3. Sensor mounting in gutters, on rooftops and on satellite
systems
4. Connection diagrams
5. Commissioning
6. Display and pushbutton functions
7. Operation, menu and error codes
8. Technical data, safety instructions
Ice and Snow Detector Type 1773
for the TF-E System
Introduction
In cooperation with the moisture and temperature sensors of the TF-E system, the 1773 Ice and Snow Detector
is used for early detection of ice and snow and for keeping the monitored surface or gutter free by switching on
a defrosting device. One or two sensors can be connected to the 1773 Ice and Snow Detector. The sensor
function (temperature and/or moisture monitoring) and other settings can be defined for each sensor
individually. The individual parameters and measured values can be diplayed and changed in the menu using
the display and three operating buttons. An LED shows the current operating state.
The sensor type 3354 (or its predecessor 3351) can be used for gutters, flat rooftops or satellite systems. Open
areas such as driveways or parking lots can be monitored with the sensor types 3355 and 3356 (predecessors
3352 and 3353), which resist mechanical load such as cars driving over them.
Most ice and snow detection systems use exposed metal electrodes. Their disadvantage is that these
electrodes can accumulate dirt, suffer from corrosion or get short circuited by external conductive objects.
Therefore their sensors need periodical maintenance work in order to avoid that environmental influences impair
the accuracy of moisture measurement.
The TF-E system takes advantage of the increase of thermal capacity due to moisture, i. e. the availability of
water in liquid or solid form (snow, ice) on the sensor. With the help of a patented measurement and evaluation
method, the temperature variation with regard to the sensor is used to detect moisture on the sensor surface.
This guarantees a maintenance-free and secure operation.
1. Functions
If the sensor temperature is below the defined critical temperature limit, the moisture control is activated. If
moisture is detected, the heating system is switched on. If not, the moisture is measured again periodically. At
the earliest when the defined minimum heating time has expired, the heating system is switched off again if
there is no more moisture on the sensor.
In addition to the limit value of the critical temperature range (0 to +5 °C) a lower value can be set between -5
and –20 °C. This is useful because in case of very low outdoor temperatures there will no longer be any dripping
melt water or snow. If snow falls despite the extreme temperature, it will be dry, light and not slippery. In such a
case the heating would not be powerful enough to completely melt the snow on the surface. Thus the danger of
slippery conditions would rather be increased if the heating were switched on.
- 1 -
Connecting the sensor inputs
In order to adapt to the desired monitoring functions, you can choose to wire the inputs in three different ways:
Operation with one sensor
The Type 33.. sensor is connected to sensor input 1 for temperature and moisture monitoring.
Operation with two sensors
Two sensors can be connected to the ice and snow detector: either two combi sensors for moisture/temperature
or one combi sensor and one temperature sensor. This type of operation is recommended in case of differences
in topography or areas with pronounced differences of sun and shadow.
The measured values are collected one by one. If one of the combi sensors indicates moisture, the heating of
the open area will be activated.
The relevant measurement functions of the sensors are set in the configuration menu "Sensor".
Slab idle temperature operation
A combi sensor and a temperature sensor are connected to the ice and snow detector. A Type 33.. sensor is
connected to sensor input 1 for temperature and moisture monitoring; a type 31.. temperature sensor is
connected to sensor input 2 in order to measure the outdoor temperature (also refer to "Slab idle temperature").
Moisture measurement
If the measured temperature falls below the set "high temperature limit", the sensor heating will heat up the
sensor surface and subsquently assess if the sensor is dry or moist. If the set moisture sensitivity is exceeded,
the heating is switched on for the set minimum heating time. After the minimum heating time has passed, there
will be another moisture measurement. If the sensor is still moist, the heating will remain switched on. If the
temperature measured in the sensor reaches the set "high temperature limit" during the second or further
measurements, the switch output will be switched off prematurely.
Note: Also for sensors which are only activated for moisture monitoring, the integrated temperature sensor must
be connected and operational because the sensor temperature is required for determining moisture. Therefore
there will also be an error message for these sensors if "only" the temperature measurement is impaired.
In order to avoid incorrect measurements, the supply voltage of the ice and snow detector is monitored before
and during moisture measurement. In case the value is outside the voltage area for which correct functioning is
guaranteed, there will be an error message (refer to chapter "Error codes").
The system automatically optimizes the duration of one measurement cycle depending on the type of sensor,
the supply voltage and the sensor temperature.
Ambient temperature of moisture sensors
Depending on the type of sensor, the ambient temperature cannot be measured during the moisture
measurement and for a certain time after the measurement. This is because the temperature of the integrated
temperature sensor is influenced by the moisture measurement. During this time the system works with the last
measured ambient temperature.
Slab temperature
If two sensors are used to measure the slab temperature, the relevant slab temperature is calculated according
to the following pattern (with a hysteresis of 0,5K each) :
- Both sensors above or below the range of the high to low temperature limit: The relevant slab
temperature is the average value of both measured values.
- Both sensors within the range of the high to low temperature limit: The relevant slab temperature is the
average value of both measured values.
- One sensor outside and one sensor within the range of the high to low temperature limit: The relevant
slab temperature is the value measured within this range.
- One sensor above and one sensor below the range of the high to low temperature limit: For the relevant
slab temperature an "-!-" is displayed as an indication that there is an installation or configuration problem
(slab heating is not activated).
In this way the moisture measurement is activated at the earliest possible point in time.
Slab idle temperature mode
In the operating mode "Slab idle temperature" a temperature and moisture sensor has to be connected to
sensor input 1 and a temperature sensor (Series 31..) has to be connected to sensor input 2 (terminals 6/7) in
order to measure the outdoor temperature. The sensor types need to be defined accordingly in the configuration
menu!
- 2 -
As soon as the outdoor temperature is below the high temperature limit (within the range of the "high and low
temperature limit"), the slab temperature measured by the sensor at input 1 is kept at the level of the setpoint
value (with an hysteresis of 1K). Additionally the moisture is measured regularly. If moisture is detected, the
heating will be switched on. If there is no moisture, the slab temperature will be kept at the setpoint value for as
long as the outdoor temperature is below the temperature limit.
Emergency operation (not in the "Slab idle temperature" mode)
If two sensors are connected (moisture and temperature), the controller will switch to emergency operation in
case one of the two temperature or moisture measurement circuits is impaired and the corresponding function is
activated for both sensors in the "Sensor status". In this case the evaluations will only be made with one
measurement circuit. The LED indicating the operating mode will flash red/green in order to indicate the error.
Moisture value and setting of the moisture limit
The sensors determine the moisture value as a number (without measurement unit). It lies in the range from 1 to
99. The moisture value is determined by the sensor type, the present moisture and the installation situation. By
all means the optimum moisture limit should therefore be determined during installation. In doing so, the user's
preferences need to be taken into account, i. e. if the slab heating should already be switched on in case of very
little moisture or only if a certain amount of moisture has developed. The factory default setting of 50 can be
used as an indicator. If the moisture limit is set to 50, all measured moisture values above 50 lead to the result
"moisture detected" and trigger the heating unit.
Counter for operating hours
The ice and snow detector has a counter for operating hours with two display levels. The first level "Time Mtr 1"
can be reset to zero. In this way it can be monitored for how many hours the heating was switched on since the
last reset (e. g. during one heating period). The second level shows the operating time of the heating unit since
the controller has been taken into use. This level cannot be reset.
Invertible alarm output
In case of an error there is a voltage of 24V between the terminals of alarm output A+ and A-. In this way the
alarm may, for example, be detected by a central control centre via the type 1798 coupling relay.
The state of the alarm output may be inverted using the menu, i. e. in the normal state (no error) the alarm
output is supplied with 24V or in case of an error 0V. Like this the control centre may detect a power failure of
the system.
PC interface
The controller has an interface for connection to a PC. The optional connection cable and software are available
as accessories and allow for a display of all settings and measured values. Please contact us for more
information.
2. Sensor mounting in open areas(sensor type 3352, 3353, 3355 or 3356)
The sensors designed for use in open areas used by vehicles and pedestrians are cast in a body in brass GMs63. The sensors have a fixed supply line. For type 3352 it is fed into the sensor body from the bottom and for
type 3353 from the side. For types 3355 und 3356 the supply line can be variably fed into the body.
The sensors type 3352, 3355 and 3356 may be installed in a ground socket. When the open area is built, this
ground socket is placed into the surface without the sensor in such a way that there will be an even surface after
installation of the sensor. Refer to the mounting example below for detailled information.
Especially in case of surfaces which need a high processing temperature, such as poured asphalt (> 75 °C), the
fitting of a ground socket should be well provided for. In order to avoid that the ground socket sinks into a soft
surface later (e. g. in a sand bed for stone paving), it is recommended to create a firm footing for the socket (e.
g. by putting a concrete slab underneath it).
Note: A protective tube needs to be used for the sensor supply line. This is beneficial both during a new
installation and in case of a necessary replacement. Depending on the weight and material of the surface either
a plastic pipe or an armoured steel tube DN20 can be used. Make sure that the openings of the empty conduit
and the ground socket are securely closed during the construction of the open area to keep out building
material.
- 3 -
When choosing the sensor's installation location, unfavourable circumstances such as aisles, shady areas,
Installation in flat open areas
The sensor needs to be installed inside the area
to be monitored and heated in such a way that
the sensor surface is in level with the surrounding
surface material and the sensor surface remains
free. The sensor must not stick out of the open
area but can rather be a few mm lower so that
draining water is collected.
Installation in open areas with a slope
In case of slopes it needs to be made sure that
the sensor surface lies horizontally in order to
be able to collect snow or melt water.
warm air outlets in underground parking lots etc. need to be avoided. The sensor should be installed in a place
where the critical criteria "moisture and low temperature” causing the formation of ice are most likely to occur
first.
To make sure that the ice and snow detection system works properly, take care that the minimum
heating time is long enough so that melt water can moisten the sensor.
The sensor location must be chosen in such a way that the draining melt water runs onto the sensor's
measuring surface. This ensures that moisture is detected as long as there is any.
Installation in open areas with minimum construction height
The type 3353 sensor, which has a supply line at the side of the sensor case, or the type 3355 and 3356
sensors with a variable supply line location are particularly suited to open areas with a low construction height.
Take care not to damage the sensor when constructing the surface, e. g. by an excessive processing
temperature (>75 °C) or by mechanical load due to the use of compactors. Use a suitable protective tube (DN20
in plastic or armoured steel) to ease installation and protect the supply line.
- 4 -
Installation example with two sensors
Two sensors can be connected to the snow and ice detector. In this way it is possible to optimally monitor large
or separated open areas, which may have different local conditions (such as sun in the southern part of the area
and shadow in the northern part or due to shading by a roof as in the illustration below).
Dimensions: Type 3352 and 3353 sensors [mm]
Dimensions: Type 3355 and 3356 sensors [mm]
- 5 -
Technical data: Types 3352, 3353, 3355, 3356
3
1
2
5
1
4
2
6
Supply line: SL-Y11Y, length 6 m, 20 m, 50 m
resistant to microbes and oil according to DIN VDE 0472/9.21 para. 8036
Degree of protection: IP 68
Temperature resistance: –30 ...+75 °C
Sensor 3352/3353 Sensor 3355 Sensor 3356
Length of supply lines
The total length of the type SL-Y11Y supply line must not exceed 50 m. Provided that the clamping point
between the standard supply line and the extension is absolutely watertight and contact secure, the standard
supply lines may be extended by 6 m or 20 m up to the total length listed in the following overview. In order to
ensure operational safety, it is recommended to use a line extension only inside a building where it is dry.
Starting from the standard supply lines of 6 m or 20 m the total line length is as follows:
Standard line 6 m + Extension in 1.0 mm² (44 m) = Total length 50 m
Standard line 6 m + Extension in 1.5 mm² (66 m) = Total length 72 m
Standard line 6 m + Extension in 2.5 mm² (110 m) = Total length 116 m
Standard line 6 m + Extension in 4.0 mm² (176 m) = Total length 182 m
Standard line 20 m + Extension in 1.0 mm² (30 m) = Total length 50 m
Standard line 20 m + Extension in 1.5 mm² (45 m) = Total length 65 m
Standard line 20 m + Extension in 2.5 mm² (75 m) = Total length 95 m
Standard line 20 m + Extension in 4.0 mm² (120 m) = Total length 140 m
3. Sensor mounting in gutters, on rooftops and on satellite systems
(sensor type 3354)
The sensor must be installed in such a way that draining melt water runs off across the sensor. This ensures
that moisture is detected, if there is any.
In case the sensor is installed in a gutter or on a flat rooftop, it should be located as close as possible to the
downpipe or the drain In case it is used in connection with a parabolic aerial, the sensor should be placed
horizontally below the drip edge.
Installation position in the gutter
Explanation of the graphic:
1 cable tie for fastening the heat conductors
2 heat conductor
3 sensor 3354
4 distance of sensor and heat conductor minimum 2.0 cm
5 gutter
6 protruding roof surface
- 6 -
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.