Xylem HV 1.2 Operating Instructions

Operating Instructions
HV 1.1-HV 1.2
Incl. RS 485 - interface
771079212 MANUAL HV1_1-1_2-EN ENGLISH
V 2012/03A
3
Index
1 IMPORTANT SAFETY INSTRUCTIONS ............................................................................................5
2 SYSTEM DESIGN...........................................................................................................................7
3 PRESSURE TANK ..........................................................................................................................8
4 TRANSDUCER ...............................................................................................................................9
4.1 P
RESSURE TRANSMITTER SERIES PA-21 R ..........................................................................................9
4.2 D
IFFERENTIAL PRESSURE TRANSMITTER SERIES PD 39 M .....................................................................10
5 TECHNICAL DATA - FREQUENCY INVERTER AND GENERAL DATA..............................................11
5.1 D
IMENSIONS ................................................................................................................................12
6 HYDROVAR MOUNTING .............................................................................................................13
6.1 M
OUNTING THE HYDROVAR ON THE PUMP ....................................................................................... 13
6.1.1 Included components...........................................................................................................13
6.1.2 Mechanical mounting ..........................................................................................................14
6.1.3 Mounting the thermistor (4) ................................................................................................17
6.1.4 Mounting of the pressure transducer..................................................................................18
6.2 E
LECTRIC INSTALLATION AND WIRING..................................................................................................19
6.2.1 Means of protection ............................................................................................................19
6.2.2 Wiring the Hydrovar to the motor........................................................................................19
6.2.3 Control.................................................................................................................................22
6.2.4 Terminals .............................................................................................................................22
6.3 F
RONT PLATE ................................................................................................................................24
7 OPERATION WITHOUT EXTERNAL PROGRAMMING DEVICE.......................................................25
8 POSSIBLE INDICATIONS OF THE LED ON THE HYDROVAR..........................................................26
9 OPERATION IN THE MAIN MENU................................................................................................27
10 CONNECTING THE EXTERNAL PROGRAMMING DEVICE TO THE HYDROVAR .............................28
11 TYPICAL APPLICATIONS..............................................................................................................29
11.1 S
ETTING SINGLE PUMP CONSTANT PRESSURE .......................................................................................29
11.2 S
INGLE PUMP - PUMP PROTECTION ....................................................................................................30
11.3 S
INGLE PUMP SYSTEM CURVE COMPENSATION ..................................................................................32
11.4 E
NTERING COMPENSATION VALUES ...................................................................................................33
M
ULTIPLE PUMP CONSTANT PRESSURE AND SYSTEM COMPENSATION ....................................................................35
12 SETTINGS AT THE INVERTERMENU.............................................................................................40
13 SETTINGS AT THE SUBMENU-PARAMETER .................................................................................41
13.1 P
RESSURE CHANGE......................................................................................................................... 41
13.2 A
UTO START .................................................................................................................................41
13.3 M
ODE.........................................................................................................................................42
13.4 C
ONTROL RESPONSE....................................................................................................................... 42
13.4.1 Dimension unit ...................................................................................................................42
13.5 S
UBMENU INVERTER .......................................................................................................................42
13.5.1 Maximum Frequency...........................................................................................................42
13.5.2 Minimum frequency............................................................................................................43
13.5.3 Boost ..................................................................................................................................43
13.5.4 Operation of the minimum frequency.................................................................................43
13.5.5 Delay time for Fmin.............................................................................................................43
13.6 S
UBMENU CONTROLLER ..................................................................................................................44
13.6.1 Window - %........................................................................................................................44
13.6.2 Ramp Hysteresis..................................................................................................................44
4
13.6.3 Fast acceleration time .........................................................................................................44
13.6.4 Fast deceleration time.........................................................................................................44
13.6.5 Slow acceleration time........................................................................................................ 44
13.6.6 Slow deceleration time .......................................................................................................45
R
AMP WINDOW ......................................................................................................................................45
13.6.7 Compensation Frequency....................................................................................................45
13.6.8 Lift-Intensity........................................................................................................................46
13.7 S
UBMENU MULTICONTROLLER ..........................................................................................................47
13.7.1 Lift Value ............................................................................................................................47
13.7.2 Fall Value ............................................................................................................................48
13.7.3 Release – Follow up pump ..................................................................................................48
13.7.4 Switch Interval ....................................................................................................................49
13.8 S
UBMENU RELAY ...........................................................................................................................49
13.8.1 Relay Configuration ............................................................................................................49
13.8.2 Start frequency of the slave pump......................................................................................49
13.8.3 Stop frequency of the slave pump ......................................................................................49
13.9 S
UBMENU SENSOR.........................................................................................................................50
13.9.1 Sensor – Adjust...................................................................................................................50
13.9.2 SensorMax-Adjust...............................................................................................................50
13.10 S
UBMENU TEST-RUN ......................................................................................................................50
13.10.1 Start of manual test run....................................................................................................50
13.10.2 Sequence for automatic test run.......................................................................................51
13.10.3 Test Run: Frequency .........................................................................................................51
13.10.4 Test Run: Boost.................................................................................................................51
13.11 S
UBMENU ERROR...........................................................................................................................51
13.11.1 Conveyor Limit..................................................................................................................51
13.11.2 Error Delay........................................................................................................................51
13.12 S
ET PASSWORD .............................................................................................................................52
13.13 D
EFAULT SETTINGS.........................................................................................................................52
13.14 S
UBMENU DIAGNOSIS.....................................................................................................................52
13.14.1 Pump Runtime ..................................................................................................................52
13.14.2 Pump Address...................................................................................................................52
13.14.3 Error memory.................................................................................................................... 52
13.14.4 Software Version ..............................................................................................................53
13.15 S
ET PASSWORD .............................................................................................................................53
14 CONTROLLER MENU (OF THE PROGRAMMING DEVICE) ............................................................53
14.1 C
ONTROLLER MENU CONFIGURATION .................................................................................................53
14.1.1 Automatic connection to the programming device.............................................................54
14.1.2 Software Version of the programming device.....................................................................54
14.2 S
UBMENU ADDRESS........................................................................................................................54
14.2.1 Change of pump address....................................................................................................54
15 POSSIBLE ERROR MESSAGES......................................................................................................55
15.1 L
OW WATER.................................................................................................................................55
15.2 O
VERHEATING MOTOR .................................................................................................................55
15.3 O
VERVOLTAGE ..............................................................................................................................55
15.4 U
NDERVOLTAGE ............................................................................................................................55
15.5 O
VERLOAD...................................................................................................................................55
15.6 O
VERHEATING OF THE HEAT SINK .......................................................................................................56
15.7 S
ENSOR FAULT ..............................................................................................................................56
15.8 C
ONVEYOR LIMIT FAULT...................................................................................................................56
15.9 A
DDITIONAL INTERNAL PROCESSOR ERROR MESSAGES: ...........................................................................56
16 MAINTENANCE...........................................................................................................................57
Follow the Pump Operating and Maintenance Instructions
We reserv the right to alter specifications
5
1 Important safety instructions
Read and follow the operating instructions
and safety instructions carefully before
starting operations! All modifications must be
done by qualified technicians!
In addition to the instructions contained in these operating instructions please pay attention to universal safety and accident prevention regulations.
The HYDROVAR drive head must be disconnected from the power supply before any work can be carried out in the electrical or mechanical part of the system. Installation, maintenance and repair work may only be carried out by trained, skilled and qualified personnel. Unauthorised modifications or changes to the system make all guarantees null and void. When in operation the motor can be stopped by remote control, whereby the drive head and the motor remain under voltage. For safety reasons, the unit must be disconnected from the power supply when carrying out work on the machinery as locking out the equipment by switching off the release mechanism or set value cannot prevent accidental starting of the motor.
When the drive head is connected to power supply, the components of the power unit as well as certain components of the master control unit are also connected to the power supply.
Touching these components seriously endangers life !
Before removing the frequency inverter cover the system must be disconnected from the power supply. After switching off the power supply wait at least 5 minutes before starting work on or in the HYDROVAR drive head (the capacitors in the intermediate circuit have to be discharged by the installed discharge resistors first).
Voltages of up to 400 volts are possible (if there are faults it can be higher).
All work carried out when the frequency inverter is open may only be performed by qualified authorised staff.
Furthermore, care must be taken not to short circuit the neighbouring components when connecting the external control wires and that open cable ends which are not in use are insulated.
6
The HYDROVAR drive head contains electronic safety devices which switch off the control element in the event of faults, whereby the motor has zero current but remains energised and comes to a halt. The motor can also be halted by mechanical blocking. If it is switched off electronically the motor is disconnected from the mains voltage through the electronics of the frequency converter but is not potential-free in the circuit. In addition voltage fluctuations, especially power failures can cause the system to switch off itself.
Repair of faults can cause the motor to start up again.
The system may only be put into operation when it has been earthened. In addition, equipotential bonding of all pipes must be ensured.
The operating instructions must be read, understood and followed by the operating personnel. We point out that we accept no liability for damage and operating disorders which are the result of non-compliance with the operating instructions.
Please note:
High voltage tests of the inverter or the motor may damage the electronic components! Hence bridge before the in- and outgoing terminals L -N -- U- V-W. To avoid incorrect metering by capacitors incorporated in the electronic part isolate the motor from the Hydrovar Drive head.
7
2 System Design
The following diagrams show typical single pump and multi-pump systems using the Hydrovar control unit. Connection can be made directly to a water supply or water can be drawn from a break tank or well. In the case of break tanks and wells, level switches, should be used to shut down the pumps when water is low. In the direct connection, a pressure switch on the suction side should be used.
Single pump layout
Multiple pump Layout
(1) pump with drive head (2) diaphragm tank (3) distribution panel (4) gate valves (5) non return valves
(8) incoming pressure switch (9) pressure gauges (14) pressure transmitter
8
3 Pressure tank
A diaphragm pressure tank is used on the discharge side of the pump or pumps to maintain pressure in the line when there is no demand. This will keep the pumps from continuing to run. With the Hydrovar control unit, it is not necessary to have a large tank for supply purposes. In selecting a tank, make sure it can withstand systems pressure. The tank should have a capacity of more than 10% of the maximum system flow rate l/min of one pump.
Ask of required certificates needed for your country!
Precharge the tank to the following:
Before checking the precharge pressure, take care, that the tank, is
pressureless (no water inside).
Solldruck / required pressure [bar]
9
4 Tran sducer
4.1 Pressure Transmitter Series PA-21 R
The sensor of this transmitter is a piezoresistive silicon pressure sensor, mounted on a tape (TAP) freely floating in an oil chamber. The pressure is transferred to the sensor by a separate nickel diaphragm in the oil chamber.
Specifications Range (FS): 10 bar (other ranges upon request) Max. pressure-P
max
: 20 bar
Class of protection : IP 67
Output signal: 0,5 – 4,5 V DC (ratiometric) Supply: 5 VDC +/- 5 %
Operating temperature: -20...+80°C Storage Temperature: -40...+100°C
connections:
+ VCC ⇒ brown = supply voltage + Out ⇒ white = analogue output signal GND ⇒ green = Ground
Materials: Body: steel and brass
diaphragm: nickel
Pressure Transmitter:
Plug:
10
4.2 Differential Pressure Transmitter
Series PD 39 M
The sensors of this differential pressure transmitter are two piezoresistive silicon pressure sensors, mounted on a tape (TAP) freely floating in an oil chamber. The pressure is transferred to the sensor by a separate steel diaphragm in the oil chamber.
Specifications
Range(FS):
4 bar
differential
Over-pressure- Pmax:
16 bar single-sided
Class of protection : IP 65
Output Signal: 0,5 – 4,5 V DC (ratiometric) Supply: 5 VDC +/- 10 % Load Resistance: > 5 k
Linearity:: ±0.20 % FS; max. ±0.5% FS Stability: ±0.1 % FS; max. ±0.2% FS
Operating temperature: -10...+80°C Storage Temperature: -40...+80°C
Material: Body and diaphragm: 1.4435 Stainless steel Screw joint and cover: Steel electroplated for Emetorpipe d=8mm
Plug: mPm 193
Incl. 2m cable:
Out (white) + Vcc (brown) GND (green) Screen
P -
P +
11
5 Technical Data - Frequency Inverter And General Data
HYDROVAR Hydrovar output to
the Motor
Supply Voltage (Uin) Prefuse
min.
Type Rated
output
Voltage Max.
current
Mains frequency
48-62 Hz HV 1.1 1,1 kW 3x 230 V 4,8 A 1x 220-240 V±15% 10 Ampere HV 1.15 1,5 kW 3x 230V 7,0 A 1x 220-240 V ±15% 10 Ampere HV 1.2 2,2 kW 3x 230V 10,0 A 1x 220-240 V ±15% 16 Ampere
Output voltage: 3x 0...Uin VAC / 0-70 Hz (depends on the input voltage) Min. frequency: 0 – max. frequency Electrical efficiency: > 95%
Protection against: Short circuit, over- and undervoltage, overheating of the
electronics (overload) and additional external protective functions via PTC (motor temperature) and low water switch. A mains filter is fitted to ensure interference immunity.
The HV Series frequency converter complies with the general EMC provisions and has been tested according to the following standards:
Disturbance voltage: EN 55011
EMC – Immunity: EN 61000-4-3 and ENV 50204
Electrostatic discharge: EN 61000-4-2
Ambient temperature: 5° C ... + 40°C Storage temperature: -25° C ... + 55° C
(+70°C during max. 24 hours.) Humidity: rH max. 50% at 40°C, unlimited rH max. 90% at 20°C, max. 30 days per year Condensation not permitted !
Air pollution:
The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines. Excessive amounts of dust, acids, corrosive gases, salts etc. are not permitted
Altitude:: max. 1000m above sea level
At higher altitudes the max. available power has to be reduced. Please ask the manufacturer for further details.
Class of protection : IP55
12
5.1 Dimensions
HV1.1:
HV1.15,1.2:
closing cap
7
∅12
Type: Weight [Kg]
HV 1.1 2,00 HV 1.15 4,70 HV 1.2 4,70
closing cap
cable entries
cable gland
13
6 HYDROVAR mounting
6.1 Mounting the HYDROVAR on the pump
6.1.1 Included components
Variant for HV1.1:
Variant for HV1.15-1.2:
mounting and distance ring
washer
screw
cable gland
thermistor
thermistor
cable gland
screw M5x50
mounting clam
p
14
6.1.2 Mechanical mounting
Variant for HV1.1
1. Remove the motor fan cover from
your 3-phase motor by removing the mounting screws.
2. Put the mounting and distance ring
(1) between the fan cover and the Hydrovar and fix them together with the screw (3) by using the included washer(2).
3. Use the fan cover screws to mount
the fan cover/Hydrovar combination to the motor
Attention:
Don’t forget the washer between the screw and the motor fan cover!
Hydrovar
(1) mounting and distance ring
motor fan cover
(2) washer
(3) screw
15
Variant for HV1.15-1.2:
Gasket
Thermistor
Transducer
Connection Motor conduit box
4 mounting clamps
Center bit
4 screw M5x50
Don’t forget the gaskets for the 3 screws . Ensure that there is no water on the unit before you open the cover.
Mounting:
u Remove the 3 screws from the Hydrovar cover. u Place the centre bit in the Hydrovar fan cover. u Place the Hydrovar fan cover on the motor . u Hang the 4 clamps by the Motor fan cover and mounted with the 4 screws. u Mounted the cover with the 3 screws.
16
If you use a motor with plastic fan cover, you must use a mountingring.
Mountingring
17
6.1.3 Mounting the thermistor (4)
Variant A:
Variant B:
1. Open the cover of the conduit box and remove also the terminal block inside.
2. Fix the thermistor (Variant A or B)
3. Electrical connection of the motor cables see chapter 7.3.
motor
thermistor
terminal block
rubber gasket
cover of the conduit box
Thermistor
18
6.1.4 Mounting of the pressure transducer
In the delivery of the pressure transducer there are included:
1. The transducer has an mechanical connection of G ¼”. If it is necessary put the reducer
(3/8” – 1/4”) into the pump or pipe by using included gaskets.
2. Electrical connection to the Hydrovar see chapter (6.2.4)
(1) pressure transducer (2) gasket (3) reducer
3
/8“ – ¼“
(4) brass gasket
(4)
(1)
(2)
(3)
19
6.2 Electric installation and wiring
6.2.1 Means of protection
Ask your power supply company which means of protection are required.
Applicable: AC and DC current-operated circuit breaker (FI), TN systems, protective
circuits.
When using a FI protection switch, make sure that it also releases in the event of a DC fault, use for each Hydrovar a separate FI-switch!
6.2.2 Wiring the Hydrovar to the motor
Remove the 3 screws holding the top of the Hydrovar. Carefully lift the top, loose the earth screw and put the Hydrovar cover aside. Now you can see the 2 main parts
(1) control card with all terminals for the control signals and the RS485
interface
(2) main card with all power components and terminals for power supply
and motor
Note: All installations and maintenance MUST be performed by trained and qualified personal with proper tools!!
Warning: In case of a failure, disconnect and lockout electrical power and wait five minutes for capacitor discharge before servicing the Hydrovar. Otherwise it can cause shock, burns, or death.
20
6.2.2.1 Main part overview
HV1.1:
HV1.15, 1.2:
6.2.2.2 Connecting the power cables
Motor connections
main supply connections
Cable gland (for power supply 5­10mm)
control card (1)
main board (2)
Cableintroduction for motor cable (at least 11,5mm)
Cableintroduction for control cable (at least 5mm)
motor connections
main supply connections
control card (1
)
main board (2)
cable introduction for control cable
21
a) motor cable:
Locate the motor connections, labeled U, V, W inside the Hydrovar. Connect wires to the terminals and rout the cable through the cable gland. You must take a motor cable at least Ø 11.5mm if you want protection IP55. (only HV1.1)
The earth-wire of the cable has to be fixed with the screws with the earth-symbol to the cooling body of the Hydrovar.
Connections in the conduit box
The connection of the motor cable depends on the type of the motor and can be done in star or delta connection: (you have to use the connection for a motor voltage of 3x230V shown on the motor label)
Star-connection
Delta-connection
b) supply cable
The main power cable is connected to the terminals labelled L1, N for the 230 VAC, single phase input (shown in the diagram 6.2.2.1).
22
6.2.3 Control
By using the HYDROVAR drive head for constant pressure control, together with a pressure or differential pressure transmitter, or, if required, according to external manual control by reference of 0,5-4,5VDC, this external signal has to be connected to the terminals X2/1, X2/2 and X2/3 of the control terminals.
6.2.4 Terminals
All externally used cables have to be shielded. Do not connect the mass of the electronic components to other higher potentials.
All electronic ground and GND of the RS 485-interface are internally connected. For external off/on and low water, switch contacts suitable for <10 V are necessary. The control cable must be at least Ø 5mm. If unshielded control cables are used, signal interference may occur and interfere with the function of the inverter.
When connecting together the variable speed pumps (max. 4 pumps) via the interface RS 485, the terminals X3/1 and X3/2 and X3/3 are to be connected in parallel by means of a shielded cable to every HYDROVAR drive head and programmed accordingly (* Programming Sequential Operations see chapter 13.7)
control terminals
terminals of the RS485 interface
HV1.1
HV1.15, 1.2
23
Control-Terminals:
Power supply for external control 5VDC
External release Ri 10kOhm, 5VDC (use gold plated contact)
Thermistor
Ground (not earthened)
0,5-4,5 VDC
24
6.3 Front plate
HV 1.1-1.2:
push buttons
indication LED
25
7 Operation without external programming device
Attn:
Before you start the system, the pump must be filled and all wiring and piping have to be done!
Change Pressure: enabled Auto Start: enabled
Other possibilities to use the push buttons of the Hydrovar:
The Pump could be STARTED with the button (if Autostart is disabled, the pump can be started by
pressing the button and then the button at the first startup or after a power supply failure) or
STOPPED with the button.
Both buttons are on the front plate of the Hydrovar
Change pressure without programming device:
To change the pressure without the external programming device you have to follow:
1. Start the pump with the push button
on the front plate of the Hydrovar
2. Then press the and buttons together for longer than 3 sec.
3. The colour of the LED changes to orange
4. Now you can change the pressure with the and buttons.
The only way to check the set pressure is given by a pressure gauge.
5. If there is no action for more than 5 sec., the HYDROVAR returns to normal
operation automatically, and the new required pressure is saved.
The H
y
drovar is delivered with these settings as standard!
26
8 Possible indications of the LED on the HYDROVAR
.) Green shining Motor stopped
(via external stop with terminals X2/4; X2/5 or the unit is stopped with the button on the front plate)
.) Green slow flashing Inverter is active, but the motor has stopped
.) Green fast flashing Motor runs
.) Orange shining required pressure can be changed without the
programming device with the buttons and ,
or the external programming device is connected and the pump is stopped with the button on the Hydrovar or with the external release input (terminals X2/4 and X2/5).
.) Orange slow flashing connected remote control and the inverter is released,
but the pump is not running (because of the required pressure is reached).
.) Orange fast flashing connected external programming device and the pump is
running.
.) Red shining ⇒ error signalling (type of the Error is shown on the
display of the external programming device)
.) Red flashing signalling of a fatal error (HYDROVAR has to be cut
from the power supply!)
27
9 Operation in the main menu
Menu overview
28
General for working with the external programming device:
With Í and Î you can select the different parameters in the menu. To enter a submenu, press the Ð button. To leave the submenu, you have to press the buttons Í or Î for longer than 3 sec. With Ï or Ð you can change the parameters. Each change in the settings is saved after leaving this parameter with the buttons Í or Î. When you have changed a parameter and you leave it, the LCD shows you the following message
SAVE
PARAMETER
for about 2 sec.
10 Connecting the external programming device to the HYDROVAR
After connection of the HYDROVAR – head to the power supply and plug in of the external programming device, there can be shown two different messages:
1. If the AUTOCONNECTION (14.1.1) is disabled (standard) you reach:
Address 01
Lost
This message is shown, when the Remote Control is new connected
At this time the Hydrovar searches for an available address
If address 01 is available, the display changes to
Address 01
Detected
The actual pump-address is shown
Statusinformations by systems with activated Multicontroller:
P1: Masterpump P2: Slavepump P3: Slavepump P4: Slavepump P.: Follownumber is not useful
Hold: pump stops through the pressure transmitter Run: pump runs Stop: pump stops through the leadpump Disabled: pump stops through the stopbutton or the terminal block Error: pump stops through an error
Ð Follow pump stopped Ï Regulator from the follow pump is release
Pump don’t work at the follow pump
29
If the actual pump address 01 is not available the display does not change and you will see again
Address 01
Lost
Then you could change the address with Ï and Ð and confirm the selected address with Î.
Press Î on the controller and you enter the INVERTERMENU (see chapter 12)
2. If the AUTOCONNECTION (14.1.1) is enabled, following message is shown:
SCAN
CONNECTION
This message is shown during the connecting, when AUTOCONNECTING (chapter 14.1.1) is enabled
In this time the Hydrovar searches for the given or entered address!
Then the display changes to the 1st display
PRESS X.X bar
SPEED X.X Hz
The actual input value [bar] and the actual output frequency [Hz] are displayed.
11 Typical applications
11.1 Setting Single Pump Constant Pressure
At the first startup, “Change Pressure” and “Autostart” of the external programming unit are enabled. After connecting, on the display of the programming unit there is shown
Scan
Connection
This message is shown when the external programming device is set up to the Hydrovar
and scanning a valid pump address.
After a few seconds, the display changes automatically to the 1st display
Press x.x bar
Speed x.x Hz
This window shows the actual values of the Hydrovar (a required pressure of 3,5 bar is
previously set)
Press
Î
on the controller to change to
Pressure
xx.x bar
To select required pressure use the buttons Ï
and Ð.
After changing of the value, you have to confirm with the Î-button. Then you will get the message “SAVE PARAMETER” for a short time, when the new setting is saved! After changing of the value, you have to confirm with the Î-button.
Then press Í on the controller to change back to the 1st display
Press x.x bar
Speed x.x Hz
30
11.2 Single Pump - Pump Protection
31
Note:
Low/no suction depends on the installation of a suction line pressure switch, or float switch for a tank. This is connected to the Hydrovar as described earlier in the Electrical Installation section (see chapter 6.2). The cut off setting for this switch should be the maximum NPSH required by the pump.
To set run out protection:
Note:
Run out protection is available for one pump systems and multiple pump systems with a common suction pipe. In multiple pump systems with separate suction pipes, you can not avoid dry running by measuring the system pressure, because the pressure is produced from another pump in the system.
From the 1st display, press the Î button twice, until you reach
SUBMENU
PARAMETER
Then press the Ð button and the display will change to
PASSWORD
0000
Password:
The Password protection prevents untrained personal from accidentally changing the base setting
Press the Ï button until you reach the number 0066
PASSWORD
0066
Press the Î button repeatedly until you reach
SUBMENU
ERROR
Press the Ð button to enter the submenu and change to
CONVEYOR LIMIT
0,0 bar
CONVEYOR LIMIT
0.0 bar” means disabled conveyor limit. An adjusted value >0 has to be reached till the programmed “ERROR DELAY”-time. Doesn’t this value be reached the failure “CONVEYOR CONTROL ERROR” will be indicated and the pump stops.
By pressing the Ï and Ð button, enter the pressure setting (bar) at which you want the pump to shutoff.
CONVEYOR LIMIT
0 bar
Typically a setting of about 1 bar less than the standard pressure setting would be entered After changing of the value, you have to confirm with the Î button. Then you will get the message “SAVE PARAMETER” for a short time, when the new setting is saved!
Press the Î button to change to
ERROR DELAY
10 s
32
ERROR DELAY:
Adjustable between 0...100 sec. Delayed switch-off in the event of low water, terminal X2/6-X2/7) and also for the conveyor limit ( see chapter 13.11.1).
By pressing the Ï and Ð button, you will be entering the amount of time (sec) that the pump will run at the
ERROR DELAY
10 s
programmed conveyor limit before it automatically shuts off. After changing of the value, you have to confirm with the Î button. Then you will get the message “SAVE PARAMETER” for a short time, when the new setting is saved!
Hold the Î button down for 3 seconds and you will be returned to:
SUBMENU
ERROR
Hold the Î button down again for 3 seconds to return to the 1st display
PRESSURE x.x bar
SPEED xx Hz
11.3 Single Pump – System Curve Compensation
The Hydrovar can automatically compensate for system friction losses due to increased flow. Tables are available in most pump catalogues indication the amount of friction loss that can be expected in various sizes of pumps at different flow rates. Use these tables to determine the friction loss for the pipe size you are using at maximum flow rate.
This Diagram shows a typical system curve. The system pressure set point is shown at shutoff and pressure increase is shown for increasing flow. Calculate the pressure required to overcome friction loss at maximum flow.
33
11.4 Entering Compensation Values
34
Instructions:
From the 1st display, press the Î button twice, until you reach
SUBMENU
PARAMETER
Then press the Ð button and the display will change to
PASSWORD
0000
Password:
The Password protection prevents untrained personal from accidentally changing the base setting
Press the Ï button until you reach the number 0066
PASSWORD
0066
Press the Î button repeatedly until you reach
SUBMENU
CONTROLLER
Press the Ð button to enter the submenu and change to
WINDOW
5,0 %
Now press the Î button until you reach the parameter “LIFT FREQUENCY”
LIFT FREQUENCY
30 Hz
LIFT FREQUENCY:
This indicates the frequency at which the increase of the set pressure should begin.
It should be the speed at which the pump works at the set pressure and at delivery rate of
0 m³/h. On a 50 Hz system, there is virtually no flow below about 30 Hz, on a 60 Hz
system about 40Hz.
Press the Ï and Ð button until you reach desired frequency.
LIFT FREQUENCY
30 Hz
After changing of the value, you have to confirm with the Î button. Then you will get the message “SAVE PARAMETER” for a short time, when the new setting is saved!
Now press the Î button to change to
LIFT INTENSITY
0,0 bar
LIFT INTENSITY:
This value states, how much the required value should be continually increased, till the
maximum speed (maximum volume) is reached. Further description, see chapter 13.6.8.
Press the Ï and Ð button until you reach desired value
LIFT INTENSITY
0,0 bar
After changing of the value, you have to confirm with the Î button. Then you will get the message “SAVE PARAMETER” for a short time, when the new setting is saved!
Hold the Î button down for 3 seconds to return to:
SUBMENU
CONTROLLER
35
11.5 Multiple pump constant pressure and system compensation
36
When two, three or four Hydrovar speed controlled pumps are connected together in a system via the RS485-interface, they can be programmed to work together to maintain system pressure up to the maximum flow rate of all the pumps combined. As the first pump reaches its maximum speed and flow, the second pump will automatically turn on (and so on). In addition, the sequence of the pump that will run first (lead pump) can be automatically varied to reduce premature wear on any one pump in the system.
Instructions:
!! Refer to chapter 11.1 (setting single pump constant pressure).
Follow these instructions for setting the required pressure and then continue with the following steps.
From the 1st display, press the Î button twice, until you reach
SUBMENU
PARAMETER
Then press the Ð button and the display will change to
PASSWORD
0000
Password:
The Password protection prevents untrained personal from accidentally changing the base setting
Press the Ï button until you reach the number 0066
PASSWORD
0066
Press the Î button repeatedly until you reach
SUBMENU
MULTICONTROLLER
Press the Ð button to enter the submenu and change to
ACTUAL VALUE INCREASE
0.15 bar
ACTUAL PRESSURE INCREASE (= Lift value):
This value, together with the fall value (ACTUAL VALUE DECREASE) determines the increase of the required value after starting of the following pumps (see attached application example on next page)
37
Generally a slight pressure drop is allowed on the first pump before the next is started. This allows for brief systems fluctuations without pump cycling. Once the
next pump starts, however, you will want the system to resume its normal set pressure.
For example, if the pressure drop allow 0,35 bar before the next pump starts, and the increased pressure needed to compensate for system losses is 0,2 bar, you would enter 0,35 + 0,20 = 0,55 bar (= calculated value of the parameter ACTUAL VALUE INCREASE) to compensate for both system pressure drop and compensation requirements.
Application example:
1) Pump 1 reaches the speed of ENABLE SEQ: CONTROL
2) Pressure falls and reaches the start-value of the 2
nd
pump
(= REQUIRED VALUE – ACTUAL VALUE DECREASE)
3) Pump 2 is switched on automatically
4) The required value is calculated new, after the start of the 2
nd
pump in the
following way!
New required value = REQUIRED VALUE – ACTUAL VALUE DECREASE + ACTUAL
VALUE INCREASE
Generally:
k ... Number of active pumps (k >1) P = P
set
+ (k-1)*[lift value – fall value]
• Lift value = Fall value ⇒ Pressure constant when pumps switch on
• Lift value > Fall value ⇒ Pressure rises when lag-pump switches on
• Lift value < Fall value ⇒ Pressure falls when lag-pump switches on
Note:
This value is cumulative. An extra 0,2 bar will be added to the total system pressure with each additional pump which turns on. For example, if the initial system pressure was 3,5 bar, pump two would create 3,7 bar, pump three would create 3,9 bar, and pump four would create 4,1 bar system pressure.
To do this, enter the amount of pressure drop you will allow before the next pump starts (=value of parameter ACTUAL VALUE DECREASE). The diagram shows the pressure drop and increase.
To increase the pressure even more to compensate for system loss at higher flows, enter the total of the system drop allowed before next pump starts and the increased pressure (ACTUAL VALUE INCREASE) desired.
38
Enter the required value by pressing the Ï and Ð button
ACTUAL VALUE INCREASE
0,15 bar
After changing of the value, you have to confirm with the Î button. Then you will get the message “SAVE PARAMETER” for a short time, when the new setting is saved!
Press the Î button to change to
ACTUAL VALUE DECREASE
0,15 bar
ACTUAL PRESSURE DECREASE (= Fall value):
This value determines amount of pressure drop you will allow before the next pump starts. (see application example on previous page)
Enter the required value by pressing the Ï and Ð button
ACTUAL VALUE DECREASE
0,15 bar
After changing of the value, you have to confirm with the Î button. Then you will get the message “SAVE PARAMETER” for a short time, when the new setting is saved!
Press the Î button to change to
ENABLE SEQ. CONTROL
48 Hz
ENABLE SEQUENCE CONTROL:
The follow-up pump only starts, when the start-value is reached (see chapter 13.7.2) and
the lead pump has reached the programmed release-frequency. (Adjustable from 0.0 Hz to
70 Hz). Normally this start frequency is set 1 to 2Hz lower than the MAX. FREQUENCY (see
chapter 13.5.1)
If you don’t want to start a following pump this value has to be set higher than the MAX.
FREQUENCY. (see application example on previous page)
Enter the required value by pressing the Ï and Ð button
ENABLE SEQ. CONTROL
49 Hz
After changing of the value, you have to confirm with the Î button. Then you will get the message “SAVE PARAMETER” for a short time, when the new setting is saved!
Press the Î button to change to
SWITCH INTERVAL
24 HOURS
SWITCH INTERVAL
This time determines the interval of the changeover of the master pump in order to
achieve even operating hours of all pumps in the system. Adjustable between 0 and 250
hours
Enter the required value by pressing the Ï and Ð button
SWITCH INTERVAL
24 HOURS
39
After changing of the value, you have to confirm with the Î button. Then you will get the message “SAVE PARAMETER” for a short time, when the new setting is saved!
Use the settings of this submenu (lift value, fall value, enable sequence control and switch interval) for each pump in the Hydrovar system
Hold the Î button down for 3 seconds to return to:
SUBMENU
CONTROLLER
Hold the Î button down again for 3 seconds to return to the 1st display
PRESSURE x.x bar
SPEED xx Hz
If you set the addresses in a multiple pump system the first time, connect only the Hydrovar unit where you want to set the address to power supply otherwise all Hydrovars in the system connected over the RS485-interface will change their address, too
In the following section you will give the pump an address number. Generally, the first programmed pump will be number 1, the second will be number 2, and so on. The purpose of this is to help the Hydrovar sequence the start and stop activity of the pumps in the system including the selection of the lead and lag pumps.
From the 1st display, hold the Î button for longer than 3 sec. to get the display, where the actual address is show
Address 01
Detected
or
When there is no active address, there is shown
Address 01
L O S T
Then press the Í button twice to change to
Submenu
Address
Press the Ð button to enter the submenu and change to
Address Change
00 --> 00 *
Addresses from 01 to 04 and also 00 can be set in this parameter. To change the address it is not necessary to cut the interface connection to other HYDROVARS. On the left side there is shown the address of the HYDROVAR, which you are actually speaking (select the address by using the buttons Ï or Ð). On the right side, then you can give the HYDROVAR a new address also with the buttons Ï and Ð. You only can give an address, which is not used in the pump group! To change between left and right side, press buttonÍ or Î. The star shows the actual used side.
To save the new selected address press both buttons (Ï
and Ð) together for 2 sec. If it
was successfully you will see the same address on both sides.
40
Example:
To change the Hydrovar with address 01 to address 04:
press the Í button to change the * to the left side
Address Change
00* --> 00
Select the address of the Hydrovar, you want to change the address with the Ï and Ð button
Address Change
01* --> 00
press the Î button to change the * to the right side
Address Change
01 --> 00*
Select the address you want to give this Hydrovar with the Ï and Ð button
Address Change
01 --> 04*
To confirm and save the new selected address press both buttons (Íand Î) together for 2 sec. If it was successfully you will see the same address on both sides.
Address Change
04 --> 04*
The definition of the address you have to do for each pump in the system.
Hold the Î button down for 3 seconds to return to:
SUBMENU
Address
Hold the Î button down again for 3 seconds to return to the 1
st
display
PRESSURE x.x bar
SPEED xx Hz
12 Settings at the Invertermenu
1st display PRESS X.X bar
SPEED X.X Hz
The actual input value [bar] and the actual output frequency [Hz] are displayed.
Press Î on the controller to change to
PRESSURE
XX.X bar
There you can set required pressure with the buttons Ï
and Ð
Press Î on the controller to change to
SUBMENU
PARAMETER
To enter the submenu “Parameter”, press Ð
button
Press Î on the controller to change to 1st display
41
13 Settings at the Submenu-Parameter
Important: Before entering the secondary menu these instructions must be read carefully to prevent incorrect settings which will cause malfunction.
After entering the SUBMENU PARAMETER, the display
... will change to
PASSWORD
0000
Set Password 0066 by pressing Ï and Ð
PASSWORD
0066
Confirm by pressing Î and the first parameter of the sub menu is shown
Change Pressure
Enabled
13.1 Pressure change
Change Pressure
Enabled
You can decide between Ï (Enabled) or Ð
(
Disabled)
If the pressure setting is enabled, you can change the required pressure on the Hydrovarhead with decrease and increase (see chapter 7) without an external programming device.
Press Î on the controller to change to
13.2 Auto start
Auto Start
Enabled
You can select between Ð Disabled and Ï Enabled
Autostart Enabled means, that the pump starts again automatically after an interruption of the power supply (power failure). If Autostart Disabled is set, the pump has to be restarted manually after a power failure, by pressing and .
Press Î on the controller to change to
Note: The password must be entered at each entry
42
13.3 Mode
Mode
Controller
Select with buttons Ð and Ï between:
Multicontroller sequence control for max. 4 pumps
Controller pressure control for a single pump If only one HYDROVAR-pump is in
operation, set Controller. If more than one HYDROVAR-pumps are working together via the RS485-interface, the
Multicontroller must be selected. Actuator external frequency setting. The application Actuator is only used, if you
have an external controller and the HYDROVAR works like a standard frequency converter (external frequency signal 0,5-4,5VDC to the terminals X2/1 and X2/2).
Press Î on the controller to change to
13.4 Control Response
Regulation Mode
Normal
Normal: Speed is increased with falling actual value Signals. (e.g.: Control at constant output pressure).
Inverse: Speed is reduced with falling actual value signal, (e.g.: Control of constant suction pressure or at constant level before the pump).
Press Î on the controller to change to
13.4.1 Dimension unit
Dimension unit
Bar
Here you could choose your favourite unit (with buttons Ð and Ï) Bar, psi or % for the 1st display.
Press
Î
on the controller to change to
13.5 Submenu Inverter
Submenu
Inverter
To enter this menu you have to press the Ð
key, to
leave the menu, press the Î key longer than 3 sec.
Press Î on the controller to change to
13.5.1 Maximum Frequency
Max. Frequency
50.0 Hz
Possible setting between min. 40 and max. 70 Hz.
Attention: Settings higher than 50 Hz may overload the motor!
Settings of 10% above nominal frequency cause 33% more power consumption!
43
Press
Î
on the controller to change to
13.5.2 Minimum frequency
Min. Frequency
0.0 Hz
Here you can set the minimum frequency. Attention!: If there is set F>Fmin in the parameter
CONFIG FMIN (see chapter 13.5.4) the pump will not stop in the normal mode. It will keep running with the set minimum frequency. !! Possibility of overheating of the pump !!
Press Î on the controller to change to
13.5.3 Boost
B O O S T
5.0 %
The stated value determines the course of the U/f-curve.
Setting of the motor starting voltage in % of rated voltage.
Settings of 0...25% of maximum output voltage are possible. However, care should be taken that settings are kept as low as possible so that the motor does not become thermally overloaded.
Press Î on the controller to change to
13.5.4 Operation of the minimum frequency
Config. Fmin
F Fmin
If you have selected „F->0“ the frequency will go down to the selected minimum frequency (13.5.2).
Then the inverter will run for the selected time(13.5.5)and after this time the Hydrovar will stop automatically. With the selection is „F->F
min
“ you can not run the pump below the set minimum frequency. In the controller, actuator and multicontroller mode the pump will never run below the set minimum frequency (the pump will only stop with the external on/off­terminals or in case of a failure).
Press
Î
on the controller to change to
13.5.5 Delay time for Fmin
Fmin Time
0 s
After running the pump for this selected time at minimum frequency, the pump will stop, if parameter
CONFIG Fmin (see chapter 13.5.4) it set to F ⇒ 0 Adjustable between 0 and 100s.
To leave the submenu press the Î key longer than 3 sec.!
44
13.6 Submenu Controller
Submenu
Controller
To enter this menu you have to press the Ð key, to leave the menu, press the Î key longer than 3 sec.
13.6.1 Window - %
Window
5 %
This value indicates the max. variation of the outgoing pressure (ref. Ramp window in chapter 13.6.6).
Possible setting: between 0% - 100% of required pressure.
Press Î on the controller to change to
13.6.2 Ramp Hysteresis
Hysteresis
80%
Level, where the fast ramp changes to the slow ramp within the window.
Possible setting: between 0%..100% of the window
Press Î on the controller to change to
13.6.3 Fast acceleration time
Time setting at Ramp 1, 2, 3, or 4 will influence the control of the pump and SHOULD NOT BE CHANGED at normal operation. Possible setting for each ramp 0,05 - 1000 sec.
Accel. High
4 Sec
Excessively fast running up time may overload the inverter.
Excessively slow running up time may cause a break down of the outgoing pressure.
Press
Î
on the controller to change to
13.6.4 Fast deceleration time
Decel. High
4 Sec
Excessively fast running down time tends to cause oscillation or hunting or can cause an error
(OVERVOLTAGE) during pump down of the pump. Excessively slow running down time tends to generate over pressure.
Press
Î
on the controller to change to
13.6.5 Slow acceleration time
45
Accel. Low
70 Sec
A too slow running up time during variation of demand the outgoing pressure may break.
A too fast running up time may lead to over oscillation and /or overload of the inverter.
Press Î on the controller to change to
13.6.6 Slow deceleration time
Decel. Low
70 Sec
A too fast setting leads to oscillation A too slow setting delays the switching off too
much and may generate over pressure.
Ramp Window
Press Î on the controller to change to
13.6.7 Compensation Frequency
Control according to a system curve (increase of the set pressure depending on the delivery rate or speed).
LIFT FREQUENCY
30.0 Hz
Adjustable between 6 Hz and the set MAXIMUM FREQUENCY, this setting states at which frequency
the set pressure should be increased. That is the speed at which the pump works at the set pressure and at delivery rate 0.
Press
Î
on the controller to change to
46
13.6.8 Lift-Intensity
LIFT – INTENS.
0.0 bar
Adjustable from 0 to 100% of the range of the used pressure transmitter.
This value states how much the required value should be continually increased, till the maximum speed (maximum volume) is reached.
47
Figure: Lift-Intensity
To leave the submenu press the Î key longer than 3 sec.!
13.7 Submenu Multicontroller
Submenu
Multicontroller
To enter this menu you have to press the Ð key, to leave the menu, press the Î key longer than 3 sec.
13.7.1 Lift Value
ACTU. VALUE INC.
0.15 BAR
Adjustable between 0 and 2,5 bar. This value, together with the fall value determines the
48
increase of the required value after starting of the following pumps (see attached application example in chapter 13.7.2)
Press Î on the controller to change to
13.7.2 Fall Value
For scaling the required value for 1 to 4 pumps
Actu. Value Dec.
0.15 bar
Adjustable between 0 and 2,5 bar. This value determines the start value of the 2nd and the
other following pumps. (Start-Value = REQUIRED VALUE – ACT. VALUE DEC.)
Application example:
1) Pump 1 reaches f
max
(maximum speed )
2) Pressure falls and reaches the start-value of the 2
nd
pump
(= REQUIRED VALUE – ACTU. VALUE DEC.)
3) Pump 2 is switched on automatically
4) The required value is calculated new, after the start of the 2
nd
pump in the
following way!
New required value = REQUIRED VALUE – ACTU. VALUE DEC. + ACU. VALUE INC.
Generally:
k ... Number of active pumps (k >1) P = P
set
+ (k-1)*[lift value – fall value]
• Lift value = Fall value ⇒ Pressure constant when pumps switch on
• Lift value > Fall value ⇒ Pressure rises when lag-pump switches on
• Lift value < Fall value ⇒ Pressure falls when lag-pump switches on
Press Î on the controller to change to
13.7.3 Release – Follow up pump
Enable Seq. Ctl.
48.0 Hz
The follow-up pump only starts, when the start­value is reached (see chapter 13.7.2) and the lead
49
pump has reached the programmed release-frequency. (Adjustable from 0.0 Hz to 70 Hz). If you don’t want to start a following pump this value has to be set higher than the MAX. FREQUENCY (see chapter 13.5.1)
Press Î on the controller to change to
13.7.4 Switch Interval
Switch Interval
24 hours
For changing the master pump and follow-up pump in order to achieve even operating hours of
the pumps. Adjustable between 0 and 250 hours
To leave the submenu press the Î key longer than 3 sec.!
13.8 Submenu Relay
Submenu
Relay
To enter this menu you have to press the Ð key, to leave the menu, press the Î key longer than 3 sec.
13.8.1 Relay Configuration
Relay Configu.
Simple Multicnt.
Possible selections with buttons Ð and Ï: Simple Multicnt. allows to start a following
(simple multi- constant speed pump. controller) (see chapter 13.8.2 / 13.8.3.)
Run Signalling Run indication over the relay Error Signalling fault indication over the relay
Attn:
Max. contact load 500mA / 125V
Press
Î
on the controller to change to
13.8.2 Start frequency of the slave pump
Slave-On Limit
50,0 Hz
Here you can set the frequency of the speed controlled HYDROVAR-pump, when the full speed
slave pump should start, if “simple multicontroller” is set in the parameter Relay configuration (see capter 13.8.1). In this case, the slave pump runs with full speed and the HYDROVAR-pump controls the additional demand.
Press
Î
on the controller to change to
13.8.3 Stop frequency of the slave pump
Slave-Off Limit Here you can set the frequency of the speed
50
30.0 Hz controlled HYDROVAR-pump, where the full speed
slave pump should stop, if “simple multicontroller” is set in the parameter Relay configuration (see capter 13.8.1).
To leave the submenu press the Î key longer than 3 sec.!
13.9 Submenu Sensor
Submenu
Sensor
To enter this menu you have to press the Ð key, to leave the menu, press the Î key longer than 3 sec.
13.9.1 Sensor – Adjust
SENSOR_ADJUST ?
Out of range
Zero adjustment of the transmitter Depressurise the system and press keys Ð + Ï
simultaneously. After adjustment "adjusted" appears on the display. If “out of range” is shown on the display, no adjustment is possible (e.g. when pressure is in the
system....)
Press Î on the controller to change to
13.9.2 SensorMax-Adjust
SENSORMAX-ADJUST
0,5 – 4,5 V
The analogue input (terminal X2/2) is prepared for a transmitter signal of 0,5 – 4,5VDC.
When there is used a transmitter with another signal range, you can also choose an input signal of 0,5 – 2,5VDC ( for example a 4-20mA-transmitter with an external load resistor of 125 ohm/0,25W) with the buttons Ð + Ï.
To leave the submenu press the Î key longer than 3 sec.!
13.10 Submenu Test-Run
Submenu
Testrun
To enter this menu you have to press the Ð
key, to
leave the menu, press the Î key longer than 3 sec.
13.10.1 Start of manual test run
Start Test Run
Ï + Ð
By simultaneously pressing Ï + Ð a test run will be released even if the test cycle is not set.
After starting this test run, the pump will speed up with the fasten ramp 1 to the in the parameter 13.10.3 setted speed and then will ramp down with the fasten ramp 2.
51
Press
Î
on the controller to change to
13.10.2 Sequence for automatic test run
Time Test Run
100 h
Adjustable between 1...100 hours. The test run starts the pump at the set time after
the last stop for 20 seconds with the in parameter 13.10.3 set speed. Deactivating test run: Set 0 hours, by using Ï
and Ð.
Repeating the test run: Select test run and set the desired hours using the key
Ï.
Press Î on the controller to change to
13.10.3 Test Run: Frequency
Test Frequency
30.0 Hz
Frequency for manual and automatic test run. Can be set from 0 Hz up to 70 Hz.
Press Î on the controller to change to
13.10.4 Test Run: Boost
BOOST Test Run
10.0 %.
Start voltage in % of rated voltage in order to ensure that the motor starts safely. Adjustable between 0%
and 25%
To leave the submenu press the Î key longer than 3 sec.!
13.11 Submenu Error
Submenu
Error
To enter this menu you have to press the Ð
key, to
leave the menu, press the Î key longer than 3 sec.
13.11.1 Conveyor Limit
Conveyor Limit
0.0 bar
Disabled or adjustable between 0 and 10 bar of the analogue input signal range.
0.0 bar” means disabled conveyor limit. An adjusted value >0 has to be reached till the programmed “ERROR DELAY”-time. Doesn’t this value be reached the failure “ERROR WATER” will be indicated and the pump stops.
Press Î on the controller to change to
13.11.2 Error Delay
52
Error Delay
10 Sec.
Adjustable between 0...100 sec. Delayed switch-off in the event of low water,
(Terminal X2/6-X2/7) and also for the conveyor limit ( see chapter 13.11.1).
To leave the submenu press the Î key for 3 sec.!
13.12 Set Password
Set Password
0066
The pre-set password can be changed if necessary with the Ï and Ð keys.
Press Î on the controller to change to
13.13 Default Settings
Default Ï + Ð
To load DEFAULT – PARAMETER, press buttons Ï + Ð together, till the timer is run down.
Press Î on the controller to change to
13.14 Submenu Diagnosis
Submenu Diagnosis
To enter this menu you have to press the Ð key, to leave the menu, press the Î key longer than 3 sec.
13.14.1 Pump Runtime
Pump Runtime
0000 Std.
Shows the running hours of the pump.
Press Î on the controller to change to
13.14.2 Pump Address
Pump-Address
1
This window shows the adjustment of the pump address (only read).
Press Î on the controller to change to
13.14.3 Error memory
The last three error messages are always stored in an internal memory. The error signals can not be deleted!
53
Last Error
........................
Shows the last error:
2nd Error
........................
Shows the Error before the last error:
3rd Error
........................
Shows the Error before Error 2
Press Î on the controller to change to
13.14.4 Software Version
Software
CP – VOG: 004
In this parameter, there is shown the used software version of the HYDROVAR.
To leave the submenu press the Î key for 3 sec.!
13.15 Set Password
Password
O.K.
Here the set or changed password must be confirmed.
14 Controller menu (of the programming device)
To reach the controller menu, you have to press Î on the controller for longer than 3 sec., when the
1st display PRESS X.X bar
SPEED X.X Hz
The actual input value [bar] and the actual output frequency [Hz] are displayed.
is shown. Then the display will change to
Address 01
Detected
The actual pump-address is shown
Then press Í on the controller to change to
14.1 Controller menu Configuration
Submenu
Configuration
To enter this menu you have to press the Ð key, to leave the menu, press the Î key longer than 3 sec.
54
14.1.1 Automatic connection to the programming device
Auto Connecting
Enabled
!Only valid for programming device! Auto connecting enabled: that after plug in of the
programming device, it changes automatically to the inverter menu. During this auto connection the programming device is looking for a valid address and “SCAN CONNECTION” is shown on the display (see chapter 10.2).
Auto connecting will be stored after leaving the submenu Configuration. Auto connecting disabled: there is no automatic connecting with the pump (choose the address)
Press Î on the controller to change to
14.1.2 Software Version of the programming device
Software:
Software: VOGREM-004
In the second line of the display, there is shown the version of the software of the programming device
and also the date of programming of this software.
To leave the submenu press the Î key for 3 sec.!
14.2 Submenu address
Submenu
Address
To enter this menu you have to press the Ð key, to leave the menu, press the Î key longer than 3 sec.
14.2.1 Change of pump address
Address Change
00--> 00 *
Addresses from 01 to 04 and also 00 can be set in this parameter. To change the address it is
not necessary to cut the interface connection to other HYDROVARS. On the left side there is shown the address of the HYDROVAR, which you want to speak (select the address by using the buttons Ï or Ð). On the right side, then you can give the HYDROVAR a new address also with the buttons Ï and Ð
. You only can
give an address, which is not used in the pump group! To change between left and right side, press button Í or Î. The star shows the actual used side.
To save the new selected address press both buttons (Í and Î) together for 2 sec. If it was successfully you will see the same address on both sides.
To leave the submenu press the Î key for 3 sec.!
55
15 Possible Error messages
15.1 Low Water
XXX
Error Water
Remedy: Check incoming pressure
If incoming pressure is normal the unit restarts itself. If there is no external low water protection (e.g. circulating systems), you have to bridge terminals X2/6 and X2/7.
15.2 Overheating – Motor
XXX
Error-Mot-Temp
Possible causes: insufficient cooling, ambient temperature is too high or motor
overloaded. After the cause has been remedied, the malfunction has to be reset by cutting off the power supply for >30 seconds.
15.3 Overvoltage
XXX
Error-Overvolt
Possible cause: Check mains supply, supply voltage too high, peak voltage owing to
switch heavy loads on the network, or RAMP 2 is to fast! Find the cause and take countermeasures (e.g. network filter, RC-elements). Disconnect the power supply for > 30 seconds (acknowledgement).
15.4 Undervoltage
XXX
Error-Undervolt
Possible cause: Check mains supply, faulty fuse or phase Unsymmetry.
Disconnect the power supply for > 30 seconds (acknowledgement).
15.5 Overload
XXX
Error Overload
Possible causes: false data settings or the pump is working at a capacity significantly in
excess of its performance data. Ramp 1 to fast: (see chapter 13.6.3) Max. frequency to high: (see chapter 13.5.1) Boost to low: (see chapter 13.5.3) Disconnect the power supply for > 30 seconds (acknowledgement).
56
15.6 Overheating of the heat sink
XXX
Error KK-Temp
The thermal sensor, mounted on the cooling body of the HYDROVAR indicates over
temperature. Possible causes: insufficient cooling, ambient temperature is too high or motor overloaded. After the cause has been remedied, the malfunction has to be reset by cutting off the power supply for >30 seconds.
15.7 Sensor fault
XXX
Sensor Fault
The voltage level of the incoming analogue input signal is supervised.
If the signal falls below the 0,5VDC-level, an Error will be displayed. Possible causes: break of the sensor cable or the sensor itself, bad connection of the plug of the sensor. After the cause has been remedied, the malfunction has to be reset by cutting off the power supply for >30 seconds.
15.8 Conveyor limit fault
XXX
Error Water
The value of the programmed Conveyor limit is not reached within the programmed delay
time Error Delay( see chapter 13.11.1 and 13.11.2). Possible causes can be: break of the pipe before or after the pump, closed valve before the pump, air in the pump. After the cause has been remedied, the malfunction has to be reset by cutting off the power supply for >30 seconds.
15.9 Additional internal processor Error messages:
ERROR 1 :
EEPROM-ERROR (corresponding data block malfunction)
ERROR 2 : Not used
ERROR 3 : Processor RAM error
ERROR 4 : Not used
ERROR 5 : Processor ROM error
ERROR 6 : Watchdog error
ERROR 7 : Clock error (quarz)
ERROR 8 : Programme error
These ERROR signals are acknowledged by disconnecting the power supply for > 30 seconds. If the error signal should appear again, contact customer service and provide a detailed description of the error.
57
16 Maintenance
The HV1.1-1.2 control unit does not require special maintenance. However, the cooling fan and the vent should be freed of dust occasionally.
Notes:
When replacing the control card in a plant with more than one pump ensure, that the same control card version (V/STK/X) is used in all Hydrovar units.
Fur further information, please ask your distributor!
58
59
XYLEM WATER SOLUTIONS AUSTRIA GMBH Ernst-Vogel Strasse 2 2000 Stockerau Österreich Telefon: +43 (0) 2266 / 604 Telefax: +43 (0) 2266 / 65311 e-mail: info.austria@xyleminc.com web: www.xylemaustria.com
Xylem Water Solutions Austria GmbH reserves the right to make modifications without prior notice. © 2012 Xylem, Inc
Loading...