Rockwell Automation 1766-L32 User Manual

Pump Station Controller
Quick Start
Important User Information
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 Automation sales office or online at http://www.rockwellautomation.com/literature/ between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from your local Rockwell
) describes some important differences
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Allen-Bradley, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Table of Contents Preface
Configuration and Operation
Drawing Set

Table of Contents

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Chapter 1
Pump Station Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Chapter 2
Pump Station Controller Hardware Drawings . . . . . . . . . . . . . . . . . . . 41
1Publication IASIMP-QS037A-EN-P - May 2013 2013 1
2 Publication IASIMP-QS037A-EN-P - May 2013 2013

Preface

Introduction

This Quick Start Guide contains step-by-step instructions for configurating and operating the Pump Station Controller. The Controller consists of a standard pre-engineered package using off-the-shelf products including the MicroLogix 1400 PLC, PanelView Component C600 HMI and PowerFlex drives. Application files are also supplied so no PLC programming is required and HMI screens are pre-programmed.
This package includes the PLC and HMI application code plus a full set of system, panel, and electrical drawings that includes a bill of material. You can download the application code and drawings by going to the Rockwell Automation Integrated Architecture Tools Website,
http://www.ab.com/go/iatools
tab. The Pump Station Controller application download can be found on this page.
and selecting the “Beyond Getting Started”
3Publication IASIMP-QS037A-EN-P - May 2013 3
Preface
Notes:
4 Publication IASIMP-QS037A-EN-P - May 2013

Configuration and Operation

Chapter
1

Pump Station Controller

Introduction
This application uses the MicroLogix 1400 and PanelView Component C600 to provide a "stand alone" multifunction pump controller that allows the user the ability to choose between a pump down (lift station), pump up (water tank), or a pressure follower (water distribution) control process, with just a few simple screen selections.
Functionality includes:
Control of up to 4 pumps.
User assignable inputs.
Use of floats, analog or a combination of both to control the process.
Control of VFDs through Modbus communication, which reduces the
control wiring to the drives (PowerFlex 4/40/400 VFDs only)
Pump control can be done with starters, PowerFlex 4 series VFDs or with another manufactures VFD.
Pump sequencing control.
User selectable alarms with the ability to choose which ones can be used
to initiate an alarm dialer (user supplied)
Pump statistics.
The ability to save and load VFD parameters from the HMI. (PF4
VFDs only).
Selectable pump interlocks.
Screen access security.
5Publication IASIMP-QS037A-EN-P - May 2013 5
Chapter 1
Flashes when a Warning exists
Flashes when an Alarm exists Common header
Not visible until an application has been selected
Only visible if analog device is being used
Legend depends on if Pressure Follower, Level Pump Down or Level Pump Up mode is selected
Legend depends on if Pressure Follower” mode is selected or Level mode is selectd
Main Screen
The main screen displays configuration, monitoring and maintenance controls. Some control label content displays based on the current configuration.
Several of the buttons on the Main screen do not display until the application has been set up. So the first step is to go through the Application Config button.
6 Publication IASIMP-QS037A-EN-P - May 2013
Chapter 1
Configuring the Application
The functions available when you select the Application Config button include:
Select the pumps and pump modes
Select primary and secondary measuring devices
Select control devices for all active pumps
Assign digital inputs and their states
Assign backup pumps
Each of the configuration screens contains standard navigational tools:
Press Prev or Next to navigate between screens.
Press Up, Down, or Enter to navigate available choices on a single
screen.
Press Exit to return to the Main menu.
To use the configuration controls:
1. From the Main screen, press Application Config to display the configuration screen.
From the configuration screen you can:
– Use the Up/Down/Enter buttons to select from the three available
operation modes
– Press Enter The Number Of Pumps to select the number of
pumps (1-4) in use in the system
– View a description of the selected mode
Publication IASIMP-QS037A-EN-P - May 2013 7
Chapter 1
TIP
TIP
2. Press Next to proceed to the Measuring Setup screen.
From the Measuring Setup screen you can:
– Use the Up/Down buttons to select the primary measuring device.
If Pressure Follower mode is selected then Analog "In 0" is the only option for the primary measuring device.
Select a secondary measuring device
If the primary measuring device is an analog device, you can assign a float to be used as backup (not available if primary measuring is floats).
– Use the second analog input (IN 1) to measure flow rate from an
analog transmitter or as the process variable if the default analog input (IN 0) fails.
When analog input "IN 1" (I:1.1) is set for Flow the flow is totalized using a calculation in the PLC. A more accurate way to totalize would be to use digital input I:0/0 as a totalized pulse.
8 Publication IASIMP-QS037A-EN-P - May 2013
Chapter 1
3. Press Next to proceed to the Motor Control Setup screen. In the example shown, four pumps have been configured; the screen will only display as many pumps as you set up in the initial configuration screen.
From the Motor Control Setup screen you can use the Up/Down buttons to select the pump control device.
The Starter and Other VFD selections use physical outputs from the PLC to control the start/stop operation of the motors, while the
PowerFlex 4 option uses Modbus communication to control the VFD.
4. Press Next to proceed to the first Digital Inputs Assign screen. There
are four Digital Inputs Assign screens in total.
From the first Digital Inputs Assign screen you can:
– Use Digital input I:0/0 as a pulsed input to totalize flow only or to
totalize flow and calculate a flow rate.
Publication IASIMP-QS037A-EN-P - May 2013 9
Chapter 1
As a flow totalizer this can be very accurate. However, using it to calculate flow rate is not as accurate as using analog input I:1.1 as a flow rate input.
– Press Enter Gallons Per Pulse to set the appropriate gallons per
input pulse
5. Press Next to proceed to the next Digital Inputs Assign screen.
From the remaining Digital Inputs Assign screens you can:
– Press Normally Open or Normally Closed to set the state to
match the way the digital input is wired on the field device.
– Use the Up/Down and End/Home buttons to scroll through the
list of selections
– Digital inputs I:0/0 – I:0/17 are assignable to any of the 31
selections listed; however, depending on the application, they may not all be applicable. For example, if you only have two pumps in your system, selection #20 Pump 3 seal fail would not apply
10 Publication IASIMP-QS037A-EN-P - May 2013
Chapter 1
NOT USED --­(Selection 0 of 31)
Low Level (Selection 1 of 31)
Pumps Stop (Selection 2 of 31)
Lead Start (Selection 3 of 31)
Lag Start (Selection 4 of 31)
High Level Selection 5 of 31)
Pump 1 Running (Selection 6 of 31)
Pump 2 Running (Selection 7 of 31)
Pump 3 Running (Selection 8 of 31)
Pump 4 Running (Selection 9 of 31)
Pump 2 OL/Fault (Selection 11 of 31)
Pump 3 OL/Fault (Selection 12 of 31)
Pump 4 OL/Fault (Selection 13 of 31)
Pump 1 Motor Over Temp (Selection 14 of 31)
Pump 2 Motor Over Temp (Selection 15 of 31)
Pump 3 Motor Over Temp (Selection 16 of 31)
Pump 4 Motor Over Temp (Selection 17 of 31)
Pump 1 Seal Fail (Selection 18 of 31)
Pump 2 Seal Fail (Selection 19 of 31)
Pump 3 Seal Fail (Selection 20 of 31)
Low Pressure (Selection 22 of 31)
High Pressure (Selection 23 of 31)
Power failure (Selection 24 of 31)
Generator Running (Selection 25 of 31)
Generator Fault (Selection 26 of 31)
General Fault (Selection 27 of 31)
Pump #1 Auto (Selection 28 of 31)
Pump #2 Auto (Selection 29 of 31)
Pump #3 Auto (Selection 30 of 31)
Pump #4 Auto (Selection 31 of 31)
Pump 1 OL/Fault (Selection 10 of 31)
Pump 4 Seal Fail (Selection 21 of 31)
Publication IASIMP-QS037A-EN-P - May 2013 11
Chapter 1
TIP
TIP
TIP
If during the measuring
buttons will enable or
device setup, floats are selected as secondary (backup) then these
disable the pumps from running in backup mode.
Press Next to proceed to the Backup Pump Select screen.
The Backup Pump Selection screen is visible only if Float is selected as the backup on the Measuring Setup screen.
Press the Delay Between Pump Starts (Seconds) to enter the delay before the next one starts when more than one backup pump is enabled.
If on the “Measuring Setup” screen (above) the “Secondary (backup) Measuring Device” is set to “NOT USED”, then no pumps will run in backup.
If on the “Measuring Setup” screen (above) the “Secondary (backup) Measuring Device” is set to “Floats”, then backup pumps will start when the “Lead Start” float is activated, and continue until the “Pumps Stop” float is activated.
A “lead start” and a “pumps stop” selection must be assigned to an input on one of the “Digital Input Assign” screens.
12 Publication IASIMP-QS037A-EN-P - May 2013
Chapter 1
Because this is a backup operation likely due to a failure, the pumps do not alternate.
Setup Examples
Example 1: In a pump down application. Floats are being used as backup. On the Pump Sequence Setup screen, the Primary selection for all pumps is set to Alternate, and the Secondary selections are set to Lag1. And on the Backup Pump Selection screen, lead, lag1 and lag2
pumps are all allowed to run as backup. As the level rises and activates the Lead Start float. The lead pump (because all are set for alternate, it could be any of the four pumps) starts. Let’s say that the Delay Between Pump Starts (see graphic above) is set for 60 sec. If the Pumps Stop float does not clear in this time, all of the pumps assigned to Lag1 as Secondary will start (in this case all of them). If a pump was set to Lag2 as the Secondary selection, it will start 60 sec. after the Lag1 pump(s) start. If all of the pumps are set to Lag2 as Secondary, then no pumps will start during the first 60 sec. (Lag1 time). The sequence is: lead pump --- delay --- lag1 pump(s) --- delay --- lag2 pump(s). Once a pump starts, it will continue to run until the Pumps Stop float clears.
Example 2: Same setup as above except the Secondary selections are now as shown. Let’s say that pump 2 is the lead pump. Lead Start float is activated.
Pump 2 starts --- 60 sec. time delay --- pump 1 (lag1) starts --- 60 sec. time delay --- pump 3 (lag2) starts. Because pump 4 is set to Not Used it does not run.
Example 3: The setup is as shown, however now the Lag1 pump is not allowed to run in backup. Again, let’s say that pump 2 is the lead pump. Lead Start float is activated. Pump 2 starts
--- 60 sec. time delay --- and although pumps 1 and 3 are both set for lag1, they do no
Publication IASIMP-QS037A-EN-P - May 2013 13
Chapter 1
IMPORTANT
run because the lag1 pumps are not allowed to run due to the selection on the Backup Pump Selection screen --- 60 sec. time delay --- pump 4 (lag2) starts.
Configuring Analog Inputs
Now that the application has been set up, you can continue through the rest of the configuration.
1. From the Main screen, press Analog Inputs Config to display the configuration screen.
This button is not visible unless an analog device is being used (Measurement Setup screen).
The screen includes displays showing the raw data coming from the analog input card and mA value of the input from the calibrated (zero and span set) card.
2. Select one of the two following calibration methods:
Apply a 4mA signal to the cards input (I:1.0), then push Apply a
4mA Signal To Analog "In 0" to make the zero adjustment. After making the zero adjustment, choose Apply a 20mA Signal To Analog "In 0" to make the span adjustment if a signal is available.
Select No 4-20mA Signal Available? to calibrate the analog input
using the card's default values if no current calibrator is available.
You must use one of these calibration methods to ensure proper operation.
3. Enter a scaled value in the Enter 4mA Signal Value field. For example: 0 Ft.
4. Enter a scaled value in the Enter 20mA Signal Value field. For example: 10 Ft.
14 Publication IASIMP-QS037A-EN-P - May 2013
Loading...
+ 36 hidden pages