The DHW Control 257 is used for dedicated domestic hot water systems. The control operates two on/off boilers, or one
two-stage boiler to maintain the DHW Target temperature at the DHW Sensor. The control can operate in Proportional (P)
mode, or Proportional, Integral, Derivative (PID) mode.
Additional functions include:
Boiler rotation
•
Cumulative boiler run time hours
•
P or PID staging modes of operation
•
CSA and UL certified for use in the USA and Canada
•
Input
24 V (ac)
Power Supply
Meets Class B:
Canadian ICES
FCC Part 15
Made in Canada
tektra 906-11
Stage ModeDelay
Item
DHW Control 257
Two Sta ge
Rotate
1234
On
PowerHeat 1
CR
Off
Power: 24 V ±10% 50/60 Hz 3 VA
Relays: 240 V (ac) 10 A 1/3 hp
The Control Settings section of this brochure describes
the various items that are adjusted and displayed by the
control. The control functions of each adjustable item are
described in the Sequence of Operation.
Testing the Wiring .................................................... 6
Electrical Connections to the Control ....................... 7
Control Settings ............................................................ 8
The 257 uses a Liquid Crystal Display (LCD) to display
information. Use the LCD to set up and monitor the
operation of the system. The 257 has three push buttons
(Item, ▲, ▼) for selecting, viewing, and adjusting settings.
As you program the control, record the settings in the
ADJUST menu table which is found in the second half of
this brochure.
Item
The selected item will be displayed using a pointer in the
display. To view the next available item, press the Item
button. Once you have reached the last available item,
pressing the Item button again will return the display to
the first item.
Item
Adjust
To make an adjustment to a setting in the control, press and
hold simultaneously for 1 second all three (3) buttons. The
display will then show the word PRGM. Select the desired
item using the Item button. Finally, use the ▲ or ▼ button
to make the adjustment.
When the DHW Control 257 is powered up all LCD segments
are displayed for 2 seconds followed by the version number
being displayed for 2 seconds. The control then enters
Staging Operation
Proportional Staging Mode (P)
When the Stage Mode is set to P, the on/off points of the
HEAT 1 and HEAT 2 relays are determined by the Target
DHW setpoint, the Differential 1 and the Differential 2
settings. This is a manual way of staging the boilers. See
figure 1 for a visual representation.
Target
DHW
Increasing
Temperature
Increasing Time
OFF
Stage 1
Stage 1
Stage 1 & 2
into the normal operating mode and the LCD defaults to
displaying the current DHW temperature.
Differential 1 & Differential 2 (P Mode)
Manually adjust Differential 1 and 2 to set the on points
of stage 1 and 2. Stage 1 will fire when the temperature
falls below Target DHW minus Differential 1. Stage 2 will
fire when the temperature falls below Target DHW minus
differential 1 minus differential 2.
To provide proper boiler staging and accurate DHW
Target temperatures, PID mode should be used. When
the Stage Mode is set to PID, the on and off points of
the HEAT 1 and HEAT 2 relays are determined by PID
logic and the differential setting.
What is PID?
Proportional Error - How far is the temperature from theTarget?
•
Integral Error - How long has the temperature been there?
•
Derivative Error - How fast it is the temperature changing?
•
By considering these three errors, the control can better
decide when to turn on a boiler stage. This function provides
greater boiler plant efficiency and also prevents water
temperature drop that is commonly seen on proportional
staged systems.
Figure 1 - Staging operation for proportional logic
Differential (PID Mode)
If Differential is set to Auto, the control will calculate an
appropriate differential to reduce boiler short cycling.
If a boiler short cycles, the differential is automatically
increased. If auto differential is not desirable, the installer
may select a manual differential.
Minimum On and Off Times
The minimum on and off time for each boiler is 30
seconds.
DHW Maximum
If the DHW temperature rises 2°F above the Target DHW
setpoint due to minimum boiler on times, the control will
open both the Heat 1 and Heat 2 relays.
This function rotates the firing sequence of the two boilers
based on the accumulated running hours of each stage. The
HEAT 1 and HEAT 2 items in the default menu display the
accumulated running hours of each stage. When one stage
has accumulated 48 hours more running hours than the
other stage, the operating sequence is rotated. The stage
with less running hours is rotated in the firing sequence to
turn on first, while the stage with more running hours will
turn on last. This function increases the quality and reliability
of the boiler plant by ensuring equal running times of both
boilers. When this item is set to off, HEAT 1 is always the
first stage to fire.
Forced Rotation:
If the difference in run times reaches 60 hours, then boiler
rotation takes place immediately. This could occur if the
DHW tank has a constant load causing one boiler to fire
for an extended period of time.
Relay Run Times
The control logs the number of run time hours for the HEAT
1 and HEAT 2 relay in the default menu. To reset back to
zero hours, press and hold the up and down buttons for
3 seconds.
12
500 Hours452 Hours
Reset Rotation:
To reset the rotation sequence back to 1-2, clear both run
time hours in the default menu by pressing and holding the
up and down buttons. Next, switch the rotation dip switch
to the off position and then back to the on position. Both
stages now have 0 hours accumulated run time and the
firing sequence is 1-2.
Delay
When P Staging Mode is selected, you are then able to
adjust the minimum stage delay between when stage
1 and stage 2 fires. This item is default at 30 seconds
and is adjustable between 0 seconds and 19 minutes 50
seconds.
When PID Staging Mode is selected, PID logic is able
to determine when to bring on stage 1 and stage 2.
The minimum stage delay now becomes the default 30
seconds.
Selecting a Delay Time:
For low mass boilers, select a shorter delay time.
•
For high mass boilers, select a longer delay time.
Improper installation and operation of this control could
result in damage to the equipment and possibly even
personal injury. It is your responsibility to ensure that this
control is safely installed according to all applicable codes
and standards. This electronic control is not intended
for use as a primary limit control. Other controls that are
intended and certified as safety limits must be placed into
the control circuit.
Step One — Getting Ready
Check the contents of this package. If any of the contents
listed are missing or damaged, please contact your
wholesaler or tekmar sales representative for assistance.
Type 257 includes: One DHW Control 257, One Universal
Sensor 082 Data Brochures D 257, D 070, D 001, Application
Brochure A 257.
Note: Carefully read the details of the Sequence of
Operation to ensure that you have chosen the proper
control for your application.
Step Two — Mounting
The control is mounted in accordance with the instructions in the Data Brochure D 001.
Step Three — Rough-in Wiring
The wiring terminates in the two wiring chambers on the
control. Determine whether the low voltage wiring enters
the wiring chamber through the back or the bottom of the
control. The wiring is roughed-in prior to installation of the
control (see Brochure D 001). Standard 18 AWG solid wire
is recommended for all low voltage wiring, and multi-strand
16 AWG wire is recommended for 120 V (ac) wiring.
Step Four — Testing the Wiring
The following tests are to be performed using standard
testing practices and procedures, and should only be
carried out by properly trained and experienced persons.
A good quality electrical test meter, capable of reading from
at least 0 - 300 V (ac) and at least 0 - 2,000,000 Ohms, is
essential to properly test the wiring and sensors.
Test the Sensors
In order to test the sensors, the actual temperature at
each sensor location must be measured. A good quality
digital thermometer with a surface temperature probe is
recommended for ease of use and accuracy. Where a
digital thermometer is not available, a spare sensor can be
strapped alongside the one to be tested, and the readings
compared. Test the sensors according to the instructions
in the Data Brochure D 070.
Power must not be applied to any of the wires during
the rough-in wiring stage.
Install the DHW Sensor 082 according to the instructions
•
in the Data Brochure D 070, and run the wiring back to
the control.
Run wires from the 24 V (ac) power to the control. Use a
Make sure exposed wires and bare terminals are not in
contact with other wires or grounded surfaces.
If a 24 V (ac) transformer is used, make sure the voltmeter
is set to AC. Turn on the power and measure the voltage
across the 24 V (ac) power supply. The reading should be
between 22 and 26 V (ac).
LN
Class 2
Transformer
RC
Test the Outputs
Heat 1 and Heat 2
Make sure power is off to the boiler circuits and connect
the TT contacts on the boilers to the Heat 1 and Heat 2
contacts on the control. Install jumpers at the Heat 1 and
Heat 2 terminals to externally close the switch. When
the boiler circuits are powered up, the boilers should fire.
If the boilers do not turn on, refer to any installation or
troubleshooting information supplied with the boilers (the
boilers may have a flow switch that prevents firing until the
boiler pumps are running). If the boilers operate properly,
disconnect the power and remove the jumpers.
34
Heat 1
Jumper wire
between
terminals
DHW
Control 257
T-T contacts
on boiler
Step Five — Electrical Connections to the Control
The installer should test to confirm that no voltage is present
at any of the wires.
Powered Input Connections
24 V (ac) Power
Connect the 24 V (ac) power supply to the Power C and
Power R terminals (1 and 2). This connection provides
power to the microprocessor and display of the control.
LN
12
Power
RC
Output Connections
Heat 1 and Heat 2 Contacts
The Heat 1 and Heat 2 contacts are an isolated output in the
257. There is no power available on these terminals from the
control. These terminals are to be used as a switch to either
make or break the boiler TT circuit. When the 257 requires
boiler 1 to run, it closes the contact between terminals 3
and 4, and when the 257 requires boiler 2 to run, it closes
the contact between terminals 5 and 6.
CR
3456
Heat 1Heat 2
Sensors
Do not apply power to these terminals as this will
damage the control.
DHW Sensor
Connect the two wires from the DHW Sensor 082 to the
Com and DHW terminals (7 and 8). The DHW Sensor is
used by the 257 to measure the DHW tank temperature.
No Power
78
Com
DHW
Sen Sen
Locate the sensor in a well in the tank. The 082 sensor is
3/8” OD and will insert into a standard 1/2” well.
The Off | On – Rotate DIP switch is used to turn boiler
rotation on or off. When using a single boiler with two
stages, the DIP switch should be in the off (down) position.
When using two single-stage boilers, the DIP switch should
be in the on (up) position.
To test the control, push and hold the up button for 3
seconds while in the default menu. While in Field Test
“tSt” is displayed.
Step 1: Heat 1 relay will close and Heat 2 relay will open
for 10 seconds
Step 2:
If rotate switch is off, both Heat 1 and Heat 2 relays
will close for 10 seconds. If rotate switch is on, Heat
1 relay will open and Heat 2 relay will close for 10
seconds.
Step 3:
The test routine ends and the control resumes normal
operation.
Error Messages
EEPROM READ ERROR
The control was unable to read a piece of information stored in it’s memory. Because
of this, the control was required to reload factory settings for all items in the PRGM
menu. The control will stop operation until all of the items in the PRGM menu have
Stage ModeDelay
Tar get DHW
DifferentialDHW
been checked.
Stage ModeDelay
Item
Tar get DHW
DifferentialDHW
Stage ModeDelay
Tar get DHW
DHW SENSOR ERROR
The control is no longer able to read the DHW Sensor due to an open or short circuit.
Locate and repair the problem as described in the Data Brochure D 070. The outputs
Literature — D 257, A 257, D 001, D 070
Control — Microprocessor control; This is not a safety (limit) control
Packaged weight — 0.78 lb. (355 g)
— Enclosure C, White PVC Plastic
Dimensions — 4-3/4” H x 2-7/8” W x 7/8” D (120 x 74 x 22 mm)
o
Approvals — CSA C US, CSA 22.2 N
ICES & FCC Part 15
Ambient conditions — Indoor use only, 32 to 122°F (0 to 50°C),
< 90% RH non-condensing
Power supply — 24 V (ac) ±10%, 50/60 Hz, 3 VA
Relay — 240 V (ac) 10 A 1/3 hp
Sensors — NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892
included: — 1 of Universal Sensor 82
optional: — tekmar type # 078
24 and UL 873, meets class B:
Limited Warranty and Product Return Procedure
Meets Class B:
Canadian ICES
FCC Part 15
Made in Canada
tektra 906-11
Stage Mode Delay
Item
DHW Control 257
Two Stag e
Rotate
1234
On
Power Heat 1
CR
Off
Power: 24 V ±10% 50/60 Hz 3 VA
Relays: 240 V (ac) 10 A 1/3 hp
Targ et D HW
Signal wiring
56
must be rated
Heat 2
at least 300V
DifferentialDHW
No Power
7
Com
Sen
DHW
H3014B
Date Code
8
Sen
Limited Warranty The liability of tekmar under this warranty is limited. The Purchaser, by taking receipt of any tekmar product (“Product”), acknowledges the terms of the Limited Warranty in effect at
the time of such Product sale and acknowledges that it has read
and understands same.
The tekmar Limited Warranty to the Purchaser on the Products sold
hereunder is a manufacturer’s pass-through warranty which the
Purchaser is authorized to pass through to its customers. Under
the Limited Warranty, each tekmar Product is warranted against
defects in workmanship and materials if the Product is installed and
used in compliance with tekmar’s instructions, ordinary wear and
tear excepted. The pass-through warranty period is for a period of
twenty-four (24) months from the production date if the Product is
not installed during that period, or twelve (12) months from the documented date of installation if installed within twenty-four (24) months
from the production date.
The liability of tekmar under the Limited Warranty shall be limited to, at
tekmar’s sole discretion: the cost of parts and labor provided by tekmar
to repair defects in materials and/or workmanship of the defective product; or to the exchange of the defective product for a warranty replacement product; or to the granting of credit limited to the original cost of the
defective product, and such repair, exchange or credit shall be the sole
remedy available from tekmar, and, without limiting the foregoing in any
way, tekmar is not responsible, in contract, tort or strict product liability, for any other losses, costs, expenses, inconveniences, or damages,
whether direct, indirect, special, secondary, incidental or consequential,
arising from ownership or use of the product, or from defects in workmanship or materials, including any liability for fundamental breach of
contract.
The pass-through Limited Warranty applies only to those defective Products returned to tekmar during the warranty period. This Limited Warranty does not cover the cost of the parts or labor to remove or transport
the defective Product, or to reinstall the repaired or replacement Product,
all such costs and expenses being subject to Purchaser’s agreement and
warranty with its customers.
Any representations or warranties about the Products made by Purchaser
to its customers which are different from or in excess of the tekmar Limited Warranty are the Purchaser’s sole responsibility and obligation. Purchaser shall indemnify and hold tekmar harmless from and against any
and all claims, liabilities and damages of any kind or nature which arise
out of or are related to any such representations or warranties by Purchaser to its customers.
The pass-through Limited Warranty does not apply if the returned Product has been damaged by negligence by persons other than tekmar,
accident, fire, Act of God, abuse or misuse; or has been damaged by
modifications, alterations or attachments made subsequent to purchase
which have not been authorized by tekmar; or if the Product was not
installed in compliance with tekmar’s instructions and/or the local codes
and ordinances; or if due to defective installation of the Product; or if the
Product was not used in compliance with tekmar’s instructions.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS
OR IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO
CONTRACTUALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION,
IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR
A PARTICULAR PURPOSE, DURABILITY OR DESCRIPTION OF THE
PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS
OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VIOLATION OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY
LEGISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY
CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT
EX TEND BEYOND TWENT Y-FO UR (24) MON THS FR OM THE PRODUCTION DATE , TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY
THE GOVERNING LAW.
Product Warranty Return Procedure All Products that are believed to
have defects in workmanship or materials must be returned, together
with a written description of the defect, to the tekmar Representative
assigned to the territory in which such Product is located. If tekmar
receives an inquiry from someone other than a tekmar Representative,
including an inquiry from Purchaser (if not a tekmar Representative) or
Purchaser’s customers, regarding a potential warranty claim, tekmar’s
sole obligation shall be to provide the address and other contact information regarding the appropriate Representative.
tekmar Control Systems Ltd., Canada
tekmar Control Systems, Inc., U.S.A.
Head Office: 5100 Silver Star Road
Vernon, B.C. Canada V1B 3K4
(250) 545-7749 Fax. (250) 545-0650
Web Site: www.tekmarcontrols.com