The Boiler Control 256 is designed to control a single stage heat source in order to provide outdoor reset. The control has a Liquid
Crystal Display (LCD) to view system status and operating information.
Additional functions include:
• Quick Setup for easy installation and programming of control
• User comfort adjustment to increase or decrease building space
temperature
• Advanced settings to fi ne-tune building requirements
Press & Release:
all 3 buttons, to adjust menu
Press & Hold:
Item, to view settings
, to test.
tektra 909-01
BOIL
• Test sequence to ensure proper boiler operation
• Setback input for energy savings
• CSA C US certifi ed (approved to applicable UL standards)
Power: 24 V ±10% 50/60 Hz
3 VA Class 2
Relay: 240 V (ac) 5 A 1/6 hp
Meets Class B:
Canadian ICES
FCC Part 15
H1190D
F
Input
Universal Sensor
Included
Input
Outdoor Sensor
Included
Terminal UnitBoiler Demand
Item
Boiler Control 256
One Stage Boiler
Do not apply power
1
Boil2Out3Com4UnO
Inst / Adv
Input
tekmar Timer
Optional
Sw
TIME
1
PRGM
AMPM
2
UNOCC
OVR
S
SMWTFT
OCC
Designed &
Assembled in
Canada
Signal wiring
must be rated
at least 300V
5
Boiler
67T8
Output
Boiler
Power
R+
Date Code
9
C-
Input
24 V (ac)
Power Supply
Input
Boiler Demand
Signal
Note:
Boiler demand must have
an electrical closure
between terminals 7
and 9 before the boiler
is able to fire.
This brochure is organized into four main sections. They are: 1) Sequence of Operation, 2) Installation, 3) Control Settings, and 4)
Troubleshooting. The Sequence of Operation section has three sub-sections. We recommend reading Section A: General Operation
of the Sequence of Operation, as this contains important information on the overall operation of the control. Then read the sub-sections that apply to your installation. For quick installation and setup of the control, refer to the Installation section, DIP Switch Setting
section, followed by the Quick Setup section.
The Control Settings section (starting at DIP Switch Setting) of this brochure, describes the various items that are adjusted and displayed
by the control. The control functions of each adjustable item are described in the Sequence of Operation.
Table of Contents
User Interface ..................................................... pg 2
Description of Display Elements ....................... pg 3
Sequence of Operation ...................................... pg 4
The 256 uses a Liquid Crystal Display (LCD) as the method of supplying information. You use the LCD in order to set up and monitor the
operation of your system. The 256 has three push buttons (Item, , ) for selecting, viewing, and adjusting settings. As you program
your control, record your settings in the ADJUST menu table which is found in the second half of this brochure.
Item
The abbreviated name of the selected item will be displayed in the item fi eld of the
display. To view the next available item, press and release the Item button. Once you
have reached the last available item, pressing and releasing the Item button will return
the display to the fi rst item.
Item
Adjust
To make an adjustment to a setting in the control, press and hold simultaneously for
1 second, all 3 buttons. The display will then show the word ADJUST in the top right
corner. Then select the desired item using the Item button. Finally, use the and / or
button to make the adjustment.
To exit the ADJUST menu, either select the ESC item and press the
leave the adjustment buttons alone for 20 seconds.
When the Item button is pressed and held in the VIEW menu, the display scrolls through all the control adjust items in both access
levels.
Additional information can be gained by observing the status fi eld and pointers of the LCD. The status fi eld will indicate which of the
control’s outputs are currently active. Most symbols in the status fi eld are only visible when the VIEW menu is selected.
Displays when the control is in occupied (Day)
mode.
Unoccupied Schedule
Displays when the control is in unoccupied
(Night) mode.
F, °C
°
°F, °C
Displays the unit of measure that all of the
temperatures are to be displayed in the control.
Pointer
Displays the control operation as indicated by
the text.
Page 4
Sequence of Operation
Section A
General Operation
Page 4
Section B
Boiler Reset
Page 5-8
Section A — General Operation
POWERING UP THE CONTROL
When the Boiler Control 256 is powered up, the control displays the
control type number in the LCD for 2 seconds. Next, the software version
is displayed for 2 seconds. Finally, the control enters into the normal
operating mode, and the LCD defaults to displaying the current outdoor
air temperature.
OPERATION
The 256 operates a single on / off heat source to control the supply
water temperature to a hydronic system. The supply water temperature
is based on the current outdoor air temperature and the Characterized Heating Curve settings.
Terminal Unit
Indoor Design
Decreasing Outdoor Temperature
Outdoor Design
Design Supply
Increasing Water Temperature
SETBACK (UNOCCUPIED)
To provide greater energy savings, the 256 has a setback capability. With setback, the supply
water temperature in the system is reduced when the building is unoccupied. By reducing
the supply water temperature, air temperature in the space may be reduced even when
thermostat(s) are not turned down. Any time the Com (3) and the UnO Sw (4) terminals
are shorted together, the control operates in the unoccupied (Night) mode. When in the
unoccupied (Night) mode, the UNOCC segment is displayed in the LCD. The 256 adjusts
the supply water temperature based on the UNOCC settings made in the control.
FACTORY DEFAULTS
The control comes preset with several factory defaults. These defaults are based on the terminal unit selection (see section B2). To
fi ne-tune building requirements, these defaults may be changed. If a factory default value for a terminal unit is changed, the terminal
unit number will fl ash when selected in the ADJUST menu.
To reload the factory defaults listed in section B2, power down the control and wait for 10 seconds. Power up the control while simultaneously
holding the Item and buttons. The terminal unit number should now be displayed constantly in the LCD rather than fl ashing.
A boiler demand is required in order for the 256 to provide heat to the heating system. A
boiler demand is generated by connecting terminal T(7) to terminal C-(9) through a switching
device. Once the switching device closes, the Boiler Demand pointer is displayed in the
LCD. The 256 calculates a BOIL TARGET supply temperature based on the outdoor air
temperature and settings.
BOILER OPERATION
When the 256 determines that boiler operation is required, the Boiler contact terminals (5 and 6) close. While the Boiler contact is
closed, the burner segment in the LCD is displayed.
24 V (ac)
Boiler demand switches
CHARACTERIZED HEATING CURVE
The 256 varies the supply water temperature based on the outdoor air temperature. The control takes into account the type of terminal
unit that the system is using. Since different types of terminal units transfer heat to a space using different proportions of radiation,
convection and conduction, the supply water temperature must be controlled differently. Once the control is told what type of terminal
unit is used, the control varies the supply water temperature according to the type of terminal unit. This improves the control of the
air temperature in the building.
BOILER TARGET TEMPERATURE (BOIL TARGET)
The BOIL TARGET temperature is determined from the Characterized Heating Curve settings and the outdoor air temperature. The
control displays the temperature that it is currently trying to maintain as the boiler supply temperature. If the control does not presently
have a requirement for heat, it does not show a boiler target temperature. Instead, “- - -” is displayed in the LCD. At no time does the
control operate the boiler above 248°F (120°C).
Section B2: Installer
OUTDOOR DESIGN (OUTDR DSGN)
The OUTDR DSGN is the outdoor air temperature that is the typical
coldest temperature of the year where the building is located. This
temperature is used when doing the heat loss calculations for the
building. If a cold outdoor design temperature is selected, the boiler
supply temperature rises gradually as the outdoor temperature drops.
If a warm outdoor design temperature is selected, the boiler supply
temperature rises rapidly as the outdoor temperature drops.
The ROOM is the desired room temperature for the boiler zones, and it
provides a parallel shift of the Characterized Heating Curve. The room
temperature desired by the occupants is often different from the design
indoor temperature (BOIL INDR). If the room temperature is not correct,
adjusting the ROOM setting increases or decreases the amount of
heat available to the building. A ROOM setting is available for both the
occupied (Day) and unoccupied (Night) modes.
TERMINAL UNITS
When using a Characterized Heating Curve, the control requires the selection of a terminal unit. The terminal unit determines the shape
of the Characterized Heating Curve according to how the terminal unit delivers heat into the building space (refer to Essay E 003). The
256 provides for selection between six different terminal unit types: two types of radiant fl oor heat, fancoil, fi n-tube convector, radiator
and baseboard. When a terminal unit is selected, the control automatically loads the design supply temperature (BOIL DSGN) and
minimum supply temperature (BOIL MIN). The factory defaults are listed below. To change defaults, refer to section B3. If a default
has been changed, refer to section A to reload the factory defaults.
This type of a hydronic radiant fl oor is embedded in either a thick concrete or gypsum
pour. This heating system has a large thermal mass and is slow acting.
Default values: BOIL DSGN = 120°F (49°C), BOIL MIN = OFF
Low Mass Radiant (2)
This type of radiant heating system is either attached to the bottom of a wood sub-fl oor,
suspended in the joist space, or sandwiched between the sub-fl oor and the surface.
This type of radiant system has a relatively low thermal mass and responds faster than
a high mass system.
Default values: BOIL DSGN = 140°F (60°C), BOIL MIN = OFF
High Mass Radiant
(1)
Low Mass Radiant
(2)
Fancoil
(3)
Fin-tube Convector
(4)
Radiator
(5)
Baseboard
(6)
Fancoil (3)
A fancoil terminal unit or air handling unit (AHU) consists of a hydronic heating coil and
either a fan or blower. Air is forced across the coil at a constant velocity by the fan or
blower, and is then delivered into the building space.
Default values: BOIL DSGN = 190°F (88°C), BOIL MIN = 140°F (60°C)
Fin–tube Convector (4)
A convector terminal unit is made up of a heating element with fi ns on it. This type of
terminal unit relies on the natural convection of air across the heating element to deliver
heated air into the space. The amount of natural convection to the space is dependant
on the supply water temperature to the heating element and the room air temperature.
Default values: BOIL DSGN = 180°F (82°C), BOIL MIN = 140°F (60°C)
A radiator terminal unit has a large heated surface that is exposed to the room. A radiator
provides heat to the room through radiant heat transfer and natural convection.
Default values: BOIL DSGN = 160°F (71°C), BOIL MIN = 140°F (60°C)
Baseboard (6)
A baseboard terminal unit is similar to a radiator, but has a low profi le and is installed at
the base of the wall. The proportion of heat transferred by radiation from a baseboard
is greater than that from a fi n-tube convector.
Default values: BOIL DSGN = 150°F (66°C), BOIL MIN = 140°F (60°C)
Section B3: Advanced
BOILER INDOOR (BOIL INDR)
The BOIL INDR is the room temperature used in the original heat loss calculations for the building. This setting establishes the beginning
of the Characterized Heating Curve for the boiler zones.
BOILER DESIGN (BOIL DSGN)
The BOIL DSGN temperature is the supply water temperature required to heat the boiler zones when the outdoor air temperature is
as cold as the OUTDR DSGN setting.
BOILER MAXIMUM
The boiler maximum is the highest water temperature that the control
is allowed to calculate as the BOIL TARGET temperature. The boiler
maximum is the BOIL DSGN plus 10°F (5°C), but limited to 225°F
(107°C). If the control does target the boiler maximum, and the BOIL
temperature is near the boiler maximum temperature, the MAX segment
will be displayed in the LCD while either the BOIL TARGET temperature
or the BOIL temperature is being viewed. At no time does the control
operate the boiler above 248°F (120°C).
BOILER MINIMUM (BOIL MIN)
The BOIL MIN is the lowest water temperature that the control is allowed
to use as the BOIL TARGET temperature. During mild conditions, if the
256 calculates a BOIL TARGET temperature that is below the BOIL MIN
setting, the BOIL TARGET temperature is adjusted to at least the BOIL
MIN setting. During this condition, if the boiler is operating, the MIN segment turns on in the LCD while the BOIL TARGET or BOIL temperature
is being viewed. If the installed boiler is designed for low temperature
operation, set the BOIL MIN adjustment to OFF.
An on / off heat source such as a boiler, must be operated with a differential in order to prevent short cycling. With the 256, either a
fi xed or an auto differential may be selected.
Differential = 10°F (5°C)
Fixed Differential
The boiler differential is divided around the BOIL TARGET temperature.
The contact will close when the supply water temperature is 1/2 of the
differential setting below the BOIL TARGET temperature, and will open
when the supply water temperature is 1/2 of the differential setting
above the BOIL TARGET temperature.
Auto Differential (Ad)
165°F(74° C)
160°F (71° C)
155°F (68° C)
Supply Water Temperature
B
o
i
l
e
n
o
r
e
l
i
o
B
Off
r
o
f
f
Time
n
o
r
le
i
o
B
B
o
i
l
e
r
o
f
f
If the Auto Differential is selected, the 256 automatically determines
the best differential as the load changes. This setting is recommended
as it reduces potential short cycling during light loads.
WARM WEATHER SHUT DOWN (WWSD) OCC & UNOCC
Differential
Time
On
Heating Load
When the outdoor air temperature rises above the WWSD setting, the 256 turns on the WWSD segment in the display. When the
control is in Warm Weather Shut Down, the Boiler Demand pointer is displayed, if there is a demand. However, the control does not
operate the heating system to satisfy this demand.
Installation
CAUTION
Improper installation and operation of this control could result in damage to the equipment and possibly even personal injury. It
is your responsibility to ensure that this control is safely installed according to all applicable codes and standards. This electronic
control is not intended for use as a primary limit control. Other controls that are intended and certifi ed as safety limits must be
placed into the control circuit.
STEP ONE
GETTING READY
Check the contents of this package. If any of the contents listed are missing or damaged, please contact your wholesaler or tekmar
sales representative for assistance.
Type 256 includes: One Boiler Control 256, One Outdoor Sensor 070, One Universal Sensor 071, Installation & Operation
Manual D 256, Application Brochure A 256.
Note: Carefully read the details of the Sequence of Operation to ensure that you have chosen the proper control for your application.
Enclosure C is designed for smaller controls and their wiring. This enclosure
has either a large or a small window opening depending on the control used.
Mounting the C Enclosure
Grasp the front cover by the fi ngertip grips on the top and bottom of the enclosure
and pull the front cover off. Remove the wiring cover screw. The enclosure is
either mounted fl ush onto a wall or it can be placed onto a 2” x 4” electrical box.
The mounting holes in the enclosure accept #6 screws. Wiring to the control
enters the wiring chamber through the back or bottom of the enclosure. To
reassemble the enclosure, fi rst replace the wiring chamber cover and then push
the front cover onto the enclosure until it snaps into place.
Caution:
of electromagnetic interference, shielded cable or twisted pair should be used or the wires can be run in a grounded metal conduit. If
using shielded cable, the shield wire should be connected to the Sensor Common terminal on the control and not to earth ground.
All electrical wiring terminates in the two wiring chambers on the control. If the control is to be mounted on an electrical box, the wiring
can be roughed-in at the electrical box prior to installation of the control.
Power must not be applied to any of the wires during the rough-in wiring stage.
Install the Outdoor Sensor and Universal Sensor according to the directions on the following page.
Do not run sensor wires parallel to telephone or power cables. If the sensor wires are located in an area with strong sources
SENSOR INSTALLATION
Page 10
Mounting the Outdoor Sensor
Note: The temperature sensor (thermistor) is built into the
enclosure.
Remove the screw and pull the front cover off the sensor
enclosure.
The sensor can either be mounted directly onto a wall or a
2” x 4” electrical box. When wall mounted, the wiring should
enter through the back or bottom of the enclosure. Do not
mount the sensor with the conduit knockout facing upwards
as rain could enter the enclosure and damage the sensor.
In order to prevent heat transmitted through the wall from
affecting the sensor reading, it may be necessary to install
an insulating barrier behind the enclosure.
The Outdoor Sensor should be mounted on a wall which
best represents the heat load on the building (a northern wall
for most buildings and a southern facing wall for buildings
with large south facing glass areas). The sensor should not
be exposed to heat sources such as ventilation or window
openings.
The sensor should be installed at an elevation above the
ground that will prevent accidental damage or tampering.
Sensor with rear
entry wiring
Wiring the Outdoor Sensor
Connect 18 AWG or similar wire to the two terminals provided in
the enclosure and run the wires from the sensor to the control.
Do not run the wires parallel to telephone or power cables. If
the sensor wires are located in an area with strong sources of
electromagnetic interference (EMI), shielded cable or twisted
pair should be used or the wires can be run in a grounded
metal conduit. If using shielded cable, the shield wire should
be connected to the Com or Com Sen terminal on the control
and not to earth ground.
Follow the sensor testing instructions in this brochure and
connect the wires to the control.
Note: This sensor is designed to mount on a pipe or in a temperature
immersion well.
The Universal Sensor should be placed downstream of a pump or
after an elbow or similar fi tting. This is especially important if large
diameter pipes are used as the thermal stratifi cation within the pipe
can result in erroneous sensor readings. Proper sensor location
requires that the fl uid is thoroughly mixed within the pipe before it
reaches the sensor.
Strapped to Pipe
The Universal Sensor can be strapped directly to the pipe using the
cable tie provided. Insulation should be placed around the sensor to
reduce the effect of air currents on the sensor measurement.
Immersion Well
If a Universal Sensor is mounted onto 1” (25 mm) diameter L
type copper pipe, there is approximately an 8 second delay
between a sudden change in water temperature and the time the
sensor measures the temperature change. This delay increases
considerably when mild steel (black iron) pipe is used. In general,
it is recommended that a temperature well be used for steel pipe
of diameter greater than 1-1/4” (32 mm). Temperature wells are
also recommended when large diameter pipes are used and fl uid
stratifi cation is present.
Retaining Clip
Universal
Sensor
Conduit Connection
The Universal Sensor and Universal Sensor Enclosure 080 (sold
separately) are specifi cally designed to mount onto a 3/8” (10 mm)
ID temperature well that is supplied with an end groove. To install
the well, plumb a ‘T’ into the pipe and fi x the well into the ‘T’. The 080
enclosure has a 7/8” (22 mm) back knockout that must be removed
and fi tted over the temperature well. The sensor is then inserted
into the well and the retaining clip supplied with the enclosure is
snapped onto the well end groove. If the well has a threaded end,
the installer must supply a standard threaded conduit retaining ring.
The two wires from the sensor are connected to the terminal block
provided in the enclosure. The other side of the terminal block is
used to connect wires from the control.
No wires should be connected to the control during the testing.
The following tests are to be performed using standard testing practices and procedures, and should only be carried out by properly
trained and experienced persons.
A good quality electrical test meter, capable of reading from at least 0 - 300 V (ac) and at least 0 - 2,000,000 Ohms, is essential to
properly test the wiring and sensors.
TESTING THE WIRING
Test The Sensors
Ensure the sensor wires are not connected to the control terminals before testing. In order
to test the sensors, the actual temperature at each sensor location must be measured. A
good quality digital thermometer with a surface temperature probe is recommended for
ease of use and accuracy. Where a digital thermometer is not available, a spare sensor
can be strapped alongside the one to be tested, and the readings compared. Test the
sensors according to the following section.
Ω
Ω
Ω
V
Test The Sensor Wiring
A good quality test meter capable of measuring up to 5,000 kΩ (1 kΩ = 1000 Ω) is required to measure the sensor resistance. In
addition to this, the actual temperature must be measured with either a good quality digital thermometer, or if a thermometer is not
available, a second sensor can be placed alongside the one to be tested and the readings compared.
First measure the temperature using the thermometer and then measure the resistance of the sensor at the control. The wires
from the sensor must not be connected to the control while the test is performed. Using the chart below, estimate the temperature
measured by the sensor. The sensor and thermometer readings should be close. If the test meter reads a very high resistance,
there may be a broken wire, a poor wiring connection or a defective sensor. If the resistance is very low, the wiring may be shorted,
there may be moisture in the sensor or the sensor may be defective. To test for a defective sensor, measure the resistance directly
at the sensor location.
Do not apply voltage to a sensor at any time as damage to the sensor may result.
Make sure exposed wires and bare terminals are not in contact with other wires or grounded
surfaces. Turn on the power and measure the voltage across the 24 V (ac) power supply
with an AC voltmeter. The reading should be between 22 and 26 V (ac).
V
Class 2
Transformer
24 V (ac)
V
Ω
C
R
Test The Powered Inputs
Boiler Demand
V
Measure the voltage between the boiler demand wire and the power wire that goes
Ω
to R+ of the control. The voltmeter should read between 21 and 27 V (ac) when the
V
boiler demand device calls for heat.
Boiler demand
switch
Class 2
Test The Outputs
Transformer
24 V (ac)
C
R
Boiler
Make sure power to the boiler circuit is off and short the boiler wires. When the boiler circuit is powered up, the boiler should
fi re. If the boiler does not turn on, refer to any installation or troubleshooting information supplied with the boiler. (The boiler may
have a fl ow switch that prevents fi ring until the boiler loop pump is running). If the boiler operates properly, remove power from
the boiler circuit.
The installer should test to confi rm that no voltage is present at any of the wires.
Powered Input Connections
24 V (ac) Power
Connect the 24 V (ac) power supply to the Power R+ and Power C- terminals (8 and
9). This connection provides power to the microprocessor and display of the control.
Boiler Demand
To generate a boiler demand, terminal T(7) must be connected to terminal C-(9)
through a switching device.
9
8
Power
R+
C-
24 V (ac)
7
8
9
Power
T
C-
R+
Output Connections
Boiler Contact
The Boiler terminals (5 and 6) are an isolated output in the 256. There is no power
available on these terminals from the control. These terminals are to be used as a
switch to either make or break the boiler circuit. When the 256 requires the boiler to
fi re, it closes the contact between terminals 5 and 6.
Sensor and Unpowered Input Connections
Do not apply power to these terminals as this will damage the control.
Outdoor Sensor
Connect the two wires from the Outdoor Sensor to the Out and Com terminals (2 and
3). The outdoor sensor is used by the 256 to measure the outdoor air temperature.
Universal Sensor
Connect the two wires from the Universal Sensor to the Boil and Com terminals
(1 and 3). This sensor is used by the 256 to measure the supply (outlet) water
temperature from the boiler.
Boil
24 V (ac)
T
T
Boiler demand switches
T
T
Out
5
Boiler
2
6
3
Com
Boiler
3
1
2
Com
Out
sensor
Unoccupied Switch
If an external timer (tekmar Timer 033) or switch is used, connect the two wires from
the external switch to the Com and UnO Sw terminals (3 and 4). When these two
terminals are shorted together, the control registers an unoccupied signal.
The Advanced / Installer DIP switch is used to select which items are available to be viewed and / or adjusted
in the user interface.
Do not apply power
1234
Inst/Adv
Boi l
Out
Com
UnO
Sw
Quick Setup
To enter the Installer programming mode, set the Advanced / Installer DIP switch to Installer.
Access the ADJUST menu by pressing and holding simultaneously for 1 second, all 3 buttons. The display will now show the word
ADJUST in the top right corner.
ADJUST
°
ROOM
ROOM
OUTDR
F
The ROOM OCC adjustment is the fi rst item displayed. Use the or
OCC
The ROOM OCC setting is set to the desired room air temperature during the occupied (Day) mode.
Note: To increase or decrease space temperature during the occupied (Day) mode, only adjust the ROOM
OCC setting.
ADJUST
°
F
Press and release the Item button to advance to the ROOM UNOCC adjustment. Use the
set the desired temperature. The ROOM UNOCC setting is set to the desired room air temperature during
UN
OCC
the unoccupied (Night) mode.
Note: To increase or decrease space temperature during the unoccupied (Night) mode, only adjust the ROOM
ADJUSTDSGN
UNOCC setting. This is only used if a tekmar timer is installed.
°
F
Press and release the Item button to advance to the OUTDR DSGN adjustment. Use the
set the outdoor design temperature. The OUTDR DSGN setting is set to the typical coldest temperature of
the year.
button to set the ROOM temperature.
or
button to
or
button to
ADJUST
Press and release the Item button to advance to the Terminal Unit adjustment. Use the
or button to select
the desired terminal unit. The terminal unit number corresponds to the type of terminal that is being used to
heat the space. The table below lists the terminal units and their default values.
The Boiler Control 256 has a built-in test routine which is used to test the boiler function. The 256 continually monitors the sensors,
and displays an error message whenever a fault is found. See the following pages for a list of the 256’s error messages and possible
causes. When the button is pressed, the Boiler relay closes and the control displays the burner segment. Once the button is
released, the Boiler relay returns to normal operation.
Troubleshooting
When troubleshooting any heating system, it is always a good idea to establish a set routine to follow. By following a consistent
routine, many hours of potential headaches can be avoided. Below is an example of a sequence that can be used when diagnosing
or troubleshooting problems in a hydronic heating system.
Establish the problem. Get as much information from the customer as possible about the problem. Is there
Establish the
Problem
too much heat, not enough heat, or no heat? Is the problem only in one particular zone or area of the
building, or does the problem affect the entire system? Is this a consistent problem or only intermittent?
How long has the problem existed for? This information is critical in correctly diagnosing the problem.
Understand the
Sequence of
Operation
Sketch the
Piping in the
System
Document the
Control
Isolate the
Problem
Understand the sequence of operation of the system. If a particular zone is not receiving enough heat,
which pumps or valves in the system must operate in order to deliver heat to the affected zone? If the
zone is receiving too much heat, which pumps, valves or check valves must operate in order to stop the
delivery of heat?
Sketch the piping of the system. This is a relatively simple step that tends to be overlooked, however, it
can often save hours of time in troubleshooting a system. Note fl ow directions in the system, paying close
attention to the location of pumps, check valves, pressure bypass valves, and mixing valves. Ensure correct fl ow direction on all pumps. This is also a very useful step if additional assistance is required.
Document the control for future reference. Before making any adjustments to the control, note down all
of the items that the control is currently displaying. This includes items such as error messages, current
temperatures and settings, and which devices should be operating as indicated by the LCD. This information is an essential step if additional assistance is required to diagnose the problem.
Isolate the problem between the control and the system. Now that the sequence of operation is known
and the system is sketched, is the control operating the proper pumps and valves at the correct times?
Is the control receiving the correct signals from the system as to when it should be operating? Are the
proper items selected in the menus of the control for the device that is to be operated?
Test the contacts, voltages and sensors. Using a multimeter, ensure that the control is receiving adequate
voltage to the power terminals and the demand terminals as noted in the technical data. Use the multimeter
to determine if the internal contacts on the control are opening and closing correctly. Follow the instrutions
in the Testing the Wiring section to simulate closed contacts on the terminal blocks as required. Test the
sensors and their wiring as described in the Testing section.
Page 19
Error Messages
OUTDR
OUTDR
BOIL
BOIL
VIEW
VIEW
VIEW
VIEW
VIEW
The control was unable to read a piece of information from its EEPROM. This error can be caused by a
noisy power source. The control will load the factory defaults and stop operation until all the settings are
verifi ed.
The control is no longer able to read the outdoor sensor due to a short circuit. In this case, the control
assumes an outdoor temperature of 32°F (0°C) and continues operation. Locate and repair the problem
as described in the Testing section. To clear the error message from the control after the sensor has been
repaired, press the Item button.
The control is no longer able to read the outdoor sensor due to an open circuit. In this case the control
assumes an outdoor temperature of 32°F (0°C) and continues operation. Locate and repair the problem
as described in the Testing section. To clear the error message from the control after the sensor has been
repaired, press the Item button.
The control is no longer able to read the boiler sensor due to a short circuit. In this case, if the BOIL MIN
adjustment is set to OFF the control does not operate the Boiler contact. If the BOIL MIN adjustment is
not set to OFF and a boiler demand is present, the Boiler contact will operate for up to 10 minutes of a 20
minute cycle. Locate and repair the problem as described in the Testing section. To clear the error message
from the control after the sensor has been repaired, press the Item button.
The control is no longer able to read the boiler sensor due to an open circuit. In this case, if the BOIL MIN
adjustment is set to OFF, the control does not operate the Boiler contact. If the BOIL MIN adjustment is
not set to OFF, and a boiler demand is present, the Boiler contact will operate for up to 10 minutes of a 20
minute cycle. Locate and repair the problem as described in the Testing section. To clear the error message
from the control after the sensor has been repaired, press the Item button.
Sensor Technical Data
Outdoor Sensor 070
Literature — D 070
Packaged weight — 0.35 lb. (160 g)
Enclosure — Enclosure E, white PVC plastic
Dimensions — 4-1/2” H x 2-7/8” W x 1-1/2” D (73 x 114 x 38 mm)
Approvals — CSA C US, UL listed
Operating range — -60 to 140°F (-50 to 60°C)
Sensor —
Universal Sensor 071
Literature — D 071
Packaged weight — 0.08 lb. (35 g)
Enclosure — Brass sleeve, 12” (300 mm) 20 AWG XLPE wire
Dimensions — 3/8” OD x 3/4” (9.5 OD x 19 mm)
Approvals — CSA C US, UL listed
Operating range — -60 to 255°F (-50 to 125°C)
Sensor —
Power: 24 V ±10% 50/60 Hz
3 VA Class 2
Relay: 240 V (ac) 5 A 1/6 hp
Designed &
Assembled in
Canada
Signal wiring
must be rated
at least 300V
Meets Class B:
Canadian ICES
FCC Part 15
5
Boiler
F
67T8
H1190D
Date Code
9
Power
C-
R+
Boiler Control 256 One Stage Boiler
LiteratureD256, A256
ControlMicroprocessor control. This is not a safety (limit) control
Packaged weight1.3 lb. (580 g)
Dimensions4-3/4” H x 2-7/8” W x 7/8” D (120 x 74 x 22 mm)
EnclosureWhite PVC plastic, Nema Type 1
Approvals
Ambient conditionsIndoor use only, 32 to 104°F (0 to 40°C), RH ≤90% Non-condensing
Power supply24 V ±10%, 50/60 Hz, 3 VA, Class 2
Relay240 V (ac) 5 A 1/6 hp
Demand24 V (ac) 2 VA
SensorsNTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892
CSA C US, meets class B: ICES & FCC Part 15
Press & Release:
all 3 buttons, to adjust menu
Press & Hold:
Item, to view settings
, to test.
tektra 909-01
BOIL
Terminal UnitBoiler Demand
Item
Boiler Control 256
One Stage Boiler
Do not apply power
1
Boil2Out3Com4UnO
Inst / Adv
–IncludedOutdoor Sensor 070 and Universal Sensor 071
–Optionaltekmar type #: 033
WarrantyLimited 3 Year
The installer must ensure that this control and its wiring are isolated and/or shielded from strong sources of electromagnetic noise. Conversely,
this Class B digital apparatus complies with Part 15 of the FCC Rules and meets all requirements of the Canadian Interference-Causing Equipment Regulations. However, if this control does cause harmful interference to radio or television reception, which is determined by turning the
control off and on, the user is encouraged to try to correct the interference by reorienting or relocating the receiving antenna, relocating the
receiver with respect to this control, and/or connecting the control to a different circuit from that to which the receiver is connected.
Cet appareil numérique de la classe B respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Caution The nonmetallic enclosure does not provide grounding between conduit connections. Use grounding type bushings and jumper
wires.
Attention Un boîtier nonmétallique n’assure pas la continuité électrique des conduits. Utiliser des manchons ou des fi ls de accord spécialement
conçus pour la mise á la terre.
Limited Warranty and Product Return Procedure
Limited Warranty The liability of tekmar under this warranty is limited. The
Purchaser, by taking receipt of any tekmar product (“Product”), acknowledges the terms of the Limited Warranty in effect at the time of such Product sale and acknowledges that it has read and understands same.
The tekmar Limited Warranty to the Purchaser on the Products sold hereunder is a manufacturer’s pass-through warranty which the Purchaser is authorized to pass through to its customers. Under the Limited Warranty, each
tekmar Product is warranted against defects in workmanship and materials
if the Product is installed and used in compliance with tekmar’s instructions,
ordinary wear and tear excepted. The pass-through warranty period is for a
period of twenty-four (24) months from the production date if the Product is
not installed during that period, or twelve (12) months from the documented
date of installation if installed within twenty-four (24) months from the production date.
The liability of tekmar under the Limited Warranty shall be limited to, at tekmar’s
sole discretion: the cost of parts and labor provided by tekmar to repair defects
in materials and / or workmanship of the defective product; or to the exchange
of the defective product for a warranty replacement product; or to the granting
of credit limited to the original cost of the defective product, and such repair,
exchange or credit shall be the sole remedy available from tekmar, and, without
limiting the foregoing in any way, tekmar is not responsible, in contract, tort or
strict product liability, for any other losses, costs, expenses, inconveniences, or
damages, whether direct, indirect, special, secondary, incidental or consequential, arising from ownership or use of the product, or from defects in workmanship or materials, including any liability for fundamental breach of contract.
The pass-through Limited Warranty applies only to those defective Products
returned to tekmar during the warranty period. This Limited Warranty does not
cover the cost of the parts or labor to remove or transport the defective Product,
or to reinstall the repaired or replacement Product, all such costs and expenses
being subject to Purchaser’s agreement and warranty with its customers.
Any representations or warranties about the Products made by Purchaser to its
customers which are different from or in excess of the tekmar Limited Warranty
are the Purchaser’s sole responsibility and obligation. Purchaser shall indemnify
and hold tekmar harmless from and against any and all claims, liabilities and
damages of any kind or nature which arise out of or are related to any such
representations or warranties by Purchaser to its customers.
The pass-through Limited Warranty does not apply if the returned Product has
been damaged by negligence by persons other than tekmar, accident, fire, Act
of God, abuse or misuse; or has been damaged by modifications, alterations or
attachments made subsequent to purchase which have not been authorized by
tekmar; or if the Product was not installed in compliance with tekmar’s instructions and / or the local codes and ordinances; or if due to defective installation of
the Product; or if the Product was not used in compliance with tekmar’s instructions.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR
IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO CONTRACTUALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE,
DURABILITY OR DESCRIPTION OF THE PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VIOLATION OF ANY APPLICABLE ENVIRONMENTAL,
HEALTH OR SAFETY LEGISLATION; THE TERM OF ANY OTHER WARRANTY
NOT HEREBY CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT
SHALL NOT EXTEND BEYOND TWENTY-FOUR (24) MONTHS FROM THE
PRODUCTION DATE, TO THE EXTENT THAT SUCH LIMITATION IS AL LOWED
BY THE GOVERNING LAW.
Product Warranty Return Procedure All Products that are believed to have
defects in workmanship or materials must be returned, together with a written
description of the defect, to the tekmar Representative assigned to the territory
in which such Product is located. If tekmar receives an inquiry from someone
other than a tekmar Representative, including an inquiry from Purchaser (if not
a tekmar Representative) or Purchaser’s customers, regarding a potential warranty claim, tekmar’s sole obligation shall be to provide the address and other
contact information regarding the appropriate Representative.
tekmar Control Systems Ltd., Canada
tekmar Control Systems, Inc., U.S.A.
Head Office: 5100 Silver Star Road
Vernon, B.C. Canada V1B 3K4
(250) 545-7749 Fax. (250) 545-0650
Web Site: www.tekmarcontrols.com