Schneider Electric TAC Xenta 280, TAC Xenta 300, TAC Xenta 401 Users Manual

Page 1
TAC Vista
TAC Pangaea
WorkStation
TAC Xenta 280/300/401
Product Manual
Page 2
Page 3
TAC Vista
TAC Xenta 280/300/401
Product Manual
Page 4
Copyright © 2007-2011 Schneider Electric Buildings AB. All rights reserved. This document, as well as the product it refers to, is only intended for licensed users. Schneider Electric Buildings AB owns the copyright of
Do not use the product for other purposes than those indicated in this document. Only licensed users of the product and the document are permitted to use the document or any information therein. Distribution, disclosure,
copying, storing or use of the product, the information or the illustrations in the document on the part of non-licensed users, in electronic or mechanical form, as a recording or by other means, including photo copying or information storage and retrieval systems, without the express written permission of Schneider Electric Buildings AB, will be regarded as a violation of copyright laws and is strictly prohibited.
Trademarks and registered trademarks are the property of their respective owners.
Page 5
TAC Xenta, TAC Xenta 280/300/401 Contents

Contents

INTRODUCTION
1 About this Manual 9
1.1 Structure..................................................................................................................... 9
1.2 Typographic Conventions.......................................................................................... 10
1.3 Prerequisites............................................................................................................... 10
REFERENCE
2 TAC Xenta Components 13
2.1 Hardware Units ................................................................................................ ..... ..... 13
2.2 Configurations............................................................................................................ 14
2.3 Communications ........................................................................................................ 15
3 Technical Description 17
3.1 The TAC Xenta 280 Controller........................................................................ ..... ..... 17
3.1.1 Terminals.................................................................................................................... 17
3.1.2 Jacks........................................................................................................................... 18
3.1.3 LED Indicators and Service pin................................................................................. 19
3.1.4 Technical Data TAC Xenta 280................................................................................. 20
3.2 The TAC Xenta 300 Controller........................................................................ ..... ..... 21
3.2.1 Terminals.................................................................................................................... 21
3.2.2 Jacks........................................................................................................................... 23
3.2.3 LED Indicators and Service pin................................................................................. 23
3.2.4 Technical Data TAC Xenta 300................................................................................. 24
3.3 The TAC Xenta 401 Controller........................................................................ ..... ..... 25
3.3.1 Terminals.................................................................................................................... 25
3.3.2 Jacks........................................................................................................................... 25
3.3.3 LED Indicators and Service pin................................................................................. 26
3.3.4 Technical Data TAC Xenta 401................................................................................. 27
4 Installation 29
4.1 Mounting the Controller............................................................................................. 29
4.2 Electrical Installation ................................................................................................. 30
4.2.1 General Considerations.............................................................................................. 30
4.2.2 Cabinet Connections .................................................................................................. 32
4.2.3 Cables......................................................................................................................... 34
4.3 Terminations .............................................................................................................. 39
4.3.1 The TAC Xenta OP Operator Panel........................................................ ..... .... .......... 42
5 Configuring your System 45
5.1 Overview.................................................................................................................... 45
Schneider Electric Buildings AB, June 2011 5 (74) 04-00067-02-en
Page 6
Contents TAC Xenta, TAC Xenta 280/300/401
5.2 A Single TAC Xenta 280/300/401 Controller............................................................ 46
5.2.1 Initial Check ............................................................................................................... 46
5.2.2 OP Panel Activities..................................................................................................... 47
5.3 Two or more TAC Xenta 280/300/401 Units............................................................. 47
5.3.1 Initial Check ............................................................................................................... 47
5.3.2 Device Configuration ................................................................................................. 47
5.3.3 OP Panel Activities..................................................................................................... 48
5.4 Additional I/O Units................................................................................................... 48
5.4.1 Selecting I/O Modules................................................................................................ 48
5.4.2 Initial Check ............................................................................................................... 49
5.4.3 I/O Module Configuration.......................................................................................... 49
5.5 Setting the Date and Time.......................................................................................... 50
5.6 Clearing the Xenta Application..................................... ..... ........................................ 51
5.7 Lock a Xenta OP to a specific TAC Xenta Controller............................................... 51
5.7.1 Creating the PVI-block in the Xenta.......................................................................... 51
5.7.2 Enabling the function in TAC Xenta OP.................................................................... 52
6 The TAC Xenta Service Menu 53
6.1 Accessing the Service Menu ...................................................................................... 53
6.2 Submenus 1-8............................................................................................................. 54
6.2.1 Submenu 6: Test dial.................................................................................................. 57
APPENDIX
A Appendix A Restart Values 63
B Appendix B Restart Sequences 67
Index 71
6 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 7

INTRODUCTION

1 About this Manual
Page 8
Page 9

TAC Xenta, TAC Xenta 280/300/401 1 About this Manual

1 About this Manual
This manual describes a particular process. For information on certain products, we refer you to the manual or the Help for the product in ques­tion.
For information on how to install software, we refer you to the instruc­tions delivered with the software.
For information on third party products, we refer you to the instructions delivered with the third party product.
If you discover errors and/or unclear descriptions in this manual, please contact your Schneider Electric representative.
Note

1.1 Structure

We are continuously improving and correcting our documenta­tion. This manual may have been updated.
Please check our Docnet site at www.tac.com for the latest ver­sion.
The manual is divided into the following parts:
Introduction The Introduction section contains information on how this manual is structured and how it should be used to find information in the most efficient way.
Reference The Reference section contains more comprehensive information about various parts of the Getting Started section. It also provides you with information on alternative solutions not covered by the Getting Started section.
Schneider Electric Buildings AB, June 2011 9 (74) 04-00067-02-en
Page 10
1 About this Manual TAC Xenta, TAC Xenta 280/300/401
!

1.2 Typographic Conventions

Throughout the manual the following specially marked texts may occur.
Warning
Alerts you that failure to take, or avoid, a specific action might result in physical harm to you or to the hardware.
Caution
Alerts you to possible data loss, breaches of security, or other more serious problems.
Important
Alerts you to supplementary information that is essential to the completion of a task.
Note
Alerts you to supplementary information.
Tip
Alerts you to supplementary information that is not essential to
Advanced
Alerts you that the following information applies to complex

1.3 Prerequisites

To be able to profit from the contents in this manual, it is recommended that you read the following documents:
TA C Xenta 280 Programmable Controller datasheet
the completion of the task at hand.
tasks or tasks restricted by access.
TA C Xenta 300 Programmable Controller datasheet
TA C Xenta 400 Controller, freely programmable datasheet
10 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 11

REFERENCE

2 TAC Xenta Components
3 Technical Description
4 Installation
5 Configuring your System
6 The TAC Xenta Service Menu
Page 12
Page 13

TAC Xenta, TAC Xenta 280/300/401 2 TAC Xenta Components

TAC Xenta 280 or 300 controller
12 13 14 15 16 17 18 20
TAC Xenta 401 controller
Operator panel
12 13 14 15 16 17 18 20
I/O expansion module
2 TAC Xenta Components

2.1 Hardware Units

The TAC Xenta 280/300/400 family consists of the following units:
The TAC Xenta 280/300/401 controller. The controller contains the database of the inputs and outputs of the TAC Xenta system. It also contains the system and application software for all the func­tions that are to be performed by the controller and the connected peripheral units.
TAC Xenta OP. The operator panel includes control buttons while a screen displays the values and menus. TAC Xenta OP can be connected to any controller in the network.
I/O expansion modules. These can be used to extend the number of inputs and outputs on a TAC Xenta 300/401 controller.
The I/O modules are described in a separate manual, TAC Xenta 400 I/ O Modules.
Schneider Electric Buildings AB, June 2011 13 (74) 04-00067-02-en
Fig. 2.1: The basic units of the TAC Xenta: the controller, the operator panel, and an I/O expansion module
Page 14
2 TAC Xenta Components TAC Xenta, TAC Xenta 280/300/401
Inputs Outputs I/O Modules See section
TAC Xenta 280 3.1
TAC Xenta 281 6 6 none TAC Xenta 282 8 8 none TAC Xenta 283 6 6 none
TAC Xenta 300 3.2
TAC Xenta 301 12 8 up to 2 TAC Xenta 302 12 8 up to 2
TAC Xenta 401 none none up to 10 3.3
A number of controllers and I/O modules can form a local network and exchange data.
The TAC Xenta OP operator panel allows the user to:
Obtain access to certain parameters
Monitor the system status
Adjust setpoints and time channels
Display alarms (without communicating with a central system) Up to two OPs may be connected to each controller.

2.2 Configurations

The TAC Xenta controllers can be used in different configurations, for example:
As stand-alone units (for a TAC Xenta 401 with at least one I/O module).
With controllers and OPs in a network, with extra I/O modules as required (no I/O modules for the TAC Xenta 280).
With controllers, OPs, I/O modules and other equipment in a full network with suitable adapters, possibly with connections to a TAC Vista Central System.
14 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 15
TAC Xenta, TAC Xenta 280/300/401 2 TAC Xenta Components
+
-
TAC
Vista
TAC Xenta OP
TP/FT-10
TAC Xenta OP
TAC Xenta 401
TAC Xenta 281
TAC Xenta 901
TAC
Vista
TAC Xenta 511
TAC Xenta 301
Management level
Automation level
Field level
I/O ModuleorI/O Module
Web
Browser
IP Network
PCLTA
card
Fig. 2.2: A TAC Xenta network example

2.3 Communications

The TAC Xenta units communicate with each other in a network using a common bus, Echelon® L
10). Additional I/O units also connect to the network and may be added as required. An I/O unit can only be associated with one controller.
Explicit L operator panel and the controller.
The L defined on foreign equipment.
The Functional Block applications are modeled as true L troller Objects.
The Network Variable interface (including the Standard Network Vari­able Types, SNVTs) can be customized, and External Interface Files (XIFs) can be generated in the field using the TAC Menta tool. Avail­able SNVTs are listed in an appendix to the Engineering Applications in TAC Menta manual.
When connected to a TAC Vista Central System, the operating con­ditions of equipment such as fans, pumps, and recovery units can be dis­played as graphs on the monitor and printed as reports. All temperatures and alarms may be read, while setpoints and time settings may be altered as required
TAC Xenta controllers can be reached from TAC Vista in many ways. Using LonWorks in the Xenta controller, some examples are:
From a PCLTA card in some form, directly on the PC.
ONWORKS® Free Topology 78 kbps (FTT-
ONTALK® messages are used in communications between the
ONTALK protocol makes it possible to use Network Variables,
ONMARK Con-
Schneider Electric Buildings AB, June 2011 15 (74) 04-00067-02-en
Page 16
2 TAC Xenta Components TAC Xenta, TAC Xenta 280/300/401
Via the LTA function in the TAC Xenta 911.
Via the LTA function in the TAC Xenta 511.
Using the TAC Xenta 901.
Via an Ethernet/LON gateway.
Using the serial channel in the Xenta controller, for example:
Directly connected to a PC serial channel.
Connected to a PC serial channel via a telephone modem.
Connected to a PC serial channel via the IP modem function of the TAC Xenta 911.
Starting from v 3.1, application programs generated in TAC Menta may be downloaded from TAC Vista via the network.
The TAC Xenta 280/300/401 can communicate as follows:
It can send alarm and trend logging (versions 3.2 and higher) mes­sages.
It can answer requests for the status of inputs and outputs.
It can send/ any of the parameters/variables in the program which are freely available (“Public signal”).
It can communicate with other T AC Xenta controllers to exchange data.
It can communicate with the Operator Panel, the I/O-modules, and TAC Vis ta.
For further details, please consult the TAC Vista IV, Engineering Clas- sic/LNS Network manuals.
RS232
The TAC Xenta 280/300/401 controller has an RS232 port that can be used to:
Load the system software.
Load the application software from the TAC Menta programming tool.
Connect to TAC Menta when used as a commissioning tool.
Connect a specific controller directly to T AC V ista or via a modem (modem connection not available with TAC Xenta 280).
Retrieve the “System Error Log File” using the “Xenta System Error Log Viewer”.
16 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 17

TAC Xenta, TAC Xenta 280/300/401 3 Technical Description

3 Technical Description

3.1 The TAC Xenta 280 Controller

Fig. 3.1: The TAC Xenta 280 controller
3.1.1 Terminals
The TAC Xenta 281, 282 and 283
The TAC Xenta 280 has three I/O configurations, called the TAC Xenta 281, 282, and 283.
No external TAC Xenta 400 I/O modules can be used.
Digital
inputs Term. notation TAC Xenta 281 2-43-3 TAC Xenta 282 2244-4 TAC Xenta 283 24 --6-
XBUKVY
Thermistor inputs
Univer­sal inputs
Relay outputs
TRIAC outputs
Analog outputs
Schneider Electric Buildings AB, June 2011 17 (74) 04-00067-02-en
Page 18
3 Technical Description TAC Xenta, TAC Xenta 280/300/401
20
17
18
16
19
15
12
13
11
14
40
37
38
36
39
35
32
33
31
34
10
7
8
6
9
5
2
3
1
4
30
27
28
26
29
25
22
23
24
21
K2 KC1 K1
Y2
G0
Y1
G
M
X2
M
M
X1
M
U4
U3 U2
C2
U1
M
C1
K3
KC2
0~24 V
AC/DC
}
Comm
{
max 230 V AC
Y3
M
TAC Xenta 281
max 230 V AC
20
17
18
16
19
15
12
13
11
14
40
37
38
36
39
35
32
33
31
34
10
7
8
6
9
5
2
3
1
4
30
27
28
26
29
25
22
23
24
21
K4 KC2
KC1
K2
K1
K3
M
Y4
Y3 Y2
G0
Y1
G
M
X2
M
M
X1
M
B2
M
M
U4
U3
B1
U2
C2
U1
M
C1
0~24 V
AC/DC
}
Comm
{
TAC Xenta 282
20
17
18
16
19
15
12
13
11
14
40
37
38
36
39
35
32
33
31
34
10
7
8
6
9
5
2
3
1
4
30
27
28
26
29
25
22
23
24
21
V2
V6
V5
V1
G0 G
X2
M
M
X1
B3
M
B2
B4
M
M
B1
C2
M
C1
V3
V4
0 ~
24 V
AC/DC
}
Comm
{
24 V AC
VC
TAC Xenta 283
Fig. 3.2: The terminals of the TAC Xenta 281, 282, and 283
Inputs
All TAC Xenta 280 controllers have digital inputs (X).
The TAC Xenta 281 and 282 have universal (analog or digital, U)
inputs. The universal inputs can be used for three types of signals:
TAC thermistor 1.8 kohm at 25 °C (the same as the thermistor inputs)
Voltage input 0–10V
open/closed contact (the same as the digital inputs).
The TAC Xenta 282 also has thermistor inputs (labeled B) for
1.8 kohm.
The TAC Xenta 283 has thermistor inputs (labelled B) that can be used with either 1.8 kohm or 10 kohm thermistors.
All controller inputs are protected from transients, in compliance with the EN 50082-1 norm.
Outputs
The TAC Xenta 281 and 282 have the following outputs;
Analog (Y) — 0–10V DC outputs
Digital (K) — relay potential-free outputs
While the TAC Xenta 283 has TRIAC (V) — outputs capable of sup­plying inductive loads.
3.1.2 Jacks
18 (74) Schneider Electric Buildings AB, June 2011
The TAC Xenta 280 has two modular jacks–one for the TAC Xenta OP operator panel and one for an RS232 connection with TAC Menta.
The socket for the operator panel provides it with 24V AC or DC, depending on the supply.
04-00067-02-en
Page 19
TAC Xenta, TAC Xenta 280/300/401 3 Technical Description
Service pin
Red service diode indicates a non-configured node or a hardware fault
Green status diode indicates that the program is running
At distances greater than 10 m (32 ft.) between the TAC Xenta control­ler and the OP, an external power supply should be used. In addition, the communications connection has to follow the same rules as for other nodes.
Jack for the RS232/modem
Fig. 3.3: Location of jacks on the TAC Xenta 280 controller
3.1.3 LED Indicators and Service pin
The Service pin can be activated through a small hole on the front. Also on the front, there are two LED indicators–one red and one green.
Jack for the Operator panel
Fig. 3.4: LED Indicators and Service Pin
The red service diode is primarily an error indication. It also lights up if the Service pin is activated.
The green status diode blinks once per second to indicate that the pro­gram is running.
Schneider Electric Buildings AB, June 2011 19 (74) 04-00067-02-en
Page 20
3 Technical Description TAC Xenta, TAC Xenta 280/300/401
3.1.4 Technical Data TAC Xenta 280
Note
For a complete list of updated technical data for the Xenta 280 controller, see the TAC Xenta 280 Programmable Controller datasheet (003-2248).
Program cycle time min. 1 s Universal inputs (TAC Xenta 281, 282: U1–U4):
A/D-resolution 12 bits –as Thermistor Inputs Supply voltage 0.6V DC
Thermistor inputs (B1–B2, only TAC Xenta 282):
A/D-resolution 12 bits Accuracy (Measuring range): –50 °C to –30 °C (–58 °F to –22 °F) ±4 °C (±7.2 °F) –30 °C to –10 °C (–22 °F to +14 °F) ±2 °C (±3.6 °F) –10 °C to +10 °C (14 °F to 50 °F) ±1 °C (±1.8 °F) +10 °C to +30 °C (50 °F to 86 °F) ±0.5 °C (±0.9 °F) +30 °C to +60 °C (86 °F to 140 °F) ±1 °C (±1.8 °F) +60 °C to +120 °C (140 °F to 248 °F) ±2 °C (±3.6 °F) +120 °C to +150 °C (248 °F to 302 °F) ±4 °C (±7.2 °F)
Thermistor inputs (B1–B4, only TAC Xenta 283):
A/D-resolution 10 bits Accuracy (Measuring range): –20 °C to –10 °C (–4 °F to +14 °F) ±2 °C (±3.6 °F) –10 °C to +10 °C (14 °F to 50 °F) ±1 °C (±1.8 °F) +10 °C to +30 °C (50 °F to 86 °F) ±0,5 °C (±0.9 °F +30 °C to +60 °C (86 °F to 140 °F) ±1 °C (±1.8 °F) +60 °C to +90 °C (140 °F to 194 °F) ±2 °C (±3.6 °F) +90 °C to +120 °C (194 °F to 248 °F) ±4 °C (±7.2 °F
TRIAC outputs (TAC Xenta 283 only, V1–V6)
Load may require auxiliary power (term. 40) of up to
Pulse length (TAC Menta DOPU block)
72 VA
min. 0.5 s
Analog outputs (TAC Xenta 281: Y1–Y3, TAC Xenta 282: Y1– Y4):
D/A-resolution 12 bits
a
:
20 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 21
TAC Xenta, TAC Xenta 280/300/401 3 Technical Description
a. If the active sensor (0–10V), analog actuators and the TAC Xenta con-
troller itself are supplied by the same transformer, the following re­strictions will ensure the specified accuracy (for thermistor inputs, universal inputs, and analog outputs):
Cable length from controller to: Transformer: 3 m (10 ft.) Active sensor/actuator: 20 m (65 ft.) Number of active sensors: max. 4 Number of actuators: max.6
Network communication (C1–C2, polarity insensitive):
Protocol FTT-10, L
ONTALK®
Communication speed 78 kbits/s
Other communication:
TAC Menta RS232, up to 9600 bits/
s, RJ45
TAC Vista (version IV or higher
TP/FT-10, screw term.
required), also for appl.pgm download TAC Xenta OP TP/FT-10, modular
jack

3.2 The TAC Xenta 300 Controller.

Fig. 3.5: The TAC Xenta 300 controller
3.2.1 Terminals
TAC Xenta 301 and 302
TAC Xenta 300 has two I/O configurations: TAC Xenta 301 and TAC Xenta 302.
Digital inputs
Thermistor inputs
Universal inputs
Relay outputs
Analog outputs
Term. notation
Schneider Electric Buildings AB, June 2011 21 (74) 04-00067-02-en
XB UKY
Page 22
3 Technical Description TAC Xenta, TAC Xenta 280/300/401
Digital inputs
Thermistor inputs
Universal inputs
Relay outputs
Analog
outputs TAC Xen ta 301 44 462 TAC Xen ta 302 44 444
max 230 V AC
K4 KC2 K3 K2 KC1 K1
Y4 M Y3 Y2 M Y1 G0 G
0
}
19-40 V DC
~
24 V AC or
Comm
X4
20
M
19
X3
18
X2
17
M
16
X1
15
B4
14
M
13
B3
12
B2
11
10
M
9
B1
8
U4
7
M
6
U3
5
U2
4
M
3
U1
2
C2
{
1
C1
40 39 38 37 36 35 34 33 32 31
30 29 28 27 26 25 24 23 22 21
TAC Xenta 301
max 230 V AC
K4 KC2 K3 K2 KC1 K1 K6 KC3 K5
Y2 M Y1
0
G0
~
G
24 V AC or
}
19-40 V DC
Comm
X4
20
M
19
X3
18
X2
17
M
16
X1
15
B4
14
M
13
B3
12
B2
11
10
M
9
B1
8
U4
7
M
6
U3
5
U2
4
M
3
U1
2
C2
{
1
C1
40 39 38 37 36 35 34 33 32 31
30 29 28 27 26 25 24 23 22 21
TAC Xenta 302
Fig. 3.6: The terminals of the TAC Xenta 301 and 302
Inputs
The TAC Xenta 300 controllers have twelve inputs:
Four thermistor inputs (labeled B1–B4)
Four universal (analog or digital, U1–U4)
Four digital (X1–X4). The universal inputs can be used for three types of signals:
TAC thermistor 1.8 kohm at 25 °C (the same as the thermistor inputs)
Voltage input 0–10V
Open/closed contact (the same as the digital inputs)
All controller inputs are protected from transients, in compliance with the EN 50082-1 norm.
Outputs
The TAC Xenta 300 controllers have eight outputs:
Analog — 0–10V DC outputs
Digital — relay potential-free outputs
22 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 23
TAC Xenta, TAC Xenta 280/300/401 3 Technical Description
3.2.2 Jacks
The TAC Xenta 300 has two modular jacks–one for the TAC Xenta OP operator panel and one for an RS232 connection with TAC Menta.
The socket for the operator panel provides it with 24V AC or DC, depending on the supply.
At distances greater than 10 m (32 ft.) between the TAC Xenta control­ler and the OP, an external power supply should be used. In addition, the communications connection has to follow the same rules as for other nodes.
Jack for the RS232/modem
Fig. 3.7: Location of jacks on the TAC Xenta 280 controller
3.2.3 LED Indicators and Service pin
The Service pin can be activated through a small hole on the front. Also on the front are two LED indicators–one red and one green.
Red service diode indicates a non-configured node or a hardware fault
Jack for the Operator panel
Service pin
Green status diode indicates that the program is running
Fig. 3.8: LED Indicators and Service Pin
The red service diode is primarily an error indication. It also lights up if the Service pin is activated.
The green status diode blinks once per second to indicate that the pro­gram is running.
Schneider Electric Buildings AB, June 2011 23 (74) 04-00067-02-en
Page 24
3 Technical Description TAC Xenta, TAC Xenta 280/300/401
3.2.4 Technical Data TAC Xenta 300
Note
For a complete list of updated technical data for the Xenta 300 controller, see the TAC Xenta 300 Programmable Controller datasheet (003-1302).
Real-time clock:
Power outage TAC Xenta 301 2
Program cycle time min. 1 s Universal inputs (U1–U4):
Quantity 4 –as Thermistor Inputs Supply voltage 0.6V DC
Thermistor inputs (B1–B4):
A/D-resolutiony 12 bits Accuracy (Measuring range): –50 °C to –30 °C (–58 °F to –22 °F) ±4 °C (±7.2 °F) –30 °C to –10 °C (–22 °F to +14 °F) ±2 °C (±3.6 °F) –10 °C to +10 °C (14 °F to 50 °F) ±1 °C (±1.8 °F) +10 °C to +30 °C (50 °F to 86 °F) ±0.5 °C (±0.9 °F) +30 °C to +60 °C (86 °F to 140 °F) ±1 °C (±1.8 °F) +60 °C to +120 °C (140 °F to 248 °F) ±2 °C (±3.6 °F) +120 °C to +150 °C (248 °F to 302 °F) ±4 °C (±7.2 °F)
Digital outputs (K1–K6 or K1–K4):
Control voltage, relay outputs to be protected by max. 10 A fuse Pulse length (TAC Menta DOPU
block)
Analog outputs (Y1–Y2 or Y1–Y4)
Quantity D/A-resolution 12 bits
Network communication (C1–C2, polarity insensitive):
Protocol FTT-10, L Communication speed 78 kbits/s
¨ min. 0.5 s
1
ONTALK®
1
If the active sensor (0–10V), analog actuators, and the TAC Xenta con­troller itself are supplied by the same transformer, the following restric­tions will ensure the specified accuracy (for thermistor inputs, universal inputs, and also for analog outputs):
24 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 25
TAC Xenta, TAC Xenta 280/300/401 3 Technical Description
12 13 14 15 16 17 18 20
Cable length from controller to: Transformer: 3 m (10 ft.) Active sensor/actuator: 20 m (65 ft.) Number of active sensors: max. 4 Number of actuators: max. 6

3.3 The TAC Xenta 401 Controller

Fig. 3.9: The TAC Xenta 401 controller
3.3.1 Terminals
3.3.2 Jacks
The TAC Xenta 401 controller uses four of the screw terminals–two for power supply and two for network communication.
24 V AC
(19-40 V DC)
Comm
}
}
~ 0
G G0 C1C2
1 2 3 4 5 6 7 8 9 10
11 12 13 14 15 16 17 18 19 20
Fig. 3.10: The terminals of the TAC Xenta 401
The TAC Xenta 401 has two modular jacks–one for the TAC Xenta OP operator panel and one for an RS232 connection with TAC Menta.
The socket for the operator panel provides it with 24V AC or DC, depending on the supply.
At distances greater than 10 m (32 ft.) between the TAC Xenta control­ler and the OP, an external power supply should be used. In addition, the
Schneider Electric Buildings AB, June 2011 25 (74) 04-00067-02-en
Page 26
3 Technical Description TAC Xenta, TAC Xenta 280/300/401
Jack for the RS232/modem
Jack for the Operator panel
Service pin
Red service diode indicates a non-configured node or a hardware fault
Green status diode indicates that the program is running
communications connection has to follow the same rules as for other nodes.
Fig. 3.11: Location of jacks on the TAC Xenta 280 controller
3.3.3 LED Indicators and Service pin
The Service pin can be activated through a small hole on the front. Also on the front, there are two LED indicators–one red and one green.
Fig. 3.12: LED Indicators and Service Pin
The red service diode is primarily an error indication. It also lights up if the Service pin is activated.
The green status diode blinks once per second to indicate that the pro­gram is running.
26 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 27
TAC Xenta, TAC Xenta 280/300/401 3 Technical Description
3.3.4 Technical Data TAC Xenta 401
Note
For a complete list of updated technical data for the Xenta 280 controller, see the TAC Xenta 400 Controller, freely programma- ble datasheet (003-1629).
Program cycle time min. 1 s Network communication (C1–C2; polarity insensitive):
Protocol FTT-10, L Communication speed 78 kbits/s
ONTALK®
Schneider Electric Buildings AB, June 2011 27 (74) 04-00067-02-en
Page 28
3 Technical Description TAC Xenta, TAC Xenta 280/300/401
28 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 29

TAC Xenta, TAC Xenta 280/300/401 4 Installation

4 Installation

4.1 Mounting the Controller

The TAC Xenta 280/300/401 controller is designed to be mounted on a DIN rail inside a cabinet. The controller can also be mounted directly on a wall. A wide range of standard enclosures meeting DIN 43 880, with different enclosure ratings, are available for wall mounting.
The enclosure primarily consists of a terminal part containing screw ter­minals, and an electronics part where the printed circuit boards are sit­uated. The enclosure is designed in such a way that the entire electrical installation can be connected to the screw terminals of the terminal part when mounted on a DIN rail or on a wall.
Fig. 4.1: The terminal part (left) and the electronics part (right) of the TAC Xenta 401
The operator panel can be mounted in the front of the cabinet or on top of a TAC Xenta controller, or it can be held in the hand.
Fig. 4.2: The TAC Xenta 280/300 controller and the TAC Xenta OP operator panel mounted on a DIN rail
Schneider Electric Buildings AB, June 2011 29 (74) 04-00067-02-en
Page 30
4 Installation TAC Xenta, TAC Xenta 280/300/401
148 – 2.0 (5.83 – 0.08)
4.0
(0.16)
48 – 0,5
(1.89–0.02)
16.1
(0.63)
180 (7.09)
77.4 (3.05)
45
(1.77)
110
(4.33)
180 + 0.4 (7.09 + 0.02) to the next TAC Xenta 280/300/3000 174 + 0.4 (6.85 + 0.02) to the next TAC Xenta 400/500/900
70 –2.0 (2.76 –0.08)
10.1
(0.40)
90 (3.54)
77.4 (3.05)
45
(1.77)
2 3 4 5 6 7 8 10
12 13 14 15 16 17 18 20
90 + 0.4 (3.54 + 0.02) to the next TAC Xenta 400/500/900 96 + 0.4 (3.78 + 0.02) to the next TAC Xenta 280/300/3000
4.0
(0.16)
48 – 0,5
(1.89–0.02)
110
(4.33)
Fig. 4.3: Mounting distances for TAC Xenta 280/300
Fig. 4.4: Mounting distances for TAC Xenta 401

4.2 Electrical Installation

4.2.1 General Considerations
The installation is normally treated as a CAT III category (IEC 664), in
30 (74) Schneider Electric Buildings AB, June 2011
principle entailing permanent connection to a 230V AC mains supply. For the TAC Xenta 280/300 and the I/O modules, this is only applicable to the relay outputs.
All equipment connected to the controller has to comply with the fol­lowing standards:
EN 60 742 (or other relevant safety standard; for example ETL
listing UL 3111-1, first version and CAN/CSA C22.2 No. 1010.1-
04-00067-02-en
Page 31
TAC Xenta, TAC Xenta 280/300/401 4 Installation
~ 0
24 V AC
(19-40 V DC)
}
1 2 3 4 5 6 7 8 9 10
G G0 C1C2
Comm
}
92) for the device(s) that provide an ELV-type power supply (nor­mally 24V AC) to the controller and other connected equipment.
EN 61 010 or IEC 950 (or other relevant safety standard) for com­puters, modems, and other equipment supplied by 230V mains.
If equipment using 230 V mains is connected to one of the relay output terminals on the controller, then low-voltage equipment connected to the other relay terminals on the controller must provide at least basic insulation on all touchable parts.
Caution
We strongly recommend that switches be installed to make it possible to separate the external equipment when the relay output terminals control equipment using the 230V mains.
Terminals G, G0 and C1, C2
Mount the terminal part of the
T AC Xenta 280, 300, or 40 1 on a DIN
rail.
Connect the cables to the correct terminals (see figure below).
For the TAC Xenta 401, put the electronics part of the controller on to the terminal part (the remaining terminals are not used).
Fig. 4.5: Terminals for power supply and network communication
Remaining terminals (TAC Xenta 280 and 300)
For information on the remaining terminal connection, see the datasheets:
TAC Xenta 280 Programmable Controller (003-2248)
TAC Xenta 300 Programmable Controller (003-1302)
Note
Do not use the unlabeled terminals!
Schneider Electric Buildings AB, June 2011 31 (74) 04-00067-02-en
Page 32
4 Installation TAC Xenta, TAC Xenta 280/300/401
1 2
G G0 U1 M U2 Y1 M Y2 B1 M B2 M U3
G1 G G0
G G0 M X
G G0 MX X1
TAC Xenta 280, 300 or 400 I/O module(s)
PU
230
VAC
G
G0
N
1 2 1 2
G G0 M S
G G0 M S
R =500 Ω
Insulated signal ground rail
Cabinet terminals
R
min 1.5 mm
2
(14 AWG), max 2 m (6.5 ft)
Cabinet ground rail
4.2.2 Cabinet Connections
When cabinet mounting is used, jumpers may be used between M (mea­surement neutral) terminal pairs, as shown in the figure below. All G0 points have to be connected to protective ground.
Fig. 4.6: Skeleton diagram for cabinet connections
When connecting G0 to ground, each TAC Xenta unit has to its own connection with the ground rail, that is, jumpers cannot be used for the G0 terminals. Please refer to the figure on the next page.
Several units may share the same ground rail, but every unit with mea­suring inputs and/or analog outputs has to have all its gr ound connec-
32 (74) Schneider Electric Buildings AB, June 2011
tions with the same ground rail. In other words, a discontinuity in the ground rail cannot be allowed to
split a controller or separate it from the connected units.
04-00067-02-en
Page 33
TAC Xenta, TAC Xenta 280/300/401 4 Installation
(14 AWG)
TR
G0
2
TAC Xenta 1
G0
PU
G0
TAC Xenta 2
G0
PU
G0
min 1.5 mm
Fig. 4.7: Connections between insulated signal ground rails and the cabinet ground rail
When a Wall Module (ZS101–105) is connected to the TAC Xenta 280 or 300, the following terminals can be used (term. B2: v 3.0 or later).
2
(14 AWG),
TAC Xenta 282 or 300
G G0 C2 C1 M B1 B2
G
X1 M K1 KC1
Insulated signal ground rail
230
VAC
min 1.5 mm max 2 m (6.5 ft)
G0
N
Cabinet ground
Cabinet terminals
rail
ZS 101-105
F0 F1 F2 F3G0 G C2 C1 1 2 3 4 5 6 7 8
2
1
0
3
470 Ω
10 kΩ
(24 V AC)
Fig. 4.8: Skeleton diagram for the connection of Wall Module ZS 101– 105 to TAC Xenta 282 or 300
Schneider Electric Buildings AB, June 2011 33 (74) 04-00067-02-en
Page 34
4 Installation TAC Xenta, TAC Xenta 280/300/401
4.2.3 Cables
G and G0 (Power supply): G, min. cross-sectional area 0.75 mm² (18 AWG) G0 to TAC Xenta, min. cross-sectional
area C1 and C2 (network): The FTT-10 system allows the user to wire the control devices with
virtually no topology restrictions. Min. cross-sectional area 0.65 mm² (18 AWG) Note that the max. wire distance in one segment depends on the type
of wire and the topology. The wires are polarity insensitive, but they have to be a twisted-pair.
Terminals X (Digital inputs): Min. cross-sectional area 0.25 mm² (22 AWG) Max. cable length 200 m (660 ft.) Terminals U (Universal inputs as digital inputs): Min. cross-sectional area 0.25 mm² (22 AWG) Max. cable length 200 m (660 ft.) Terminals U (Universal inputs, device powered via
the same transformer as the base unit): Min. cross-sectional area 0.75 mm² (18 AWG) Max. cable length 20 m (65 ft.) Terminals U (Universal inputs, measurement device powered via
their own transformer, external or internal): Min. cross-sectional area 0.25 mm² (22 AWG) Max. cable length 200 m (660 ft.) Terminals B, U (as thermistor inputs): Min. cross-sectional area 0.75 mm² (18 AWG) Max. cable length
up to 75 °C, cross-sectional area 0.75 mm²75 m (250 ft.) up to 75 °C, cross-sectional area 1.5 mm²150 m (500 ft.) up to 150 °C, cross-sectional area 1.5 mm²75 m (250 ft.)
Terminals K1–K6 (Relay outputs): Cross-sectional area 0.75 – 1.5 mm² (18–14
Max. cable length 200 m (660 ft.) Terminals V1–V6 (TRIAC outputs): Cross-sectional area 0.75 – 1.5 mm² (18–14
1.5 mm² (14 AWG)
AWG)
AWG)
34 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 35
TAC Xenta, TAC Xenta 280/300/401 4 Installation
Max. cable length 200 m (660 ft.) Terminals Y (Analog outputs, for actuator powered via
the same transformer as the base unit): Min. cross-sectional area 0.75 mm² (18 AWG) Max. cable length 20 m (65 ft.) Some actuators allow greater cable length, for example:
EM52 0.5 mm².(20 AWG)80 m(260 ft.)three wires EM15LBB0.75 mm²(18 AWG)80 m(260 ft.)three wires EM420.75 mm²(18 AWG)80 m(260 ft.)four wires TAC Forta0.75 mm²(18 AWG)80 m(260 ft.)four wires
Terminals Y (Analog outputs, for actuator powered via their own transformer, ext. or int.; or when the outputs have isolated converters):
Min. cross-sectional area 0.25 mm² (22 AWG) Max. cable length 200 m (660 ft.)
TP/FT-10 Free Topology & Bus Topology Segments
Five cable types have been validated for the TP/FT-10 channel (for use with the FTT-10A Free Topology Transceiver and LPT-10 Link Power Transceiver). These cable types are:
Cable Bus Topology Free Topology
Type AWG
Belden 8471 (PVC Jacket) or equivalent
Belden 85102 (PVC Jacket) or equivalent
Category 5 24AWG 0.5 900 3 450 250
Level IV cable 22AWG 0.65 1400 3 500 400
JY (st) Y 2X2X0.8
16AWG 1.3 2700 3 500 400
16AWG 1.3 2700 3 500 500
20.4AWG 0.8 900 3 500 320
Diameter
(mm)
If a Loop is used, the bus polarity has to be observed:
Length
(m)
Stub
(m)
Length
(m)
Stub
(m)
Schneider Electric Buildings AB, June 2011 35 (74) 04-00067-02-en
Page 36
4 Installation TAC Xenta, TAC Xenta 280/300/401
Fig. 4.9: Bus polarity within a loop
TP/XF-1250 Bus Topology Segment
Two cable types have been validated for the TP/XF-1250 channel (for use with the TPT/XF-1250 Bus Topology Transceiver). These cable types are:
Cable Type AWG Diameter Bus
TIA 568A Category 5 Cable
Level IV Cable 22AWG 0.65 mm 130 m 0.3 m
24AWG 0.5 mm 130 m 0.3 m
For the TP/FX-1250 Channel operating in a bus topology, the maximum bus length of TIA 568A Category 5 cabling is 130 meters, with a max­imum stub length of 0.3 meters. There are topology restrictions associ­ated with the use of this channel - refer to www.echelon.com.
Note
If a shielded cable is used in TP/FT-10, the shield shall be con­nected to link power source that is ground to a 470kW, 1/4Watt, > 10%, metal film resistor to prevent static charge buildup.
A gas discharge tube can be connected in parallel with the resistor for lightning protection.
A restriction for TP/XF-1250 is the 8-in-16 rule, which says that the number of nodes in an arbitrary 16-meter section of the cable cannot exceed eight.
If circumstances require that more nodes have to be gathered at a certain part, this can be done in two ways, while still observing the rule.
1 Add more cable between suitable nodes; remember, though, that
the maximum length of the bus is still 130 m.
2 Split the channel in two by inserting a router in such a way that the
rule is observed for each part.
36 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 37
TAC Xenta, TAC Xenta 280/300/401 4 Installation
TAC Xenta 1
C1 C2
C1 C2
C1 C2
C1 C2
TAC Xenta 1
TAC Xenta 2
TAC Xenta 2
470 kΩ
¼ W
If a shielded communication cable is used, the shield can only be grounded at one point.
Redundant wires (second pair of Siemens J-Y(st)Y) are cut at the end of the shield.
Fig. 4.10: Connecting the communication cable
Schneider Electric Buildings AB, June 2011 37 (74) 04-00067-02-en
Page 38
4 Installation TAC Xenta, TAC Xenta 280/300/401
5
4
3
2
1
9
8
7
6
GND (Red)
RxD-TxD (Green)
TxD-RxD (Y ellow)
1 3 5 7
2 4 6 8
~10 cm
(4")
TAC Xenta
Modular jacks, 8/8 male, emission damper and cable
Modular jack, female (from inside of adapter)
D9, female (from inside of adapter)
TAC Xenta
RS232 RS232
PC
TxD
RxD
GND
G0G
0 V
230 V
24 V
Earth current in GND wire
Transformer
Transformer
RS232
Modular jack for RS232 serial comm. portmax. 10 m (32 ft.)
Fig. 4.11: RS232 cable connections and adaptor for PC
Caution
The G terminal of the TAC Xenta should never be connected to protective ground. This may cause a short-circuit via a Laptop, where the earth of the RS232 port is directly connected to protec­tive ground in the power supply.
Fig. 4.12: Incorrect G, G0 connection, short-circuited via the RS232 connection.
38 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 39
TAC Xenta, TAC Xenta 280/300/401 4 Installation
13
12
11
10
9
8
7
6
5
4
3
2
1
25
24
23
22
21
20
19
18
17
16
15
14
1 3 5 7
2 4 6 8
DCD
GND
DSR
CTS
RTS
RxD
TxD
DTR
Modular jack, female (from inside of adapter)
D25 male
This type of connection has to be avoided. One way to protect the cir­cuits is to use battery power on the laptop if you are uncertain of the con­nections.
TAC Xenta
RS232 RS232
G0G
24 V
TxD
RxD
GND
Fig. 4.13: Correct G, G0 connection
PC
230 V
0 V

4.3 Terminations

Schneider Electric Buildings AB, June 2011 39 (74) 04-00067-02-en
Fig. 4.14: RS232 connection between the TAC Xenta controller and a modem
Each network segment requires a termination for proper data transmis­sion performance. The terminations are connected differently, depend-
Page 40
4 Installation TAC Xenta, TAC Xenta 280/300/401
To Network
C1
+
R1
C2
+
C1, C2: 100 mF, >50 V R1: Resistance: see the text 1%, 0,125 W
ing on the network topology. Terminations are sometimes built into a node in, for example, a linked power supply.
Free Topology Segment
In a Free Topology segment only one termination is required and can be placed anywhere on the segment.
If there is a router or a repeater, it is convenient to put the termination near it, generally on the “downstream” side.
If there is a supervisory PC in the segment equipped with a PCLTA board, a termination on the board can be connected for this segment.
Doubly Terminated Bus Topology Segment
In a doubly terminated bus topology, exactly two terminations are required – one at each end of the segment – at the true endpoints.
TP/FT-10
The termination is built from the following components, where a total termination impedance of approximately 53
Ω is required.
Fig. 4.15: Network Terminator for a TP/FT-10 connection
Observe polarity shown for C1 and C2. These capacitors are recom­mended.
Free topology: one termination with R1 = 52,3 W Doubly terminated bus topology: two terminations, one on each end of
the segment, each with R1 = 105 W. A LonWorks termination device (single/double) is available from
Schneider Electric, part no. 007309051.
40 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 41
TAC Xenta, TAC Xenta 280/300/401 4 Installation
.15 μF 10%
.33 μF 10%
59
Ω
1%
340
Ω
1%
102
Ω
1%
TP/XF-1250
Doubly terminated bus topology. The termination has a different circuit diagram from that of TP/FT-10.
Fig. 4.16: Network Terminator for a TPT/XF-1250 connection
With the free topology, connections may be made anywhere on the seg­ment and only one terminator is required.
The total length of all wires of the segment, can be up to 500 m under optimal conditions. Stub length 3 m.
With the bus topology two terminations - one at each end - are required. When a TP/FT-10A channel is used, the total length of all wires of the
segment can be up to 2700 m, under optimal conditions. If a TP/XF­1250 channel is used, the total length of all wires of the segment can be up to 130 m, under optimal conditions. Stub length 0.3 m.
Schneider Electric Buildings AB, June 2011 41 (74) 04-00067-02-en
Page 42
4 Installation TAC Xenta, TAC Xenta 280/300/401
4
3
21
C1 C2 G G0
Socket and screw terminals for TAC Xenta controller connection
TAC Xenta controller
Socket for connection to operator panel
4.3.1 The TAC Xenta OP Operator Panel
Cable between the controller and the operator panelmax. 10 m (32 ft.) There are two ways to connect the operator panel (see figures below):
Use the modular socket on the front of the TAC Xenta controller and on the back of the operator panel. A modular jack 4/4 cable is supplied with the OP for this purpose.
Use the screw terminals, labeled 1–4, located on the back of the operator panel. T erminals 1 and 2 are used for communication and terminals 3 and 4 for 24V AC.
Fig. 4.17: The OP panel
To adjust the contrast of the display, use the potentiometer on the rear of the operator panel.
Normally, there is a logout time once you have logged into the OP. It is, however, possible to override this timeout and obtain a permanent display by setting a bit in the SYSREG block. Please refer to the TAC Vista IV, Engineering Applications in TAC Menta manual.
42 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 43
TAC Xenta, TAC Xenta 280/300/401 4 Installation
Options for connecting the OP to the Controller
Modular jack
G0 G C2 C1
4321
TAC Xenta OP
C1 C2 G G0
4321
Fig. 4.18: Modular jack for connection of TAC Xenta OP to TAC Xenta 280/300/401 or to a separate jack
max. 10 m (32 ft.)
TAC Xenta Controller TAC Xenta OP
G0 22 G21 C2 2 C1 1
G0 4 G3 C2 2 C1 1
Fig. 4.19: Terminal connection TAC Xenta 280/300/401 - TAC Xenta OP, power supply from controller
230 V / 24 V
TAC Xenta Controller TAC Xenta OP
G0 22 G21 C2 2 C1 1
0
~
G0 4 G3 C2 2 C1 1
Fig. 4.20: Terminal connection TAC Xenta 280/300/401 (or the network directly) - TAC Xenta OP, local power supply
Schneider Electric Buildings AB, June 2011 43 (74) 04-00067-02-en
Page 44
4 Installation TAC Xenta, TAC Xenta 280/300/401
44 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 45

TAC Xenta, TAC Xenta 280/300/401 5 Configuring your System

PC
TAC Menta:
- Address allocation
- Download application
- Online simulation
TAC Xenta controller
(Part no. 0-073-0920)
RS232
5 Configuring your System

5.1 Overview

A TAC Xenta 280/300/401 controller is delivered as a freely program­mable controller. A customer-specific application is created using the programming tool TAC Menta.
A PC that has TAC Menta installed and running is connected, using the Programming Serial Kit cable (part no. 007309200), to the RS232 port of the TAC Xenta controller to be loaded. How this is done is described in the Engineering Applications in TAC Menta manual.
During the customizing process, the online/simulation mode of TAC Menta can also be used to monitor the input and output status of the TAC Xenta controller. Parameter tuning can also be done from TAC Menta.
Note
Starting from TAC Xenta v 3.1, the application program down­load may also be done from TAC Vista via the network.
However, the online/simulation mode in TAC Menta still has to use the RS232 port.
Fig. 5.1: Commissioning tool (principle of operation)
Devices have to be configured in the following situations:
When there are I/O modules (see sections 5.3 and 5.4 of this man­ual)
When there are several controllers (see section 5.5 of this manual)
Schneider Electric Buildings AB, June 2011 45 (74) 04-00067-02-en
Page 46
5 Configuring your System TAC Xenta, TAC Xenta 280/300/401

5.2 A Single TAC Xenta 280/300/401 Controller

5.2.1 Initial Check
Caution
TAC Xenta 280/300: It is important that the electronics part has the same input/output configuration as the terminal part.
After the wires have been connected, but before the electronics part has been mounted on the terminal part, perform these checks:
1 Turn on the power. 2 Check that the supply voltage, 24V AC or 19–40V DC, is con-
nected to the proper terminals G and G0.
3 T AC Xenta 280/300: Check that the voltage levels of the input and
output terminals are appropriate, bearing in mind their use and possible preset values.
4 TAC Xenta 280/300: Check the voltage, both AC and DC,
between G0 and the other (labeled) terminals.
5 Repeat step 4 with G as the reference terminal. 6 Turn off the power and mount the electronics part on the terminal
part.
7 Turn on the power again. 8 If previously unloaded, load the program, using TAC Menta,
according to the method described in the Engineering Applications in TAC Menta manual.
9 Check that the green status LED on the front starts to blink, indi-
cating that the internal program is running.
Service pin
Red service diode indicates a non-configured node or a hardware fault
Green status diode indicates that the program is running
Neuron ID (on the rear)
Fig. 5.2: LEDs and service pin in the controller
10 If additional I/O-units are used, follow the steps in section 5.4.
46 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 47
TAC Xenta, TAC Xenta 280/300/401 5 Configuring your System
Network address:
- Subnet no. 1
- Node no. 10
TAC Xenta
Device name:
CU_1
PC
RS232
Device Configuration tool
Device name:
CU_2
Network address:
- Subnet no. 1
- Node no. 20
TAC Xenta
TAC Xenta controller
5.2.2 OP Panel Activities
1 Connect the TAC Xenta OP to the TAC Xenta unit. 2 TAC Xenta 280/300: Select the Temp & Status menu (or equiva-
lent) to check that all inputs have appropriate values.

5.3 Two or more TAC Xenta 280/300/401 Units

5.3.1 Initial Check
Perform the steps described in section 5.2.1.
5.3.2 Device Configuration
Before it can start to communicate, each TAC Xenta unit has to be assigned a network address (a subnet/node address and a device name). This is done using a separate Device Configuration programming tool. The tool is either run on a PC and started from TAC Menta or it is run as a stand-alone tool.
The procedure is fully explained in the Engineering Applications in TAC Menta manual.
If two or more units have the same Device name, they have to be given unique names. This is also done using the Device Configuration tool.
The figure below indicates some of the parameters that are involved. The use of network addresses is explained in the TAC Vista IV, Engi- neering Classic/LNS Networks manuals.
Fig. 5.3: Device Configuration parameters (example)
Schneider Electric Buildings AB, June 2011 47 (74) 04-00067-02-en
Page 48
5 Configuring your System TAC Xenta, TAC Xenta 280/300/401
5.3.3 OP Panel Activities
When an operator panel is connected to a network that includes a num­ber of TAC Xenta controllers, the following will happen:
1 The operator panel (OP) will send a request to the network for any
TAC Xenta controller that is not occupied to start acting as a server and send texts to the operator panel.
2 The first available Xenta controller will send a list of all the
groups in the network. These will be shown on the OP and when one of them has been selected, the TAC Xenta controllers of the group will be shown on the operator panel. As all TAC Xenta con­trollers know which other TAC Xenta controllers are present in the network, an operator panel can be served by any TAC Xenta controller in the network.
3 From this list, the desired TAC Xenta controller will be chosen by
the user, and the controller that first acted as a server will be released from its duties.
4 The selected TAC Xenta controller will then supply the operator
panel with the menu on the highest level in the program.
5 TAC Xenta 280/300: Select the Temp & Status menu (or equiva-
lent) to check that all inputs have reasonable values.
6 Now select another controller from the top menu and repeat steps
5-6, as many times as required.

5.4 Additional I/O Units

5.4.1 Selecting I/O Modules
There are two types of I/O modules:
Configured (older, for older versions of the Base unit)
Unconfigured (newer, for Base units of version 3.2 or higher)
Note
The TAC Xenta 280 does not use extra I/O modules.
48 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 49
TAC Xenta, TAC Xenta 280/300/401 5 Configuring your System
Service pin
Neuron ID (on the side)
Service LED: red ind. = hardware fault
Comm. status LED, green flashing light:
• once every other sec: communication with Base unit
• faster: the unit is off-line
5.4.2 Initial Check
Note
It is important that the electronics part has the same input/output configuration as the terminal part.
Perform these checks after the wires have been connected to the I/O modules, but before the electronics part has been mounted on the termi­nal part.
1 Turn on the power. 2 Check that the supply voltage, 24V AC or 19–40V DC, is con-
nected to the proper terminals (G and G0).
3 Check that the voltage levels of the input and output terminals are
appropriate, bearing in mind their use and possible preset values.
4 Check the voltage, both AC and DC, between G0 and all the other
terminals.
5 Repeat steps 1-4 with G as the reference terminal. 6 Turn off the power and mount the electronics part on the terminal
part.
7 Turn on the power again. 8 Check the LEDs for the following:
The red service LED on the front will now blink once.
The green communication status LED on the front starts
flashing rapidly (about 2-3 Hz), indicating that the unit is off­line.
Fig. 5.4: LEDs and service pin of the I/O modules
5.4.3 I/O Module Configuration
Schneider Electric Buildings AB, June 2011 49 (74) 04-00067-02-en
An I/O module always belongs to a specific TAC Xenta controller. Before the module can be utilized, it has to be linked to that controller by using the Device Configuration programming tool. The tool is either run on a PC and started from TAC Menta or it is run as a stand-alone tool.
Page 50
5 Configuring your System TAC Xenta, TAC Xenta 280/300/401
The procedure is described in the manual Engineering Applications in TAC Menta.
In some versions of TAC Xenta OP, these items can also be set from the Service menu. This is described in chapter 6 (‘IO Module Config’) of this manual. Please note that this menu can only be reached from the Service access level.
The figure below indicates some of the parameters that are involved. The use of network addresses is described in the TAC Vista IV, Engi- neering Classic/LNS Networks manuals.
Device Configuration
PC
tool
RS232
TAC Xenta
I/O
Module no.: 1 Module type: 421
I/O
Module no.: 2 Module type: 411
Network address:
- Subnet no. 1
- Node no. 10
Network address:
- Subnet no. 1
- Node no. 13
Fig. 5.5: I/O module configuration parameters (example)
About 45 seconds after the configuration procedure has completed, the green LED should start to blink at a rate of about once every other sec­ond. This will indicate that the unit is communicating with the applica­tion in the Base unit.

5.5 Setting the Date and Time

Set the current date and time from TAC Menta during commissioning (Online mode). The setting affects only the controller that is connected to TAC Menta. Please refer to the Engineering Applications in TAC Menta manual for further details.
Date and time can also be set from the TAC Xenta OP, if the operator has logged on at the appropriate access level (usually the medium level). For details, refer to the TAC Xenta OP Handbook.
If the controllers are connected to a supervisory system like TAC Vista, the date and time can be set in all units with one command from TAC Vista.
Network address:
- Subnet no. 1
- Node no. 14
A TAC Xenta Master unit broadcasts its clock time once every 24 hours.
In both cases, the date and time are sent periodically. This will ensure that even if some units are offline when the time data is sent, they will eventually be updated with the values from the central system or, with regards to standalone, from the Master.
50 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 51
TAC Xenta, TAC Xenta 280/300/401 5 Configuring your System
1 3 5 7
2 4 6 8
DTR CTSDCD
Modular jack (seen from the underside, with the fastening flap)
2 DCD 3 DTR 7 CTS
TAC Vista sends the time in GMT format. The time value is trans­formed in each separate TAC Xenta to the valid time zone and the cur­rent standard or daylight saving time.

5.6 Clearing the Xenta Application

If a Xenta 280/300/401 application has crashed and refuses to accept a new download, both from Vista and Menta, there is a way to clear the application (Xenta version 3.61 or higher).
1 Manufacture a jack with the following pins short-circuited.
Fig. 5.6: A “Clear application” device
2 Turn off power to the controller. 3 Put the jack in the RS232 port. 4 Turn on power to the controller; a forced Clear Application will be
made.
5 Remove the jack.

5.7 Lock a Xenta OP to a specific TAC Xenta Controller

You can lock a Xenta OP to a specific TAC Xenta 280/300/401 control­ler.
To be able to do this you have to enable the function by adding a PVI block in the Menta application in the Xenta and enable the function in the Xenta OP.
5.7.1 Creating the PVI-block in the Xenta
1 Create a Public PVI-block with the name XENTASYSREG and
set this block’s initial value to 8.
Schneider Electric Buildings AB, June 2011 51 (74) 04-00067-02-en
Page 52
5 Configuring your System TAC Xenta, TAC Xenta 280/300/401
Fig. 5.7: XENTASYSREG With the initial value to 8
If you have multiple TAC Xenta OP panels in the network, each one connected to a specific Xenta Controller, you have to create this special PVI block in every one of these Xenta Controller’s Menta code.
5.7.2 Enabling the function in TAC Xenta OP
1 Open the TAC Xenta OP local service menu. 2 Press and hold the “escape” and “enter” buttons for a few seconds. 3 Enter the bottom command: “11 OP connects to”. 4 Enter this sub-command, and then type in, using “+” or “-“, the
specific T AC Xenta controller’ s subnet and node you want t his OP to be “locked” to.
The TAC Xenta controller subnet and node addresses can easily be found in TAC Vista Workstation; select “properties” for the TAC Xenta controller and the subnet / node will be displayed.
Note
When you select, in the OP panel’s new menu, the node number and press enter the TAC Xenta OP will restart and seek for the selected TAC Xenta controller.
It will still be possible to access the TAC Xenta controller from another T AC Xenta OP in the network if the TAC Xenta OP is of a version prior to 3.70 or if the lock-function is not enabled in the TAC Xenta OP. Ho wever doing t his, you will only h ere also “see the local Xenta controller”. In this case you will be able to exit this TAC Xenta controller again by pressing “escape”. While in the locked TAC Xenta OP you will not be able to exit from the TAC Xenta controller it is locked to.
52 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 53

TAC Xenta, TAC Xenta 280/300/401 6 The TAC Xenta Service Menu

TAC Service menu
1. Name
2. LON Address
3. Wink
4. Restart
5. IO Module Config
6. Test Dial
7. System info
6 The TAC Xenta Service Menu

6.1 Accessing the Service Menu

When a TAC OP is connected to a TAC Xenta controller 280, 300, or 401, menus appear on the display.
Use the password-protected Service menu for system information and actions.
Schneider Electric Buildings AB, June 2011 53 (74) 04-00067-02-en
Fig. 6.1: Connecting TAC Xenta OP (left) to the controllers 300 or 401 (right).
The Service menu has the following options (the frame symbolizes the four-line display window of the OP):
Page 54
6 The TAC Xenta Service Menu TAC Xenta, TAC Xenta 280/300/401
AHU2: West Status Temperature
Alarm . .
Password
Password
CODE:
Enter code to
extend menu
. .
Status
Password
Service menu
To access the Service menu, press “Enter” ( ) directly after start­up. The menu will look something like this:
Move the cursor to Password and press Enter to get:
Enter the code ”1919” by using + or – , Enter and finally “Home” ( ). The Start-up menu reappears.
The bottom line will now include the Service menu option.

6.2 Submenus 1-8

Submenu 1: Device Name and
Submenu 2 Lon address
To get the Name and address of a specific controller:
1 Disconnect the controller from the network. 2 Connect the OP to this unit and select the Service menu, where the
name and address can be checked. Please note that this menu is only available from the “Service” access level.
3 Select submenu “
1. Name” or ”2. LON address”:
54 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 55
TAC Xenta, TAC Xenta 280/300/401 6 The TAC Xenta Service Menu
Name
LON address
Subnet: 1
Node : 10
Wink node
While pressing HOME,
LED stays ON for
3 seconds.
Restart type: _
0:No restart
1:Warm 2:Cold
3:Orig. appl.
Reconnect the unit to the network.
Repeat steps 1–4, as many times as required.
Submenu 3: Wink node
In some cases, it may be necessary to know which physical unit corre­sponds to a certain node address. Select submenu “
3. Wink”:
1:Warm
2:Cold
3:Orig. appl.
When you press the Home key ( ), the green status diode of the selected Base unit will light up for about three seconds.
Submenu 4: Restart
There are different types of restarts. These are selected from submenu “
4. Restart”:
Upon restarting, parameters and values will be retrieved as follows (also refer to Appendix 1, Restart Values):
Most values according to the ones already present in RAM.
Most values are reset to the original, downloaded application, except for saved PV Block values, Public parameters,
and certain OPT values.
Resets all values to the original, downloaded application.
Submenu 5: IO module Config, Configuring I/O modules via the OP
Schneider Electric Buildings AB, June 2011 55 (74) 04-00067-02-en
Chapter 5 contains information about configured and unconfigured I/O modules, as well as instructions for “Initial checks” on the newly con­nected units.
Page 56
6 The TAC Xenta Service Menu TAC Xenta, TAC Xenta 280/300/401
T AC Xent a
I/O
I/O
Module no.: 1 Module type: 421
LonTalk
protocol
Module no.: 2 Module type: 411
Network address:
- Subnet no. 1
- Node no. 10
Network address:
- Subnet no. 1
- Node no. 13
Network address:
- Subnet no. 1
- Node no. 14
IO Module Config
Module No: 1
Node Addr.: 13
Valid Service Pin: 0
An I/O module always belongs to a specific TAC Xenta controller (the Base unit). Before an I/O module can be utilized, it has to be linked to that controller.
To do this, go to menu “
5. IO Module Config”.
The I/O modules will automatically get the same Subnet number as the base unit. Normally, this is the number that should be used.
The figure below indicates the parameters that are involved.
Fig. 6.2: I/O module configuration parameters (example)
1 On the operator panel, select the list of controllers on the network. 2 Select the TAC Xenta to configure. 3 Select submenu “5. IO Module Config” and enter the address
value:
4 Press the service pin on the corresponding unit (see diagram
below). Following this, Valid Service Pin: 0 should change to 1.
5 Press Enter to confirm the configuration within 20 seconds or so. 6 About 45 seconds after configuration has finished, the green LED
will start blinking slowly , showing that the unit is communicating with the Base unit.
7 Repeat steps 3–6 if there is a second I/O module. 8 Repeat steps 2-7 for all the listed controllers with I/O modules.
56 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 57
TAC Xenta, TAC Xenta 280/300/401 6 The TAC Xenta Service Menu
Service pin
Red service diode indicates a non-configured node or a hardware fault
Neuron ID (on the rear)
Green status diode indicates that a program is running
Please note the angle of the screwdriver being used to activate the service pin! Upon activation, the red service diode will flash momentarily.
Service pin
Neuron ID (on the side)
Comm. status LED, green flashing light:
• once every other sec: communication with Base unit
• faster: the unit is off-line
Fig. 6.3: LEDs and service pin of the controller (Base unit)
Fig. 6.4: Activating the service pin of the controller or the I/O module
Fig. 6.5: LEDs and service pin of the TAC Xenta 400 I/O modules
6.2.1 Submenu 6: Test dial
This function is used in dial-up systems (not applicable to the TAC Xenta 280) and is explained in the TAC Vista IV, Engineering Classic/LNS Networks manuals.
Schneider Electric Buildings AB, June 2011 57 (74) 04-00067-02-en
Page 58
6 The TAC Xenta Service Menu TAC Xenta, TAC Xenta 280/300/401
Test dial
Dial 0
Status 08
0000 0000 0010 0100
9 Select “6. Test dial” and the following menu will appear:
10 On Dial use:
•The value 0 for the normal telephone number
or toggle to
•The value 1 for the alternative telephone number
11 Press Enter to initiate a dial-up between the controller and a super-
visory system.
The two Status lines will display codes containing information about the procedure as described below.
(Dynamic) Status (upper integer value) shows the progress of the dial-up sequence.
Code Meaning
IDLE 00 This is the state before any attempts to dial have been made.
LINE_BLOCKED 01 The line was blocked.
NO_DIAL_STRING 02 No dial string was defined, so no dial attempt was made.
SENDING_DIAL_STR. 03 We are either in the process of sending the dial string to the modem or
waiting for the response.
BUSY 04 The line was busy.
NO_ANSWER 05 No one picked up the phone at the other end.
NO_CARRIER 06 There was no modem at the other end which could answer.
ERROR 07 Something was wrong with the dial string.
NO_DIAL_TONE 08 No normal dial tone.
TIMEOUT 09 The modem did not reply to the dial string at all.
CONNECT 10 We are connected to the remote modem.
NO_LOGIN_REPLY 11 Attempting to log in, but no reply from TAC Vista.
LOGIN_FAIL 12 Our password (and/or network ID) was not accepted by TAC Vista.
LOGIN_OK 13 Connection established!
58 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 59
TAC Xenta, TAC Xenta 280/300/401 6 The TAC Xenta Service Menu
Date: 2002-02-11 Ver: X300 3.50 By: TAC 302NP (Neuron ID: 12 chars)
(Static)
Status (lower 16-bit string) pertains to the modem and communication envi-
Code Meaning
---- ---- ---- ---1
---- ---- ---- --1-
---- ---- ---- -1--
---- ---- ---- 1---
ronment, that is, the availability of the modem and other communica­tion issues.
DSR is set when TAC Xenta detects that the modem is driving the Data Set Ready line. Possible reasons for DSR being low: modem not connected, modem not powered on, DSR line not connected in the cable.
AT OK is set when TAC Xenta has sent an AT command to the modem and received an OK reply. Possible reasons for not receiving AT OK: modem configured to not respond to modem commands.
Reset OK is set when AT OK is not set and TAC Xenta has sent an AT&F sequence ordering the modem to reset to the factory defaults, and an OK reply was received. Possible reasons for not receiving Reset OK: RX line not connected in the cable or the modem is config­ured to not respond to modem commands.
Init string defined is set when TAC Vista has defined a modem initial­ization string.
---- ---- ---1 ----
---- ---- --1- ----
---- ---- -1-- ----
---- ---- 1--- ----
Init OK is set when the Init string defined is set and TAC Xenta has sent the init string and received an OK reply. Possible reasons for not receiving Init OK: the init string contained a command that has turned replies off, the init string contained an illegal command.
No contact.
Ready.
Phone number defined is set when TAC Vista has defined a modem dial string.
Submenu 7: System info and
Submenu 8: Boot info
To obtain information about the controller program version, select sub­menu “
7. System info”.
Schneider Electric Buildings AB, June 2011 59 (74) 04-00067-02-en
Page 60
6 The TAC Xenta Service Menu TAC Xenta, TAC Xenta 280/300/401
Date: 2002-02-11 Ver: X400 B 3.52-01 By: TAC
To obtain information about the Boot program, select submenu
8. Boot info”.
60 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 61

APPENDIX

A Appendix A Restart Values
B Appendix B Restart Sequences
Page 62
Page 63

TAC Xenta, TAC Xenta 280/300/401 A Appendix A Restart Values

A Appendix A Restart Values
There are two kinds of memory in the controller: 1 RAMworking memory, cu rrent val ues;
the contents will be lost after 72 hours without power 2 Flash program memory, nonvolatile storage memory Certain items which are used in RAM are also saved in the Flash mem-
ory when the value is changed, so that they will not be lost during lengthy power outages.
The Flash memory is also the location of the original application and the trend log definition values. These are the values specified in the most recent application downloaded from TAC Menta.
During a restart, whether caused by a power outage or by operator demand, it is important to know which start values will apply.
Below are some examples of the value as taken from RAM, from the value saved in Flash memory, or from the original application value (also in Flash memory).
Internal status and output values of Function Blocks
(may affect the control of actuators, fans, or other equipment)
PV Blocks, for example, the set values
(it may be important not to lose the newly adjusted set values)
Public parameters
(values which affect other nodes of the plant)
Trend log definition
(log channels, log interval, storage area)
Trend log data
(stored values)
Optimization parameters
(automatically adjusted values, taking a long time to settle)
Time parameters
(local time zone, current Daylight Saving Time status)
Modem parameters
(such as phone numbers, dial-up interval, and initialization com-
mands) During a restart, the system has to have usable start values in the work-
ing areas of RAM. The start values used will depend on:
Schneider Electric Buildings AB, June 2011 63 (74) 04-00067-02-en
Page 64
A Appendix A Restart Values TAC Xenta, TAC Xenta 280/300/401
which type of restart has been ordered,
Whether or not the content of RAM is still valid (< power outage
) and
72 h after a
Whether or not the Backup boxes for the Function and PV Blocks in TAC Menta have been checked
If the Backup box has been checked, this means that as soon as a value has changed, the system will save it and use it as a start value during a Warm start and, with regards to the PV Blocks, during a Cold start as well.
The Public parameters (which do not use RAM at all) and certain calcu­lated OPT values are always saved in the Flash memory.
The table below shows the principal storage locations.
Value Backup
Stored in
indication
Status and output values of Function Blocks x (default) RAM
PV Blocks x (default) Flash
Public parameters (always) Flash
Trend log definition (always) Flash
Trend log data (always) RAM
Certain OPT values (always) Flash
Time parameters (always) Flash
Modem parameters (always) Flash
Applied to the three types of restart, this gives us:
Warm start (operator request or due to power outage <72 h; RAM intact)
Almost all values are the current ones, kept in RAM; among them are the trend log definitions and data. An event is added to the trend log data, stating that a Warm start has occurred.
Exception: Function Block internal state values, if Backup was not checked, in which case the original values will be used instead.
Cold start (operator request or due to power outage >72 h; RAM not intact)
Almost all values (for example all Function Block internal state values) are retrieved from the original application values resident in the Flash memory. The trend log definitions are re-stored in the RAM, based on the stored values in the Flash memory, while the trend log values are being cleared.
64 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 65
TAC Xenta, TAC Xenta 280/300/401 A Appendix A Restart Values
Exceptions:
Original application
The table below shows the status that the different start values will have during different types of restart.
Value Backup
indication
FB internal state values
x –
The most recently stored PV Block values, if Backup was checked:
- Public constants
- Trend log definitions
- Certain OPT values
- Modem parameters
All start values are retrieved from the original application values resident in the Flash memory. All SNVT bindings (version 3.0 and later) are erased.
“Original application” means the most recent application that has been downloaded from TAC Menta.
(If no application has been loaded, there is always the LonMark ”Plant Controller” application shipped from the factory.)
Restart type:
Warm start (<72h)
Current value
Original value
2
a
Cold start Original appl.
b
Original value
Current value
Original value
Current value
b
PV Block x
Current value
Original value
Current value
Original value
Original value Original value
Public parameters (always) Current value Current value Original value
Trend log def. (always) Current value Current value Original value
Trend log data (always) Current value Cleared Original value
Certain OPT
c
values
(always) Current value Current value Original value
Time parameters (always) Current value Default value Current value
Modem parameters (always) Current value Current value Current value
a. After a power outage > (more than) 72 hours, a Warm start cannot be used, as the ‘Current value’ in the
memory may have been changed. b. Original value are the values from the most recent application downloaded from TAC Menta. c. Applies to the following OPT block values:
- Curve points
- Holiday compensation
Schneider Electric Buildings AB, June 2011 65 (74) 04-00067-02-en
Page 66
A Appendix A Restart Values TAC Xenta, TAC Xenta 280/300/401
66 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 67

TAC Xenta, TAC Xenta 280/300/401 B Appendix B Restart Sequences

0 *
15 s
1 - 30 s
40 s
60 s
60 s
5 - 60 s
"Download B"
Waiting for external unit to Restart
Re­set
(Restart)
Delay
Appl. B
Application B
In.val
Application B
In.val
Application A
Application A
Application A
Subscribing to Base Unit 1 (A)
Subscribing to Base Unit 1 (B)
(Appl.dependant)
Base Unit 2:
Base Unit 1: Outputs
I/O module: Outputs
Base Unit 1: Appl. software
TAC Menta:
Appl. A
Initial values
Appl. code download
Code gen., etc
Running
(Dep. on selected Period)
*All Universal Inputs are defined as Digital Inputs. All Analog Outputs are set to 0. All Digital Outputs are set to 0.
B Appendix B Restart Sequences
The figure shows the Download sequence for:
TAC Menta, which initiates the Downloading of a new applica­tion, B, to Base Unit 1.
Xenta Base Unit 1, whose application A is disrupted and then replaced by the new application, B.
The Outputs of Base Unit 1, which will be reset for 1–30 seconds after the Restart of Base Unit 1.
The I/O module Outputs that will change to Initial Values, first of Appl A then of Appl B, as the module temporarily loses contact with its Base Unit.
Base Unit 2, which subscribes to a value in Base Unit 1 and also temporarily loses contact with that unit.
Schneider Electric Buildings AB, June 2011 67 (74) 04-00067-02-en
Page 68
B Appendix B Restart Sequences TAC Xenta, TAC Xenta 280/300/401
0 *
15 s
0
40 s
60 s
60 s
Re­set
Delay
Appl. A
Application A
No Back-up flag: In.val
Application A
Application A
Application A
Application A
Subscribing to Base Unit 1 (A)
Subscribing to Base Unit 1 (A)
(Appl.dependant)
Base Unit 2:
Base Unit 1: Outputs
I/O module: Outputs
Base Unit 1: Appl. software
Power level Base Unit 1:
Appl. A
Running
Back-up flag: Prev.val
(Dep. on selected Period)
Override values (or Initial values)
Override values, or else:
* All Universal Inputs are defined as Digital Inputs. All Analog Outputs are set to 0. All Digital Outputs are set to 0.
TAC Xenta 280 and 300
The figure shows the Power outage (less than 72 h) sequence for:
Xenta Base Unit 1, whose application A goes down and, after a restart and delay, starts running again.
The Outputs of Base Unit 1, which go down during the power out­age and whose values during the restart will be set to the Override values, or, if these are not set, t o dif fer ent values depending on the status of the backup flags in TAC Menta.
The I/O module Outputs that will change to the Forced values (or, if these are not set, the Initial values of the application), as the module temporarily loses contact with its Base Unit.
Base Unit 2, which subscribes to a value in Base Unit 1 and also temporarily loses contact with that unit.
68 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 69
TAC Xenta, TAC Xenta 280/300/401 B Appendix B Restart Sequences
15 s
1 - 30 s
40 s
60 s
60 s
5 - 60 s
"Download B"
Waiting for external unit to Restart
Re­set
(Restart)
Delay
Appl. B
Application B
In.val
Application A
Application A
Subscribing to Base Unit 1 (A)
Subscribing to Base Unit 1 (B)
(Appl.dependant)
Base Unit 2:
I/O module: Outputs
Base Unit 1: Appl. software
TAC Menta:
Appl. A
Initial values
Appl. code download
Code gen., etc
Running
(Dep. on selected Period)
TAC Xenta 401
The figure shows the Download sequence for:
TAC Menta, which initiates the Downloading of a new applica­tion, B, to Base Unit 1.
Xenta Base Unit 1, whose application A is disrupted and then replaced by the new application, B.
The I/O module Outputs that will change to Initial Values, first of Appl A then of Appl B, as the module temporarily loses contact with its Base Unit.
Base Unit 2, which subscribes to a value in Base Unit 1 and also temporarily loses contact with that unit.
Schneider Electric Buildings AB, June 2011 69 (74) 04-00067-02-en
Page 70
B Appendix B Restart Sequences TAC Xenta, TAC Xenta 280/300/401
15 s
40 s
60 s
60 s
Re­set
Delay
Appl. A
Application A
Application A
Application A
Subscribing to Base Unit 1 (A)
Subscribing to Base Unit 1 (A)
(Appl.dependant)
Base Unit 2:
I/O module: Outputs
Base Unit 1: Appl. software
Power level Base Unit 1:
Appl. A
Running
(Dep. on selected Period)
Override values (or Initial values)
TAC Xenta 401
The figure shows the Power outage (less than 72 h) sequence for:
Xenta Base Unit 1, whose application A goes down and, after a restart and delay, starts running again.
The I/O module Outputs that will change to Forced values (or, if there are none, to the Initial values of the application), as the mod­ule temporarily loses contact with its Base Unit.
Base Unit 2, which subscribes to a value in Base Unit 1 and also temporarily loses contact with that unit.
70 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 71
TAC Xenta, TAC Xenta 280/300/401 Index

Index

Numerics
8-in-16 rule 36
A
additional I/O units 48 application crash
B
Backup box 64 Boot info Bus Topology
C
C1, C2 31 cables
34
clear application Cold start communications configured (I/O module) configuring the system contrast of the display
51
59
36
51
55
15
42
45
48
ground rail groups
32
48
I
I/O expansion modules 13 I/O module IEC-listing Indicators installation IO module Config
49
31
26
29
55
L
LED Indicators 19, 23 log-out time Lon address LonTalk® LonWorks®
42
54
15
15
M
M terminal 32 Master unit modem Modular jack modular jack modular jacks
50
16
38
18
23, 25
D
date and time 50 device name Device Name (OP menu) Dial
58
DIN rail display (OP) Docnet
47
54
29
42
9
E
electronics part 49 EN-standards
30
F
Flash memory 63 Free Topology FTT-10
15
15
G
G, G0 31
Schneider Electric Buildings AB, June 2011 71 (74) 04-00067-02-en
N
Name (Device ~) 54 network address Network Variables node
47
47
O
Operator Panel 42 operator panel Orig. appl.
48
55
P
P/FT-10 36 PCLTA card protective ground Public signal PV Blocks
15
32
16
63
R
RAM memory 63
15
Page 72
Index TAC Xenta, TAC Xenta 280/300/401
Restart 55 restart values RS232 RS232 port
63
38
18
S
serial channel 16 service diode Service Menu service pin shielded cable SNVTs Status status diode subnet/node SYSREG block System info
19
53
19, 23, 26
37
15
58
19
47
42
59
T
TAC Menta 16, 45 TAC Vista TAC Xenta 280/300/400 family TAC Xenta 280/300/401 TAC Xenta 281, 282, 283 TAC Xenta 301, 302 TAC Xenta 401 TAC Xenta 511 TAC Xenta 901, 911 TAC Xenta OP Technical Data
Xenta 280 Xenta 300
Xenta 401 terminal part terminals Terminations Test dial thermistor inputs time TP/FT-10
termination TP/XF-1250
termination
15, 51
46
17
22 25 16
16
13
20 24 27
49
18
39
57
18, 22
50
40 41
13
W
wall modules 33 Warm start Wink node
55 55
Z
ZS101–105 33
U
UL-listing 30 unconfigured (I/O module) universal inputs
18, 22
48
V
version 3.2 (hw) 48
72 (74) Schneider Electric Buildings AB, June 2011
04-00067-02-en
Page 73
Page 74
Copyright © 2007-2011, Schneider Electric Buildings AB All brand names, trademarks and registered trademarks are the property of their respective owners. Information con­tained within this document is subject to changewithout no­tice. All rights reserved.
04-00067-02-en
For more information visit
Last Manual Page
Page 75
TAC Xenta, TAC Xenta 280/300/401 Imported Images
Pictures/Default/Logo_SE_Green_CMYK_A4.eps 1 Pictures/Default/Vista_SE.eps 1 Pictures/Default/Logo_SE_Black_A4.eps 3 Pictures/Default/note.eps 9 Pictures/Default/warning.eps 10 Pictures/Default/caution.eps 10 Pictures/Default/Important.eps 10 Pictures/Default/note.eps 10 Pictures/Default/Tip.eps 10 Pictures/Default/Advanced.eps 10 Pictures/1.eps 13 Pictures/2.eps 15 Pictures/3.eps 17 Pictures/12.eps 18 Pictures/4.eps 19 Pictures/5.eps 19 Pictures/Default/note.eps 20 Pictures/3.eps 21 Pictures/13.eps 22 Pictures/4.eps 23 Pictures/5.eps 23 Pictures/Default/note.eps 24 Pictures/15.eps 25 Pictures/16.eps 25 Pictures/4.eps 26 Pictures/5.eps 26 Pictures/Default/note.eps 27 Pictures/6.eps 29 Pictures/7.eps 29 Pictures/17.eps 30 Pictures/18.eps 30 Pictures/Default/caution.eps 31 Pictures/19.eps 31 Pictures/Default/note.eps 31 Pictures/20.eps 32 Pictures/21.eps 33 Pictures/22.eps 33 Pictures/8.eps 36 Pictures/Default/note.eps 36 Pictures/23.eps 37 Pictures/24.eps 38 Pictures/Default/caution.eps 38 Pictures/25.eps 38 Pictures/26.eps 39 Pictures/27.eps 39 Pictures/9.eps 40
Schneider Electric Buildings AB, 2011-08-23 1 (2) 04-00067-02-en
Page 76
TAC Xenta, TAC Xenta 280/300/401 Imported Images
Pictures/10.eps 41 Pictures/11.eps 42 Pictures/28.eps 43 Pictures/29.eps 43 Pictures/30.eps 43 Pictures/Default/note.eps 45 Pictures/41.eps 45 Pictures/Default/caution.eps 46 Pictures/42.eps 46 Pictures/43.eps 47 Pictures/Default/note.eps 48 Pictures/Default/note.eps 49 Pictures/44.eps 49 Pictures/45.eps 50 Pictures/46.eps 51 Pictures/1.tif @ 150 dpi 52 Pictures/Default/note.eps 52 Pictures/31.eps 53 Pictures/32.eps 54 Pictures/32.eps 54 Pictures/32.eps 55 Pictures/33.eps 56 Pictures/34.eps 57 Pictures/35.eps 57 Pictures/36.eps 57 Pictures/37.eps 67 Pictures/38.eps 68 Pictures/39.eps 69 Pictures/40.eps 70 Pictures/Default/Logo_SE_Green_CMYK_A4.eps 74
Schneider Electric Buildings AB, 2011-08-23 2 (2) 04-00067-02-en
Loading...