Important User Information2
About the Module4
System Assembly7
Mounting Expansion I/O8
Replacing a Single Module Within a System11
Module Spare/replacement Parts12
Grounding the Module12
I/O Memory Mapping17
Specifications22
Additional Resources2
2 Compact 1769-OF4CI Isolated Analog Output Module
Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical
equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls
(Publication SGI-1.1
http://www.rockwellautomation.com/literature/
solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also
because of the wide variety of uses for solid-state equipment, all persons responsible for applying this
equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the
many variables and requirements associated with any particular installation, Rockwell Automation, Inc.
cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from your local Rockwell Automation sales office or online at
WARNING: Identifies information about practices or circumstances that can cause an
explosion in a hazardous environment, which may lead to personal injury or death,
property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to
personal injury or death, property damage, or economic loss. Attentions help you identify
a hazard, avoid a hazard and recognize the consequences.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, drive or motor,
to alert people that dangerous voltage may be present.
) describes some important differences between
BURN HAZARD: Labels may be on or inside the equipment, for example, drive or motor,
to alert people that surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of the
product.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 3
North American Hazardous Location Approval
The following information applies
when operating this equipment in
hazardous locations.
Products marked "CL I, DIV 2, GP A, B, C, D" are
suitable for use in Class I Division 2 Groups A, B, C,
D, Hazardous Locations and nonhazardous
locations only. Each product is supplied with
markings on the rating nameplate indicating the
hazardous location temperature code. When
combining products within a system, the most
adverse temperature code (lowest "T" number) may
be used to help determine the overall temperature
code of the system. Combinations of equipment in
your system are subject to investigation by the
local Authority Having Jurisdiction at the time of
installation.
WARNING:
Explosion Hazard -
•Do not disconnect equipment
unless power has been removed
or the area is known to be
nonhazardous.
•Do not disconnect connections to
this equipment unless power has
been removed or the area is
known to be nonhazardous.
Secure any external connections
that mate to this equipment by
using screws, sliding latches,
threaded connectors, or other
means provided with this product.
•Substitution of components may
impair suitability for Class I,
Division 2.
•If this product contains batteries,
they must only be changed in an
area known to be nonhazardous.
Informations sur l’utilisation de cet
équipement en environnements
dangereux.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu'à une utilisation en environnements
de Classe I Division 2 Groupes A, B, C, D dangereux et
non dangereux. Chaque produit est livré avec des
marquages sur sa plaque d'identification qui indiquent
le code de température pour les environnements
dangereux. Lorsque plusieurs produits sont combinés
dans un système, le code de température le plus
défavorable (code de température le plus faible) peut
être utilisé pour déterminer le code de température
global du système. Les combinaisons d'équipements
dans le système sont sujettes à inspection par les
autorités locales qualifiées au moment de
l'installation.
AVERTISSEMENT:
Risque d’Explosion –
•Couper le courant ou s'assurer que
l'environnement est classé non
dangereux avant de débrancher
l'équipement.
•Couper le courant ou s'assurer que
l'environnement est classé non
dangereux avant de débrancher les
connecteurs. Fixer tous les
connecteurs externes reliés à cet
équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou
autres moyens fournis avec ce
produit.
•La substitution de composants peut
rendre cet équipement inadapté à
une utilisation en environnement de
Classe I, Division 2.
•S'assurer que l'environnement est
classé non dangereux avant de
changer les piles.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
4 Compact 1769-OF4CI Isolated Analog Output Module
2a
1
5
b
About the Module
OK
Analog
Do Not Remove RTB Under Power
10a
10
10b
DANGER
Unless Area is Non-Hazardous
N/C
I out 0 -
I out 0 +
N/C
I out 1 -
I out 1 +
N/C
I out 2 -
I out 2 +
N/C
I out 3 -
I out 3 +
N/C
Ensure Adjacent
Bus Lever is Unlatched/Latched
Before/After
Removing/Inserting Module
1769-OF4CI
3
N/C
N/C
N/C
N/C
N/C
4
8a
7a
OK
Analog
2b
7a
a
9
7b
7b
5
6
8b
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 5
ItemDescriptionItemDescription
1Bus lever (with locking function)7aUpper tongue-and-groove slots
2aUpper panel mounting tab7bLower tongue-and-groove slots
2bLower panel mounting tab8aUpper DIN rail latch
3Module status LED8bLower DIN rail latch
4Module door with terminal
identification label
5aMovable bus connector with
female pins
5bStationary bus connector with
male pins
6Nameplate label10bRTB lower retaining screw
9Write-on label (user ID tag)
10Removable terminal block (RTB) with
finger-safe cover
10aRTB upper retaining screw
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
6 Compact 1769-OF4CI Isolated Analog Output Module
Module Installation
Compact I/O is suitable for use in an industrial environment when installed
in accordance with these instructions.
Prevent Electrostatic Discharge
ATTENTION: Electrostatic discharge can damage integrated
circuits or semiconductors if you touch bus connector pins or the
terminal block. Follow these guidelines when you handle the
module:
• Touch a grounded object to discharge static potential.
• Wear an approved wrist-strap grounding device.
• Do not touch the bus connector or connector pins.
• Do not touch circuit components inside the module.
• Use a static-safe work station, if available.
• When not in use, keep the module in its static-shield box.
Remove Power
ATTENTION: Remove power before removing or inserting this
module. When you remove or insert a module with power applied,
an electrical arc may occur. An electrical arc can cause personal
injury or property damage by:
• sending an erroneous signal to your system’s field devices,
causing unintended machine motion.
• causing an explosion in a hazardous environment.
Electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create electrical
resistance.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 7
System Assembly
The module can be attached to the controller or an adjacent I/O module before
or after mounting.
• For mounting instructions, see Panel Mounting
Mounting on page 11.
• To work with a system that is already mounted, see Replacing a Single
Module Within a System on page 11.
The following procedure shows you how to assemble the Compact I/O system.
on page 10, or DIN Rail
3
4
2
1
1
5
ItemDescriptionItemDescription
1Tongue-and-groove slots4Bus lever
2Bus connectors5End-cap terminator
3Positioning tab6End-cap bus terminator
1. Disconnect power.
2. Check that the bus lever of the module to be installed is in the unlocked
(fully right) position.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
6
8 Compact 1769-OF4CI Isolated Analog Output Module
3. Use the upper and lower tongue-and-groove slots (1) to secure the
modules together (or to a controller).
4. Move the module back along the tongue-and-groove slots until the bus
connectors (2) line up with each other.
5. Push the bus lever back slightly to clear the positioning tab (3). Use your
fingers or a small screwdriver.
6. To allow communication between the controller and module, move the
bus lever fully to the left (4) until it clicks. Make sure it is locked firmly
in place.
ATTENTION: When attaching I/O modules, it is very important
that the bus connectors are securely locked together for proper
electrical connection.
7. Attach an end cap terminator (5) to the last module in the system by
using the tongue-and-groove slots as before.
8. Lock the end cap bus terminator (6).
IMPORTANT
A 1769-ECR or 1769-ECL right or left end cap must be used to
terminate the end of the serial communication bus.
Mounting Expansion I/O
ATTENTION: During panel or DIN rail mounting of all devices, be
sure that all debris, such as metal chips or wire strands, is kept
from falling into the module. Debris that falls into the module
could cause damage on power up.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 9
Minimum Spacing
Maintain spacing from enclosure walls, wireways, adjacent equipment, etc. Allow
50 mm (2 in.) of space on all sides for adequate ventilation.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
10 Compact 1769-OF4CI Isolated Analog Output Module
Spacing for single-wide modules 35mm (1.378 in.)
N
t
M
Panel Mounting
Mount the module to a panel using two screws per module. Use M4 or #8
panhead screws. Mounting screws are required on every module.
Panel Mounting Using the Dimensional Template
Spacing for one-and-a half-wide modules 52.5mm (2.067 in.)
Refer to host controller documentation for this dimension.
Host Controller
ote: Overall hole spacing
olerance: ±0.4mm (0.016 in.).
30535-
Panel Mounting Procedure Using Modules as a Template
The following procedure lets you use the assembled modules as a template for
drilling holes in the panel. If you have sophisticated panel mounting equipment,
you can use the dimensional template provided on page 10
mounting hole tolerance, it is important to follow these procedures.
1. On a clean work surface, assemble no more than three modules.
2. Using the assembled modules as a template, carefully mark the center of
all module-mounting holes on the panel.
3. Return the assembled modules to the clean work surface, including any
previously mounted modules.
4. Drill and tap the mounting holes for the recommended M4 or #8 screw.
5. Place the modules back on the panel, and check for proper hole
alignment.
. Due to module
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 11
6. Attach the modules to the panel by using the mounting screws.
TIP
7. Repeat steps 1
If mounting more modules, mount only the last one of this group
and put the others aside. This reduces remounting time during
drilling and tapping of the next group.
… 6 for any remaining modules.
DIN Rail Mounting
The module can be mounted using the following DIN rails:
• 35 x 7.5 mm (1.38 x 0.30 in.; EN 50 022 - 35 x 7.5)
• 35 x 15 mm (1.38 x 0.59 in.; EN 50 022 - 35 x 15)
Before mounting the module on a DIN rail, close the DIN rail latches. Press
the DIN rail mounting area of the module against the DIN rail. The latches
will momentarily open and lock into place.
Replacing a Single Module Within a System
The module can be replaced while the system is mounted to a panel (or DIN
rail). Follow the steps below in order:
1. Remove power.
2. On the module to be removed, remove the upper and lower mounting
screws from the module (or open the DIN latches by using a
screwdriver).
3. Move the bus lever to the right to disconnect (unlock) the bus.
4. On the right-side adjacent module, move its bus lever to the right
(unlock) to disconnect it from the module to be removed.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
12 Compact 1769-OF4CI Isolated Analog Output Module
5. Gently slide the disconnected module forward.
If you feel excessive resistance, check that the module has been
disconnected from the bus, and that both mounting screws have been
removed (or DIN latches opened).
TIP
6. Before installing the replacement module, be sure that the bus lever on
the module to be installed, and on the right-side adjacent module are in
the unlocked (fully right) position.
7. Slide the replacement module into the open slot.
8. Connect the modules together by locking (fully left) the bus levers on
the replacement module and the right-side adjacent module.
9. Replace the mounting screws (or snap the module onto the DIN rail).
It may be necessary to rock the module slightly from front to back
to remove it, or, in a panel-mounted system, to loosen the screws
of adjacent modules.
Module Spare/replacement Parts
• Terminal block, catalog number 1769-RTBN18 (1 per kit)
• Door, catalog number 1769-RD (2 per kit)
Grounding the Module
This product is intended to be mounted to a well-grounded mounting surface,
such as a metal panel. Additional grounding connections from the module’s
mounting tabs or DIN rail (if used), are not required unless the mounting
surface cannot be grounded. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1
, for additional information.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 13
System Wiring Guidelines
Consider the following when wiring your system:
• Channels are isolated from each other.
• Use Belden 8761, or equivalent, shielded wire.
• Under normal conditions, the drain wire and shield junction must be
connected to earth ground, via a panel or DIN rail mounting screw at
the analog I/O module end. Keep the shield connection to ground as
short as possible.
TIP
• For optimum accuracy, limit overall cable impedance by keeping your
cable as short as possible. Locate the I/O system as close to your sensors
or actuators as your application will permit.
• Load resistance for each current output channel must remain between
0…500 Ω..
In environments where high frequency noise may be present, it
may be necessary to ground the shield via a 0.1 µF capacitor at
the load end and also ground the module end without a capacitor.
Wiring Output Devices
ATTENTION: Miswiring of the module to an AC/DC source will
damage the module.
Be careful when stripping wires. Wire fragments that fall into a
module could cause damage at power up. Once wiring is complete,
ensure the module is free of all metal fragments.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
14 Compact 1769-OF4CI Isolated Analog Output Module
Labeling the Terminals
A removable, write-on label is provided with the module. Remove the label
from the door, mark the identification of each terminal with permanent ink,
and slide the label back into the door. Your markings (ID tag) will be visible
when the module door is closed.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 15
Removing the Finger-safe Terminal Block
To remove the terminal block, loosen the upper and lower retaining screws. The
terminal block will back away from the module as you remove the screws. When
replacing the terminal block, torque the retaining screws to 0.46 N
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
16 Compact 1769-OF4CI Isolated Analog Output Module
Wiring the Finger-safe Terminal Block
When wiring the terminal block, keep the finger-safe cover in place.
1. Loosen the terminal screws to be wired.
2. Route the wire under the terminal pressure plate. You can use the bare
wire or a spade lug.
The terminals will accept a 6.35 mm (0.25 in.) spade lug.
TIP
3. Tighten the terminal screw making sure the pressure plate secures the
wire. Recommended torque when tightening terminal screws is
0.68 N•m (6 in•lb).
TIP
The terminal screws are non-captive. You can use a ring lug
[maximum 6.35 mm (0.25 in.) o.d. with a 3.53 mm (0.139 in.)
minimum i.d. (M3.5)] with the module.
If you need to remove the finger-safe cover, insert a screwdriver
into one of the square wiring holes and gently pry the cover off. If
you wire the terminal block with the finger-safe cover removed,
you will not be able to put it back on the terminal block because
the wires will be in the way.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 17
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires with the following restrictions:
Wire TypeWire SizeTerminal Screw
Torque
SolidCu-90 °C (194°F) #14…#22 AWG0.68 N•m
Stranded Cu-90 °C (194°F) #16…#22 AWG0.68 N•m
(6 in•lbs)
(6 in•lbs)
Retaining Screw
Tor qu e
0.46 N•m
(4.1 in-•bs)
0.46 N•m
(4.1 in•lbs)
I/O Memory Mapping
Output Data File
For each module, slot x, words 0…3 in the output data file contain the channel
0 …3 output data. Word 4 is used to unlatch any condition that has been latched.
Refer to your module’s user manual for additional details.
Bit Position
1514131211109876543210
Word
0 SGNAnalog Output Data Channel 0
1 SGNAnalog Output Data Channel 1
2 SGNAnalog Output Data Channel 2
3 SGNAnalog Output Data Channel 3
4UU3 UO3 UU2 UO2 UU1 UO1 UU0 UO0
• SGN = Sign bit in two’s complement format (must be set to 0).
• UO = Unlatch over-range (or high clamp exceeded) alarm.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
18 Compact 1769-OF4CI Isolated Analog Output Module
Input Data File
For each module, slot x, input data file words 2…5 contain the state of the
module’s output data (output data echo) file words 0…3. During normal
operation, these input words represent the analog values that the outputs are
directed to by the control program.
Bit Position
1514131211109876543210
Word
0S3S2S1S0
1H3U3O3H2U2O2H1U1O1H0U0O0
2Channel 0 Data Value
3Channel 1 Data Value
4Channel 2 Data Value
5Channel 3 Data Value
• S = General status (over-range, under-range, or low/high clamp
exceeded).
• H = Output held bit.
• U = Under-range (or low-clamp exceeded) alarm.
• O = Over-range (or high-clamp exceeded) alarm.
IMPORTANT
The output module’s input data file reflects the analog output
data echo of the module, not necessarily the electrical state of
the output terminals. It does not reflect shorted or open outputs.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 19
Configuration Data File
The manipulation of the bits from this file is normally done with programming
software (for example, RSLogix 500 software or RSNetworx for DeviceNet
software) during initial configuration of the system. In that case, graphical
screens are provided by the programmer to simplify configuration.
However, some systems, like the 1769-ADN DeviceNet Adapter, also allow the
bits to be altered as part of the control program, using communication rungs. In
that case, it is necessary to understand the bit arrangement. The channel
configuration words, the first two words of each eight word group, are described
on page 20
Word DescriptionWord Description
0Channel 0 Configuration Word 016Channel 2 Configuration Word 0
1Channel 0 Configuration Word 117Channel 2 Configuration Word 1
2Channel 0 Fault Value Word18Channel 2 Fault Value Word
3Channel 0 Program Idle Mode
4Channel 0 Low Clamp20Channel 2 Low Clamp
5Channel 0 High Clamp21Channel 2 High Clamp
6Channel 0 Ramp Rate22Channel 2 Ramp Rate
7Channel 0 Spare23Channel 2 Spare
8Channel 1 Configuration Word 024Channel 3 Configuration Word 0
9Channel 1 Configuration Word 125Channel 3 Configuration Word 1
10Channel 1 Fault Value Word26Channel 3 Fault Value Word
11Channel 1 Program Idle Mode
. Refer to your module’s user manual for additional details.
Word
Word
19Channel 2 Program Idle Mode
Word
27Channel 3 Program Idle Mode
Word
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
20 Compact 1769-OF4CI Isolated Analog Output Module
Channel Configuration Words
The first two words of each eight word group in the configuration file allow
you to change the parameters of each channel independently. For example,
words 8 and 9 correspond to channel 1 while words 16 and 17 correspond to
channel 3.
Word/Bit151413121110987654321
Word 0EReservedSIU SIO LA ER FM PM HI
Word 1ReservedOutput Data
Format Select
ReservedOutput
Type/Range
• E = Channel Enable: (0 = Disabled, 1 = output Enabled, process
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 21
DefineIndicate thisThese bit settings
1514131211109876543210
Program
(Idle) to Fault
Enable
Hold for
Initialization
Program
(Idle) Mode
Fault Mode Hold Last State
Enable
Ramping
System
Interrupt
High Clamp
System
Interrupt Low
Clamp
Enable
Channel
(1) These functions are not supported by all controllers (for example, MicroLogix 1500) using any
Program (Idle)
Mode Data
(1)
Applied
Fault Mode Data
(1)
Applied
Disabled
Enabled1
Hold Last State
User-Defined
Valu e
User-Defined
Fault Value
(1)
(1)
(1)
(1)
Disabled0
Enabled1
Disabled0
(1)
Enabled
Disabled0
(1)
Enabled
Disabled0
Enabled1
configuration method. Refer to your controller manual for details.
0
1
1
1
0
1
0
0
1
DefineIndicate thisThese bit settings
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Output
Range
Select
Output
Data
Select
0…20 mA DC00
4…20 mA DC00
Raw/Proportional
Counts
0 0 0
Engineering Units001
Scaled for PID010
Percent Range011
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
0
0
1
22 Compact 1769-OF4CI Isolated Analog Output Module
Specifications
Specification1769-OF4CI
Dimensions118 mm (height) x 87 mm (depth) x 35 mm
Approximate Shipping Weight
(with carton)
Storage Temperature-40°C to +85°C (-40°F to +185°F)
Operating Temperature0°C to +60°C (32°F to +140°F)
Operating Humidity5% to 95% non-condensing
Operating Altitude2000 meters (6561 feet)
VibrationOperating: 10 to 500 Hz, 5G, 0.030 in.
(1) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency
range is 30 MHz to 1000 MHz.
(width)
height including mounting tabs is 138 mm
4.65 in. (height) x 3.43 in (depth) x 1.38 in
(width)
height including mounting tabs is 5.43 in.
270g (0.6 lbs.)
peak-to-peak
(20G, 11 ms DIN rail mounted)
Non-Operating: 40G panel mounted
(30G DIN rail mounted)
• UL 508 listed
• CE compliant for all applicable directives
Groups A, B, C, D (ISA 12.12-01, C-UL under
CSA C22.2 No. 213)
following levels:
modulation
(1)
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 23
Specification1769-OF4CI
Analog Normal Operating Ranges
Full Scale Analog Ranges
(1)
(1)
0 to 20 mA, 4 to 20 mA
0 to 21 mA, 3.2 to 21 mA
Number of Outputs4 isolated differential
Bus Current Draw (max.)5V, 165mA
24V, 110mA
Heat Dissipation2.68 Total Watts (All points - 21 mA into
250Ω - worst case calculated.)
Digital Resolution Across Full Range16 bits (unipolar)
+4 to +20 mA: 15.59 bits, 0.323 µA/bit
0 to +20 mA: 15.91 bits, 0.323 µA/bit
Conversion Rate (all channels) max.110 ms
Step Response to 63%
(2)
<2.9 ms
Resistive Load on Current Output0 to 500 Ω (includes wire resistance)
Max. Inductive Load0.1 mH
Field CalibrationNone required
Overall Accuracy
(1) The over- or under-range flag will come on when the normal operating range (over/under) is exceeded.
The module will continue to convert the analog output up to the maximum full scale range. The flag
automatically resets when within the normal operating range unless configured to latch.
(2) Step response is the period of time between when the D/A converter was instructed to go from
minimum to full range until the device is at 63% of full range.
(3) Includes offset, gain, drift, non-linearity and repeatability error terms.
(3)
±0.35% full scale at 25°C
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
24 Compact 1769-OF4CI Isolated Analog Output Module
Specification1769-OF4CI
Accuracy Drift with Temperature±0.0058% FS per °C
Output Ripple
range 0 to 50 kHz
(referred to output range)
Non-linearity (in percent full scale)±0.05%
Repeatability
(in percent full scale)
Output Error Over Full Temperature Range
(0 to 60°C [+32 to +140°F])
Output Impedance>1 MΩ
Open and Short-Circuit ProtectionYes
Maximum Short-Circuit Current21 mA
Output Overvoltage ProtectionYes
Output Response at System Power Up and
Power Down
Rated Working Voltage
Output Group to Bus Isolation500V ac or 710V dc for 1 minute (qualification
Module OK LEDOn: module has power, has passed internal
Channel DiagnosticsOver- or under-range by bit reporting
(1) Output ripple is the amount a fixed output varies with time, assuming a constant load and
(2) Repeatability is the ability of the output module to reproduce output readings when the same
(3) Rated working voltage is the maximum continuous voltage that can be applied at the output terminal,
(1)
(2)
±0.05%
±0.05%
±0.55%
No power up or power down current glitch
(3)
30V ac/30V dc
test)
30V ac/30V dc working voltage (IEC Class 2
reinforced insulation)
diagnostics, and is communicating over the
bus.
Off: Any of the above is not true.
temperature.
controller value is applied to it consecutively, under the same conditions and in the same direction.
including the output signal and the value that floats above ground potential (for example, 10V dc
output signal and 20V dc potential above ground).
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 25
Specification1769-OF4CI
System Power Supply Distance RatingThe module may not be more than 8 modules
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or
non-hazardous locations only. The following ATTENTION statement applies
to use in hazardous locations.
WARNING: EXPLOSION HAZARD
• Substitution of components may impair suitability for Class I,
Division 2.
• When in hazardous locations, turn off power before wiring or
replacing modules.
• Do not disconnect equipment unless power has been switched off
or the area is known to be non-hazardous.
• This product must be installed in an enclosure.
• All wiring must comply with N.E.C. article 501-4(b).
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
26 Compact 1769-OF4CI Isolated Analog Output Module
Environnements dangereux
Cet équipement est conçu pour être utilisé dans des environnements de Classe 1,
Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante
s’applique à une utilisation dans des environnements dangereux.
AVERTISSEMENT: DANGER D’EXPLOSION
La substitution de composants peut rendre cet équipement impropre à
une utilisation en environnement de Classe 1, Division 2.
Ne pas remplacer de composants ou déconnecter l'équipement sans
s'être assuré que l'alimentation est coupée et que l'environnement est
classé non dangereux.
Ne pas connecter ou déconnecter des composants sans s'être assuré
que l'alimentation est coupée ou que l'environnement est classé non
dangereux.
Ce produit doit être installé dans une armoire.
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Compact 1769-OF4CI Isolated Analog Output Module 27
Additional Resources
These documents contain additional information concerning related Rockwell
Automation products.
ResourceDescription
Compact I/O Analog Modules User Manual,
publication 1769-UM002
MicroLogix 1500 Programmable Controllers
User Manual, publication 1764-UM001
1769-ADN DeviceNet Adapter User Manual,
publication1769-UM001
Industrial Automation Wiring and Grounding
Guidelines, publication1770-4.1
Product Certifications website,
http://www.ab.com
You can view or download publications at
http://www.rockwellautomation.com/literature/
technical documentation, contact your local Rockwell Automation distributor
or sales representative.
Provides detailed information on installing,
programming, and troubleshooting
Compact analog I/O modules.
Provides a detailed description for installing
and using Compact I/O modules with a
MicroLogix 1500 programmable controller.
Provides a detailed description of how to
install and use Compact I/O modules with
the 1769-ADN DeviceNet Adapter.
Provides general guidelines for installing a
Rockwell Automation industrial system.
Provides declarations of conformity,
certificates, and other certification details.
. To order paper copies of
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At
http://www.rockwellautomation.com/support/
technical and application notes, sample code and links to software service packs, and a MySupport feature
that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we
offer TechConnect support programs. For more information, contact your local distributor or Rockwell
Automation representative, or visit http://www.rockwellautomation.com/support/
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's
contained in this manual. You can also contact a special Customer Support number for initial help in getting
your product up and running.
contact your local Rockwell Automation representative.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from
the manufacturing facility. However, if your product is not functioning and needs to be returned, follow
these procedures.
United States
Outside United States
Contact your distributor. You must provide a Customer Support case number
(call the phone number above to obtain one) to your distributor to complete
the return process.
Please contact your local Rockwell Automation representative for the return
procedure.
, you can find technical manuals, a knowledge base of FAQs,
.
at
, or
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to
improve this document, complete this form, publication RA-DU002
http://www.rockwellautomation.com/literature/
Allen-Bradley, Compact I/O, CompactLogix, MicroLogix, RSLogix, RSLogix 500, RSNetWorx, Rockwell Software, Rockwell
Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Ro ckwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel : +90 (216) 5698400
.
Publication 1769-IN075B-EN-P - August 2010PN-83819