Samsung AQ09, AQ12, AQ09A1VE-XSA Troubleshooting

4.5 (2)

5. Troubleshooting

5-1 Items to be checked first

1)Is the voltage of the power correct? The input voltage shall be 198-264VAC.

The airconditioner may not operate properly if the voltage is out of this range.

2)Is the link cable linking the indoor unit and the outdoor unit linked properly? The indoor unit and the outdoor unit shall be linked by 5 cables.

Check the terminals if the indoor unit and outdoor unit are properly linked by the same number of cables. Otherwise the airconditioner may not operate properly.

3)When a problem occurs due to the contents illustrated in the table below it is a symptom not related to the malfunction of the airconditioner.

NO

Operation of air conditioner

Explanation

 

 

 

1

The COOL operation indication LED (Green) blinks when a

It indicates power is on. The LED stops blinking if the operation

 

power plug of the indoor unit is plugged in for the first time.

ON/OFF button on the remote control unit is pushed.

 

 

 

2

In a COOL operation mode, the compressor does not

In happens after a delay of 3 minutes when the compressor is reoper-

 

operate at a room temperature higher than the setting

ated. The same phenomenon occurs when a power is on.

 

temperature that the IN DOOR FAN should operate.

As a phenomenon that the compressor is reoperated after a delay of

 

In a HEAT operation mode, the compressor does not

3 minutes, the indoor fan is adjusted automatically with reference

 

operate at a room temperature lower than the setting

to a temperature of the air blew

 

temperature that

indoor fan should

 

 

operate.

 

 

 

 

 

3

Fan speed setting is not allowed in AUTO or DRY mode.

The speed of the indoor fan is set to LL in DRY mode.

 

 

 

Fan speed is 5 steps is selected automatically in AUTO mode.

 

 

 

4

Compressor stops operation intermittently in DRY mode.

Compressor operation is controlled automatically in DRY mode

 

 

 

depending on the room temperature and humidity.

 

 

 

5

Compressor of the outdoor unit is operating although it is

When the unit is turned off while de-ice is activated, the compressor

 

turned off in a HEAT mode.

 

continues operation for up to 9 minutes (maximum) until the deice is

 

 

 

completed.

 

 

 

 

6

Timer LED only of the indoor unit

lights up and the

Timer is being activated and the unit is in ready mode.

 

air conditioner does not operate.

 

The unit operates normally if the timer operation is cancelled.

 

 

 

7

The compressor and indoor fan stop intermittently in HEAT

The compressor and indoor fan stop intermittently if room temperature

 

mode.

 

exceeds a setting temperature in order to protect the compressor from

 

 

 

overheated air in a HEAT mode.

 

 

 

8

Indoor fan and outdoor fan stop operation intermittently in

The compressor operates in a reverse cycle to remove exterior ice in a

 

a HEAT mode.

 

HEAT mode, and indoor fan and outdoor fan do not operate intermit-

 

 

 

tently for within 20% of the total heater operation

 

 

 

9

The compressor stops intermittently in a COOL mode or DRY

The compressor stops intermittently or the fan speed of the indoor unit

 

mode, and fan speed of the indoor unit decreases.

decreases to prevent inside/outside air frozen depending on the

 

 

 

inside/outside air temperature.

 

 

 

 

4)Indoor unit observes operation condition of the air conditioner, and displays self diagnosis details on the display panel.

NO

Display

Self Diagnosis

 

 

 

1

Operating LED blinking (1Hz)

Restore from power failure (input initial power)

 

 

 

2

TIMER LED blinking (1Hz)

Indoor unit Room sensor Error (open or short)

 

 

 

3

OPERATING and TIMER LED blinking (1Hz)

Indoor unit heat exchanger temperature sensor Error (open or short)

 

 

 

4

FAN LEA blinking (1Hz)

Indoor fan malfunctioning (for spead is Below 38Orpm)

 

 

 

Samsung Electronics

5-1

Samsung AQ09, AQ12, AQ09A1VE-XSA Troubleshooting

5-2 Fault Diagnosis by Symptom

5-2-1 No Power (completely dead)-Initial diagnosis

1)Checklist :

(1)Is input voltage normal? (198-264V~)

(2)Is AC power linked correctly?

(3)Are connections between primary side, secondary side of the power transformer and PCB good.

(4)Is output voltage of DC regulator IC KA7812 (IC01) normal? (11VDC-12.5VDC)

(5)Is output voltage of DC regulator IC KA7805 (IC02) normal? (4.5VDC-5.5VDC)

Remove power cord and plug in again in approx. 5 seconds

 

 

NO

YES

Is DC voltage of PCB

 

display normal?

 

 

NO

Replace

Is 198~264VAC

applied to the

PCB display

primary

side of the

 

power transformer?

 

 

NO

 

 

NO

 

•Check linkage

 

between

 

power cord and

 

terminal tap

 

•Check fuse

 

Is 14~18VAC appear in

 

the secondary side of the

 

power transformer?

 

NO

YES

Replace power transformer

NO

Replace resonator (X501)

Is operation normal?

NO

YES

OK

Is operation lamp blinking?

 

YES

 

Does operation start when

YES

run/stop button on the remote

 

controller unit pushed?

 

NO

 

Is transmission display of the

NO

remote controller unit blinking?

 

YES

 

Is "beep"sound heard from the

 

main unit?

 

YES

 

Is DC voltage of the PCB

NO

module normal?

 

YES

 

Are voltages of #62 (compressor),

 

#60(4 way valve) and #61 (outdoor

 

fan) of the micom normal? 5VDC

YES

Is voltage of #63 (indoor fan) of the

 

micom normal?

 

DC5V

 

10ms

 

NO

 

Is voltage at #32 terminal of the Micom normal?

 

0VDC

 

Is voltage at #64 terminal of the Micom normal?

 

5VDC

 

YES NO

Is voltage at #25 terminal of the micom normal?

10ms

YES NO

Are voltage at #30 and #31 of the micom normal?

100ns

YES

Replace

micom

Normal

Refer to remote control unit fault diagnosis

Replace PCB

module.

Are voltages at RY71(Compressor) RY73(4-way valve) and SY72(outdoor fan)

normal? DC12V

Is voltage at SS71(indoor fan)

YES

NO

Check connec-

Replace

tions compressor

RY71,

4-way valve, out-

RY73,

door fan and

RY72 and

indoor fan.

SS71

Is output voltage of ICO2 normal?

YES

 

NO

Check PCB pattern.

Replace

Replace main PCB.

ICO2

Is voltage output

terminal of

D101~D105(IN4007) normal?

YES

 

NO

OK

Replace IN4007

5-2

Samsung Electronics

Troubleshooting

5-2-2 When the Indoor Unit Fan Does Not Operate. (Initial Diagnosis)

1)Checklist :

(1)Is the indoor unit fan motor properly connected with the connector (CN73)?

(2)Is the AC voltage correct?

(3)Is HALL IC in indoor fan motor properly connected with the connector (CN43)?

(4)Is the running capacitor properly connected with the terminal?

2)Troubleshooting procedure

After unplugging out the power cord should be reconnected within five seconds.

YES

Does the operating lamp(Green) blink?

YES

Does the Solid State Relay(SS71) work properly?

Test rod location

Normal

Voltage

+-

SS71-

SS71-

12V

YES

NO

Check as in the procedur “NO power parts”

 

 

Refer tp page 5-2.

NO

Microcomputer is out of order.

Is the supply voltage of the fan

NO

PCB is

PCB should

 

motor sufficient?

 

 

out of order.

be replaced.

Test rod location

Normal

 

 

 

 

 

 

 

 

PCB CN73

Condition

voltage

 

 

 

 

 

 

 

 

Fan operate

AC 180V

 

 

 

 

YES

 

 

MF-C is out of order

Replace MFC

 

 

 

 

Fan motor

Fan motor

should be

is out of order.

replaced.

 

Samsung Electronics

5-3