Tecfluid TR420 User Manual

Page 1
Converter
instrumentation
for fluids
TR420
Instructions Manual
R-MI-TR420 Rev.: 1 English Version
Page 2
TABLE OF CONTENTS
2.2 Sensor connection .................................................................... 3
2.3 Output connection ...................................................................... 3
3 TEST AND ADJUSTMENTS ................................................................... 3
4 SELECTION OF OUTPUT MODES ........................................................ 4
5 TECHNICAL CHARACTERISTICS ...……..........................……............. 5
5.1 Power supply ............................................................................. 5
5.3 Level probe input ....................................................................... 5
6 DIMENSIONS ……………………............................................................. 6
2
Page 3
1 INTRODUCTION
The TR420 converters provide a voltage or current output proportional to the variation of the resistance at the input.
It can be adapted to LE and LTE series of level meters, and to PT, PS and 6000 series of flowmeters.
NOTE: Throughout the manual, indicating the word “level” means “height of the float”, and therefore can be applied to both level meters and flow meters.
When the float position changes, the associate sensor changes its resistance, and its value is converted to an output signal.
In all the output modes the converter is active, that is, it supplies the power, therefore the receivers should be passive.
2 INSTALLATION
The TR420 is housed in an IP40 plastic case for mounting on a panel inside an electric control panel. The DIP switch in the front of the converter is exclusively for testing and it must be handled only by maintenance personnel. The plastic case has two holes for mounting with screws to DIN 46 121 and DIN 43 660, and also it has a snap fastener for fitting to DIN 46 277 and DIN EN 50 022 assembly rails.
Screw terminals are provided for external wiring. The terminals are protected against accidental contact in accordance with VDE 0100 Part 750, VDE 0160 Part 100 and VBG 4.
2.1 Power supply connection
Connect the power supply voltage indicated on the label to the terminals 1 & 2. IMPORTANT NOTE: In order to comply with the electrical safety requirements as per IEC
1010-1, the installation of the equipment must provide equipment. This switch must be marked as the disconnecting device for the equipment and be within easy reach of the operator.
The power supply to the converter can be either 24, 110 or 220 VAC or 24 VDC. In the event that the converter is powered at 24 V and the polarity is not indicated on the connection label, the equipment can be connected to both 24 VAC or 24 VDC without taking into account the polarity.
2.2 Sensor connection
The connection between the sensor and the converter TR420 needs only two wires as indicated in the following figure.
a mains switch to disconnect the
3
Page 4
2.3 Output connection
In case of current output (4-20 mA), it is recommended that the impedance of the receiver does not exceed 350 .
3 TEST AND ADJUSTMENTS
3.1 Testing
Remove the transparent cover, and access to the eight contact DIP switch. Move the switches 1 & 2 to the "OFF" position and switches 3 & 4 to the "ON" position (TEST configuration). The LED lamp lights up, indicating TEST mode. Use the four switches 5, 6, 7 & 8 to select the different output levels. With all four switches in the "OFF" position we have an output equivalent to 0% of level and with all four switches in the "ON" position we have an output for a 100% of level.
No. in ON Level Output
In order to visualise the output current, use the level indicator provided in the plant or alternatively use a multimeter on the scale of mA.
When the test procedure is over, move the switches 1, 2, 3 & 4 to the normal service position and the LED lamp will turn off.
3.2 Adjustment
The converters include two potentiometers for adjusting the output range with the individual probes installed. The potentiometer P01 (marked ZERO on the face plate) is used to adjust the 0 point, and the potentiometer P02 (marked SPAN) is used to adjust the full scale output (100% of the level). Adjustment must be made with the switches in "SERVICE" position.
In order to reach the adjustment potentiometers, one must use a fairly long fine screwdriver since the screw heads of the potentiometers are situated at about 25 mm below the face plate.
In order to adjust the output the float must be placed at the minimum level position. Then adjust P01 for a 4 mA output (or minimum output in the event of using other output modes).
Place the float at the maximum level position and adjust P02 to obtain 20 mA or the maximum output.
4. SELECTION OF OUTPUT MODES
The level converter is designed to have 6 possible output modes that can be adapted to different signal receivers. All output modes are active outputs, which means that the converter supplies the current or voltage to the receiver.
The six output modes are the following:
NONE 0 % 4 mA 5 25 % 8 mA 5 & 6 50 % 12 mA 5, 6 & 7 75 % 16 mA 5, 6, 7 & 8 100 % 20 mA
1. 4 - 20 mA output
2. 0 - 20 mA output
3. 1 - 5 V output
4. 0 - 5 V output
5. 2 - 10 V output
6. 0 - 10 V output
4
Page 5
The different output modes are selected by means of jumpers on headers inside the converter.
Before opening the converter the power supply must be disconnected.
In order to open the converter to change the output mode, first remove the transparent top cover, then press outwards the sides of the plastic case to free the clips in the sides of the terminal blocks and slide the terminal blocks out together with the printed circuits. It is not necessary to slide the printed circuits completely out of the case, as the jumpers are just below the terminal block.
The position of the jumpers is as follows:
JP1 JP2 JP3
4 - 20 mA X
0 - 20 mA
1 - 5 V X X X
0 - 5 V X X
2 - 10 V X X
0 - 10 V X
There is a fourth jumper lower down on the printed circuit. It must not be removed as it is only used for factory adjustments.
5
Page 6
5. TECHNICAL CHARACTERISTICS
5.1 Power supply
Standard: 220 VAC 50/60 Hz
Other: 240, 110, 24 VAC 50/60 Hz. 24 VDC
Power consumption: Less than 1 VA.
5.2 Analog output
The analog outputs are active. This means that the TR420 supplies the electric current to the output. The loads that can be applied to the output are the following:
0-20 mA and 4-20 mA. Maximum resistive load: 350
0-5 V and 1-5 V. Minimum resistive load: 100 k
0-10 V and 2-10 V. Minimum resistive load: 200 k
5.3 Level probe input
The TR420 is designed to work with a probe with 1000 ohms per meter of length. In order to adapt the probe to the LE-70 a fixed resistor of 10,000 ohm per meter of probe length is used, this means that the adapting resistor will have ten times the maximum resistance of the probe. The adapting resistor must be a metal film type with a thermal coefficient of 50 ppm.
5.4 General characteristics
Ingress protection: IP40
Ambient temperature range: From 0 to 60ºC
Conforms with LV Directive 73/23/EEC
Conforms with EMC Directive EMC 89/336/EEC Conforms with WEEE Directive 2002/96/EC
6
Page 7
6 DIMENSIONS
7
Page 8
WARRANTY
Tecfluid S.A. GUARANTEES ALL ITS PRODUCTS FOR A PERIOD OF 24 MONTHS, after consignment, against all defects in materials and workmanship.
This warranty does not cover failures which can be imputed to misuse, use in an application different to that specified in the order, the result of service or modification by un-authorized persons, bad handling or accident.
This warranty is limited to cover the repair or replacement defective parts which have not been damaged by misuse.
This warranty is limited to the repair of the equipment and all further and eventually following damages are not covered by this warranty.
Any consignment of equipment to our factory or distributor must be previously authorised. The consignment should be done with the equipment well packed, clean of any liquids, grease or hazardous materials. Tecfluid S.A. will not accept any responsibility for damage done during transport. Together with the equipment, a note should be enclosed indicating the failure observed, the name, address and telephone number of the sender.
SHIPMENT In case of damages during shipping, please claim directly to the forwarder over a period of less than 24 hours. Tecfluid is not responsible for any damage caused during the shipment of material.
TECFLUID, S.A. Narcís Monturiol, 33 E-08960 Sant Just Desvern Tel. + 34 93 3724511 - Fax + 34 93 4734449 E-mail: tecfluid@tecfluid.com Internet: www.tecfluid.com
The technical data in this document is subject to modification without notification, if the technical innovations in the product or manufacturing processes so require.
Loading...