siemens 805SM User Manual

SIROTEC ACR 20 SINUMERIK 805SM/840C Link to SINEC L2–DP with IM 329–N Module
Description 04.95 Edition
Manufacturer Documentation
SIROTEC ACR 20 SINUMERIK 805SM/840C
General 1
Hardware 2
COM ET 200 for IM 329–N 3
Link to SINEC L2–DP with IM 329–N Module
Description
Manufacturer Documentation
Description of the Slave Functionality
Description of the Master Functionality
Abbreviations A
References B
Index C
4
5
04.95 Edition
3ls
SINUMERIK documentation
Printing history
Brief details of this edition and previous editions are listed below. The status of each edition is shown by the code in the “Remarks” column.
Status code in the “Remarks” column.
A New documentation.. . . .
B Unrevised reprint with new Order No.. . . .
C Revised edition with new status.. . . .
If factual changes have been made on the page since the last edition, this is indicated by a new edition coding in the header on that page.
Edition Order No. Remarks
04.95 6ZB5 430–0BH02–0AA1 A
Siemens quality for software and training to DIN ISO 9001, Reg. No. 2160–01
This publication was produced with Interleaf V 5.3 The reproduction, transmission or use of this document or its
contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved.
Siemens AG 1995. All rights reserved.
Order No. 6ZB5 430–0BH02–0AA1 Printed in the Federal Republic of Germany
Siemens AG 1995 All Rights Reserved 6ZB5 430–0BH02–0AA1
Other functions not described in this documentation might be executable in the control. This does not, however, represent an obligation to supply such functions with a new control or when servicing.
We have checked that the contents of this publication agree with the hardware and software described herein. The information given in this publication is reviewed at regular intervals and any corrections that might be necessary are made in the subsequent printings. Suggestions for improvement are welcome at all times.
Subject to change without prior notice.
Siemens–Aktiengesellschaft
04.95 Description

PRELIMINARY REMARKS

Notes to the reader
Target group
Contents
This description is aimed at machine manufacturers and service personnel and describes the use of the IM 329–N module in SINUMERIK and SIRO­TEC as a slave and master in the ET 200 Distributed I/O System.
This manual provides information on
jumper settings on the module as well as interfaces and operating
elements
data required for configuring the moduleinstallation and startup of the moduleerror messages and application examples
Note
The description of the ET 200 Distributed I/O System is to be found in: Reference: /1/, ET 200 Distributed I/O System Manual For the distributed I/O stations ET 200U, ET 200B and ET 200C etc. the
following separate manuals are available: Reference: /2/, Distributed I/O Station Manual
Objective
Corrections/ suggestions
Searching aids
This description contains the information required for start–up and service.
A page for your corrections and suggestions is provided at the end of this manual. Please fill in this form and send it back to us. This will help us to improve the next edition.
So that you can find the information you need, this document not only con­tains a table of contents, a list of figures and a list of tables, but in the appen­dix you will also find:
1. A list of abbreviations
2. A list of references
3. An index
Siemens AG 1995 All Rights Reserved 6ZB5 430–0BH02–0AA1 SIROTEC ACR 20, SINUMERIK 805SM / 840C (BS)
i
04.95Description
Note
T ext marked in this way is important information to which the reader must pay special attention.
Important
!
This symbol appears in documents wherever important information is given.
Ordering data option
This symbol indicates functions for which an ordering data option is required (options). The function described can only be executed if the option designa­ted is present.
ii
6ZB5 430–0BH02–0AA1 Siemens AG 1995 All Rights Reserved
SIROTEC ACR 20, SINUMERIK 805SM / 840C (BS)
04.95 Description
Safety notes
Warning
!
Qualified personnel
!
When electrical devices are in operation, certain parts of them are inevitably subjected to hazardous voltages. Improper interference with the device/system or failure to observe the warning advice can result in serious physical injury or material damage. Only appropriately trained personnel familiar with the assembly, installa­tion, starting up or operation of the product are permitted to interfere with this device/sytem.
Warning
Qualified persons as referred to in the safety guidelines (in the documenta­tion or affixed to the product itself) are persons who, for instance:
Have received training or instruction and authorization to energize and
de-energize, ground and tag electric circuits and equipment in accor­dance with established safety practices.
Have received training or instruction in accordance with established
safety practices in the care, use and repair of appropriate safety equipment.
Have received training or instruction in working with electrostatically
sensitive components or modules.
Have been instructed as operators to work with automation technology
equipment and are familiar with the contents in the Operator’s and/or Programming Guide referring to operation.
Note
When planning, installing, starting up and operating the control, personnel concerned must be familiar with the documentation relevant to their jobs.
Siemens AG 1995 All Rights Reserved 6ZB5 430–0BH02–0AA1 SIROTEC ACR 20, SINUMERIK 805SM / 840C (BS)
iii
Danger notices
!
!
04.95Description
The notices and guidelines that follow are intended to ensure personal safety and to protect the product described here or connected devices and machines against damage.
The safety notices and guidelines intended to avert danger to human life and health and to avoid material damage are emphasized in this Manual by the terms defined below. The terms have the following meanings in the context of this Manual and the notices on the product itself:
Danger
This symbol means that death, serious injury or considerable material da­mage will occur, if the precautionary measures indicated are not taken.
Caution
indicates that personal injury or property damage can result if proper pre­cautions are not taken.
!
Intended use
Warning
indicates that death, severe personal injury or substantial property damage can result if proper precautions are not taken.
The device/system or system component must be used only for the
applications specified in the Catalog and Reference Manual and only in conjunction with such non-Siemens devices and components as have been recommended and approved by Siemens.
The product described in the manual has been developed, manufactured,
tested and documented in compliance with the relevant safety standards. Provided the handling instructions and safety guidelines described for planning, assembling, proper operation and maintenance are observed, the product will not normally be a source of danger leading to material damage or physical injury.
iv
6ZB5 430–0BH02–0AA1 Siemens AG 1995 All Rights Reserved
SIROTEC ACR 20, SINUMERIK 805SM / 840C (BS)
04.95 Description
Notes on product planning
As the product is generally part of larger systems or plants, these notes are intended as a guideline for safe integration of a product in its environment.
Note the following in particular:
Note
Even when a maximum of safety has been included in the design of automa­tion equipment, e.g. by means of a multi-channel configuration, the instruc­tions given in the documentation must be followed exactly because incorrect handling can render ineffective the preventive measures incorporated to protect against dangerous faults or create new sources of danger.
Active and passive faults in automation equipment
Depending on the paricular task for which the electronic automation
equipment is used, both active and passive faults can be dangerous faults. In the case of a drive control, for example, active faults are ge­nerally dangerous because they lead to unauthorized startup of the drive. On the other hand, a passive fault can result in a dangerous operating state not being reported to the operator.
This differentiation between possible faults and their task-related classifi-
cation as dangerous and non-dangerous faults is important for all the safety considerations in respect of the product supplied.
Warning
!
Wherever a fault in the automation equipment can cause serious material damage or even physical injury, in other words wherever dangerous faults can occur, additional external precautions must be taken or devices provided which will insure or enforce safe operating conditions even in the event of a fault (e.g. by means of independent limit switches, mechanical interlocks etc.).
Note
The information contained in this documentation is checked and updated regularly and can be changed at any time without further notice.
Siemens AG 1995 All Rights Reserved 6ZB5 430–0BH02–0AA1 SIROTEC ACR 20, SINUMERIK 805SM / 840C (BS)
v
Technical notes
04.95Description
Checking the assignments
Operating the module
Response of the module
Difference between the IM 328–N and IM 329–N modules
Before start–up, please set the assignments on the module and on the front panel as required for the application or check that they are set.
The IM 329–N module can be operated as follows:
Straight slave operationStraight master operationSimultaneous slave and master operation
From the point of view of the control, the module responds like an I/O module.
The modules IM 328–N and IM 329–N differ as follows
IM 328–N IM 329–N
Functionality Slave Slave and master
For information on the IM 328–N see: Reference: /6/, Description
Link to SINEC L2–DP with IM 328–N Module
Trademarks
SIMATIC
, SINEC and SINUMERIK are registered trademarks of
SIEMENS AG.
vi
6ZB5 430–0BH02–0AA1 Siemens AG 1995 All Rights Reserved
SIROTEC ACR 20, SINUMERIK 805SM / 840C (BS)
04.95 Description

Contents

1 General 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 Hardware 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 Module IM 329–N, master and slave 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Jumper settings 2-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.1 Jumper settings on the slave 2-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.2 Jumper settings on the master 2-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Elements on the front plate 2-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.1 Elements for the slave 2-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.2 Elemente für Master 2-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.4 Technical data 2-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 COM ET 200 for IM 329–N 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Installation 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 COM ET 200 parameterization software 3-2. . . . . . . . . . . . . . . . . . . . . . . . .
4 Description of the Slave Functionality 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 Notes on parameterization of the slaves 4-1. . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Configuration example for slave 4-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Procedure for installation and startup 4-4. . . . . . . . . . . . . . . . . . . . . . . . . . .
4.4 Example of application 4-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5 Status display messages 4-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5.1 Normal operating state 4-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5.2 Fault during data transmission 4-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5.3 Fault on the module (system error message) 4-11. . . . . . . . . . . . . . . . . . . . .
4.6 Diagnostics functions in the STEP 5 program of the master IM 308–B 4-12
4.6.1 Example: Diagnostics overview 4-16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.6.2 Example: PLC STOP in the slave station 4-17. . . . . . . . . . . . . . . . . . . . . . . .
5 Description of the Master Functionality 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1 General information about the master interface of the
IM 329–N 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 Information about configuring the master interface 5-1. . . . . . . . . . . . . . . .
5.3 Sequence for start–up 5-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4 Signals and the status display 5-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.1 Normal operating state 5-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.2 Faults and signals 5-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.5 Application example 5-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A Abbreviations A-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B References B-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C Index Index-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Siemens AG 1995 All Rights Reserved 6ZB5 430–0BH02–0AA1 SIROTEC ACR 20, SINUMERIK 805SM / 840C (BS)
vii
04.95 Description 1 General
1

General

SINEC L2–DP field bus
Distributed I/O system ET 200
Master stations
1
The SINEC L2–DP (DP = Distributed Peripherals) field bus is a distributed I/O version of the SINEC L2 and is designed for minimum response times in the communication with distributed I/O devices.
The ET 200 distributed I/O system (ET = Electronic Terminator) for SIMA- TIC S5 uses the SINEC L2–DP field bus. The system is based on the PROFI­BUS communications standard (DIN 19245, Part 1) and works on the master/ slave principle with the distributed I/O devices being the slaves.
The following devices can be master stations:
SIMATIC S5 control
115U 135U 155U with IM 308–B,
IM 308–C interface
Programming device
PG 730, PG 750 or PG 770 with CP 5410–S5DOS/ST interface
SINUMERIK 805SM SINUMERIK 840C SIROTEC ACR 20
with module IM 329–N, master
or other master stations with PROFIBUS–DP
Fig. 1-1 Master stations
SINUMERIK
SIROTEC
+
or
Siemens AG 1995 All Rights Reserved 6ZB5 430–0BH02–0AA1 SIROTEC ACR 20, SINUMERIK 805SM / 840C (BS)
1-1
1 General
04.95Description
1
Slave stations
Example
The following can be slave stations:
Distributed I/O devices
e. g. ET 200B ET 200U ET 200C S5–95U–DP
SINUMERIK 805SM SINUMERIK 840C SIROTEC ACR 20
SINUMERIK or SIROTEC
with IM 329–N, DP slave module or other PROFIBUS–DP slaves
Fig. 1-2 Slave stations
The diagram below gives an example of how to connect the master and slave stations to the SINEC L2–DP field bus:
PG
Interface module CP 5410–S5DOS/ST master
Field bus SINEC L2–DP
Slaves
ET 200
SINUMERIK or SIROTEC with interface module
IM 329–N
Slaves
PG
Interface module CP 5410–S5DOS/ST master
Fig. 1-3 Using the module IM 329–N as a slave and master
Slave Master
ET 200ET 200
SIMATIC
S5–155U
ET 200
Field bus SINEC L2–DP
Interface module IM 308–B/C
master
ET 200ET 200
SINUMERIK or SIROTEC with interface module
IM 329–N
J
1-2
6ZB5 430–0BH02–0AA1 Siemens AG 1995 All Rights Reserved
SIROTEC ACR 20, SINUMERIK 805SM / 840C (BS)
04.95 Description

2.1 Module IM 329–N, master and slave

Hardware

2.1 Module IM 329–N, master and slave
Order No.: 6FC5 012–0CA02–0AA0
ON
S2.
8
X339
5 3
1
X21
DC/DC
converter
Slave
DC/DC
converter
Master
FEPROM
Quartz
Quartz
SPC
Dual port RAM (DPR)
ON
8
5 3
1
S3.
80C32
Master
module
0
10
1
10 100–199
0–99
PARAMETERIZATION
(+ Station address slave = 0)
RUN
(+ Station address slave between 3 and 124)
RUN (green LED)
Slave
ACCESS (green LED)
Bus connector
Master
2
2
Station address for slave
Units place Tens place Hundreds place
Operating mode master
Status display FAULT (red LED)
Interface
X111
Status display FAULT (red LED)
Interface
X112
X339: Both jumpers open
Fig. 2-1 Module IM 329–N, master and slave
Siemens AG 1995 All Rights Reserved 6ZB5 430–0BH02–0AA1 SIROTEC ACR 20, SINUMERIK 805SM / 840C (BS)
2-1

2.2 Jumper settings

2.2 Jumper settings

2.2.1 Jumper settings on the slave

04.95Description
2
Selecting the control system (S2.5, S2.6, S2.7 and S2.8)
Setting of address range (number of input and output bytes) (S2.1 and S2.2)
The module can be used in the control systems listed. The control type must be set with switches S2.5, S2.6, S2.7 and S2.8 as follows:
S2.5 S2.6 S2.7 S2.8
SINUMERIK 805SM OFF ON OFF ON
SIROTEC ACR 20 ON ON ON ON
SINUMERIK 840C ON ON ON ON
Note
The IM 329–N module can only be used for SINUMERIK 805SM in the central controller.
Switches S2.1 and S2.2 must be set according to the table below in order to set the address range of 4, 8, 16 or 32 input or output bytes.
Address range S2.1 in position S2.2 in position
4 bytes OFF OFF
8 bytes OFF ON 16 bytes ON OFF 32 bytes ON ON
2-2
Note
Address range of, for example, 4 bytes means that 4 input bytes and 4 output bytes are available with the same base address.
6ZB5 430–0BH02–0AA1 Siemens AG 1995 All Rights Reserved
SIROTEC ACR 20, SINUMERIK 805SM / 840C (BS)
04.95 Description
2.2 Jumper settings
Setting the base address (S3.1 to S3.8)
Base address for 4-byte address range
The following switches are used to set the module numbers (base address)
S3.1 to S3.8 for an address range of 4 bytesS3.2 to S3.8 for an address range of 8 bytesS3.3 to S3.8 for an address range of 16 bytesS3.4 to S3.8 for an address range of 32 bytes
Note
The switches not required for the 8, 16 and 32–bytes address ranges are irre­levant and any setting is permissible.
Switch S2.1 = OFF and S2.2 = OFF
Base address S3.8 S3.7 S3.6 S3.5 S3.4 S3.3 S3.2 S3.1
0 ON ON ON ON ON ON ON ON 4 ON ON ON ON ON ON ON OFF
8 ON ON ON ON ON ON OFF ON 12 ON ON ON ON ON ON OFF OFF 16 ON ON ON ON ON OFF ON ON
: : : : : : : : :
1020 OFF OFF OFF OFF OFF OFF OFF OFF
Significance 2
=512
9
8
2
=256
7
2
=128
2
=64
6
2
=32
5
2
=16
4
2
=8
3
=4
2
2
2
Base address for 8-byte address range
Switch S2.1 = OFF and S2.2 = ON
Base address S3.8 S3.7 S3.6 S3.5 S3.4 S3.3 S3.2 S3.1
0 ON ON ON ON ON ON ON x
8 ON ON ON ON ON ON OFF x 16 ON ON ON ON ON OFF ON x 24 ON ON ON ON ON OFF OFF x 32 ON ON ON ON OFF ON ON x
: : : : : : : :
1016 OFF OFF OFF OFF OFF OFF OFF x
Significance 2
=512
9
8
2
=256
2
=128
x: Switch position of no significance
Siemens AG 1995 All Rights Reserved 6ZB5 430–0BH02–0AA1 SIROTEC ACR 20, SINUMERIK 805SM / 840C (BS)
7
2
=64
6
2
=32
5
2
=16
4
2
=8
3
2-3
2.2 Jumper settings
04.95Description
2
Base address for 16-byte address range
Base address for 32-byte address range
Switch S2.1 = ON and S2.2 = OFF
Base address S3.8 S3.7 S3.6 S3.5 S3.4 S3.3 S3.2 S3.1
0 ON ON ON ON ON ON x x 16 ON ON ON ON ON OFF x x 32 ON ON ON ON OFF ON x x 48 ON ON ON ON OFF OFF x x 54 ON ON ON OFF ON ON x x
: : : : : : :
1008 OFF OFF OFF OFF OFF OFF x x
Significance 2
=512
9
8
2
=256
7
2
=128
2
=64
6
2
=32
5
2
=16
4
x: Switch position of no significance
Switch S2.1 = ON and S2.2 = ON
Base address S3.8 S3.7 S3.6 S3.5 S3.4 S3.3 S3.2 S3.1
0 ON ON ON ON ON x x x 32 ON ON ON ON OFF x x x 64 ON ON ON OFF ON x x x 96 ON ON ON OFF OFF x x x
: : : : : :
992 OFF OFF OFF OFF OFF x x x
Significance 2
=512
9
8
2
=256
7
2
=128
2
=64
6
2
=32
5
Example of address setting
2-4
x: Switch position of no significance
Note
Base addresses are only possible for 4–byte, 8–byte, 16–byte or 32–byte steps depending on the address range. For example, an address range of 32 bytes permits only 0, 32, 64, 96 etc. as initial addresses.
Address range = 8 bytes and the base address is to be 24 S2.1 = OFF and S2.2 = ON S3.8, S3.7, S3.6, S3.5, S3.4 = ON and S3.3, S3.2 = OFF The assigned input and output area is from IB 24/QB 24 to IB 31/QB 31.
6ZB5 430–0BH02–0AA1 Siemens AG 1995 All Rights Reserved
SIROTEC ACR 20, SINUMERIK 805SM / 840C (BS)
04.95 Description
2.2 Jumper settings
Danger
!
An incorrect setting of the base address (e.g. dual address assignment or ad­dress conflict with other I/O modules) results in “wrong signal states” and can cause an undefined behaviour of the control and the machine!
2
Enable slave (S2.3)
I/O ranges
S2.3 must be used to enable the slave functionality.
Switch S2.3 in position Function
OFF Slave disabled
ON Slave enabled
In assigning the slaves, please note that the following I/O ranges are availa­ble on the SIROTEC ACR 20, SINUMERIK 805SM and SINUMERIK 840C controls:
SINUMERIK 805SM (SW4)
Inputs IB 0 to IB 47 I 1 to I 1024
Outputs QB 0 to QB 47 Q 1 to Q 1024
Physical inter­face without process image
PB 0 to PB 255
SIROTEC ACR 20
(SW5)
(IB 0 to IB 127)
(QB 0 to QB 127)
SINUMERIK 840C
(SW4)
IB 0 to IB 127
QB 0 to QB 127
For the allocation of the I/O range for each control see: Reference: /3/, SINUMERIK 805SM,
Interface Description, Part 2 – Connection Conditions
Reference: /4/, SIROTEC ACR 20, Configuration Instructions
Note
The I/O range must be addressed without gaps with SIROTEC ACR 20
Reference: /5/, SINUMERIK 840C
Interface Description, Part 2 – Connection Conditions
Siemens AG 1995 All Rights Reserved 6ZB5 430–0BH02–0AA1 SIROTEC ACR 20, SINUMERIK 805SM / 840C (BS)
2-5
Loading...
+ 38 hidden pages