount + Low NPSH
A = 115-230 H = 190/380 R = 220
B = 230 J = 115/208-230 S = 415
C = 230-460 K = 208 T = 220/380 WYE
D = 460 L = 208-230 U = 380-660 WYE
E = 575 M = 190/380/415 V = 208-230/460 WYE
F = 208-230/460 N = 380
G = 200 P = 110/220
HP RatingA = 0.50 H = 7.5 R = 50
B = 0.75 J = 10 S = 60
C = 1.00 K = 15 T = 75
D = 1.50 L = 20
E = 2 M = 25
F = 3 N = 30
G = 5 P = 40
ConfigurationG = Round-CI-304
N = Round-316
125SV ONLY
Reduced Trim Diameter A = 141 mm B = 136 mm C = 145 mm (full dia.)Blank if 33-92SV
Number of Reduced Trin Impeller (0, 1, 2)
Total Number of Impeller Stages (may be 1 or 2 characters)
Product Line:
SV – Stainless Vertical
Nominal Flow:
33 = 175 GPM 92 = 485 GPM
46 = 240 GPM 125 = 660 GPM
66 = 350 GPM
6
SAFETY INSTRUCTIONS
DANGER
WARNING
CAUTION
WARNING
Hazardous fluids
can cause fire,
burns or death.
WARNING
TO AVOID SERIOUS OR FATAL PERSONAL
INJURY OR MAJOR PROPERTY DAMAGE, READ
AND FOLLOW ALL SAFETY INSTRUCTIONS IN
MANUAL AND ON PUMP.
THIS MANUAL IS INTENDED TO ASSIST IN THE
INSTALLATION AND OPERATION OF THIS UNIT
AND MUST BE KEPT WITH THE PUMP.
This is a SAFETY ALERT SYMBOL.
When you see this symbol on the pump
or in the manual, look for one of the
following signal words and be alert
to the potential for personal injury or
property damage.
Warns of hazards that WILL cause
serious personal injury, death or major
property damage.
Warns of hazards that CAN cause
serious personal injury, death or major
property damage.
Warns of hazards that CAN cause personal injury or property damage.
NOTICE: INDICATES SPECIAL INSTRUCTIONS
WHICH ARE VERY IMPORTANT AND
MUST BE FOLLOWED.
THOROUGHLY REVIEW ALL INSTRUCTIONS
AND WARNINGS PRIOR TO PERFORMING ANY
WORK ON THIS PUMP.
MAINTAIN ALL SAFETY DECALS.
that are in contact with the pumped liquid are made of
stainless steel, others are made of cast iron. They are
available in different versions according to the position
of the suction and delivery ports and the shape of the
connection flanges. For the sizes 33SV-125SV, some of
the metal parts in contact with the pumped liquid are
made of stainless steel, others are made of cast iron. A
special version is available, in which all the metal parts
in contact with the pumped liquid are made of stainless
steel. If you purchase a pump without the electric motor,
make sure that the motor you use is suitable for coupling
to the pump. All e-SV pumps are equipped with a special
mechanical seal designed for easy replacement without
having to disassemble the entire pump.
These pumps are suitable for civil and industrial water
distribution systems, pressure booster, irrigation (agriculture, sporting facilities), water treatment, boiler feed,
parts washing, cooling - air conditioning - refrigeration
and fire fighting applications.
1. NAMEPLATE
Do not use this pump/electric pump unit to
handle flammable and/or explosive liquids.
Do not use this pump to handle liquids
containing abrasive, solid or fibrous sub-
stances.
UNIT NOT DESIGNED FOR USE
WITH HAZARDOUS LIQUIDS OR
FLAMMABLE GASES. THESE
FLUIDS MAY BE PRESENT IN
CONTAINMENT AREAS.
The purpose of this manual is to provide the necessary information for proper installation, operation and
maintenance of the e-SV pump. The instructions and
warnings provided below concern the standard version,
as described in the sale documents. Special versions may
be supplied with supplementary instructions leaflets.
Please refer to the sale contract for any modifications or
special version characteristics. Always specify the exact
pump type and identification code when requesting
technical information or spare parts from our Sales and
Service department. For instructions, situations or events
not considered in this manual or in the sale documents,
please contact your distributor.
Read this manual before installing and using the product.
Improper use may cause personal injury and
damage to property and lead to the forfeiture of
the warranty coverage.
The e-SV pump is a vertical multistage, non-self priming
pump which can be coupled to standard electric motors.
For the pump sizes 1SV-22SV, some of the metal parts
1 Goulds Water Technology Catalog Number
2 Capacity Range
3 TDH Range
4 Rated Speed
5 Rated Horsepower
6 Maximum Operating Pressure
7 Maximum Operating Temperature
8 Pump Serial Number
Confirm that the pump is capable of meeting the desired
operating conditions.
1. MINIMUM INLET (SUCTION) PRESSURE
In general, the minimum suction pressure required
is that which provides adequate NPSHA necessary to
feed the pump. The required NPSHr, expressed in
feet, can be found on the performance curve for the
pump at the specific duty point. It is recommended
that the NPSHA exceeds the NPSHr by a minimum
of (2) two feet as a safety margin and to insure long
term reliable performance of your e-SV pump.
7
PS
WARNING
WARNING
WARNING
= NPSHr + 2 ft.
MIN
NOTE: THE NPSHA MUST BE CALCULATED FOR
THE SPECIFIC SYSTEM TO WHICH THE
e-SV PUMP IS TO BE INSTALLED. PLEASE
CONTACT YOUR DEALER/DISTRIBUTOR IF
YOU REQUIRE ASSISTANCE.
2. SUCTION
In theory, a pump could suck water from a source
located 10.33 meters lower than the pump’s own
installation level, but this does not happen because
the pump offers its own intrinsic flow resistance,
moreover the suction capacity is reduced as a result
of flow resistance in the piping, height difference,
liquid temperature and elevation above sea level.
A wrong choice in the altimetric placement of the
pump could lead to cavitation.
With reference to Figure below and given Z as the
maximum height the pump can be installed to, with
reference to the level of the liquid source it can be
stated the following:
In SI Units:
Z = Pb • 10,2 – NPSH – Hf - Hv -0,5 [m]
Pb = Barometric pressure [bar] (absolute)
NPSHr = NPSH required by pump [m]
Hf = Losses [m] in suction piping
Hv = Vapor pressure [m] at application temp [C]
1,5 = 1,5 [m] safety factor
Do not use the pump if cavitation
occurs, as its internal components
could be damaged.
If hot water is pumped, guarantee an
appropriate condition on the suction
side to prevent cavitation.
Make sure that the sum of the
pressure on the suction side (water
system, gravity tank) and the maximum pressure delivered by the pump does not exceed the maximum
working pressure allowed (nominal pressure PN) for
the pump.
3. MAXIMUM INLET PRESSURE, 60 HZ
p
≤ PN - pmax
1max
Having the following meaning of the symbols:
p
= Maximum pressure delivered by the pump
max
p
= Maximum inlet pressure
1max
PN = Maximum operating pressure
If a motor with an axially locked shaft (standard) is
used, be sure that the above formula is fulfilled, if
not please contact the Sales and Service Department.
In English Units:
Z = Pb – NPSHr – Hf – Hv – 1.5
Pb = Barometric pressure [ft] (absolute)
NPSHr = NPSH required by pump [ft]
Hf = Losses [ft] in suction piping
Hv = Vapor pressure [ft] at application temp [F]
1.5 = 1.5 [ft] safety factor
With meanings given in the above table it can be
stated that:
If Z ≥ 0 pump can work with a maximum suction
height equal to Z.
If Z <0 pump must be provided of an inlet pressure
The following table shows the maximum permissible
inlet pressure. However, the actual inlet pressure +
pressure against a closed valve must always be lower
than the maximum permissible operating pressure.
Pump Stages
(psig)
2-5 145
1SV 6-10 218
11-30 PN-Pmax
2-3 145
3SV 4-7 218
8-30 PN-Pmax
2-3 145
5SV 4-6 290
7-27 PN-Pmax
1-2 145
10SV 3-5 290
6-20 PN-Pmax
1-2 145
15SV 3 290
4-15 PN-Pmax
1-2 145
22SV 3 290
4-12 PN-Pmax
P
1max
Pump Stages
(psig)
1/1-2/2 45
2/1-5/2 145
33SV
5/1-7/2 218
7/1-10 PN-Pmax
1/1-1 145
2/2-2 218
46SV
3/2-4/1 290
4-10/2 PN-Pmax
1/1-3/2 72
3/1-4/1 145
66SV
4-5/1 218
5-6 PN-Pmax
1/1-2/2 72
2/1-3/2 145
92SV
3/1-3 218
4/2-5/1 PN-Pmax
1-3/3B 290
125SV
3-5/5A PN-Pmax
P
1max
8
WARNING
WARNING
WARNING
WARNING
4. MAXIMUM OPERATING PRESSURE
(staging at 3500 RPM)
Pump Stages PSI / Bar
30 580 / 40
24-30 580 / 40
24-27 580 / 40
15-20 580 / 40
12-15 580 / 40
12 580 / 40
7-10 580 / 40
6-10 580 / 40
6 580 / 40
92SV 1-5 362 / 25
125SV 1-6 362 / 25
1-29 362 / 25
1SV
1-23 362 / 25
3SV
1-23 362 / 25
5SV
1-14 362 / 25
10SV
1-11 362 / 25
15SV
1-11 362 / 25
22SV
1-6 362 / 25
33SV
1-5 362 / 25
46SV
1-5 362 / 25
66SV
NOTE: Oval flange (1-22SV) maximum working
pressure is 232 psi (16 bar).
5. TEMPERATURE CAPABILITY
The e-SV pump is capable of pumping liquids within
the below temperature range:
Standard Seal
1SV-22SV -22°F to 250°F (-30°C to 120°C)
33SV-125SV -22°F to 250°F (-30°C to 120°C)
High Temperature Seal
1SV-22SV -22°F to 340°F (-30°C to 171°C)
33SV-125SV N/A
NOTE: In order to provide adequate cooling for the
electric motor, the ambient temperature must
be 32º F to 104º F and the relative humidity at
104º F must not exceed 50%.
For temperatures above 104º F and for installations
sites located at elevation in excess at 3000 feet above
sea level it may be necessary to derate the motor
performance. Please contact your distributor/dealer for
assistance.
6. MINIMUM NOMINAL FLOW RATE
To prevent overheating of the internal pump components, make sure that a minimum water flow is
always guaranteed when the pump is running.
For continuous operation the minimum flow rate
recommended is specified below.
NOTE: If this cannot be achieved, then a bypass/
recirculate line is recommended.
Do not run the pump against a closed discharge for longer than a few seconds.
7. NUMBER OF STARTS PER HOUR
For electric pumps coupled to motors supplied by
Goulds Water Technology, the maximum number
of work cycles (starts and stops) in one hour are as
follows:
standard one supplied by Goulds Water
Technology, please consult with the motor manufacturer to find out the maximum number of work
cycles allowed.
8. POWER SUPPLY REQUIREMENTS
Make sure that the supply voltages and
frequencies are suited to the characteristics
of the electric motor. Check the motor rating plate.
In general, the supply voltage tolerances for motor
operation are as follows:
Hz Phase
V ±%
UN
60 1 230 10
60 3 230 / 460 10
60 3 460 10
1. TRANSPORTATION AND HANDLING OF
PACKED PRODUCT
The e-SV pump is packed in cartons
or wooden crates having different
dimensions and shapes.
Some cartons (the supporting base is made of
wood) are designed to be transported and handled
in the vertical position. Other cartons, as well as
the wooden crates, are designed to be transported
and handled in the horizontal position. Protect the
product against humidity, heat sources and mechanical damage (collisions, falls, ...). Do not place heavy
weights on the cartons.
9
Lift and handle the product carefully,
using suitable lifting equipment. Observe all
the accident prevention regulations.
When you receive the pump, check the outside of
the package for evident signs of damage. If the
product bears visible signs of damage, notify our
distributor within 8 days from the delivery date.
2. STORING THE PACKED PRODUCT
Ambient temperature 32º F to 104º F.
Short Term: (Less than 6 months) Goulds Water
Technology normal packaging procedure is designed
to protect the pump during shipping. Upon receipt,
store in a covered and dry location.
Long Term: (More than 6 months) Rotate shaft
several times every 3 months. Refer to driver and
coupling manufacturers for their long term storage
procedures. Store in a covered dry location.
3. UNPACKING THE PRODUCT
Use suitable equipment. Observe all the
accident prevention regulations in force. Lift
and handle the product carefully, using
suitable lifting equipment.
When you receive the pump, check the outside of the
package for evident signs of damage. If the product
bears visible signs of damage, notify our distributor
within 8 days from the delivery date.
4. HANDLING THE PRODUCT
Lift and handle the product carefully, using
suitable lifting equipment. Observe the
accident prevention regulations in force.
The product must be securely harnessed for lifting
and handling. Some electric pumps have eyebolts
that can be used for this purpose.
1. SITE SELECTION
Make sure that no obstructions or obstacles hinder
the normal flow of the cooling air delivered by the
motor fan. Make sure there is adequate clearance
around the pump for the maintenance operations.
Whenever possible, raise the pump slightly from the
level of the floor. See the figures below and at the top
of the next column for possible installation configurations. Horizontal operation requires special mounting with a horizontally configured pump.
2. ANCHORING
The pump must be anchored securely with bolts to
a concrete foundation or equivalent metal structure
(shelf or platform). If the pump is large-sized and
needs to be installed near rooms inhabited by people,
suitable vibration-damping supports should be provided to prevent the transmission of the vibrations
from the pump to the reinforced concrete structure.
The dimensions of the pump base and anchoring
holes are shown.
The installation operations must be carried out by
qualified and experienced personnel. Use suitable
equipment and protections. Observe the accident
prevention regulations in force.
Always refer to the local and/or national regulations,
legislation and codes in force relating to the selection of the installation site and the water and power
connections.
10
L4
ø A x N
L2
L1
L3
3. FLANGE ALIGNMENT AND LOADING
Angular alignment of the suction and discharge
flanges can best be accomplished using calipers at the
bolt locations. See figure below.
NOTICE: DO NOT DRAW PIPING INTO PLACE BY
FORCING THE PUMP SUCTION OR DISCHARGE CONNECTIONS.
If pump is installed above the liquid source, the
following MUST be provided:
To avoid air pockets, no part of the suction piping should be above the pump suction.
On any horizontal piping sections, slope piping
upward from liquid source.
All suction pipe joints MUST be airtight.
Use a foot valve for priming, or for holding
prime during intermittent duty.
The suction strainer or suction bell MUST be at least
3 times the suction pipe diameter.
Insure that the size and minimum liquid submergence, over the suction inlet, is sufficient to prevent
air from entering through a suction vortex. See typical suction piping Figures 1 through 4.
Install a discharge check valve, suitable to handle the
flow and liquids, to prevent backflow.
Install an appropriately sized gate valve, AFTER the
discharge valve, to regulate the pump capacity, for
pump inspection and for maintenance.
When a pipe increaser is required, install between
the check valve and the pump discharge.
4. PIPING
Discharge and suction piping should be no smaller
than the respective pump opening and should be
kept as short as possible, avoiding unnecessary
fittings to minimize friction losses.
NOTICE: PIPING MUST BE INDEPENDENTLY SUP-
PORTED AND NOT PLACE ANY PIPING
LOADS ON THE PUMP.
If suction piping larger than pump suction is required, an eccentric pipe reducer, WITH THE STRAIGHT SIDE UP, must be installed at the pump
suction.
If the pump is installed below the liquid source,
install a full flow isolation valve in the suction piping
for pump inspection or maintenance.
NOTICE: DO NOT USE THE ISOLATION VALVE
ON THE SUCTION SIDE OF THE PUMP
TO THROTTLE PUMP. THIS MAY CAUSE
LOSS OF PRIME, EXCESSIVE TEMPERATURES, DAMAGE TO PUMP AND VOID
WARRANTY.
H min.
D
Figure 1Figure 2
D
8D
min.
4D
min.
3D
H min.
3D
2
min.
3D
H min.
D
H
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
H = Min. Submergence in feet
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 V
V = Velocity in feet per second
= GPM x 0.321
Area
GPM x 0.4085
2
D
Figure 3Figure 4
5. SHAFT ALIGNMENT – MOTOR TO PUMP
When the pump is purchased less motor, the pump
will be supplied with a motor assembly shim positioned between the motor adapter and the coupling.
To assemble the motor to the pump remove the
plastic shipping straps, the 2 stainless steel coupling
guard halves, and the expanded polyurethane.
Insure that the motor assembly shim is properly positioned between the coupling and the motor adapter.
If the motor assembly shim is not available, a 0.203"
(5 mm) shim may be used to locate the pump shaft
assembly and to set the correct height. See figures
below.
11
2. WIRING AND GROUNDING
WARNING
Hazardous
voltage
208-230V 3/60460V 3/60
4
5
6
1
7
2
8
3
9
L
1
L
2
L
3
4
7
5
8
6
9
1
2
3
L
1
L
2
L
3
G
G
MOTOR LEADS
MOTOR LEADS
POWER CABLE LEADS
POWER CABLE LEADS
THREE PHASE MOTOR WIRING DIAGRAM
WARNING
Install, ground and wire according to local and National Electrical Code requirements.
Install an all leg disconnect
switch near pump.
For 1-22SV pumps using motor frame sizes 213TC
– 256TC, place adapter ring on top ange of motor
adapter. For 33-125SV pumps using motor frame
sizes 284TC – 286TC, motor frame sizes 213TC and
larger, attach the motor adapter flange to the motor
using 4 hex cap screws. Torque to values shown in
the “ENGINEERING DATA” section of this manual.
Loosen the 4 coupling socket head screws enough
to provide an adequate opening in the coupling to
receive the motor shaft.
With an adequately sized crane, carefully lower
the motor assembly onto the pump motor adapter
and into the coupling. Secure the 4 motor hex cap
screws, torquing to the value provided in the
“ENGINEERING DATA” section of this manual.
Torque the 4 coupling socket head screws to the
value provided in “ENGINEERING DATA” section
of this manual. After assembly, the gap between the
coupling halves should be equal.
For the 33 through 125SV sizes using a cartridge
seal, after coupling bolts have been properly torqued,
there are four set screws on the collar of the cartridge seal that require tightening before removing
the shim. The four hex head set screws require a 1/8"
allen wrench and are to be tightened hand-tight approximately 5 lbs.-ft. (7 N•m).
Remove the motor assembly shim and retain for
future use.
Install the 2 coupling guard halves.
Hazardous voltage
can shock, burn or
cause death.
Disconnect and lockout electrical power before installing or
servicing pump.
Electrical supply MUST match pump’s nameplate specifications. Incorrect voltage can cause
fire, damage motor and voids warranty.
Motors equipped with automatic thermal protectors open the motor’s electrical circuit when
an overload exists. This can cause the pump to
start unexpectedly and without warning.
Use only stranded copper wire to motor and ground.
Wire size MUST limit the maximum voltage drop to
10% of the motor nameplate voltage, at the motor
terminals. Excessive voltage drop will affect performance and void motor warranty. The ground wire
must be at least as large as the wires to the motor.
Wires should be color coded for ease of
maintenance.
Three phase motors require all leg protection with
properly sized magnetic starters and thermal overloads.
PERMANENTLY GROUND THE
PUMP, MOTOR AND CONTROLS
PER NEC OR LOCAL CODES BE-
FORE CONNECTING TO ELECTRICAL POWER. FAILURE TO DO SO CAN
CAUSE SHOCK, BURNS OR DEATH.
Connect the electrical leads to the motor, as follows:
Single Phase Motors – Connect the BLACK wire to
the BLACK motor wire. Connect the WHITE wire
to the WHITE motor wire. Connect the GREEN
wire to the GREEN motor wire.
Three Phase Motors – See gure below.
1. WATER CONNECTION
The water connections must be made by qualified
installation technicians in compliance with the regulations in force.
In case of connection to the water system, the regulations issued by the competent authorities (municipal,
public utility company) must be observed. Authorities often require the installation of a backflow prevention device, such as a disconnector, check valve
or disconnection tank.
12
NOTICE: UNIT ROTATION IS DETERMINED WHEN
VIEWED FROM MOTOR END. SEE PAGE 17
FOR MOTOR ROTATION DETAIL. INCORRECT ROTATION MAY CAUSE DAMAGE TO
THE PUMP AND VOIDS WARRANTY.
WARNING
Check pump rotation by observing the motor fan or
WARNING
Hazardous
machinery
WARNING
Hazardous
voltage
the coupling THROUGH the coupling guard. DO
NOT confuse the flow arrows, stamped on the pump
body, with the rotation arrows on the coupling and
motor adapter. Three phase motors only – If rotation
is incorrect, have a qualified electrician interchange
any two of the three power cable leads.
WARNING
DO NOT OPERATE UNIT WITHOUT SAFETY GUARD IN PLACE.
TO DO SO CAN CAUSE SEVERE
PERSONAL INJURY.
3. PRIMING/VENTING
For installations with the liquid level above the pump:
Close the discharge valve.
Remove the vent plug.
For models 1SV, 3SV and 5SV only, it is neces-
sary to fully unscrew the pin located in the
drain plug. See figures below.
DRAIN PLUG
WITH PIN CLOSED
DRAIN PLUG
WITH PIN OPEN
For sizes 10SV-125SV the vent plug is supplied
with an internal needle valve, so it is not necessary to remove the vent plug. Simply unscrew
the needle valve half way to open the valve to
allow air to escape. (For sizes 33SV-92SV, if the
pump is supplied with a cartridge seal, remove
the vent plug located on the gland plate beneath
the coupling.)
Open the suction valve until liquid flows out of
the vent plug opening.
NOTICE: DO NOT REMOVE AND REPLACE DRAIN
PLUG WITH ANOTHER PLUG OR PIPING
FIXTURE FROM ANY OTHER MANUFACTURER, OR SIGNIFICANT LOSS OF
PUMP PERFORMANCE MAY OCCUR AS A
RESULT.
NOTE: Place a loose rag over the open vent port to pre-
vent large amounts of liquid from being sprayed
on the pump and adjacent equipment.
Care should be exercised if you are pumping
hot water or chemicals to avoid personal injury.
Install and torque the vent plug to the values
provided in the “ENGINEERING DATA” sec-
tion of this manual. Close the drain plug pin
(1SV, 3SV and 5SV only) and open the discharge valve.
For installations with the liquid level below the pump:
Install foot valve at suction end.
For models 1SV, 3SV and 5SV only, it is
necessary to fully unscrew the pin located in the
drain plug. See figures above.
With the provided plastic funnel, completely fill
the casing with liquid.
Install and torque the vent plug, close the drain
plug pin (1SV, 3SV and 5SV only) and open the
suction valve.
Hazardous machinery
can cause personal
injury or death.
NOTICE: PUMP MUST BE COMPLETELY PRIMED
BEFORE OPERATION.
WARNING
DO NOT OPERATE PUMP AT OR
NEAR ZERO FLOW. TO DO SO
CAN CAUSE EXTREME HEAT,
DAMAGE TO THE PUMP, INJURY
OR PROPERTY DAMAGE.
Extreme heat can
cause personal injury
or property damage.
Start the pump, keeping the on-off valve downstream from the pump closed. Open the on-off valve
gradually. The pump must run smoothly and noiselessly. If necessary, reprime the pump. Check the current absorbed by the motor and, if necessary, adjust
the setting of the thermal relay. Any air pockets
trapped inside the pump may be released by loosening the air screw for all e-SV pumps.
If a pump installed in a location where
freezing may occur remains inactive, you
must drain it through the drain plugs. This operation is not necessary if a suitable antifreeze has been
added to the water.
Make sure that the drained liquid does not
cause damage or injuries.
After stabilizing the system at normal operating
conditions, check piping for correct alignments. If
necessary, adjust pipe supports.
HAZARDOUS MACHINERY.
MOTOR THERMAL PROTECTORS CAN RESTART MOTOR
UNEXPECTEDLY AND WITHOUT WARNING, CAUSING
SEVERE PERSONAL INJURY.
See the “ENGINEERING DATA” section in this
manual for the recommended maximum pump starts
per hour.
DISCONNECT AND LOCKOUT
ELECTRICAL POWER BEFORE
ATTEMPTING ANY MAINTENANCE. FAILURE TO DO SO
CAN CAUSE SHOCK, BURNS OR
DEATH.
13
MOTOR LUBRICATION
Recommended Motor Bearing Lubrication Intervals
Interval Service Environment
1 – 2 Years Light Duty in Clean Atmosphere
1 Year 8 – 16 hours/day – Clean, Dry Atmosphere
6 Months 12 – 24 hours/day – Moisture Present
3 Months 12 – 24 hours/day – Dirty, High Moisture
When lubricants are operated at elevated temperatures, the lubrication frequency should be increased.
DO NOT intermix grease bases (lithium, sodium,
etc.). Completely purge old grease if changing
grease base.
Over greasing can cause excessive bearing temperatures, lubricant and bearing failure.
(e-SV 1–125)
1. Close all necessary suction and discharge valves to
isolate the pump from the system.
2. Drain the liquid from the pump by removing the
drain plug and opening the needle valve on the
vent plug.
3. Remove the coupling guards, the 4 coupling hex
cap screws, the coupling and coupling drive pin.
See 1-3, Figure 5.
4. Remove the 4 motor hex cap screws (inner screws)
on the seal housing. See step 4.
5. Remove the seal housing plate on 33-125SV
models, using the two tapped holes provided.
Threading 2 of the hex cap screws into these
holes and evenly tightening the screws. Lift and
remove the seal housing between the pump and
motor shaft. Exercise care when sliding the seal
housing between the shaft to prevent damage to
the stationary seat. See step 5.
6. Turn the seal housing upside down and remove
the stationary seat and o-ring. Remove and discard
the large o-ring used to seal the seal housing to the
pump head. Inspect the seal seat for any burrs or
debris. Make sure that the seat is clean. Lubricate
the new o-ring for the seal seat with a lubricant
compatible with the o-ring and install the new
seat by pressing it into the seal housing with your
thumb. DO NOT USE EXCESSIVE FORCE and,
if possible, place a clean soft cloth over the seal
face to protect the seal faces during installation.
7. Remove the rotary portion at the mechanical seal
by sliding the rotary unit axially upwards along
the pump shaft. Inspect the pump shaft for any
burns or debris. Any burrs should be ground
smooth with (fine grit) emery paper. See step 7 in
Figure 5.
8. Lubricate the o-ring located in the ID of the
rotary unit of the mechanical seal with a lubricant
compatible with the seal elastomers. Carefully
slide the rotary unit of the mechanical seal down
the shaft. Rotate the seal to locate the pin on
the bottom of the seal with the holes in the shaft
sleeve (33-125SV only). Cycle seal up and down to
lubricate o-ring and prevent seal from sticking to
shaft. See step 8 in Figure 5.
9. Install a new seal housing o-ring on the seal
housing. A lubricant can be used to hold the
o-ring on the diameter of the seal housing.
Carefully reinstall the seal housing between the
pump and motor shaft and slide the seal housing
down the shaft into position. Use caution when
mounting the seal housing between the pump/
motor shaft so that the seal face on the stationary
seat is not damaged. See step 9 in Figure 5.
10. Reinstall the 4 hex cap screws, tightening the
screws evenly and then torquing them to the
values given in the engineering data. See step 10
in Figure 5.
11. Reinstall the coupling pin and locate the space
shim on the shaft on the seal housing. If the shim is not available, a 5 mm spacer can be used. See
step 11 in Figure 5.
12. Reinstall the coupling halves and evenly tighten
the coupling bolts and torque them to the values
given in the coupling section. Remove the spacer
shim and save for future use. See step 12 in Figure
5.
13. Rotate the shaft by hand to insure that the pump
and motor rotate freely. Reinstall the coupling
guard.
14. The pump and system should be vented prior to
starting the pump. See Section 3, page 13, for
venting procedures.
(Sizes 33SV-125SV) Fitted with Cartridge Seals
1. Complete steps 1-4 as defined above for conven-
tional seals.
2. Loosen the 4 set screws located around the ID of
the pump shaft.
3. Remove the cartridge seal using the two tapped
holes provided on the gland of the cartridge seal
by threading two of the hex cap screws into these
holes and evenly tightening these screws. Lift and
remove the cartridge seal between the pump and
motor shaft.
4. Inspect the pump shaft for any burrs or debris.
Any burrs should be ground smooth with (fine
grit) emery paper.
5. Install a new o-ring on the turned fit of the new
cartridge seal. Lubricate the o-ring located in the
ID of the cartridge seal. Use a lubricant compatible with the seal elastomers to hold the o-ring.
6. Install the new cartridge seal on the pump by carefully sliding it between the pump and motor shaft
and then sliding it into position.
7. Complete steps 11-14 as defined above for the
conventional seals.
8. After installing the coupling, tighten the four set
screws located in the collar of the cartridge seal to
secure the seal to the pump shaft.
9. Rotate the shaft by hand to insure that the pump
and motor rotate freely. Reinstall the coupling
guard.
10. Use vent connections on cartridge seal for proper
venting.
14
Figure 5
To remove the motor follow steps 1 through 4, as
provided in the “MECHANICAL SEAL REPLACE-MENT” section of this manual.
For motor frames 213TC and larger, remove the 4 motor hex cap screws and the motor adapter.
Install the motor adapter flange onto the new motor,
torquing the 4 hex cap screws to the values provided in
the “ENGINEERING DATA” section of this manual.
Complete the reassembly following steps 17 through
22 in the “MECHANICAL SEAL REPLACEMENT”
section of this manual.
All additional unit service or maintenance, not addressed in this manual, should be performed at a
qualified service location. Contact your local dealer or
Goulds Water Technology distributor for assistance.
15
WARNING
Hazardous
voltage
DISCONNECT AND LOCKOUT ELECTRICAL POWER BEFORE
ATTEMPTING ANY MAINTENANCE. FAILURE TO DO SO CAN
CAUSE SHOCK, BURNS OR DEATH.
SYMPTOM
MOTOR NOT RUNNING
See Probable Cause – 1 through 5
LITTLE OR NO LIQUID DELIVERED BY PUMP
See Probable Cause – 6 through 12
POWER CONSUMPTION TOO HIGH
See Probable Cause – 3, 12, 13, 15
EXCESSIVE NOISE AND VIBRATION
See Probable Cause – 3, 6 - 8, 10, 12, 13, 16
PROBABLE CAUSE
1. Motor thermal protector tripped.
2. Open circuit breaker or blown fuse.
3. Impellers binding.
4. Motor improperly wired.
5. Defective motor.
6. Pump is not primed, air or gases in liquid.
7. Discharge, suction plugged or valve closed.
8. Incorrect rotation (three phase only).
9. Low voltage or phase loss.
10. Impellers worn or plugged.
11. System head too high.
12. NPSHA too low – excessive suction lift or losses.
13. Discharge head too low – excessive ow rate.
14. Fluid viscosity, specific gravity too high.
15. Worn bearing.
16. Pump, motor or piping loose.
TORQUE VALUES
HP Motor Bolt Adapter Flange
1-5SV 10-22SV 33-92SV
0.75-7.5 HP 20 lbs ft (27 N·m) – 15 lbs ft (20 N·m) 40 lbs ft (54 N·m) 37 lbs ft (50 N·m)
10-75 HP 45 lbs ft (61 N·m) 48 lbs ft (65 N·m)* 15 lbs ft (20 N·m) 40 lbs ft (54 N·m) 48 lbs ft (65 N·m)
*213TC and 215TC Adapter Flange use 30 lbs ft (40 N m)
Coupling
TORQUE VALUES
Pump Size Tie Rod Nuts Vent and Drain
1-5SV 22 lbs ft (30 N·m) 15 lbs ft (20 N·m)
10-22SV 37 lbs ft (50 N·m) 15 lbs ft (20 N·m)
33-125SV 44 lbs ft (60 N·m) 29 lbs ft (40 N·m)
VENT NEEDLE
Pump Size
1-5SV
10-22SV 7 lbs ft (9.5 N·m)
33-125SV
NOTE: Discharge loop must be high enough to keep liquid in the bottom stages during shut-down.
16
1-22SV MAJOR COMPONENTS
1 Pump Body
2 Impeller
3 Diffuser
4 Casing
5 Shaft
6 Adapter
7 Base
8 Coupling
9 Seal Plate
10 Mechanical Seal
11 Elastomers
12 Coupling Guard
13 Shaft Sleeve and Bushing
14 Fill/Drain Plugs
15 Tie Rods
16 Wear Ring
17 Seal Gland
17
33SV - 92SV MAJOR COMPONENTS
45
44
29
3
16
19
4
38
30
24
31
26
39
25
35
7
42
1
12
18
18
18
15
12
10
LESS PISTON
34
18
1 O-Ring, Piston Seal
2 O-Ring, Mechanical Seal
3 O-Ring, Seal housing
4 O-Ring, Sleeve
5 Mechanical Seal
5A Cartridge Seal (not shown)
6 Screw, Guard
36
6
8
11
13
9
3
28
1
1210
23
18
14
40
WITH PISTON
41
49
46
48
5
2
30
20
21
47
35
37
27
27A
32
22
33
28
40
23
10
7 Screw, Piston Holding Disc
8 Screw, Coupling
9 Screw, MA and Seal Housing
10 Screw, Impeller
11 Washer, Coupling
12 Washer, Impeller
13 Pin, Coupling
14 Plug, with Piston
15 Plug, without Piston
16 Plug, Fill
17 Plug, Vent (not shown)
18 Plug, Drain
19 Pump Head
20 Impeller, Full Diameter
21 Impeller, Reduced Diameter
22 Lower Bearing Assembly
23 Piston
24 Diffuser, Final
25 Diffuser with Carbon Bushing
26 Diffuser with Tungsten Bushing
27 Outer Sleeve, 25 Bar
27A Outer Sleeve, 40 Bar
28 Holding Disc, Piston Seal
29 Seal Housing
30 Spacer, Impeller Final
31 Spacer, Shaft Bushing
32 Spacer, Impeller
33 Spacer, Impeller Lower (66-92SV)
34 Bushing, Non-Piston
35 Tungsten Carbide Bushing
36 Coupling Guard
37 Shaft
38 Mechanical Seal Shaft Sleeve
39 Wear Ring, Impeller
40 Piston Seal
41 Stop Ring, Impeller
42 Pump Body
43 Motor Adapter Plate (not shown)
44 Motor Adapter
45 Coupling, Half
46 Nut, Tie-Rod
47 Tie-Rod
48 Washer, Tie-Rod
49 Spring, Final Diffuser
125SV MAJOR COMPONENTS
1 Pump Body
2 Impeller
3 Diffuser
4 Casing
5 Shaft
6 Adapter
7 Elastomer O-ring
8 Coupling
9 Seal Plate
10 Mechanical Seal
11 Elastomer O-ring
12 Coupling Guard
13 Shaft Sleeve and Bushing
14 Shaft Bushing
15 Fill/Drain Plugs
16 Tie Rods
17 Elastomer O-ring
19
Software License Agreement
BY USING THE i-Alert™ CONDITION MONITOR, YOU AGREE TO BE BOUND BY THE TERMS AND
CONDITIONS OF THE FOLLOWING LICENSE AGREEMENT. PLEASE READ THIS AGREEMENT CAREFULLY.
ITT Corporation and its subsidiaries, affiliates, either directly, or through its authorized sublicensees ("ITT")
grants you a limited, non-exclusive license to use the software embedded in this device ("Software") in binary
executable form in the normal operation of the i-Alert™ condition monitor for monitoring the condition of any
ITT Goulds Pump Models, Xylem Bell & Gossett Series 1510 Pump and Xylem eSV pump models. Title, ownership
rights, and intellectual property rights in and to the Software remain in ITT or its third-party providers. You agree
that this license agreement does not need to be signed for it to take effect.
You acknowledge that this Software is the property of ITT and is protected under United States of America
copyright laws and international copyright treaties. You further acknowledge that the structure, organization,
and code of the Software are valuable trade secrets of ITT and/or its third-party providers and that the Software
in source code form remains a valuable trade secret of ITT. You agree not to decompile, disassemble, modify,
reverse assemble, reverse engineer, or reduce to human readable form the Software or any part thereof or create
any derivative works based on the Software. You agree not to export or re-export the Software to any country in
violation of the export control laws of the United States of America.
20
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.