Rockwell Automation 1769-OF4CI User Manual

Installation Instructions
Compact 1769-OF4CI Isolated Analog Output Module
Catalog Number 1769-OF4CI
Topic Page
Important User Information 2 About the Module 4 System Assembly 7 Mounting Expansion I/O 8 Replacing a Single Module Within a System 11 Module Spare/replacement Parts 12 Grounding the Module 12 I/O Memory Mapping 17 Specifications 22 Additional Resources 2
2 Compact 1769-OF4CI Isolated Analog Output Module

Important User Information

Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1
http://www.rockwellautomation.com/literature/
solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from your local Rockwell Automation sales office or online at
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to alert people that dangerous voltage may be present.
) describes some important differences between
BURN HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to alert people that surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of the
product.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 3

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous locations.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
WARNING: Explosion Hazard -
•Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
•Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
•Substitution of components may impair suitability for Class I, Division 2.
•If this product contains batteries, they must only be changed in an area known to be nonhazardous.
Informations sur l’utilisation de cet équipement en environnements dangereux.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
AVERTISSEMENT: Risque d’Explosion –
•Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement.
•Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
•La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
•S'assurer que l'environnement est classé non dangereux avant de changer les piles.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
4 Compact 1769-OF4CI Isolated Analog Output Module
2a
1
5
b

About the Module

OK
Analog
Do Not Remove RTB Under Power
10a
10
10b
DANGER
Unless Area is Non-Hazardous
N/C
I out 0 -
I out 0 +
N/C
I out 1 -
I out 1 +
N/C
I out 2 -
I out 2 +
N/C
I out 3 -
I out 3 +
N/C
Ensure Adjacent Bus Lever is Unlatched/Latched Before/After Removing/Inserting Module
1769-OF4CI
3
N/C
N/C
N/C
N/C
N/C
4
8a
7a
OK
Analog
2b
7a
a
9
7b
7b
5
6
8b
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 5
Item Description Item Description
1 Bus lever (with locking function) 7a Upper tongue-and-groove slots 2a Upper panel mounting tab 7b Lower tongue-and-groove slots 2b Lower panel mounting tab 8a Upper DIN rail latch 3 Module status LED 8b Lower DIN rail latch 4 Module door with terminal
identification label
5a Movable bus connector with
female pins
5b Stationary bus connector with
male pins
6 Nameplate label 10b RTB lower retaining screw
9 Write-on label (user ID tag)
10 Removable terminal block (RTB) with
finger-safe cover
10a RTB upper retaining screw
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
6 Compact 1769-OF4CI Isolated Analog Output Module

Module Installation

Compact I/O is suitable for use in an industrial environment when installed in accordance with these instructions.

Prevent Electrostatic Discharge

ATTENTION: Electrostatic discharge can damage integrated
circuits or semiconductors if you touch bus connector pins or the terminal block. Follow these guidelines when you handle the module:
Touch a grounded object to discharge static potential.
Wear an approved wrist-strap grounding device.
Do not touch the bus connector or connector pins.
Do not touch circuit components inside the module.
Use a static-safe work station, if available.
When not in use, keep the module in its static-shield box.

Remove Power

ATTENTION: Remove power before removing or inserting this
module. When you remove or insert a module with power applied, an electrical arc may occur. An electrical arc can cause personal injury or property damage by:
sending an erroneous signal to your system’s field devices, causing unintended machine motion.
causing an explosion in a hazardous environment.
Electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 7

System Assembly

The module can be attached to the controller or an adjacent I/O module before or after mounting.
For mounting instructions, see Panel Mounting
Mounting on page 11.
To work with a system that is already mounted, see Replacing a Single
Module Within a System on page 11.
The following procedure shows you how to assemble the Compact I/O system.
on page 10, or DIN Rail
3
4
2
1
1
5
Item Description Item Description
1 Tongue-and-groove slots 4 Bus lever 2 Bus connectors 5 End-cap terminator 3 Positioning tab 6 End-cap bus terminator
1. Disconnect power.
2. Check that the bus lever of the module to be installed is in the unlocked
(fully right) position.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
6
8 Compact 1769-OF4CI Isolated Analog Output Module
3. Use the upper and lower tongue-and-groove slots (1) to secure the
modules together (or to a controller).
4. Move the module back along the tongue-and-groove slots until the bus
connectors (2) line up with each other.
5. Push the bus lever back slightly to clear the positioning tab (3). Use your
fingers or a small screwdriver.
6. To allow communication between the controller and module, move the
bus lever fully to the left (4) until it clicks. Make sure it is locked firmly in place.
ATTENTION: When attaching I/O modules, it is very important that the bus connectors are securely locked together for proper electrical connection.
7. Attach an end cap terminator (5) to the last module in the system by
using the tongue-and-groove slots as before.
8. Lock the end cap bus terminator (6).
IMPORTANT
A 1769-ECR or 1769-ECL right or left end cap must be used to terminate the end of the serial communication bus.

Mounting Expansion I/O

ATTENTION: During panel or DIN rail mounting of all devices, be
sure that all debris, such as metal chips or wire strands, is kept from falling into the module. Debris that falls into the module could cause damage on power up.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 9

Minimum Spacing

Maintain spacing from enclosure walls, wireways, adjacent equipment, etc. Allow 50 mm (2 in.) of space on all sides for adequate ventilation.
1
6
44
Item Description Item Description
1Top 4Side 2 Compact I/O modules 5 Bottom 3 End cap 6 Host controller
2
2
2
2
5
2
3
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
10 Compact 1769-OF4CI Isolated Analog Output Module
Spacing for single-wide modules 35mm (1.378 in.)
N
t
M

Panel Mounting

Mount the module to a panel using two screws per module. Use M4 or #8 panhead screws. Mounting screws are required on every module.
Panel Mounting Using the Dimensional Template
Spacing for one-and-a half-wide modules 52.5mm (2.067 in.)
Refer to host controller documentation for this dimension.
Host Controller
ote: Overall hole spacing
olerance: ±0.4mm (0.016 in.).
30535-
Panel Mounting Procedure Using Modules as a Template
The following procedure lets you use the assembled modules as a template for drilling holes in the panel. If you have sophisticated panel mounting equipment, you can use the dimensional template provided on page 10 mounting hole tolerance, it is important to follow these procedures.
1. On a clean work surface, assemble no more than three modules.
2. Using the assembled modules as a template, carefully mark the center of
all module-mounting holes on the panel.
3. Return the assembled modules to the clean work surface, including any
previously mounted modules.
4. Drill and tap the mounting holes for the recommended M4 or #8 screw.
5. Place the modules back on the panel, and check for proper hole
alignment.
. Due to module
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 11
6. Attach the modules to the panel by using the mounting screws.
TIP
7. Repeat steps 1
If mounting more modules, mount only the last one of this group and put the others aside. This reduces remounting time during drilling and tapping of the next group.
6 for any remaining modules.

DIN Rail Mounting

The module can be mounted using the following DIN rails:
35 x 7.5 mm (1.38 x 0.30 in.; EN 50 022 - 35 x 7.5)
35 x 15 mm (1.38 x 0.59 in.; EN 50 022 - 35 x 15)
Before mounting the module on a DIN rail, close the DIN rail latches. Press the DIN rail mounting area of the module against the DIN rail. The latches will momentarily open and lock into place.

Replacing a Single Module Within a System

The module can be replaced while the system is mounted to a panel (or DIN rail). Follow the steps below in order:
1. Remove power.
2. On the module to be removed, remove the upper and lower mounting
screws from the module (or open the DIN latches by using a screwdriver).
3. Move the bus lever to the right to disconnect (unlock) the bus.
4. On the right-side adjacent module, move its bus lever to the right
(unlock) to disconnect it from the module to be removed.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
12 Compact 1769-OF4CI Isolated Analog Output Module
5. Gently slide the disconnected module forward.
If you feel excessive resistance, check that the module has been disconnected from the bus, and that both mounting screws have been removed (or DIN latches opened).
TIP
6. Before installing the replacement module, be sure that the bus lever on
the module to be installed, and on the right-side adjacent module are in the unlocked (fully right) position.
7. Slide the replacement module into the open slot.
8. Connect the modules together by locking (fully left) the bus levers on
the replacement module and the right-side adjacent module.
9. Replace the mounting screws (or snap the module onto the DIN rail).
It may be necessary to rock the module slightly from front to back to remove it, or, in a panel-mounted system, to loosen the screws of adjacent modules.

Module Spare/replacement Parts

Terminal block, catalog number 1769-RTBN18 (1 per kit)
Door, catalog number 1769-RD (2 per kit)

Grounding the Module

This product is intended to be mounted to a well-grounded mounting surface, such as a metal panel. Additional grounding connections from the module’s mounting tabs or DIN rail (if used), are not required unless the mounting surface cannot be grounded. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
, for additional information.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 13

System Wiring Guidelines

Consider the following when wiring your system:
Channels are isolated from each other.
Use Belden 8761, or equivalent, shielded wire.
Under normal conditions, the drain wire and shield junction must be
connected to earth ground, via a panel or DIN rail mounting screw at the analog I/O module end. Keep the shield connection to ground as short as possible.
TIP
For optimum accuracy, limit overall cable impedance by keeping your
cable as short as possible. Locate the I/O system as close to your sensors or actuators as your application will permit.
Load resistance for each current output channel must remain between
0…500 Ω..
In environments where high frequency noise may be present, it may be necessary to ground the shield via a 0.1 µF capacitor at the load end and also ground the module end without a capacitor.

Wiring Output Devices

ATTENTION: Miswiring of the module to an AC/DC source will
damage the module. Be careful when stripping wires. Wire fragments that fall into a
module could cause damage at power up. Once wiring is complete, ensure the module is free of all metal fragments.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
14 Compact 1769-OF4CI Isolated Analog Output Module

Labeling the Terminals

A removable, write-on label is provided with the module. Remove the label from the door, mark the identification of each terminal with permanent ink, and slide the label back into the door. Your markings (ID tag) will be visible when the module door is closed.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 15

Removing the Finger-safe Terminal Block

To remove the terminal block, loosen the upper and lower retaining screws. The terminal block will back away from the module as you remove the screws. When replacing the terminal block, torque the retaining screws to 0.46 N
(4.1 in•lb).
m
3
2
Item Description
1 Wiring the finger-safe terminal block 2 Lower retaining screws 3 Upper retaining screws
1
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
16 Compact 1769-OF4CI Isolated Analog Output Module

Wiring the Finger-safe Terminal Block

When wiring the terminal block, keep the finger-safe cover in place.
1. Loosen the terminal screws to be wired.
2. Route the wire under the terminal pressure plate. You can use the bare
wire or a spade lug.
The terminals will accept a 6.35 mm (0.25 in.) spade lug.
TIP
3. Tighten the terminal screw making sure the pressure plate secures the
wire. Recommended torque when tightening terminal screws is
0.68 N•m (6 in•lb).
TIP
The terminal screws are non-captive. You can use a ring lug [maximum 6.35 mm (0.25 in.) o.d. with a 3.53 mm (0.139 in.) minimum i.d. (M3.5)] with the module.
If you need to remove the finger-safe cover, insert a screwdriver into one of the square wiring holes and gently pry the cover off. If you wire the terminal block with the finger-safe cover removed, you will not be able to put it back on the terminal block because the wires will be in the way.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 17

Wire Size and Terminal Screw Torque

Each terminal accepts up to two wires with the following restrictions:
Wire Type Wire Size Terminal Screw
Torque
Solid Cu-90 °C (194°F) #14…#22 AWG 0.68 N•m
Stranded Cu-90 °C (194°F) #16…#22 AWG 0.68 N•m
(6 in•lbs)
(6 in•lbs)
Retaining Screw
Tor qu e
0.46 N•m
(4.1 in-•bs)
0.46 N•m
(4.1 in•lbs)

I/O Memory Mapping

Output Data File

For each module, slot x, words 0…3 in the output data file contain the channel 0 …3 output data. Word 4 is used to unlatch any condition that has been latched. Refer to your module’s user manual for additional details.
Bit Position
1514131211109876543210
Word
0 SGN Analog Output Data Channel 0 1 SGN Analog Output Data Channel 1 2 SGN Analog Output Data Channel 2 3 SGN Analog Output Data Channel 3 4 UU3 UO3 UU2 UO2 UU1 UO1 UU0 UO0
SGN = Sign bit in two’s complement format (must be set to 0).
UU = Unlatch under-range (or low clamp exceeded) alarm.
UO = Unlatch over-range (or high clamp exceeded) alarm.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
18 Compact 1769-OF4CI Isolated Analog Output Module

Input Data File

For each module, slot x, input data file words 2…5 contain the state of the module’s output data (output data echo) file words 0…3. During normal operation, these input words represent the analog values that the outputs are
directed to by the control program.
Bit Position
1514131211109876543210
Word
0 S3S2S1S0 1 H3U3O3 H2U2O2 H1U1O1 H0U0O0 2 Channel 0 Data Value 3 Channel 1 Data Value 4 Channel 2 Data Value 5 Channel 3 Data Value
S = General status (over-range, under-range, or low/high clamp
exceeded).
H = Output held bit.
U = Under-range (or low-clamp exceeded) alarm.
O = Over-range (or high-clamp exceeded) alarm.
IMPORTANT
The output module’s input data file reflects the analog output data echo of the module, not necessarily the electrical state of the output terminals. It does not reflect shorted or open outputs.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 19

Configuration Data File

The manipulation of the bits from this file is normally done with programming software (for example, RSLogix 500 software or RSNetworx for DeviceNet software) during initial configuration of the system. In that case, graphical screens are provided by the programmer to simplify configuration.
However, some systems, like the 1769-ADN DeviceNet Adapter, also allow the bits to be altered as part of the control program, using communication rungs. In that case, it is necessary to understand the bit arrangement. The channel configuration words, the first two words of each eight word group, are described
on page 20
Word Description Word Description
0 Channel 0 Configuration Word 0 16 Channel 2 Configuration Word 0 1 Channel 0 Configuration Word 1 17 Channel 2 Configuration Word 1 2 Channel 0 Fault Value Word 18 Channel 2 Fault Value Word 3 Channel 0 Program Idle Mode
4 Channel 0 Low Clamp 20 Channel 2 Low Clamp 5 Channel 0 High Clamp 21 Channel 2 High Clamp 6 Channel 0 Ramp Rate 22 Channel 2 Ramp Rate 7 Channel 0 Spare 23 Channel 2 Spare 8 Channel 1 Configuration Word 0 24 Channel 3 Configuration Word 0 9 Channel 1 Configuration Word 1 25 Channel 3 Configuration Word 1 10 Channel 1 Fault Value Word 26 Channel 3 Fault Value Word 11 Channel 1 Program Idle Mode
12 Channel 1 Low Clamp 28 Channel 3 Low Clamp 13 Channel 1 High Clamp 29 Channel 3 High Clamp 14 Channel 1 Ramp Rate 30 Channel 3 Ramp Rate 15 Channel 1 Spare 31 Channel 3 Spare
. Refer to your module’s user manual for additional details.
Word
Word
19 Channel 2 Program Idle Mode
Word
27 Channel 3 Program Idle Mode
Word
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
20 Compact 1769-OF4CI Isolated Analog Output Module
Channel Configuration Words
The first two words of each eight word group in the configuration file allow you to change the parameters of each channel independently. For example, words 8 and 9 correspond to channel 1 while words 16 and 17 correspond to
channel 3.
Word/Bit151413121110987654321
Word 0 E Reserved SIU SIO LA ER FM PM HI Word 1 Reserved Output Data
Format Select
Reserved Output
Type/Range
E = Channel Enable: (0 = Disabled, 1 = output Enabled, process
changes)
Reserved = Set to zero
SIU = System interrupt low clamp, under-range alarms: (0 = Disabled,
1 = Enabled)
SIO = System interrupt high clamp, over-range alarms: (0 = Disabled,
1 = Enabled)
LA = Latch low/high clamp, under/over-range alarms: (0 = Disabled,
1 = Enabled)
ER = Enable ramping: (0 = Disabled, 1 = Enabled. Ramp rate limited by
fault states.)
FM = Fault mode: (0 = Hold Last State, 1 = User Defined Value)
PM = Program mode: (0 = Hold Last State, 1 = User Defined Value)
HI = Hold for initialization: (0 = Disabled, 1 = Enabled)
PFE = Program/idle to fault enable: (0 = Disabled, 1 = Enabled)
0
PFE
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 21
Define Indicate this These bit settings
1514131211109876543210
Program (Idle) to Fault Enable
Hold for Initialization
Program (Idle) Mode
Fault Mode Hold Last State
Enable Ramping
System Interrupt High Clamp
System Interrupt Low Clamp
Enable Channel
(1) These functions are not supported by all controllers (for example, MicroLogix 1500) using any
Program (Idle) Mode Data
(1)
Applied Fault Mode Data
(1)
Applied Disabled Enabled 1 Hold Last State User-Defined
Valu e
User-Defined Fault Value
(1)
(1)
(1)
(1)
Disabled 0 Enabled 1 Disabled 0
(1)
Enabled
Disabled 0
(1)
Enabled
Disabled 0 Enabled 1
configuration method. Refer to your controller manual for details.
0 1
1
1
0
1
0
0 1
Define Indicate this These bit settings
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Output Range Select
Output Data Select
0…20 mA DC 00 4…20 mA DC 00
Raw/Proportional Counts
0 0 0
Engineering Units 001 Scaled for PID 010 Percent Range 011
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
0 0 1
22 Compact 1769-OF4CI Isolated Analog Output Module

Specifications

Specification 1769-OF4CI
Dimensions 118 mm (height) x 87 mm (depth) x 35 mm
Approximate Shipping Weight (with carton)
Storage Temperature -40°C to +85°C (-40°F to +185°F) Operating Temperature 0°C to +60°C (32°F to +140°F) Operating Humidity 5% to 95% non-condensing Operating Altitude 2000 meters (6561 feet) Vibration Operating: 10 to 500 Hz, 5G, 0.030 in.
Shock Operating: 30G, 11 ms panel mounted
Agency Certification • C-UL certified (under CSA C22.2 No. 142)
Hazardous Environment Class Class I, Division 2, Hazardous Location,
Radiated and Conducted Emissions IEC 61000-6-4 and CISPR 11 Group 1, class A
Electrical /EMC: The module has passed testing at the
ESD Immunity (IEC 61000-4-2) 4 kV contact, 8 kV air, 4 kV indirect
Radiated Immunity (IEC 61000-4-3) 10 V/m, 80 to 1000 MHz, 80% amplitude
Fast Transient Burst (IEC 61000-4-4) 2 kV, 5 kHz
Surge Immunity (IEC 61000-4-5) 1 kV galvanic gun
Conducted Immunity (IEC 61000-4-6) 10V dc, 0.15 to 80 MHz
(1) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency
range is 30 MHz to 1000 MHz.
(width) height including mounting tabs is 138 mm
4.65 in. (height) x 3.43 in (depth) x 1.38 in (width) height including mounting tabs is 5.43 in.
270g (0.6 lbs.)
peak-to-peak
(20G, 11 ms DIN rail mounted) Non-Operating: 40G panel mounted
(30G DIN rail mounted)
UL 508 listed
CE compliant for all applicable directives
Groups A, B, C, D (ISA 12.12-01, C-UL under CSA C22.2 No. 213)
following levels:
modulation
(1)
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 23
Specification 1769-OF4CI
Analog Normal Operating Ranges Full Scale Analog Ranges
(1)
(1)
0 to 20 mA, 4 to 20 mA
0 to 21 mA, 3.2 to 21 mA Number of Outputs 4 isolated differential Bus Current Draw (max.) 5V, 165mA
24V, 110mA Heat Dissipation 2.68 Total Watts (All points - 21 mA into
250Ω - worst case calculated.)
Digital Resolution Across Full Range 16 bits (unipolar)
+4 to +20 mA: 15.59 bits, 0.323 µA/bit
0 to +20 mA: 15.91 bits, 0.323 µA/bit Conversion Rate (all channels) max. 110 ms Step Response to 63%
(2)
<2.9 ms Resistive Load on Current Output 0 to 500 Ω (includes wire resistance) Max. Inductive Load 0.1 mH Field Calibration None required Overall Accuracy
(1) The over- or under-range flag will come on when the normal operating range (over/under) is exceeded.
The module will continue to convert the analog output up to the maximum full scale range. The flag automatically resets when within the normal operating range unless configured to latch.
(2) Step response is the period of time between when the D/A converter was instructed to go from
minimum to full range until the device is at 63% of full range.
(3) Includes offset, gain, drift, non-linearity and repeatability error terms.
(3)
±0.35% full scale at 25°C
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
24 Compact 1769-OF4CI Isolated Analog Output Module
Specification 1769-OF4CI
Accuracy Drift with Temperature ±0.0058% FS per °C Output Ripple
range 0 to 50 kHz (referred to output range)
Non-linearity (in percent full scale) ±0.05% Repeatability
(in percent full scale) Output Error Over Full Temperature Range
(0 to 60°C [+32 to +140°F]) Output Impedance >1 MΩ Open and Short-Circuit Protection Yes Maximum Short-Circuit Current 21 mA Output Overvoltage Protection Yes Output Response at System Power Up and
Power Down Rated Working Voltage Output Group to Bus Isolation 500V ac or 710V dc for 1 minute (qualification
Module OK LED On: module has power, has passed internal
Channel Diagnostics Over- or under-range by bit reporting
(1) Output ripple is the amount a fixed output varies with time, assuming a constant load and
(2) Repeatability is the ability of the output module to reproduce output readings when the same
(3) Rated working voltage is the maximum continuous voltage that can be applied at the output terminal,
(1)
(2)
±0.05%
±0.05%
±0.55%
No power up or power down current glitch
(3)
30V ac/30V dc
test)
30V ac/30V dc working voltage (IEC Class 2
reinforced insulation)
diagnostics, and is communicating over the
bus.
Off: Any of the above is not true.
temperature.
controller value is applied to it consecutively, under the same conditions and in the same direction.
including the output signal and the value that floats above ground potential (for example, 10V dc output signal and 20V dc potential above ground).
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 25
Specification 1769-OF4CI
System Power Supply Distance Rating The module may not be more than 8 modules
Recommended Cable Belden 8761 (shielded) Vendor I.D. Code 1 Product Type Code 10 Product Code 45 Input Words 6 Output Words 5 Configuration Words 32
away from the system power supply.

Hazardous Location Considerations

This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations only. The following ATTENTION statement applies to use in hazardous locations.
WARNING: EXPLOSION HAZARD
Substitution of components may impair suitability for Class I, Division 2.
When in hazardous locations, turn off power before wiring or replacing modules.
Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
This product must be installed in an enclosure.
All wiring must comply with N.E.C. article 501-4(b).
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
26 Compact 1769-OF4CI Isolated Analog Output Module

Environnements dangereux

Cet équipement est conçu pour être utilisé dans des environnements de Classe 1, Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante s’applique à une utilisation dans des environnements dangereux.
AVERTISSEMENT: DANGER D’EXPLOSION La substitution de composants peut rendre cet équipement impropre à
une utilisation en environnement de Classe 1, Division 2. Ne pas remplacer de composants ou déconnecter l'équipement sans
s'être assuré que l'alimentation est coupée et que l'environnement est classé non dangereux.
Ne pas connecter ou déconnecter des composants sans s'être assuré que l'alimentation est coupée ou que l'environnement est classé non dangereux.
Ce produit doit être installé dans une armoire.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 27

Additional Resources

These documents contain additional information concerning related Rockwell Automation products.
Resource Description
Compact I/O Analog Modules User Manual, publication 1769-UM002
MicroLogix 1500 Programmable Controllers User Manual, publication 1764-UM001
1769-ADN DeviceNet Adapter User Manual, publication 1769-UM001
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Product Certifications website,
http://www.ab.com
You can view or download publications at
http://www.rockwellautomation.com/literature/
technical documentation, contact your local Rockwell Automation distributor or sales representative.
Provides detailed information on installing, programming, and troubleshooting Compact analog I/O modules.
Provides a detailed description for installing and using Compact I/O modules with a MicroLogix 1500 programmable controller.
Provides a detailed description of how to install and use Compact I/O modules with the 1769-ADN DeviceNet Adapter.
Provides general guidelines for installing a Rockwell Automation industrial system.
Provides declarations of conformity, certificates, and other certification details.
. To order paper copies of
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At
http://www.rockwellautomation.com/support/
technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or Canada
Use the Worldwide Locator
http://www.rockwellautomation.com/support/americas/phone_en.html
contact your local Rockwell Automation representative.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States
Outside United States
Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process.
Please contact your local Rockwell Automation representative for the return procedure.
, you can find technical manuals, a knowledge base of FAQs,
.
at
, or
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002
http://www.rockwellautomation.com/literature/
Allen-Bradley, Compact I/O, CompactLogix, MicroLogix, RSLogix, RSLogix 500, RSNetWorx, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Ro ckwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel : +90 (216) 5698400
.
Publication 1769-IN075B-EN-P - August 2010 PN-83819
Supersedes Publication 1769-IN075A-EN-P - July 2005 Copyright © 2010 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
, available at
Loading...