The Boiler Control 260 is designed to control a single stage heat source in order to provide outdoor reset or Domestic Hot Water (DHW)
operation. The control has a Liquid Crystal Display (LCD) to view system status and operating information.
Additional functions include:
• Quick Setup for easy installation and programming of control
• User comfort adjustment to increase or decrease building space
temperature
• Advanced settings to fine-tune building requirements
• Pump and valve exercising
• Optional indoor sensor for room air temperature control
• DHW pump or valve operation
• Optional DHW priority
• Test sequence to ensure proper component operation
• Setback input for energy savings
• 120 V (ac) power supply
• CSA C US certified (approved to applicable UL standards)
• Powered boiler pump output
DHW Priority
DHW during UnOcc
Return
Off
Off
Installer Instructions
ROOM
- Set to desired room temp.
OUTDR DSGN
outdoor temp.
Terminal Unit Set to
High Mass Radiant
Low Mass Radiant
Fan Coil
Convector
Radiator
Baseboard
Refer to brochure for more information
120V + 10% 50/60 Hz 1300 VA
240V (ac) 10 A 1/3 hp
20 to 260 V (ac) 2 VA
1
8
Com
Indr
Signal wiring must be
rated at least 300V.
Out
- Set to coldest (design)
1
2
3
4
5
6
Meets Class B:
Canadian ICES
FCC Part 15
Date Code
H1154D
Note:
Boiler or DHW demand
must be powered with 20 to
260 V (ac) before the boiler
is able to fire.
BOIL
OCC
Terminal Unit
Fire Delay DHW Demand
Item
Boiler Control 260
One Stage Boiler & DHW
2345 6
1
DHW
Boiler
Demand
Demand
Power
L
VIEW
Boiler Demand
7 8
Boil
N
P1
DHW Valve
To increase or decrease the
°
F
building temperature:
Press the
simultaneously for 1 sec. to
enter the
Use the , buttons to
adjust the
Display defaults back to
menu after 20 sec.
Item
ADJUST
ROOM
,, buttons
menu
setting
VIEW
Advanced
Installer
DHW Pump
Test
Made in Canada by
tekmar Control Systems Ltd.
tektra 910-01
Reference Material: Essay E 003 “Characterized Heating Curve and Reset Ratio”
User Interface
The 260 uses a Liquid Crystal Display (LCD) as the method of supplying information. You use the LCD in order to set up and monitor
the operation of your system. The 260 has three push buttons (
your control, record your settings in the ADJUST menu table which is found in the second half of this brochure.
Item
The abbreviated name of the selected item will be displayed in the item field of the display.
To view the next available item, press and release the
reached the last available item, pressing and releasing the
display to the first item.
Adjust
To make an adjustment to a setting in the control, press and hold simultaneously for 1
second, all three buttons. The display will then show the word ADJUST in the top right
corner. Then select the desired item using the
button to make the adjustment.
To exit the ADJUST menu, either select the ESC item and press the or button, or leave the adjustment buttons alone for 20 seconds.
When the
Additional information can be gained by observing the status field and pointers of the LCD. The status field will indicate which of the
control’s outputs are currently active. Most symbols in the status field are only visible when the VIEW menu is selected.
Item
button is pressed and held in the VIEW menu, the display scrolls through all the adjust items in both access levels.
Item
Item
, , ) for selecting, viewing, and adjusting settings. As you program
When the Boiler Control 260 is powered up, the control displays the control type number in the LCD for 2 seconds. Next, the software
version is displayed for 2 seconds. Finally, the control enters into the normal operating mode and the LCD defaults to displaying the
current outdoor air temperature.
OPERATION
The 260 operates a single on / off heat source to control the supply
water temperature to a hydronic system. The supply water temperature
is based on either the current outdoor temperature, or on a DHW target.
Outdoor Reset
The 260 calculates a supply temperature based on the outdoor air
temperature. The 260 uses a
tionally indoor temperature feedback from an indoor sensor in this
calculation.
DHW Control
When a demand signal from a Domestic Hot Water (DHW) system is
present, the control will operate the boiler to maintain the supply water temperature at 180°F (82°C). Refer to section C.
Characterized Heating Curve
and op-
Design Supply
Terminal Unit
Indoor Design
Decreasing Outdoor Temperature
Outdoor Design
Increasing Water Temperature
EXERCISING
The 260 has a built-in exercising function. If a pump or valve that is connected to the control has not been operated at least once every
3 days, the control turns on the output for 10 seconds. This minimizes the possibility of a pump or valve seizing during a long period
of inactivity. While the control is exercising, the
Note
: The exercising function does not work if power to the control, valves, or pumps is disconnected.
SETBACK (UNOCCUPIED)
To provide greater energy savings, the 260 has a setback capability. With setback, the
supply water temperature in the system is reduced when the building is unoccupied. By
reducing the supply water temperature, air temperature in the space may be reduced
even when thermostat’s are not turned down. Any time the
terminals are shorted together, the control operates in the unoccupied (Night) mode. When
in the unoccupied (Night) mode, the UNOCC segment is displayed in the LCD. The 260
adjusts the supply water temperature based on the UNOCC settings made in the control.
FACTORY DEFAULTS
The control comes preset with several factory defaults. These defaults are based on the terminal unit selection (see section B2). To finetune building requirements, these defaults may be changed. If a factory default value for a terminal unit is changed, the terminal unit
number will flash when selected in the ADJUST menu.
To reload the factory defaults listed in section B2, power down the control and wait for 10 seconds. Power up the control while
simultaneously holding the
than flashing.
Test
LED flashes.
14
13
Com
UnO
Sw
UnO Sw
(13) and the
Com
(14)
Timer Switch
Item
and buttons. The terminal unit number should now be displayed constantly in the LCD rather
A boiler demand is required in order for the 260 to provide heat to the heating system. A
boiler demand is generated by applying a voltage between 24 and 240 V (ac) across the
Boiler Demand
displayed in the LCD. If the 260 is not in WWSD, the 260 closes the
260 calculates a BOIL TARGET supply temperature based on the outdoor air temperature
and settings. The 260 then fires the boiler, if required, to maintain the target supply
temperature.
BOILER PUMP OPERATION (
The boiler pump contact (
segment is displayed in the LCD. After the boiler demand has been satisfied, the 260 continues to operate the boiler pump for 20
seconds. This allows some residual heat to be purged out to the heating system. During WWSD, the boiler pump is operated based
on the exercise function. For boiler pump contact operation during DHW operation, refer to section C.
BOILER OPERATION
When the 260 determines that boiler operation is required, the
burner segment in the LCD is displayed.
terminals (1 and 2). Once voltage is applied, the
Boil P1
Boil P1
, terminal 7) closes whenever there is a boiler demand and the 260 is not in WWSD. The boiler pump
)
Boiler
Boiler Demand
Boil P1
contact (11 and 12) closes. While the
pointer is
contact. The
24 to 240 V (ac)
Boiler
contact is closed, the
1
Boiler
Demand
2
INDOOR SENSOR
The indoor sensor is connected to the
terminals (1 and 2) as described in the BOILER DEMAND section. With the indoor sensor connected, the 260 is able to sense the
actual room temperature. Indoor temperature feedback fine-tunes the supply water temperature in the heating system to maintain
room temperature. To adjust the room temperature, use the ROOM OCC or ROOM UNOCC setting in the ADJUST menu at the control.
If a multiple zone system is used with an indoor sensor, proper placement of the indoor sensor is essential. The indoor sensor should
be located in an area which best represents the average air temperature of the zones.
CHARACTERIZED HEATING CURVE
The 260 varies the supply water temperature based on the outdoor air temperature. The control takes into account the type of terminal
unit that the system is using. Since different types of terminal units transfer heat to a space using different proportions of radiation,
convection and conduction, the supply water temperature must be controlled differently. Once the control is told what type of terminal
unit is used, the control varies the supply water temperature according to the type of terminal unit. This improves the control of the air
temperature in the building.
BOILER TARGET TEMPERATURE (BOIL TARGET)
The BOIL TARGET temperature is determined from the
indoor air temperature. The control displays the temperature that it is currently trying to maintain as the boiler supply temperature. If
the control does not presently have a requirement for heat, it does not show a boiler target temperature. Instead, “- - -” is displayed in
the LCD.
Com
and
Indr
terminals (17 and 18). In addition, power must be applied to the
Boiler Demand
Characterized Heating Curve
settings, outdoor air temperature, and optionally,
The OUTDR DSGN is the outdoor air temperature that is the typical
coldest temperature of the year where the building is located. This temperature is used when doing the heat loss calculations for the building.
If a cold outdoor design temperature is selected, the boiler supply temperature rises gradually as the outdoor temperature drops. If a warm
outdoor design temperature is selected, the boiler supply temperature
rises rapidly as the outdoor temperature drops.
ROOM OCC & UNOCC (ROOM)
The ROOM is the desired room temperature for the boiler zones, and it
provides a parallel shift of the
temperature desired by the occupants is often different from the design
indoor temperature (BOIL INDR). If the room temperature is not correct,
adjusting the ROOM setting increases or decreases the amount of heat
available to the building. A ROOM setting is available for both the occupied (Day) and unoccupied (Night) modes.
TERMINAL UNITS
When using a
shape of the
Characterized Heating Curve
Characterized Heating Curve
E 003). The 260 provides for selection between six different terminal unit types: two types of radiant floor heat, fancoil, fin-tube
convector, radiator and baseboard. When a terminal unit is selected, the control automatically loads the design supply temperature
(BOIL DSGN), maximum supply temperature (BOIL MAX), and minimum supply temperature (BOIL MIN). The factory defaults are
listed below. To change defaults, refer to section B3. If a default has been changed, refer to section A to reload the factory defaults.
Characterized Heating Curve
cold
OUTDR
DSGN
warm
BOIL INDR
Increasing Water Temperature
Decreasing Outdoor Temperature
.
p
m
e
A
u
t
c
T
l
a
N
ROOM
BOIL INDR
n
g
i
s
e
D
l
a
m
r
o
. The room
Increasing Water Temperature
Decreasing OutdoorTemperature
, the control requires the selection of a terminal unit. The terminal unit determines the
according to how the terminal unit delivers heat into the building space (refer to Essay
Terminal Unit
BOIL DSGN
BOIL MAX
BOIL MIN
High Mass Radiant
(1)
120°F (49°C)
140°F (60°C)
OFF
Low Mass Radiant
(2)
140°F (60°C)
160°F (71°C)
OFF
Fancoil
(3)
190°F (88°C)
210°F (99°C)
140°F(60°C)
Fin-tube Convector
180°F (82°C)
200°F (93°C)
140°F (60°C)
High Mass Radiant (1)
This type of a hydronic radiant floor is embedded in either a thick concrete or gypsum
pour. This heating system has a large thermal mass and is slow acting.
Default values: BOIL DSGN = 120°F (49°C), BOIL MAX = 140°F (60°C), BOIL MIN = OFF
Low Mass Radiant (2)
This type of radiant heating system is either attached to the bottom of a wood sub-floor,
suspended in the joist space, or sandwiched between the sub-floor and the surface.
This type of radiant system has a relatively low thermal mass and responds faster than
a high mass system.
Default values: BOIL DSGN = 140°F (60°C), BOIL MAX = 160°F (71°C), BOIL MIN = OFF