tekmar 260 User Manual

- Data Brochure
D 260
Boiler Control 260
03/09
The Boiler Control 260 is designed to control a single stage heat source in order to provide outdoor reset or Domestic Hot Water (DHW) operation. The control has a Liquid Crystal Display (LCD) to view system status and operating information.
Additional functions include:
• Quick Setup for easy installation and programming of control
• Advanced settings to fine-tune building requirements
• Pump and valve exercising
• Optional indoor sensor for room air temperature control
• DHW pump or valve operation
• Optional DHW priority
• Test sequence to ensure proper component operation
• Setback input for energy savings
• 120 V (ac) power supply
• CSA C US certified (approved to applicable UL standards)
• Powered boiler pump output
DHW Priority
DHW during UnOcc
Return
Off Off
Installer Instructions
ROOM
- Set to desired room temp.
OUTDR DSGN
outdoor temp.
Terminal Unit Set to
High Mass Radiant Low Mass Radiant Fan Coil Convector Radiator Baseboard
Refer to brochure for more information
120V + 10% 50/60 Hz 1300 VA 240V (ac) 10 A 1/3 hp 20 to 260 V (ac) 2 VA
1
8
Com
Indr
Signal wiring must be rated at least 300V.
Out
- Set to coldest (design)
1 2 3 4 5 6
Meets Class B: Canadian ICES FCC Part 15
Date Code
H1154D
Note:
Boiler or DHW demand must be powered with 20 to 260 V (ac) before the boiler is able to fire.
BOIL
OCC
Terminal Unit
Fire Delay DHW Demand
Item
Boiler Control 260
One Stage Boiler & DHW
2345 6
1
DHW
Boiler
Demand
Demand
Power
L
VIEW
Boiler Demand
7 8
Boil
N
P1
DHW Valve
To increase or decrease the
°
F
building temperature:
Press the simultaneously for 1 sec. to enter the Use the , buttons to adjust the
Display defaults back to menu after 20 sec.
Item
ADJUST
ROOM
,, buttons
menu
setting
VIEW
Advanced
Installer DHW Pump
Test
Made in Canada by tekmar Control Systems Ltd. tektra 910-01
Power:
C US
11 12
910
Boiler
DHW
N
Pmp/Vlv
Relays: Demand:
Do not apply power
13 14 15 16 17
UnO
Com
Boil
Sw
Input
Boiler Demand
Signal
Input
DHW Demand
Signal
120 V (ac) Power
Input
Supply
Output
Boiler System
Pump
M
Output
DHW Pump OR
DHW Valve
Output
Boiler
Input
tekmar Timer
Optional
Copyright © D 260 - 03/091 of 20
Input
Indoor Sensor
Optional
Input
Outdoor Sensor
Included
Input
Universal Sensor
Included
How To Use The Data Brochure
This brochure is organized into four main sections. They are: 1)
Troubleshooting
of the
Sequence of Operation
sections that apply to your installation. For quick installation and setup of the control, refer to the
Settings
The displayed by the control. The control functions of each adjustable item are described in the
section, followed by the
Control Settings
. The
Sequence of Operation
, as this contains important information on the overall operation of the control. Then read the sub-
section (starting at
Quick Setup
DIP Switch Settings
section has three sub-sections. We recommend reading Section A:
section.
Sequence of Operation
) of this brochure, describes the various items that are adjusted and
Installation
, 2)
Sequence of Operation
Table of Contents
User Interface ................................................... pg 2
Description of Display Elements .................... pg 3
Sequence of Operation .................................... pg 4
Section A: General Operation ..............
Section B: Boiler Reset
Section C: DHW
Installation ...................................................... pg 10
DIP Switch Settings ....................................... pg 14
......................... pg 5
..................................... pg 8
pg 4
Quick Setup ........................................................ pg 14
Control Settings ................................................. pg 15
View Menu
Adjust Menu
Testing and Troubleshooting ............................ pg 17
Error Messages
Technical Data .................................................... pg 20
Limited Warranty ................................................ pg 20
................................................ pg 15
............................................. pg 16
....................................... pg 19
Control Settings
, 3)
Installation
, and 4)
General Operation
section,
DIP Switch
.
Reference Material: Essay E 003 “Characterized Heating Curve and Reset Ratio”
User Interface
The 260 uses a Liquid Crystal Display (LCD) as the method of supplying information. You use the LCD in order to set up and monitor the operation of your system. The 260 has three push buttons ( your control, record your settings in the ADJUST menu table which is found in the second half of this brochure.
Item
The abbreviated name of the selected item will be displayed in the item field of the display. To view the next available item, press and release the reached the last available item, pressing and releasing the display to the first item.
Adjust
To make an adjustment to a setting in the control, press and hold simultaneously for 1 second, all three buttons. The display will then show the word ADJUST in the top right corner. Then select the desired item using the
button to make the adjustment.
To exit the ADJUST menu, either select the ESC item and press the or button, or leave the adjustment buttons alone for 20 seconds.
When the
Additional information can be gained by observing the status field and pointers of the LCD. The status field will indicate which of the control’s outputs are currently active. Most symbols in the status field are only visible when the VIEW menu is selected.
Item
button is pressed and held in the VIEW menu, the display scrolls through all the adjust items in both access levels.
Item
Item
, , ) for selecting, viewing, and adjusting settings. As you program
Item
button. Once you have
Item
button will return the
button. Finally, use the
and / or
Item
Item
Copyright © D 260 - 03/09 2 of 20
Display
Item Field
Displays an abbreviated name of the selected item
OUTDR BOIL
ROOM WWSD INDR
Status Field
Displays the current status of the control’s inputs, outputs and operation
DSGN
TARGET
MAXMIN
UN
OCC
Fire Delay
Item
DIFF
DHW
Number Field
Displays the current value of the selected item
VIEW
ADJUST
Boiler DemandTerminal Unit
DHW Demand
°
F
°
C
min
Menu Field
Displays the current menu
Buttons
Selects Menus, Items and
{
adjusts settings
Symbol Description
Pump
Displays when the boiler pump is in operation.
DHW
OCC
DHW
Displays when the DHW pump or valve is in operation.
Burner
Displays when the boiler relay is turned on.
Occupied Schedule
Displays when the control is in occupied (Day) mode.
UNOCC
°
F, °C
Unoccupied Schedule
Displays when the control is in unoccupied (Night) mode.
°F, °C
Displays the units of measure that all of the temperatures are to be displayed in the control.
Pointer
Displays the control operation as indicated by the text.
Copyright © D 260 - 03/093 of 20
Sequence of Operation
Section A
General Operation
Page 4
Section B
Boiler Reset
Page 5-8
Section C
DHW
Page 8-10
Section A —General Operation
POWERING UP THE CONTROL
When the Boiler Control 260 is powered up, the control displays the control type number in the LCD for 2 seconds. Next, the software version is displayed for 2 seconds. Finally, the control enters into the normal operating mode and the LCD defaults to displaying the current outdoor air temperature.
OPERATION
The 260 operates a single on / off heat source to control the supply water temperature to a hydronic system. The supply water temperature is based on either the current outdoor temperature, or on a DHW target.
Outdoor Reset
The 260 calculates a supply temperature based on the outdoor air temperature. The 260 uses a tionally indoor temperature feedback from an indoor sensor in this calculation.
DHW Control
When a demand signal from a Domestic Hot Water (DHW) system is present, the control will operate the boiler to maintain the supply wa­ter temperature at 180°F (82°C). Refer to section C.
Characterized Heating Curve
and op-
Design Supply
Terminal Unit
Indoor Design
Decreasing Outdoor Temperature
Outdoor Design
Increasing Water Temperature
EXERCISING
The 260 has a built-in exercising function. If a pump or valve that is connected to the control has not been operated at least once every 3 days, the control turns on the output for 10 seconds. This minimizes the possibility of a pump or valve seizing during a long period of inactivity. While the control is exercising, the
Note
: The exercising function does not work if power to the control, valves, or pumps is disconnected.
SETBACK (UNOCCUPIED)
To provide greater energy savings, the 260 has a setback capability. With setback, the supply water temperature in the system is reduced when the building is unoccupied. By reducing the supply water temperature, air temperature in the space may be reduced even when thermostats are not turned down. Any time the terminals are shorted together, the control operates in the unoccupied (Night) mode. When in the unoccupied (Night) mode, the UNOCC segment is displayed in the LCD. The 260 adjusts the supply water temperature based on the UNOCC settings made in the control.
FACTORY DEFAULTS
The control comes preset with several factory defaults. These defaults are based on the terminal unit selection (see section B2). To fine­tune building requirements, these defaults may be changed. If a factory default value for a terminal unit is changed, the terminal unit number will flash when selected in the ADJUST menu.
To reload the factory defaults listed in section B2, power down the control and wait for 10 seconds. Power up the control while simultaneously holding the than flashing.
Test
LED flashes.
14
13
Com
UnO
Sw
UnO Sw
(13) and the
Com
(14)
Timer Switch
Item
and buttons. The terminal unit number should now be displayed constantly in the LCD rather
Copyright © D 260 - 03/09 4 of 20
Section B: Boiler Reset
Section B1
General
Section B2
Installer
Section B3
Advanced
Section B1: General
BOILER DEMAND
A boiler demand is required in order for the 260 to provide heat to the heating system. A boiler demand is generated by applying a voltage between 24 and 240 V (ac) across the
Boiler Demand
displayed in the LCD. If the 260 is not in WWSD, the 260 closes the 260 calculates a BOIL TARGET supply temperature based on the outdoor air temperature and settings. The 260 then fires the boiler, if required, to maintain the target supply temperature.
BOILER PUMP OPERATION (
The boiler pump contact ( segment is displayed in the LCD. After the boiler demand has been satisfied, the 260 continues to operate the boiler pump for 20 seconds. This allows some residual heat to be purged out to the heating system. During WWSD, the boiler pump is operated based on the exercise function. For boiler pump contact operation during DHW operation, refer to section C.
BOILER OPERATION
When the 260 determines that boiler operation is required, the burner segment in the LCD is displayed.
terminals (1 and 2). Once voltage is applied, the
Boil P1
Boil P1
, terminal 7) closes whenever there is a boiler demand and the 260 is not in WWSD. The boiler pump
)
Boiler
Boiler Demand
Boil P1
contact (11 and 12) closes. While the
pointer is
contact. The
24 to 240 V (ac)
Boiler
contact is closed, the
1
Boiler
Demand
2
INDOOR SENSOR
The indoor sensor is connected to the terminals (1 and 2) as described in the BOILER DEMAND section. With the indoor sensor connected, the 260 is able to sense the actual room temperature. Indoor temperature feedback fine-tunes the supply water temperature in the heating system to maintain room temperature. To adjust the room temperature, use the ROOM OCC or ROOM UNOCC setting in the ADJUST menu at the control.
If a multiple zone system is used with an indoor sensor, proper placement of the indoor sensor is essential. The indoor sensor should be located in an area which best represents the average air temperature of the zones.
CHARACTERIZED HEATING CURVE
The 260 varies the supply water temperature based on the outdoor air temperature. The control takes into account the type of terminal unit that the system is using. Since different types of terminal units transfer heat to a space using different proportions of radiation, convection and conduction, the supply water temperature must be controlled differently. Once the control is told what type of terminal unit is used, the control varies the supply water temperature according to the type of terminal unit. This improves the control of the air temperature in the building.
BOILER TARGET TEMPERATURE (BOIL TARGET)
The BOIL TARGET temperature is determined from the indoor air temperature. The control displays the temperature that it is currently trying to maintain as the boiler supply temperature. If the control does not presently have a requirement for heat, it does not show a boiler target temperature. Instead, - - - is displayed in the LCD.
Com
and
Indr
terminals (17 and 18). In addition, power must be applied to the
Boiler Demand
Characterized Heating Curve
settings, outdoor air temperature, and optionally,
Copyright © D 260 - 03/095 of 20
Section B2: Installer
BOIL DSGN
OUTDOOR DESIGN (OUTDR DSGN)
The OUTDR DSGN is the outdoor air temperature that is the typical coldest temperature of the year where the building is located. This tem­perature is used when doing the heat loss calculations for the building. If a cold outdoor design temperature is selected, the boiler supply tem­perature rises gradually as the outdoor temperature drops. If a warm outdoor design temperature is selected, the boiler supply temperature rises rapidly as the outdoor temperature drops.
ROOM OCC & UNOCC (ROOM)
The ROOM is the desired room temperature for the boiler zones, and it provides a parallel shift of the temperature desired by the occupants is often different from the design indoor temperature (BOIL INDR). If the room temperature is not correct, adjusting the ROOM setting increases or decreases the amount of heat available to the building. A ROOM setting is available for both the occu­pied (Day) and unoccupied (Night) modes.
TERMINAL UNITS
When using a shape of the
Characterized Heating Curve
Characterized Heating Curve
E 003). The 260 provides for selection between six different terminal unit types: two types of radiant floor heat, fancoil, fin-tube convector, radiator and baseboard. When a terminal unit is selected, the control automatically loads the design supply temperature (BOIL DSGN), maximum supply temperature (BOIL MAX), and minimum supply temperature (BOIL MIN). The factory defaults are listed below. To change defaults, refer to section B3. If a default has been changed, refer to section A to reload the factory defaults.
Characterized Heating Curve
cold
OUTDR
DSGN
warm
BOIL INDR
Increasing Water Temperature
Decreasing Outdoor Temperature
.
p
m
e
A
u
t
c
T
l
a
N
ROOM
BOIL INDR
n
g
i
s
e
D
l
a
m
r
o
. The room
Increasing Water Temperature
Decreasing OutdoorTemperature
, the control requires the selection of a terminal unit. The terminal unit determines the
according to how the terminal unit delivers heat into the building space (refer to Essay
Terminal Unit
BOIL DSGN BOIL MAX BOIL MIN
High Mass Radiant
(1)
120°F (49°C) 140°F (60°C)
OFF
Low Mass Radiant
(2)
140°F (60°C) 160°F (71°C)
OFF
Fancoil
(3)
190°F (88°C) 210°F (99°C)
140°F(60°C)
Fin-tube Convector
180°F (82°C) 200°F (93°C) 140°F (60°C)
High Mass Radiant (1)
This type of a hydronic radiant floor is embedded in either a thick concrete or gypsum pour. This heating system has a large thermal mass and is slow acting. Default values: BOIL DSGN = 120°F (49°C), BOIL MAX = 140°F (60°C), BOIL MIN = OFF
Low Mass Radiant (2)
This type of radiant heating system is either attached to the bottom of a wood sub-floor, suspended in the joist space, or sandwiched between the sub-floor and the surface. This type of radiant system has a relatively low thermal mass and responds faster than a high mass system. Default values: BOIL DSGN = 140°F (60°C), BOIL MAX = 160°F (71°C), BOIL MIN = OFF
Copyright © D 260 - 03/09 6 of 20
(4)
Radiator
(5)
160°F (71°C) 180°F (82°C) 140°F (60°C)
Baseboard
(6)
150°F (66°C) 170°F (77°C) 140°F (60°C)
Loading...
+ 14 hidden pages