tekmar 257 User Manual

Page 1
- Data Brochure
DHW Control 257
D 257
03/09
The DHW Control 257 is used for dedicated domestic hot water systems. The control operates two on/off boilers, or one two-stage boiler to maintain the DHW Target temperature at the DHW Sensor. The control can operate in Proportional (P) mode, or Proportional, Integral, Derivative (PID) mode.
Boiler rotation
• Cumulative boiler run time hours
• P or PID staging modes of operation
• CSA and UL certified for use in the USA and Canada
Input
24 V (ac)
Power Supply
Meets Class B: Canadian ICES FCC Part 15
Made in Canada tektra 906-11
Stage Mode Delay
Item
DHW Control 257
Two Sta ge
Rotate
1234
On
Power Heat 1
CR
Off
Power: 24 V ±10% 50/60 Hz 3 VA Relays: 240 V (ac) 10 A 1/3 hp
DifferentialDHW
Tar get DHW
Signal wiring
must be rated
at least 300V
56
Heat 2
No Power
7
Com
DHW
Sen
Sen
H3014B
Date Code
8
Input
Universal Sensor
Included
Output
Boiler
1 of 12 © 2009 D 257 - 03/09
Output
Boiler
Page 2
How to Use the Data Brochure
This brochure is organized into three main sections.
They are: 1) Sequence of Operation, 2) Installation, and
3) Control Settings.
Table of Contents
User Interface ............................................................... 2
Display and Symbol Description ............................... 3
Sequence of Operation ................................................. 4
Powering up the Control ........................................... 4
Staging Operation .................................................... 4
Rotation ...................................................................5
Delay ........................................................................ 5
Installation ...................................................................6
Getting Ready .......................................................... 6
Mounting .................................................................. 6
Rough-in Wiring .......................................................6
The Control Settings section of this brochure describes the various items that are adjusted and displayed by the control. The control functions of each adjustable item are described in the Sequence of Operation.
Testing the Wiring .................................................... 6
Electrical Connections to the Control ....................... 7
Control Settings ............................................................ 8
DIP Switch Settings .................................................. 8
Default Menu ............................................................9
Program Menu ....................................................... 10
Field Test .................................................................... 11
Error Messages .......................................................... 11
Technical Data ............................................................ 12
Limited Warranty ....................................................... 12
User Interface
The 257 uses a Liquid Crystal Display (LCD) to display information. Use the LCD to set up and monitor the operation of the system. The 257 has three push buttons (Item, ▲, ▼) for selecting, viewing, and adjusting settings. As you program the control, record the settings in the ADJUST menu table which is found in the second half of this brochure.
Item
The selected item will be displayed using a pointer in the display. To view the next available item, press the Item button. Once you have reached the last available item, pressing the Item button again will return the display to the first item.
Item
Adjust
To make an adjustment to a setting in the control, press and hold simultaneously for 1 second all three (3) buttons. The display will then show the word PRGM. Select the desired item using the Item button. Finally, use the ▲ or ▼ button to make the adjustment.
Item
© 2009 D 257 - 03/09 2 of 12
Page 3
°
Display
Menu Field
Displays the
current menu
Item Field
Displays the current
item selected.
Stage Mode Delay
Item
Target DHW
Number Field
Displays the current value of the selected item
Status Field
Displays the current status of the control’s inputs,
DifferentialDHW
outputs and operation
Buttons
Selects Menus, Items and adjusts settings
Symbol Description
POINTER
Displays the control operation as indicated by the text.
HEAT RELAY
Displays when the HEAT 1 relay is closed.
HEAT RELAY
Displays when the HEAT 2 relay is closed.
°F °°C
PRGM
°F, °C
Units of measurement
PROGRAM MENU
Program the control settings.
3 of 12 © 2009 D 257 - 03/09
Page 4
Sequence of Operation
Powering Up the Control
When the DHW Control 257 is powered up all LCD segments are displayed for 2 seconds followed by the version number being displayed for 2 seconds. The control then enters
Staging Operation
Proportional Staging Mode (P)
When the Stage Mode is set to P, the on/off points of the HEAT 1 and HEAT 2 relays are determined by the Target DHW setpoint, the Differential 1 and the Differential 2 settings. This is a manual way of staging the boilers. See figure 1 for a visual representation.
Target
DHW
Increasing
Temperature
Increasing Time
OFF
Stage 1
Stage 1
Stage 1 & 2
into the normal operating mode and the LCD defaults to displaying the current DHW temperature.
Differential 1 & Differential 2 (P Mode)
Manually adjust Differential 1 and 2 to set the on points of stage 1 and 2. Stage 1 will fire when the temperature falls below Target DHW minus Differential 1. Stage 2 will fire when the temperature falls below Target DHW minus differential 1 minus differential 2.
OFF
Differential 1
Stage 1
Stage 1 & 2
Differential 2
Proportional, Integral, Derivative Staging Mode (PID)
To provide proper boiler staging and accurate DHW Target temperatures, PID mode should be used. When the Stage Mode is set to PID, the on and off points of the HEAT 1 and HEAT 2 relays are determined by PID logic and the differential setting.
What is PID?
Proportional Error - How far is the temperature from theTarget?
• Integral Error - How long has the temperature been there?
Derivative Error - How fast it is the temperature changing?
By considering these three errors, the control can better decide when to turn on a boiler stage. This function provides greater boiler plant efficiency and also prevents water temperature drop that is commonly seen on proportional staged systems.
Figure 1 - Staging operation for proportional logic
Differential (PID Mode)
If Differential is set to Auto, the control will calculate an appropriate differential to reduce boiler short cycling. If a boiler short cycles, the differential is automatically increased. If auto differential is not desirable, the installer may select a manual differential.
Minimum On and Off Times
The minimum on and off time for each boiler is 30 seconds.
DHW Maximum
If the DHW temperature rises 2°F above the Target DHW setpoint due to minimum boiler on times, the control will open both the Heat 1 and Heat 2 relays.
© 2009 D 257 - 03/09 4 of 12
Page 5
Rotation
This function rotates the firing sequence of the two boilers based on the accumulated running hours of each stage. The HEAT 1 and HEAT 2 items in the default menu display the accumulated running hours of each stage. When one stage has accumulated 48 hours more running hours than the other stage, the operating sequence is rotated. The stage with less running hours is rotated in the firing sequence to turn on first, while the stage with more running hours will turn on last. This function increases the quality and reliability of the boiler plant by ensuring equal running times of both boilers. When this item is set to off, HEAT 1 is always the first stage to fire.
Forced Rotation:
If the difference in run times reaches 60 hours, then boiler rotation takes place immediately. This could occur if the DHW tank has a constant load causing one boiler to fire for an extended period of time.
Relay Run Times
The control logs the number of run time hours for the HEAT 1 and HEAT 2 relay in the default menu. To reset back to
zero hours, press and hold the up and down buttons for 3 seconds.
1 2
500 Hours 452 Hours
Reset Rotation:
To reset the rotation sequence back to 1-2, clear both run time hours in the default menu by pressing and holding the up and down buttons. Next, switch the rotation dip switch to the off position and then back to the on position. Both stages now have 0 hours accumulated run time and the firing sequence is 1-2.
Delay
When P Staging Mode is selected, you are then able to adjust the minimum stage delay between when stage 1 and stage 2 fires. This item is default at 30 seconds and is adjustable between 0 seconds and 19 minutes 50 seconds.
When PID Staging Mode is selected, PID logic is able to determine when to bring on stage 1 and stage 2. The minimum stage delay now becomes the default 30 seconds.
Selecting a Delay Time:
For low mass boilers, select a shorter delay time.
• For high mass boilers, select a longer delay time.
Stage 1
Contact Closes
Stage Delay
Stage 1
Time
Stage 2
Contact Closes
Stage 2
5 of 12 © 2009 D 257 - 03/09
Page 6
Installation
Caution
Improper installation and operation of this control could result in damage to the equipment and possibly even personal injury. It is your responsibility to ensure that this control is safely installed according to all applicable codes
and standards. This electronic control is not intended for use as a primary limit control. Other controls that are intended and certified as safety limits must be placed into the control circuit.
Step One — Getting Ready
Check the contents of this package. If any of the contents listed are missing or damaged, please contact your wholesaler or tekmar sales representative for assistance.
Type 257 includes: One DHW Control 257, One Universal Sensor 082 Data Brochures D 257, D 070, D 001, Application Brochure A 257.
Note: Carefully read the details of the Sequence of Operation to ensure that you have chosen the proper control for your application.
Step Two — Mounting
The control is mounted in accordance with the instructions in the Data Brochure D 001.
Step Three — Rough-in Wiring
The wiring terminates in the two wiring chambers on the control. Determine whether the low voltage wiring enters the wiring chamber through the back or the bottom of the control. The wiring is roughed-in prior to installation of the control (see Brochure D 001). Standard 18 AWG solid wire is recommended for all low voltage wiring, and multi-strand 16 AWG wire is recommended for 120 V (ac) wiring.
Step Four — Testing the Wiring
The following tests are to be performed using standard testing practices and procedures, and should only be carried out by properly trained and experienced persons.
A good quality electrical test meter, capable of reading from at least 0 - 300 V (ac) and at least 0 - 2,000,000 Ohms, is essential to properly test the wiring and sensors.
Test the Sensors
In order to test the sensors, the actual temperature at each sensor location must be measured. A good quality digital thermometer with a surface temperature probe is recommended for ease of use and accuracy. Where a digital thermometer is not available, a spare sensor can be strapped alongside the one to be tested, and the readings compared. Test the sensors according to the instructions in the Data Brochure D 070.
Power must not be applied to any of the wires during the rough-in wiring stage.
Install the DHW Sensor 082 according to the instructions
• in the Data Brochure D 070, and run the wiring back to the control.
Run wires from the 24 V (ac) power to the control. Use a
• clean power source to ensure proper operation.
No Power
78
Com
DHW
Sen Sen
© 2009 D 257 - 03/09 6 of 12
Page 7
Test the Power Supply
Make sure exposed wires and bare terminals are not in contact with other wires or grounded surfaces.
If a 24 V (ac) transformer is used, make sure the voltmeter is set to AC. Turn on the power and measure the voltage across the 24 V (ac) power supply. The reading should be between 22 and 26 V (ac).
LN
Class 2
Transformer
RC
Test the Outputs
Heat 1 and Heat 2
Make sure power is off to the boiler circuits and connect the TT contacts on the boilers to the Heat 1 and Heat 2 contacts on the control. Install jumpers at the Heat 1 and Heat 2 terminals to externally close the switch. When the boiler circuits are powered up, the boilers should fire. If the boilers do not turn on, refer to any installation or troubleshooting information supplied with the boilers (the boilers may have a flow switch that prevents firing until the boiler pumps are running). If the boilers operate properly, disconnect the power and remove the jumpers.
34
Heat 1
Jumper wire
between
terminals
DHW Control 257
T-T contacts
on boiler
Step Five — Electrical Connections to the Control
The installer should test to confirm that no voltage is present at any of the wires.
Powered Input Connections
24 V (ac) Power
Connect the 24 V (ac) power supply to the Power C and Power R terminals (1 and 2). This connection provides power to the microprocessor and display of the control.
LN
12
Power
RC
Output Connections
Heat 1 and Heat 2 Contacts
The Heat 1 and Heat 2 contacts are an isolated output in the
257. There is no power available on these terminals from the control. These terminals are to be used as a switch to either make or break the boiler TT circuit. When the 257 requires boiler 1 to run, it closes the contact between terminals 3 and 4, and when the 257 requires boiler 2 to run, it closes the contact between terminals 5 and 6.
CR
3456
Heat 1 Heat 2
Sensors
Do not apply power to these terminals as this will damage the control.
DHW Sensor
Connect the two wires from the DHW Sensor 082 to the Com and DHW terminals (7 and 8). The DHW Sensor is used by the 257 to measure the DHW tank temperature.
No Power
78
Com
DHW
Sen Sen
Locate the sensor in a well in the tank. The 082 sensor is 3/8” OD and will insert into a standard 1/2” well.
DHW Tank
7 of 12 © 2009 D 257 - 03/09
Page 8
1
C
Po
Rotate
On
Off
Control Settings
DIP Switch Settings
Off | On - Rotate
The Off | On – Rotate DIP switch is used to turn boiler rotation on or off. When using a single boiler with two stages, the DIP switch should be in the off (down) position. When using two single-stage boilers, the DIP switch should be in the on (up) position.
Item
DHW Control 257
Two Sta ge
Rotate
1234
On
Power Heat 1
CR
Off
Signal wiring
must be rated
at least 300V
56
Heat 2
No Power
7
Com
DHW
Sen
Sen
Date Code
8
© 2009 D 257 - 03/09 8 of 12
Page 9
Default Menu
View Next Item
Item
Item Field Range Description
Stage Mode Delay
Stage Mode Delay
Tar get DHW
Tar get DHW
The Default menu items display current operating temperatures and system status information.
Use the
Item button to view items in this menu.
DHW TEMPERATURE
-60 to 255°F
(-51 to 124°C)
DifferentialDHW
The current DHW temperature as measured by the DHW sensor. HEAT is displayed with a 1 or 2 when either the Heat 1 or Heat 2 relay is closed.
TARGET DHW
70 to 190°F
(21 to 88°C)
DifferentialDHW
The current DHW target as programmed in the PRGM menu. HEAT is displayed with a 1 or 2 when either the Heat 1 or Heat 2 relay is closed.
HEAT 1 RUN TIME
The total running time in hours of the HEAT 1 relay since this
DEFAULT MENU
0 to 1999 Hours
item was last cleared. To clear, press the ▲ and ▼ buttons simultaneously while
Stage Mode Delay
Tar get DHW
DifferentialDHW
viewing this item.
HEAT 2 RUN TIME
The total running time in hours of the HEAT 2 relay since this
0 to 1999 Hours
item was last cleared. To clear, press the ▲ and ▼ buttons simultaneously while
Stage Mode Delay
After the last item, the control returns to the first item in the menu.
Tar get DHW
DifferentialDHW
viewing this item.
9 of 12 © 2009 D 257 - 03/09
Page 10
Program Menu
Item Field Range Description Actual Setting
Stage Mode Delay
Stage Mode Delay
Stage Mode Delay
Next ItemEnter Program Menu
Tar get DHW
Tar get DHW
Tar get DHW
Change Value
The Program menu items are the programmable settings used to operate the system. Press and hold all three
ItemItem
buttons simultaneously to enter the Program menu.
70 to 190°F
(21 to 88°C)
Default = 140°F
DifferentialDHW
(60°C)
AU, 1 to 42°F
(Au, 1 to 23°C)
DifferentialDHW
Default = Au
1 to 42°F
(1 to 23°C)
Default = 2°F
DifferentialDHW
(1°C)
TARGET DHW
The DHW tank target temperature.
DIFFERENTIAL
The differential the control will use when operating the boilers in PID mode.
(Stage Mode is set to PID)
DIFFERENTIAL 1
The differential the control will use for the turn on point of the Heat 1 relay (all below target DHW).
(Stage Mode is set to P)
Stage Mode Delay
Tar get DHW
DifferentialDHW
PROGRAM MENU
Stage Mode Delay
Stage Mode Delay
Stage Mode Delay
Tar get DHW
Tar get DHW
Tar get DHW
DifferentialDHW
DifferentialDHW
DifferentialDHW
1 to 42°F
(1 to 23°C)
Default = 2°F
(1°C)
0:00 to 19:50
minutes
Default = 00:30
PID, P
Default = PID
°F, °C
Default = °F
DIFFERENTIAL 2
The differential the control will use for the turn on point of the Heat 2 relay (all below Differential 1).
(Stage Mode is set to P)
DELAY
The minimum time delay between the operation of stages.
(Stage Mode is set to P)
STAGE MODE
Selects the mode of operation for staging.
UNITS
The units of measure that all of the temperatures are to be displayed in the control.
After the last item, the control returns to the first item in the menu.
© 2009 D 257 - 03/09 10 of 12
Page 11
Field Test
To test the control, push and hold the up button for 3 seconds while in the default menu. While in Field Test “tSt” is displayed.
Step 1: Heat 1 relay will close and Heat 2 relay will open
for 10 seconds
Step 2:
If rotate switch is off, both Heat 1 and Heat 2 relays will close for 10 seconds. If rotate switch is on, Heat 1 relay will open and Heat 2 relay will close for 10 seconds.
Step 3:
The test routine ends and the control resumes normal
operation.
Error Messages
EEPROM READ ERROR
The control was unable to read a piece of information stored in it’s memory. Because of this, the control was required to reload factory settings for all items in the PRGM menu. The control will stop operation until all of the items in the PRGM menu have
Stage Mode Delay
Tar get DHW
DifferentialDHW
been checked.
Stage Mode Delay
Item
Tar get DHW
DifferentialDHW
Stage Mode Delay
Tar get DHW
DHW SENSOR ERROR
The control is no longer able to read the DHW Sensor due to an open or short circuit. Locate and repair the problem as described in the Data Brochure D 070. The outputs
DifferentialDHW
will not operate until the error is cleared.
11 of 12 © 2009 D 257 - 03/09
Page 12
Technical Data
DHW Control 257 Two Stag e
Literature — D 257, A 257, D 001, D 070 Control — Microprocessor control; This is not a safety (limit) control Packaged weight — 0.78 lb. (355 g) — Enclosure C, White PVC Plastic Dimensions — 4-3/4” H x 2-7/8” W x 7/8” D (120 x 74 x 22 mm)
o
Approvals — CSA C US, CSA 22.2 N ICES & FCC Part 15 Ambient conditions — Indoor use only, 32 to 122°F (0 to 50°C),
< 90% RH non-condensing Power supply — 24 V (ac) ±10%, 50/60 Hz, 3 VA Relay — 240 V (ac) 10 A 1/3 hp Sensors — NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892 included: — 1 of Universal Sensor 82 optional: — tekmar type # 078
24 and UL 873, meets class B:
Limited Warranty and Product Return Procedure
Meets Class B: Canadian ICES FCC Part 15
Made in Canada tektra 906-11
Stage Mode Delay
Item
DHW Control 257
Two Stag e
Rotate
1234
On
Power Heat 1
CR
Off
Power: 24 V ±10% 50/60 Hz 3 VA Relays: 240 V (ac) 10 A 1/3 hp
Targ et D HW
Signal wiring
56
must be rated
Heat 2
at least 300V
DifferentialDHW
No Power
7
Com Sen
DHW
H3014B
Date Code
8
Sen
Limited Warranty The liability of tekmar under this warranty is lim­ited. The Purchaser, by taking receipt of any tekmar product (“Prod­uct”), acknowledges the terms of the Limited Warranty in effect at the time of such Product sale and acknowledges that it has read and understands same.
The tekmar Limited Warranty to the Purchaser on the Products sold hereunder is a manufacturer’s pass-through warranty which the Purchaser is authorized to pass through to its customers. Under the Limited Warranty, each tekmar Product is warranted against defects in workmanship and materials if the Product is installed and used in compliance with tekmar’s instructions, ordinary wear and tear excepted. The pass-through warranty period is for a period of twenty-four (24) months from the production date if the Product is not installed during that period, or twelve (12) months from the docu­mented date of installation if installed within twenty-four (24) months from the production date.
The liability of tekmar under the Limited Warranty shall be limited to, at tekmar’s sole discretion: the cost of parts and labor provided by tekmar to repair defects in materials and/or workmanship of the defective prod­uct; or to the exchange of the defective product for a warranty replace­ment product; or to the granting of credit limited to the original cost of the defective product, and such repair, exchange or credit shall be the sole remedy available from tekmar, and, without limiting the foregoing in any way, tekmar is not responsible, in contract, tort or strict product liabil­ity, for any other losses, costs, expenses, inconveniences, or damages, whether direct, indirect, special, secondary, incidental or consequential, arising from ownership or use of the product, or from defects in work­manship or materials, including any liability for fundamental breach of contract.
The pass-through Limited Warranty applies only to those defective Prod­ucts returned to tekmar during the warranty period. This Limited War­ranty does not cover the cost of the parts or labor to remove or transport the defective Product, or to reinstall the repaired or replacement Product, all such costs and expenses being subject to Purchaser’s agreement and warranty with its customers.
Any representations or warranties about the Products made by Purchaser to its customers which are different from or in excess of the tekmar Lim­ited Warranty are the Purchaser’s sole responsibility and obligation. Pur­chaser shall indemnify and hold tekmar harmless from and against any and all claims, liabilities and damages of any kind or nature which arise out of or are related to any such representations or warranties by Pur­chaser to its customers.
The pass-through Limited Warranty does not apply if the returned Prod­uct has been damaged by negligence by persons other than tekmar, accident, fire, Act of God, abuse or misuse; or has been damaged by modifications, alterations or attachments made subsequent to purchase which have not been authorized by tekmar; or if the Product was not installed in compliance with tekmar’s instructions and/or the local codes and ordinances; or if due to defective installation of the Product; or if the Product was not used in compliance with tekmar’s instructions.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO CONTRACTUALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, DURABILITY OR DESCRIPTION OF THE PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VIOLA­TION OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY LEGISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT EX TEND BEYOND TWENT Y-FO UR (24) MON THS FR OM THE PRODUC­TION DATE , TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY THE GOVERNING LAW.
Product Warranty Return Procedure All Products that are believed to have defects in workmanship or materials must be returned, together with a written description of the defect, to the tekmar Representative assigned to the territory in which such Product is located. If tekmar receives an inquiry from someone other than a tekmar Representative, including an inquiry from Purchaser (if not a tekmar Representative) or Purchaser’s customers, regarding a potential warranty claim, tekmar’s sole obligation shall be to provide the address and other contact informa­tion regarding the appropriate Representative.
tekmar Control Systems Ltd., Canada tekmar Control Systems, Inc., U.S.A.
Head Office: 5100 Silver Star Road Vernon, B.C. Canada V1B 3K4 (250) 545-7749 Fax. (250) 545-0650 Web Site: www.tekmarcontrols.com
Product design, software and literature are Copyright © 2009 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc.
12 of 12
All specifications are subject to change without notice.
Printed in Canada. D 257 - 03/09.
Loading...