Because of the variety of uses for the products described in this
publication, those responsible for the application and use of this
control equipment must satisfy themselves that all necessary steps
have been taken to assure that each application and use meets all
performance and safety requirements, including any applicable laws,
regulations, codes and standards.
The illustrations, charts, sample programs and layout examples shown
in this guide are intended solely for purposes of example. Since there
are many variables and requirements associated with any particular
installation, Allen-Bradley does not assume responsibility or liability
(to include intellectual property liability) for actual use based upon
the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the
Application, Installation and Maintenance of Solid-State Control
(available from your local Allen-Bradley office), describes some
important differences between solid-state equipment and
electromechanical devices that should be taken into consideration
when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole
or part, without written permission of Rockwell Automation, is
prohibited.
Throughout this publication, notes may be used to make you aware of
safety considerations. The following annotations and their
accompanying statements help you to identify a potential hazard,
avoid a potential hazard, and recognize the consequences of a
potential hazard:
WARNING
Identifies information about practices or
circumstances that can cause an explosion in a
hazardous environment, which may lead to personal
injury or death, property damage, or economic loss.
!
ATTENTION
Identifies information about practices or
circumstances that can lead to personal injury or
death, property damage, or economic loss.
!
IMPORTANT
Identifies information that is critical for successful
application and understanding of the product.
MicroLogix, Compact I/O, and RSLogix are trademarks of Rockwell Automation.
Page 3
Summary of Changes
The information below summarizes the changes to this manual since
the last printing.
To help you find new and updated information in this release of the
manual, we have included change bars as shown to the right of this
paragraph.
The table below lists the sections that document new features and
additional or updated information on existing features.
For this information: See
Series C support for up to 16 expansion I/O
modules
List of controller series, OS FRN numbers,
and RSLogix versions
Updated list of recommended surge
suppressors
Ethernet ConnectivityPage 4-23
Typical CPU hold-up timePage A-1
Updated system loading and heat
dissipation worksheets
System loading graphs for 1769 power
supplies, including 1769-PA4 and 1769-PB4
Chapter 1
Page 1-5
Page 3-6
Appendix F
pages F-5 through F-7
iiiPublication 1764-UM001B-EN-P - March 2002
Page 4
Summary of Changes iv
Publication 1764-UM001B-EN-P - March 2002
Page 5
Hardware Overview
Table of Contents
Preface
Who Should Use this Manual. . . . . . . . . . . . . . . . . . . . . . . P-1
Read this preface to familiarize yourself with the rest of the manual. It
provides information concerning:
• who should use this manual
• the purpose of this manual
• related documentation
• conventions used in this manual
• Rockwell Automation support
Who Should Use this
Manual
Purpose of this Manual
Use this manual if you are responsible for designing, installing,
programming, or troubleshooting control systems that use
MicroLogix 1500 controllers.
You should have a basic understanding of electrical circuitry and
familiarity with relay logic. If you do not, obtain the proper training
before using this product.
This manual is a reference guide for MicroLogix 1500 controllers. It
describes the procedures you use to install, wire, and troubleshoot
your controller. This manual:
• explains how to install and wire your controllers
• gives you an overview of the MicroLogix 1500 controller system
Refer to publication 1762-RM001, MicroLogix 1200 and MicroLogix
1500 Programmable Controllers Instruction Set Reference Manual for
the MicroLogix 1200 and 1500 instruction set and for application
examples to show the instruction set in use. Refer to your
programming software user documentation for more information on
programming your MicroLogix 1500 controller.
Related Documentation
P-1Publication 1764-UM001B-EN-P - April 2002
The documents listed on page P-2 contain additional information
concerning Rockwell Automation products. If you would like a copy,
you can:
• download a free electronic version from the internet:
www.ab.com/micrologix or www.theautomationbookstore.com
• purchase a printed manual by:
– contacting your local distributor or Rockwell Automation
representative
– visiting www.theautomationbookstore.com and placing your
order
– calling 1.800.963.9548 (USA/Canada)
or 001.330.725.1574 (Outside USA/Canada)
Page 12
Preface P-2
ForRead this DocumentDocument Number
A technical overview of the MicroLogix 1500 and related
products
Information on the MicroLogix 1500 Controllers instruction setMicroLogix 1200 and 1500 Programmable
MicroLogix 1500 Programmable Controllers
Technical Data
1764-TD001
1762-RM001
Controllers Instruction Set Reference Manual
Information on mounting and wiring the MicroLogix 1500 Base
Units, including a mounting template for easy installation
MicroLogix 1500 Programmable Controllers
Base Unit Installation Instructions
1764-IN001
An overview of Compact I/OCompact I/O System Overview1769-SO001
More information on Compact I/O Power Supplies and Cables1769 Compact I/O Power Supplies and
1769-TD001
Communication Bus Expansion Cables
Technical Data
More information on Compact Analog I/O and Temperature Input
Modules
Compact Analog I/O and Temperature Input
Modules Technical Data
1769-TD004
Detailed information on using Compact I/O Analog ModulesCompact I/O Analog Modules User Manual1769-UM002
Detailed information on installing, configuring, and using
1769-IT6 Thermocouple/mV Input Modules
Detailed information on installing, configuring, and using
1769-IR6 RTD/Resistance Input Modules
Detailed information on installing, configuring, and using
1769-HSC High Speed Counter Modules
A description on how to install and connect an AIC+. This
manual also contains information on network wiring.
Compact I/O 1769-IT6 Thermocouple/mV
Input Module User Manual
Compact I/O 1769-IR6 RTD/Resistance Input
Module User Manual
Compact 1769-HSC High Speed Counter
Module User Manual
Advanced Interface Converter (AIC+) User
Manual
1769-UM004
1769-UM005
1769-UM006
1761-6.4
Information on how to install, configure, and commission a DNIDeviceNet™ Interface User Manual1761-6.5
Information on installing, connecting, and configuring an ENIEthernet Interface User Manual1761-UM001
Information on installing, configuring, and using a DeviceNet
Scanner
Information on DF1 open protocol.DF1 Protocol and Command Set Reference
Compact™ I/O 1769-SDN DeviceNet Scanner
User Manual
1761-UM009
1770-6.5.16
Manual
In-depth information on grounding and wiring Allen-Bradley
programmable controllers
A description of important differences between solid-state
programmable controller products and hard-wired
Allen-Bradley Programmable Controller
Grounding and Wiring Guidelines
Application Considerations for Solid-State
Controls
1770-4.1
SGI-1.1
electromechanical devices
An article on wire sizes and types for grounding electrical
equipment
A complete listing of current documentation, including ordering
National Electrical Code - Published by the National Fire Protection
Association of Boston, MA.
Allen-Bradley Publication IndexSD499
instructions. Also indicates whether the documents are available
on CD-ROM or in multi-languages.
A glossary of industrial automation terms and abbreviationsAllen-Bradley Industrial Automation GlossaryAG-7.1
Publication 1764-UM001B-EN-P - April 2002
Page 13
Preface P-3
Common Techniques Used
in this Manual
Rockwell Automation
Support
The following conventions are used throughout this manual:
• Bulleted lists such as this one provide information, not
procedural steps.
• Numbered lists provide sequential steps or hierarchical
information.
• Italic type is used for emphasis.
Rockwell Automation offers support services worldwide, with over 75
Sales/Support Offices, 512 authorized Distributors and 260 authorized
Systems Integrators located throughout the United States alone, plus
Rockwell Automation representatives in every major country in the
world.
Local Product Support
Contact your local Rockwell Automation representative for:
• sales and order support
• product technical training
• warranty support
• support service agreements
Technical Product Assistance
Before you contact Rockwell Automation for technical assistance, we
suggest you please review the troubleshooting information contained
in this publication first.
Publication 1764-UM001B-EN-P - April 2002
Page 14
Preface P-4
If the problem persists, call your local Rockwell Automation
representative or contact Rockwell Automation in one of the following
ways:
PhoneUnited
States/Canada
Outside United
States/Canada
Internet
⇒
1.440.646.5800
You can access the phone number for your
country via the Internet:
1. Go to http://www.ab.com
2. Click on
(http://support.automation.rockwell.com)
3. Under
Information
1. Go to http://www.ab.com
2. Click on
(http://support.automation.rockwell.com)
Product Support
Support Centers
Product Support
, click on
Contact
Your Questions or Comments on this Manual
If you find a problem with this manual, or you have any suggestions
for how this manual could be made more useful to you, please
contact us at the address below:
Rockwell Automation
Automation Control and Information Group
Technical Communication, Dept. A602V
P.O. Box 2086
Milwaukee, WI 53201-2086
Publication 1764-UM001B-EN-P - April 2002
or visit our internet page at:
http://www.rockwellautomation.com
For the latest information on MicroLogix controllers, visit
www.ab.c
om/micrologix
Page 15
Hardware Overview
Chapter
1
Hardware Features
The MicroLogix 1500 programmable controller is composed of a base
unit, which contains a power supply, input and output circuits, and a
processor. The controller is available with 24 or 28 points of
embedded I/O. Additional I/O may be added using Compact™ I/O.
A controller is composed of a processor (1764-LSP or enhanced
1764-LRP with RS-232 port) and one of the base units listed below.
The FET transistor outputs are available on the 1764-28BXB base only.
Base Units
Catalog
Number
1764-24AWA 120/240V ac (12) 120V ac(12) Relay, 2 isolated relays
1764-24BWA 120/240V ac (8) Standard 24V dc
1764-28BXB24V dc(8) Standard 24V dc
Line Power InputsOutputsHigh Speed I/O
n/a
(4) 20 kHz input
(8) 20 kHz input
(2) 20 kHz output
(4) Fast 24V dc
(8) Fast 24V dc
per unit
(12) Relay, 2 isolated relays
per unit
(6) Relay, 2 isolated relays
per unit
(4) Standard 24V dc FET
(2) Fast 24V dc FET
Publication 1764-UM001B-EN-P - April 2002
Page 17
Processors
Processor (Catalog Number 1764-LSP)
Processor (Catalog Number 1764-LRP)
Hardware Overview 1-3
Communications Port
• DTE (male) 9-pin D-shell
connector
• 30V dc isolation
Data Access Tool (Catalog Number 1764-DAT)
1764-DAT
mounted on
1764-LSP
processor.
Publication 1764-UM001B-EN-P - April 2002
Page 18
1-4 Hardware Overview
Memory Modules/Real-Time Clock
Memory module
mounted on
1764-LSP
processor.
The following memory modules and real-time clock modules are
available:
Catalog NumberFunctionMemory Size
1764-RTCReal-Time Clocknot applicable
1764-MM1Memory Module8K
1764-MM1RTCMemory Module and Real-Time Clock8K
1764-MM2
1764-MM2RTC
(1) For 1764-LRP programs greater than 8k, use the 1764-MM2 or 1764-MM2RTC.
(1)
(1)
Memory Module16K
Memory Module and Real-Time Clock16K
Cables
Use only the following communication cables in Class I, Division 2
hazardous locations.
Table 1.1 Cables for Use in Class I, Division 2 Hazardous Environment
1761-CBL-PM02 Series C or later2707-NC8 Series B or later
1761-CBL-HM02 Series C or later2707-NC9 Series B or later
1761-CBL-AM00 Series C or later2707-NC10 Series B or later
1761-CBL-AP00 Series C or later2707-NC11 Series B or later
Publication 1764-UM001B-EN-P - April 2002
Page 19
Hardware Overview 1-5
Programming
Programming the MicroLogix 1500 programmable controller is done
using RSLogix™ 500, Rev. 4.0 or later. Certain features are only
available when using the most current version of the software, as
noted in System Requirements for Using Expansion Modules on page
1-7.
The following table lists the firmware release numbers, feature and
functionality enhancements, and the required version of RSLogix 500
and RSLogix 500 Starter software.
Table 1.B Required Software Version by FRN Number
Controller Firmware
Release
Initial
Release
EnhancementOctober
Series B
Release
1764-LSP
EnhancementOctober
Available
for Sale
Date
February
1999
1999
March
2000
2000
Catalog
Number
Series
AB
AC
BA
BB
Catalog
Number
Revision
OS FRN
Number
2Initial Release3.01.00
3Power Supply and Expansion Cable
4String Data File Type,
5PTO Controlled Stop,
Feature and Functionality
Changes
Compatibility
ASCII Instruction Set,
Modbus RTU Slave Protocol,
Ramping (when using PWM outputs),
Static Data File Protection,
RTC Messaging
Memory Module Program Compare Bit
Enhancement
Required
Version of
RSLogix
500/RSLogix
500 Starter
Software
3.01.00
4.00.00
4.50.00
1764-LRP
Series C
Release
Initial
Release
EnhancementOctober
Series C
Release
September
2001
March
2000
2000
September
2001
CA
BA
BB
CA
6Floating Point Data File Support,
Programmable Limit Switch (PLS),
Real Time Clock Adjust (Copy Word),
Absolute Value,
Gray Code,
Recipe,
Message Instruction Support for
1769-SDN
4Initial Release - Same Functionality as
1764-LSP
5PTO Controlled Stop,
Memory Module Program Compare Bit
Enhancement
6Floating Point Data File Support,
Programmable Limit Switch (PLS),
Real Time Clock Adjust (Copy Word),
Absolute Value,
Gray Code,
Recipe,
Message Instruction Support for
1769-SDN
Publication 1764-UM001B-EN-P - April 2002
5.10.00
4.00.00
4.50.00
5.10.00
Page 20
1-6 Hardware Overview
Communication Options
Compact™ Expansion I/O
The MicroLogix 1500 can be connected to a personal computer. It can
also be connected to the DH-485 network using an Advanced
Interface Converter (1761-NET-AIC), to an Ethernet network using an
Ethernet Interface (1761-NET-ENI), or to a DeviceNet™ network using
a DeviceNet Interface (1761-NET-DNI) or through the DeviceNet
Scanner module (1769-SDN). The controller can also be connected to
Modbus™ SCADA networks as an RTU slave. See Communication
Connections on page 4-1 for more information on connecting to the
available communication options.
The 1764-LRP processor provides an additional communication port.
Each of the communications ports can be independently configured
for any supported communication protocol. (Channel 0 is on the base
unit and Channel 1 is on the 1764-LRP processor.)
Compact expansion I/O (Bulletin 1769) can be connected to the
MicroLogix 1500 Controller. A maximum of either 8 or 16 expansion
I/O modules can be used, depending upon your system. See System
Requirements for Using Expansion Modules on page 1-7.
See System Loading and Heat Dissipation on page F-1 for more
information on system configurations.
End Cap
An end cap terminator (catalog number 1769-ECR or 1769-ECL) must
be used at the end of the group of I/O modules attached to the
MicroLogix 1500 Controller. The end cap terminator is not provided
with the base or processor units. It is required when using expansion
I/O.
This illustration shows the right end cap (1769-ECR ). The left end cap
(1769-ECL) is shown on page 1-10.
Publication 1764-UM001B-EN-P - April 2002
Page 21
Hardware Overview 1-7
Expansion Power Supply and Cables
With Operating System Revision Number (FRN) 3 or higher, you can
connect an additional bank of I/O to your controller. Using an
expansion power supply increases the system’s capacity for adding
expansion I/O modules. The additional I/O bank is connected to the
controller via a specially designed cable. The additional I/O bank
must include a power supply and an end cap.
TIP
Depending on the system configuration, each
controller can support up to 16 expansion I/O
modules. See the System Requirements for Using
Expansion Modules below. Also see System
Guidelines on page 1-9 for system limitations and
illustrations of expansion I/O banks.
System Requirements for Using Expansion Modules
To support a maximum of 8 I/O modules in an additional I/O bank,
you must have the following:
Table 1.3 Requirements to Support a Maximum of 8 I/O Modules
ProductCatalog Number
MicroLogix 1500
Processor
MicroLogix 1500
Base Unit
Operating System
Version
1764-LSP, Series A, Revision C or higher
1764-LSP, Series B or higher
1764-LRP, Series B or higher
1764-24AWA, Series A or higher
1764-24BWA, Series A or higher
1764-28BXB, Series A or higher
Firmware Revision Number (FRN) 3 or higher
1764-LSP, Series ARSLogix 500, Version 3.01.09 or higher,
(1)
Programming
Software
1 Power Supply
(optional)
1 Cable (optional)1769-CRL1, 1769-CRL3, 1769-CRR1, 1769-CRR3
1 End Cap (required)1769-ECL, 1769-ECR
(1) You can check the FRN by looking at word S:59 (Operating System FRN) in the Status File.
1764-LSP, Series B
1764-LRP, Series B
1764-LSP, Series C
1764-LRP, Series C
1769-PA2, 1769-PA4
1769-PB2, 1769-PB4
RSLogix 500, Version 4.00.00 or higher.
RSLogix 500, Version 5.00.00 or higher.
Publication 1764-UM001B-EN-P - April 2002
Page 22
1-8 Hardware Overview
To support a maximum of 16 I/O modules in an additional I/O bank,
you must have the following:
Table 1.4 Requirements to Support a Maximum of 16 I/O Modules
ProductCatalog Number
MicroLogix 1500 Processor1764-LSP, Series C or higher
1764-LRP, Series C or higher
MicroLogix 1500 Base Unit1764-24AWA, Series B or higher
1764-24BWA, Series B or higher
1764-28BXB, Series B or higher
Operating System Version
Programming SoftwareRSLogix 500, Version 5.10.00 or higher.
1 Power Supply (optional)1769-PA2, 1769-PA4, 1769-PB2, 1769-PB4
1 Cable (optional)1769-CRL1, 1769-CRL3, 1769-CRR1, 1769-CRR3
1 End Cap (required)1769-ECL, 1769-ECR
(1) You can check the FRN by looking at word S:59 (Operating System FRN) in the Status File.
Firmware Revision Number (FRN) 6 or higher
(1)
IMPORTANT
If your processor is at an older revision, you must
upgrade the operating system to FRN 3 or higher
to use an expansion cable and power supply (or to
FRN 6 or higher to allow up to 16 expansion
modules). On the Internet, go to
http://www.ab.com/micrologix to download the
operating system upgrade. Navigate to MicroLogix
1500 for further instructions and downloads.
MicroLogix 1500 base units are not field upgradeable
from Series A to Series B.
Publication 1764-UM001B-EN-P - April 2002
Page 23
Hardware Overview 1-9
Adding an I/O Bank
System Guidelines
A maximum of one 1769 Expansion Cable can be used in a
MicroLogix 1500 system, allowing for two banks of I/O modules (one
connected directly to the controller, and the other connected via the
cable). Each I/O bank requires its own power supply (Bank 1 uses the
controller’s embedded power supply).
ATTENTION
!
ATTENTION
!
LIMIT OF ONE EXPANSION POWER SUPPLY
The expansion power supply cannot be connected
directly to the controller. It must be connected using
an expansion cable. Only one power supply
(embedded in the base unit or an expansion power
supply) may be used on an I/O bank. Exceeding
these limitations may damage the power supply and
result in unexpected operation.
REMOVE POWER
Remove system power before making or breaking
cable connections. When you remove or insert a
cable connector with power applied, an electrical arc
may occur. An electrical arc can cause personal
injury or property damage by:
• sending an erroneous signal to your system’s field
devices, causing unintended machine operation
• causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on
both the module and its mating connector.
IMPORTANT
Refer to your power supply and I/O module’s
documentation for instructions on how to set up
your system.
See the System Requirements for Using Expansion
Modules on page 1-7 to determine the maximum
number of expansion I/O modules you can use in
your MicroLogix system.
Also see System Loading and Heat Dissipation on
page F-1 for more information on system
configurations.
Publication 1764-UM001B-EN-P - April 2002
Page 24
1-10 Hardware Overview
The following illustrations show a MicroLogix 1500 with an expansion
I/O bank.
Vertical Orientation
Expansion
I/O Bank 1
1769-CRRx
Expansion Cable
1769-ECL
End Cap
(1) The x in this catalog number can be either a 1 or a 3 representing the length of the cable:
1 = 1 foot (305 mm) and 3 = 3.28 feet (1 meter).
(1)
Expansion
I/O Bank 2
Horizontal Orientation
1769-ECR
End Cap
Publication 1764-UM001B-EN-P - April 2002
Expansion
I/O Bank 1
(1) The x in this catalog number can be either a 1 or a 3 representing the length of the cable:
1 = 1 foot (305 mm) and 3 = 3.28 feet (1 meter).
1769-CRLx
Expansion Cable
(1)
Expansion
I/O Bank 2
Page 25
Hardware Overview 1-11
Addressing Expansion I/O
The expansion I/O is addressed as slots 1 through 16 (the controller’s
embedded I/O is addressed as slot 0). Power supplies and cables are
not counted as slots. Modules are counted from left to right on each
bank as shown in the illustrations below. For more information on
addressing, refer to the MicroLogix 1200 and MicroLogix 1500 Programmable Controllers Instruction Set Reference Manual,
publication 1762-RM001.
Vertical Orientation
Expansion
Embedded
I/O = Slot 0
Slot 1
I/O Bank 1
Slot 2
Horizontal Orientation
Embedded
I/O = Slot 0
Slot 1
Slot 2
Expansion I/O Bank 1Expansion I/O Bank 2
Expansion I/O Power Failure
Expansion
I/O Bank 2
Slot 3
Slot 4
Slot 3
Slot 5
Slot 4
Slot 5
Expansion I/O errors represent failures of the I/O bus or the modules
themselves. The error codes are listed in the MicroLogix 1200 and
MicroLogix 1500 Programmable Controllers Instruction Set Reference
Manual, publication 1762-RM001.
Publication 1764-UM001B-EN-P - April 2002
Page 26
1-12 Hardware Overview
Publication 1764-UM001B-EN-P - April 2002
Page 27
Chapter
2
Installing Your Controller
This chapter shows you how to install your controller system. The
only tools you require are a Flat or Phillips head screwdriver and drill.
Topics include:
• agency certifications
• compliance to European Union Directives
• using in hazardous locations
• master control relay
• power considerations
• preventing excessive heat
• controller spacing
• mounting the controller
Agency Certifications
Compliance to European
Union Directives
• UL 508
• C-UL under CSA C22.2 no. 142
• Class I, Division 2, Groups A, B, C, D
(UL 1604, C-UL under CSA C22.2 no. 213)
• CE compliant for all applicable directives
This product has the CE mark and is approved for installation within
the European Union and EEA regions. It has been designed and tested
to meet the following directives.
EMC Directive
This product is tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) and the following standards, in
whole or in part, documented in a technical construction file:
• EN 50081-2
EMC - Generic Emission Standard, Part 2 - Industrial
Environment
• EN 50082-2
EMC - Generic Immunity Standard, Part 2 - Industrial
Environment
This product is intended for use in an industrial environment.
1Publication 1764-UM001B-EN-P - April 2002
Page 28
2-2 Installing Your Controller
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low
Voltage, by applying the safety requirements of EN 61131-2
Programmable Controllers, Part 2 - Equipment Requirements and
Tests.
For specific information required by EN 61131-2, see the appropriate
sections in this publication, as well as the following Allen-Bradley
publications:
• Industrial Automation Wiring and Grounding Guidelines for
Noise Immunity, publication 1770-4.1
• Guidelines for Handling Lithium Batteries, publication AG-5.4
• Automation Systems Catalog, publication B111
Installation Considerations
Most applications require installation in an industrial enclosure
(1)
(Pollution Degree 2
(Over Voltage Category II
your controller as far as possible from power lines, load lines, and
other sources of electrical noise such as hard-contact switches, relays,
and AC motor drives. For more information on proper grounding
guidelines, see the Industrial Automation Wiring and Grounding Guidelines publication 1770-4.1.
ATTENTION
) to reduce the effects of electrical interference
(2)
) and environmental exposure. Locate
Vertical mounting of the controller is not
recommended due to heat build-up considerations.
!
ATTENTION
!
Be careful of metal chips when drilling mounting
holes for your controller or other equipment within
the enclosure or panel. Drilled fragments that fall into
the base or processor unit could cause damage. Do
not drill holes above a mounted controller if the
protective debris strips are removed or the processor
is installed.
Publication 1764-UM001B-EN-P - April 2002
(1) Pollution Degree 2 is an environment where normally only non-conductive pollution occurs except that
occasionally temporary conductivity caused by condensation shall be expected.
(2) Overvoltage Category II is the load level section of the electrical distribution system. At this level transient
voltages are controlled and do not exceed the impulse voltage capability of the products insulation.
Page 29
Installing Your Controller 2-3
Safety Considerations
Safety considerations are an important element of proper system
installation. Actively thinking about the safety of yourself and others,
as well as the condition of your equipment, is of primary importance.
We recommend reviewing the following safety considerations.
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B,
C, D or non-hazardous locations only. The following WARNING
statement applies to use in hazardous locations.
WARNING
!
EXPLOSION HAZARD
• Substitution of components may impair suitability
for Class I, Division 2.
• Do not replace components or disconnect
equipment unless power has been switched off.
• Do not connect or disconnect components unless
power has been switched off, or the area is
known to be non-hazardous.
• This product must be installed in an enclosure. All
cables connected to the product must remain in
the enclosure or be protected by conduit or other
means.
• All wiring must comply with N.E.C. article
501-4(b).
WARNING
!
When installing any peripheral device (for example,
push buttons, lamps) into a hazardous environment,
ensure that they are Class I, Division 2 certified, or
determined to be safe for the environment.
Publication 1764-UM001B-EN-P - April 2002
Page 30
2-4 Installing Your Controller
Use only the following communication cables in Class I, Division 2
hazardous locations.
Table 2.1 Cables for Use in Class I, Division 2 Hazardous Environment
1761-CBL-PM02 Series C or later2707-NC8 Series B or later
1761-CBL-HM02 Series C or later2707-NC9 Series B or later
1761-CBL-AM00 Series C or later2707-NC10 Series B or later
1761-CBL-AP00 Series C or later2707-NC11 Series B or later
Disconnecting Main Power
WARNING
EXPLOSION HAZARD
Do not replace components or disconnect
equipment unless power has been switched off.
!
The main power disconnect switch should be located where operators
and maintenance personnel have quick and easy access to it. In
addition to disconnecting electrical power, all other sources of power
(pneumatic and hydraulic) should be de-energized before working on
a machine or process controlled by a controller.
Safety Circuits
WARNING
EXPLOSION HAZARD
Do not connect or disconnect connectors while
circuit is live.
Publication 1764-UM001B-EN-P - April 2002
!
Circuits installed on the machine for safety reasons, like overtravel
limit switches, stop push buttons, and interlocks, should always be
hard-wired directly to the master control relay. These devices must be
wired in series so that when any one device opens, the master control
relay is de-energized, thereby removing power to the machine. Never
alter these circuits to defeat their function. Serious injury or machine
damage could result.
Page 31
Installing Your Controller 2-5
Power Distribution
There are some points about power distribution that you should
know:
• The master control relay must be able to inhibit all machine
motion by removing power to the machine I/O devices when
the relay is de-energized. It is recommended that the controller
remain powered even when the master control relay is
de-energized.
• If you are using a dc power supply, interrupt the load side rather
than the ac line power. This avoids the additional delay of
power supply turn-off. The dc power supply should be powered
directly from the fused secondary of the transformer. Power to
the dc input and output circuits should be connected through a
set of master control relay contacts.
Power Considerations
Periodic Tests of Master Control Relay Circuit
Any part can fail, including the switches in a master control relay
circuit. The failure of one of these switches would most likely cause
an open circuit, which would be a safe power-off failure. However, if
one of these switches shorts out, it no longer provides any safety
protection. These switches should be tested periodically to assure they
will stop machine motion when needed.
The following explains power considerations for the micro controllers.
Isolation Transformers
You may want to use an isolation transformer in the ac line to the
controller. This type of transformer provides isolation from your
power distribution system to reduce the electrical noise that enters the
controller and is often used as a step-down transformer to reduce line
voltage. Any transformer used with the controller must have a
sufficient power rating for its load. The power rating is expressed in
volt-amperes (VA).
Publication 1764-UM001B-EN-P - April 2002
Page 32
2-6 Installing Your Controller
Power Supply Inrush
During power-up, the MicroLogix 1500 power supply allows a brief
inrush current to charge internal capacitors. Many power lines and
control transformers can supply inrush current for a brief time. If the
power source cannot supply this inrush current, the source voltage
may sag momentarily.
The only effect of limited inrush current and voltage sag on the
MicroLogix 1500 is that the power supply capacitors charge more
slowly. However, the effect of a voltage sag on other equipment
should be considered. For example, a deep voltage sag may reset a
computer connected to the same power source. The following
considerations determine whether the power source must be required
to supply high inrush current:
• The power-up sequence of devices in a system.
• The amount of the power source voltage sag if the inrush
current cannot be supplied.
• The effect of voltage sag on other equipment in the system.
If the entire system is powered-up at the same time, a brief sag in the
power source voltage typically will not affect any equipment.
Loss of Power Source
The power supply is designed to withstand brief power losses without
affecting the operation of the system. The time the system is
operational during power loss is called “program scan hold-up time
after loss of power.” The duration of the power supply hold-up time
depends on the type and state of the I/O, but is typically between 10
milliseconds and 3 seconds. When the duration of power loss reaches
this limit, the power supply signals the processor that it can no longer
provide adequate dc power to the system. This is referred to as a
power supply shutdown. The processor then performs an orderly
shutdown of the controller.
Input States on Power Down
Publication 1764-UM001B-EN-P - April 2002
The power supply hold-up time as described above is generally
longer than the turn-on and turn-off times of the inputs. Because of
this, the input state change from “On” to “Off” that occurs when
power is removed may be recorded by the processor before the
Page 33
Installing Your Controller 2-7
power supply shuts down the system. Understanding this concept is
important. Write the user program, taking this effect into account.
Other Types of Line Conditions
Occasionally the power source to the system can be temporarily
interrupted. It is also possible that the voltage level may drop
substantially below the normal line voltage range for a period of time.
Both of these conditions are considered to be a loss of power for the
system.
Preventing Excessive Heat
For most applications, normal convective cooling keeps the controller
within the specified operating range. Ensure that the specified
temperature range is maintained. Proper spacing of components
within an enclosure is usually sufficient for heat dissipation.
In some applications, a substantial amount of heat is produced by
other equipment inside or outside the enclosure. In this case, place
blower fans inside the enclosure to assist in air circulation and to
reduce “hot spots” near the controller.
Additional cooling provisions might be necessary when high ambient
temperatures are encountered.
TIP
Do not bring in unfiltered outside air. Place the
controller in an enclosure to protect it from a
corrosive atmosphere. Harmful contaminants or dirt
could cause improper operation or damage to
components. In extreme cases, you may need to use
air conditioning to protect against heat build-up
within the enclosure.
Publication 1764-UM001B-EN-P - April 2002
Page 34
2-8 Installing Your Controller
Master Control Relay
A hard-wired master control relay (MCR) provides a reliable means for
emergency machine shutdown. Since the master control relay allows
the placement of several emergency-stop switches in different
locations, its installation is important from a safety standpoint.
Overtravel limit switches or mushroom-head push buttons are wired
in series so that when any of them opens, the master control relay is
de-energized. This removes power to input and output device circuits.
Refer to the figures on pages 2-10 and 2-11.
ATTENTION
Never alter these circuits to defeat their function
since serious injury and/or machine damage could
result.
!
TIP
If you are using an external dc power supply,
interrupt the dc output side rather than the ac line
side of the supply to avoid the additional delay of
power supply turn-off.
The ac line of the dc output power supply should be
fused.
Connect a set of master control relays in series with
the dc power supplying the input and output
circuits.
Place the main power disconnect switch where operators and
maintenance personnel have quick and easy access to it. If you mount
a disconnect switch inside the controller enclosure, place the switch
operating handle on the outside of the enclosure, so that you can
disconnect power without opening the enclosure.
Whenever any of the emergency-stop switches are opened, power to
input and output devices should be removed.
When you use the master control relay to remove power from the
external I/O circuits, power continues to be provided to the
controller’s power supply so that diagnostic indicators on the
processor can still be observed.
The master control relay is not a substitute for a disconnect to the
controller. It is intended for any situation where the operator must
quickly de-energize I/O devices only. When inspecting or installing
terminal connections, replacing output fuses, or working on
Publication 1764-UM001B-EN-P - April 2002
Page 35
Installing Your Controller 2-9
equipment within the enclosure, use the disconnect to shut off power
to the rest of the system.
TIP
Do not control the master control relay with the
controller. Provide the operator with the safety of a
direct connection between an emergency-stop switch
and the master control relay.
Using Emergency-Stop Switches
When using emergency-stop switches, adhere to the following points:
• Do not program emergency-stop switches in the controller
program. Any emergency-stop switch should turn off all
machine power by turning off the master control relay.
• Observe all applicable local codes concerning the placement
and labeling of emergency-stop switches.
• Install emergency-stop switches and the master control relay in
your system. Make certain that relay contacts have a sufficient
rating for your application. Emergency-stop switches must be
easy to reach.
• In the following illustration, input and output circuits are shown
with MCR protection. However, in most applications, only
output circuits require MCR protection.
The following illustrations show the Master Control Relay wired in a
grounded system.
TIP
In most applications input circuits do not require
MCR protection; however, if you need to remove
power from all field devices, you must include MCR
contacts in series with input power wiring.
Publication 1764-UM001B-EN-P - April 2002
Page 36
2-10 Installing Your Controller
L1
L2
230V ac
Disconnect
Schematic (Using IEC Symbols)
Fuse
MCR
230V ac
I/O
Circuits
Isolation
Transformer
115V ac
X1
or 230V ac
Fuse
X2
Operation of either ofthese contacts will
remove power from the external I/O
circuits, stopping machine motion.
Emergency-Stop
Push Button
(Lo)(Hi)
Line Terminals:
Connect to terminals of Power Supply
(1764-24AWA and 1764-24BWA).
Overtravel
Limit Switch
Stop
Line Terminals: Connect to 24V dc
terminals of Power Supply.
Start
MCR
MCR
dc Power Supply.
Use IEC 950/EN 60950
_
+
Master Control Relay (MCR)
Cat. No. 700-PK400A1
MCR
Suppr.
115V ac or
230V ac
I/O Circuits
24V dc
MCR
I/O
Circuits
Suppressor
Cat. No.
700-N24
Publication 1764-UM001B-EN-P - April 2002
Page 37
Schematic (Using ANSI/CSA Symbols)
Installing Your Controller 2-11
L1
230V ac
Disconnect
Isolation
Transformer
115V ac or
X1X2
230V ac
Fuse
L2
Operation of either ofthese contacts will
remove power from the external I/O
Emergency-Stop
Push Button
Overtravel
Limit Switch
Stop
Fuse
Start
MCR
MCR
Master Control Relay (MCR)
Cat. No. 700-PK400A1
MCR
115V ac or
230V ac
I/O Circuits
MCR
Suppr.
230V ac
Output
Circuits
Suppressor
Cat. No.
700-N24
(Lo)(Hi)
Line Terminals:
Connect to 1764-24AWA or
1764-24BWA terminals.
dc Power Supply.
Use NEC Class 2
_
+
Line Terminals: Connect to 24V
dc terminals of Power Supply.
MCR
24 V dc
I/O
Circuits
Publication 1764-UM001B-EN-P - April 2002
Page 38
2-12 Installing Your Controller
Base Unit Mounting
Dimensions
A
Controller Spacing
B
(1)
Dimension
Height (A)DIN latch open: 138 mm (5.43 in.), DIN latch closed: 118 mm (4.65 in.)
Width (B)168 mm (6.62 in.)
Depth (C)87 mm (3.43 in.)
(1) See Controller Dimensions on page A-9 for more dimensional information.
1764-24AWA1764-24BWA1764-28BXB
C
The base unit is designed to be mounted horizontally, with the
Compact™ expansion I/O extending to the right of the base unit.
Allow 50 mm (2 in.) minimum of space on all sides for adequate
ventilation, as shown below.
To p
Publication 1764-UM001B-EN-P - April 2002
Side
Controller
Compact I/O
Bottom
Compact I/O
Compact I/O
Compact I/O
Compact I/O
Side
End Cap
Page 39
Mounting the Controller
ATTENTION
!
Installing Your Controller 2-13
Do not remove protective debris strips until after the
base and all other equipment in the panel near the
base is mounted and wiring is complete. The debris
strips are there to prevent drill fragments, wire
strands and other dirt from getting into the controller.
Once wiring is complete, remove protective debris
strips and install processor unit. Failure to remove
strips before operating can cause overheating.
Protective
Debris Strips
ESD Barrier
ATTENTION
!
ATTENTION
!
Be careful of metal chips when drilling mounting
holes for your controller or other equipment within
the enclosure or panel. Drilled fragments that fall
into the controller could cause damage. Do not drill
holes above a mounted controller if the protective
debris strips have been removed.
Electrostatic discharge can damage semiconductor
devices inside the base unit. Do not touch the
connector pins or other sensitive areas.
Publication 1764-UM001B-EN-P - April 2002
Page 40
2-14 Installing Your Controller
TIP
If additional I/O modules are required for the
application, remove the ESD barrier to install
expansion I/O modules. A maximum of 16 I/O
modules may be connected to the base. (See page
1-7 for system requirements.) The I/O module’s
current requirements and power consumption may
further limit the number of modules connected to
the base. See System Loading and Heat Dissipation
on page F-1. An end cap terminator (catalog number
1769-ECR or 1769-ECL) is required at the end of the
group of I/O modules attached to the base.
Using a DIN Rail
The base unit and expansion I/O DIN rail latches lock in the open
position so that an entire system can be easily attached to or removed
from the DIN rail. The maximum extension of the latch is 15 mm (0.67
in.) in the open position. A flat-blade screw driver is required for
removal of the base unit. The base can be mounted to
EN50022-35x7.5 or EN50022-35x15 DIN rails. DIN rail mounting
dimensions are shown below.
Publication 1764-UM001B-EN-P - April 2002
B
A
DIN Rail Latch
DimensionHeight
ADIN latch open: 138 mm (5.43 in.), DIN latch closed: 118 mm (4.65 in.)
B47.6 mm (1.875 in.)
C47.6 mm (1.875 in) DIN latch closed
54.7 mm (2.16 in.) DIN latch open
C
Page 41
Installing Your Controller 2-15
To install your base unit on the DIN rail:
1. Mount your DIN rail. (Make sure that the placement of the base
unit on the DIN rail meets the recommended spacing
requirements, see Controller Spacing on page 2-12. Refer to the
mounting template from the inside back cover of the MicroLogix
1500 Programmable Controller Base Units Installation
Instructions, publication 1764-IN001.
2. Hook the top slot over the DIN rail.
3. While pressing the base unit down against the top of the rail,
snap the bottom of the base unit into position. Ensure DIN
latches are in the up (secured) position.
4. Leave the protective debris strip attached until you are finished
wiring the base unit and any other devices.
To remove your base unit from the DIN rail:
1. Place a flat-blade screwdriver in the DIN rail latch at the bottom
of the base unit.
2. Holding the base unit, pry downward on the latch until the latch
locks in the open position. Repeat this procedure with the
second latch. This releases the base unit from the DIN rail.
DIN Rail Latch
Publication 1764-UM001B-EN-P - April 2002
Page 42
2-16 Installing Your Controller
Base Unit Panel Mounting
Mount to panel using #8 or M4 screws.
Mounting Template
To install your base unit using mounting screws:
1. Remove the mounting template from the inside back cover of
the MicroLogix 1500 Programmable Controller Base Units Installation Instruction, publication 1764-IN001.
2. Secure the template to the mounting surface. (Make sure your
base unit is spaced properly, see Controller Spacing on page
2-12).
3. Drill holes through the template.
4. Remove the mounting template.
5. Mount the base unit.
6. Leave the protective debris strips attached until you are finished
wiring the base unit and any other devices.
Publication 1764-UM001B-EN-P - April 2002
Page 43
Installing Your Controller 2-17
Installing Controller
Components
Prevent Electrostatic Discharge
ATTENTION
!
Electrostatic discharge can damage integrated circuits
or semiconductors if you touch bus connector pins.
Follow these guidelines when you handle any
module:
• Touch a grounded object to discharge static
potential.
• Wear an approved wrist-strap grounding device.
• Do not touch the bus connector or connector
pins.
• Do not touch circuit components inside the
module.
• If available, use a static-safe work station.
When not in use, keep the module in its static-shield
bag.
ATTENTION
!
Processor
Be sure the base unit is free of all metal fragments
before removing protective debris strips and
installing the processor unit. Failure to remove strips
before operating can cause overheating.
Publication 1764-UM001B-EN-P - April 2002
Page 44
2-18 Installing Your Controller
1. Be sure base unit power is off.
2. Slide the processor into the base unit using the guide rails for
alignment.
3. Push until a click is heard. Be careful not to push on the
connector when installing the 1764-LRP processor.
IMPORTANT
It is critical that the processor is fully engaged
and locked into place.
4. Make sure the actuator is pushed closed.
5. To remove the processor from the base unit, make sure base
unit power is off. Push the actuator to the open position until
the processor is ejected slightly. Once the processor has been
ejected, it can be removed from the base unit.
Publication 1764-UM001B-EN-P - April 2002
Page 45
Installing Your Controller 2-19
Data Access Tool (DAT)
1. Remove cover from processor.
2. Holding the DAT in the proper orientation (as shown), place the
DAT onto processor. Align DAT port on the processor with the
plug on the DAT.
3. Firmly seat DAT on processor; make sure it seats into place.
Publication 1764-UM001B-EN-P - April 2002
Page 46
2-20 Installing Your Controller
4. To remove DAT, grasp using finger areas and pull upward.
Memory Module/Real-Time Clock
1. Remove the cover (or DAT if installed) from the processor as
shown below.
Publication 1764-UM001B-EN-P - April 2002
ATTENTION
!
Electrostatic discharge can damage semiconductor
devices inside the base and processor units. Do not
touch the connector pins or other sensitive areas.
Page 47
Installing Your Controller 2-21
2. Align connector on the memory module with the connector pins
on the processor.
3. Firmly seat the memory module in the processor making sure
the locking tabs click into place.
4. Replace the cover (or DAT if used).
Publication 1764-UM001B-EN-P - April 2002
Page 48
2-22 Installing Your Controller
Compact I/O
Attach and Lock Module (Module-to-Controller or Module-to-Module)
A Compact I/O module can be attached to the controller or an
adjacent I/O module before or after mounting to the panel or DIN rail.
The module can be detached and replaced while the system is
mounted to a panel or DIN rail.
ATTENTION
!
ATTENTION
!
Remove power before removing or inserting an I/O
module. When you remove or insert a module with
power applied, an electrical arc may occur. An
electrical arc can cause personal injury or property
damage by:
• sending an erroneous signal to your system’s field
devices, causing the controller to fault
• causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on
both the module and its mating connector. Worn
contacts may create electrical resistance, reducing
product reliability.
When attaching I/O modules, it is very important that
they are securely locked together to ensure proper
electrical connection.
Publication 1764-UM001B-EN-P - April 2002
Page 49
Installing Your Controller 2-23
3
4
1
1
To attach and lock modules:
TIP
1. Disconnect power.
2. Check that the bus lever of the module to be installed is in the
unlocked (fully right) position.
3. Use the upper and lower tongue-and-groove slots (1) to secure
the modules together (or to a controller).
Remove ESD barrier when attaching I/O modules to
a MicroLogix 1500 base unit.
2
6
5
4. Move the module back along the tongue-and-groove slots until
the bus connectors (2) line up with each other.
5. Push the bus lever back slightly to clear the positioning tab (3).
Use your fingers or a small screw driver.
6. To allow communication between the controller and module,
move the bus lever fully to the left (4) until it clicks. Ensure it is
locked firmly in place.
ATTENTION
When attaching I/O modules, it is very important
that the bus connectors are securely locked
together to ensure proper electrical connection.
!
Publication 1764-UM001B-EN-P - April 2002
Page 50
2-24 Installing Your Controller
7. Attach an end cap terminator (5) to the last module in the
system by using the tongue-and-groove slots as before.
8. Lock the end cap bus terminator (6).
IMPORTANT
A 1769-ECR right end cap (or a 1769-ECL left end cap
if I/O bank is located below the controller) must be
used to terminate the end of the serial
communication bus.
See Controller Dimensions on page A-9 for mounting dimensions.
Publication 1764-UM001B-EN-P - April 2002
Page 51
Chapter
Wiring Your Controller
This chapter describes how to wire your controller. Topics include:
• wiring requirements
• using surge suppressors
• grounding guidelines
• sinking and sourcing circuits
• wiring diagrams, input voltage ranges, and output voltage
ranges
• minimizing noise
3
Wiring Requirements
Wire Type
SolidCu-90°C (194°F)#14 to #22 AWG1.13 Nm (10 in-lb) rated
StrandedCu-90°C (194°F)#14 to #22 AWG
(1) Two wires maximum per terminal screw.
ATTENTION
!
Be careful when stripping wires. Wire fragments that
fall into the controller could cause damage. Once
wiring is complete, be sure the base unit is free of all
metal fragments before removing protective debris
strips and installing the processor unit. Failure to
remove strips before operating can cause
overheating.
Wire Size
(1)
Wiring Torque
1.3 Nm (12 in-lb) maximum
1Publication 1764-UM001B-EN-P - April 2002
Page 52
3-2 Wiring Your Controller
Wiring Recommendation
ATTENTION
Before you install and wire any device, disconnect
power to the controller system.
!
ATTENTION
!
• Allow for at least 50 mm. (2 in.) between I/O wiring ducts or
terminal strips and the controller.
• Route incoming power to the controller by a path separate from
the device wiring. Where paths must cross, their intersection
should be perpendicular.
Calculate the maximum possible current in each
power and common wire. Observe all electrical
codes dictating the maximum current allowable for
each wire size. Current above the maximum ratings
may cause wiring to overheat, which can cause
damage.
United States Only: If the controller is installed within
a potentially hazardous environment, all wiring must
comply with the requirements stated in the National
Electrical Code 501-4 (b).
Publication 1764-UM001B-EN-P - April 2002
TIP
• Separate wiring by signal type. Bundle wiring with similar
electrical characteristics together.
• Separate input wiring from output wiring.
• Label wiring to all devices in the system. Use tape,
shrink-tubing, or other dependable means for labeling purposes.
In addition to labeling, use colored insulation to identify wiring
based on signal characteristics. For example, you may use blue
for dc wiring and red for ac wiring.
Do not run signal or communications wiring and
power wiring in the same conduit. Wires with
different signal characteristics should be routed by
separate paths.
Page 53
Wiring Your Controller 3-3
Wiring without Spade Lugs
When wiring without spade lugs, it is recommended to keep the
finger-safe covers in place. Loosen the terminal screw and route the
wires through the opening in the finger-safe cover. Tighten the
terminal screw making sure the pressure plate secures the wire.
Finger-Safe Cover
terminal screw torque:
1.13 Nm (10 in-lbs) rated
1.3 Nm (12 in-lbs) max.
Wiring with Spade Lugs
The diameter of the terminal screw head is 5.5 mm (0.220 in.). The
input and output terminals of the MicroLogix 1500 base unit are
designed for a 6.35mm (0.25 in.) wide spade (standard for #6 screw
for up to 14 AWG) or a 4 mm (metric #4) fork terminal.
When using spade lugs, use a small, flat-blade screwdriver to pry the
finger-safe cover from the terminal blocks as shown below. Then
loosen the terminal screw.
Finger-Safe
terminal screw torque:
1.13 Nm (10 in-lbs) rated
1.3 Nm (12 in-lbs) max.
Cover
Publication 1764-UM001B-EN-P - April 2002
Page 54
3-4 Wiring Your Controller
Using Surge Suppressors
Inductive load devices, such as motor starters and solenoids, require
the use of some type of surge suppression to protect and extend the
operating life of the controller’s output contacts. Switching inductive
loads without surge suppression can significantly reduce the life
expectancy of relay contacts. By adding a suppression device directly
across the coil of an inductive device, you prolong the life of the
output or relay contacts. You also reduce the effects of voltage
transients and electrical noise from radiating into adjacent systems.
The following diagram shows an output with a suppression device.
We recommend that you locate the suppression device as close as
possible to the load device.
ac or dc
Outputs
+dc or L1
VAC/D
Out 0
Out 1
Out 2
Out 3
Out 4
Out 5
Out 6
Out 7
COM
Suppression
Device
dc COM or L2
If the outputs are dc, we recommend that you use an 1N4004 diode
for surge suppression, as shown below.
+24V dc
VAC/D
Out 0
Out 1
Relay or Solid
State dc Outputs
Out 2
Out 3
Out 4
Out 5
Out 6
Out 7
COM
IN4004 Diode
24V dc common
Suitable surge suppression methods for inductive ac load devices
include a varistor, an RC network, or an Allen-Bradley surge
suppressor, all shown below. These components must be
appropriately rated to suppress the switching transient characteristic of
the particular inductive device. See the table on page 3-6 for
recommended suppressors.
Publication 1764-UM001B-EN-P - April 2002
Page 55
Surge Suppression for Inductive ac Load Devices
Wiring Your Controller 3-5
Output Device
VaristorRC NetworkSurge
Output Device
If you connect an expansion I/O triac output to control an inductive
load, we recommend that you use varistors to suppress noise. Choose
a varistor that is appropriate for the application. The suppressors we
recommend for triac outputs when switching 120V ac inductive loads
are a Harris MOV, part number V175 LA10A, or an Allen-Bradley MOV,
catalog number 599-K04 or 599-KA04. Consult the varistor
manufacturer’s data sheet when selecting a varistor for your
application
For inductive dc load devices, a diode is suitable. A 1N4004 diode is
acceptable for most applications. A surge suppressor can also be used.
See the table on page 3-6 for recommended suppressors.
As shown in the illustration below, these surge suppression circuits
connect directly across the load device.
Output Device
Suppressor
Surge Suppression for Inductive dc Load Devices
_
Output Device
Diode
(A surge suppressor can also be used.)
+
Publication 1764-UM001B-EN-P - April 2002
Page 56
3-6 Wiring Your Controller
Recommended Surge Suppressors
Use the Allen-Bradley surge suppressors shown in the following table
for use with relays, contactors, and starters.
Suppressor DeviceCoil VoltageCatalog Number
Bulletin 509 Motor Starter
Bulletin 509 Motor Starter
Bulletin 100 Contactor
Bulletin 100 Contactor
120V ac
240V ac
120V ac
240V ac
Bulletin 709 Motor Starter120V ac 1401-N10
Bulletin 700 Type R, RM Relaysac coilNone Required
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
12V dc
12V dc
(1)
599-K04
599-KA04
199-FSMA1
199-FSMA2
199-FSMA9
(1)
(2)
(2)
Grounding the Controller
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
Bulletin 700 Type N, P, or PK Relay150V max, ac or DC
Miscellaneous electromagnetic
24V dc
24V dc
48V dc
48V dc
115-125V dc
115-125V dc
230-250V dc
230-250V dc
150V max, ac or DC
199-FSMA9
199-FSMA9
199-FSMA10
199-FSMA11
700-N24
700-N24
(2)
(2)
devices limited to 35 sealed VA
(1) Varistor – Not recommended for use on relay outputs.
(2) RC Type – Do not use with triac outputs.
In solid-state control systems, grounding and wire routing helps limit
the effects of noise due to electromagnetic interference (EMI). Run the
ground connection from the ground screw of the base unit to the
electrical panel’s ground bus prior to connecting any devices. Use
AWG #14 wire. This connection must be made for safety purposes.
Publication 1764-UM001B-EN-P - April 2002
Page 57
Wiring Your Controller 3-7
This product is intended to be mounted to a well grounded mounting
surface such as a metal panel. Refer to the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for
additional information. Additional grounding connections from the
mounting tabs or DIN rail, if used, are not required unless the
mounting surface cannot be grounded. You must also provide an
acceptable grounding path for each device in your application.
TIP
Grounding Stamping
TIP
It is recommended to use all four mounting positions
for panel mounting installation.
Grounding Stamping
This symbol denotes a protective earth ground
terminal which provides a low impedance path
between electrical circuits and earth for safety
purposes and provides noise immunity
improvement. This connection must be made for
safety purposes
ATTENTION
!
Remove the protective debris strips before applying
power to the controller. Failure to remove the strips
may cause the controller to overheat.
Publication 1764-UM001B-EN-P - April 2002
Page 58
3-8 Wiring Your Controller
Wiring Diagrams
This section shows the wiring diagrams for the MicroLogix 1500
controllers. Controllers with dc inputs can be wired as either sinking
or sourcing configuration. (Sinking and sourcing does not apply to ac
inputs.) See pages 3-12 through 3-15 for sinking and sourcing wiring
diagrams.
TIP
This symbol denotes a protective earth ground
terminal which provides a low impedance path
between electrical circuits and earth for safety
purposes and provides noise immunity improvement.
This connection must be made for safety purposes.
Miswiring - 1764-28BXB Only
The following table shows miswiring conditions and the
consequences of improper wiring:
ConditionResult
Operating with Voltage
Less than 20.4V dc
This will not damage the base unit. The base unit may not
power up.
IMPORTANT
Reverse Wiring of the Line
Terminals (0 to 30V dc)
Applied Voltage Level
Exceeds the Published
Recommended Value
(i.e. applying 120V ac to
240V ac)
Reverse wiring will not damage the base unit. The base unit
will not power up.
Exceeding the published recommended voltage may result
in permanent damage to the base unit.
This is not recommended. You must
verify that the line voltage remains
within specified limits.
Publication 1764-UM001B-EN-P - April 2002
Page 59
Wiring Your Controller 3-9
Terminal Block Layouts
The base unit terminal block layouts are shown below. The shading
on the labels indicates how the terminals are grouped. A detail of the
groupings is shown in the table following the terminal block layouts.
Group 0Group 1Group 2
Inputs
1764-24BWA
Outputs
Inputs
1764-24AWA
Outputs
85-265
VAC
85-265
VAC
L1
L1
POWER
L2
L2
DC
OUT
VAC
VDC 0
VAC
VDC 0
+24V
G
NOT
USED
O / 0
r
o
u
G
r
o
COM
VAC
VDC 1
p
0
NOT
USED
VAC
VDC 1
u
p
0
DC
I / 1
I / 3
COM 0
G
r
o
I / 0
VAC
VDC 2
u
p
1
G
r
o
I / 2
VAC
VDC 3
u
p
2
I / 4
DC
I / 5
COM 1
VAC
O / 5
VDC 4
O / 3
O / 4O / 1O / 0 O / 2O / 6O / 9 O / 11
G
r
o
u
G
p
r
3
Group 0Group 1Group 2
AC
I / 1
I / 3
O / 3
G
AC
COM 1
VAC
VDC 4
r
o
u
p
3
I / 4
O / 4
I / 5
O / 5
G
COM 0
I / 2
I / 0
VAC
VAC
VDC 2
VDC 3
O / 2O / 6O / 9 O / 11
O / 1
G
G
r
r
o
o
u
u
p
p
2
1
DC
I / 6
COM 2
I / 7
O / 7 O / 8
VAC
VDC 5
o
u
p
4
AC
I / 6
COM 2
I / 7
O / 7 O / 8 O / 10
VAC
VDC 5
r
o
u
p
4
I / 8
I / 8
I / 9
I / 9
I / 10
O / 10
G
r
o
u
G
r
o
p
5
I / 10
u
p
5
I / 11
24BWA
24BWA
I / 11
24AWA
24AWA
Inputs
1764-28BXB
Outputs
24 VDC
NOT
USED
+24V
NOT
USED
COM
Group 0Group 1Group 2
DC
COM 0
I / 0
VAC
VDC 0
I / 1I / 3
I / 2
VAC
VDC 1
G
G
r
o
u
p
0
I / 4I / 6
DC
COM 1
VDC 2O / 5O / 3
r
o
u
p
1
I / 5
DC
COM 2
I / 7
I / 8I / 10
O / 7
O / 4
O / 6O / 1O / 0O / 2O / 11
COM 2
G
r
o
u
p
2
I / 9
VDC
VAC
VDC 3
I / 12 I / 14
O / 9 O / 10
O / 8
G
r
o
u
p
3
I / 13I / 11
VAC
VDC 4
G
I / 15
r
o
u
p
28BXB
28BXB
4
Publication 1764-UM001B-EN-P - April 2002
Page 60
3-10 Wiring Your Controller
Terminal Groupings
ControllerInputs
Input GroupCommon TerminalInput Terminal
1764-24BWAGroup 0DC COM 0I/0 through I/3
Group 1DC COM 1I/4 through I/7
Group 2DC COM 2I/8 through I/11
1764-24AWAGroup 0AC COM 0I/0 through I/3
Group 1AC COM 1I/4 through I/7
Group 2AC COM 2I/8 through I/11
1764-28BXBGroup 0DC COM 0I/0 through I/3
Group 1DC COM 1I/4 through I/7
Group 2DC COM 2I/8 through I/15
ControllerOutputs
Output GroupVoltage TerminalOutput Terminal
1764-24BWAGroup 0VAC/VDC 0O/0
Group 1VAC/VDC 1O/1
Group 2VAC/VDC 2O/2
Group 3VAC/VDC 3O/3
Group 4VAC/VDC 4O/4 through O/7
Group 5VAC/VDC 5O/8 through O/11
1764-24AWAGroup 0VAC/VDC 0O/0
Group 1VAC/VDC 1O/1
Group 2VAC/VDC 2O/2
Group 3VAC/VDC 3O/3
Group 4VAC/VDC 4O/4 through O/7
Group 5VAC/VDC 5O/8 through O/11
1764-28BXBGroup 0VAC/VDC 0O/0
Group 1VAC/VDC 1O/1
Group 2VDC 2, VDC COM 2O/2 through O/7
Group 3VAC/VDC 3O/8 and O/9
Group 4VAC/VDC 4O/10 and O/11
Sinking and Sourcing Input
Circuits
Publication 1764-UM001B-EN-P - April 2002
Any of the MicroLogix 1500 DC embedded input groups can be
configured as sinking or sourcing depending on how the DC COM is
wired on the group. See pages 3-12 through 3-15 for sinking and
sourcing wiring diagrams.
TypeDefinition
Sinking Input
connection of a PNP sourcing device
Sourcing Input
connection of an NPN sinking device
The input energizes when high-level voltage is
applied to the input terminal (active high). Connect
the power supply VDC (-) to the DC COM terminal.
The input energizes when low-level voltage is
applied to the input terminal (active low). Connect
the power supply VDC (+) to the DC COM terminal.
Page 61
1764-24AWA Wiring Diagram
Input Terminals
L2
Wiring Your Controller 3-11
NOT
USEDACCOM 0
NOT
USED
L1
“NOT USED” terminals are not intended for use as connection points.
IN 1
IN 0IN 2
IN 3
AC
COM 1
L2 L1
IN 4
IN 5IN 7IN 8IN 10
IN 6
AC
COM 2
Output Terminals
L2
(Lo)
VAC/
VAC/
VAC/
VAC/
VAC
NEUT
120/240
VAC
VDC 0
EARTH
GND
VDC 1
VDC 2
VDC 3
VAC/
VDC 4
IN 9
IN 11
CRCR
OUT 6OUT 4OUT 3OUT 2OUT 1OUT 0
VDC 5
VAC/
OUT 10OUT 8OUT 7OUT 5
OUT 11OUT 9
(Hi)
L1
CRCRCRCR
Publication 1764-UM001B-EN-P - April 2002
Page 62
3-12 Wiring Your Controller
1764-24BWA Wiring Diagram with Sinking Inputs
Input Terminals
+24V
POWER
Output Terminals
L2
(Lo)
120/240
OUT
VAC
COM
VAC
NEUT
DC
COM 0
IN 0IN 2
EARTH
GND
IN 1
VAC/
VDC 0
IN 3IN 4IN 6
DC
IN 5
COM 1
-DC
+DC
VAC/
VAC/
VDC 2
VDC 1
OUT 1OUT 0
OUT 2
VAC/
VDC 3
DC
COM 2
IN 7IN 8
VAC/
VDC 4
OUT 3
OUT 4
IN 9
IN 11
IN 10
CRCR
VAC/
OUT 6
VDC 5
OUT 10OUT 8OUT 7OUT 5
OUT 11OUT 9
Publication 1764-UM001B-EN-P - April 2002
(Hi)
L1
CRCRCRCR
Page 63
Wiring Your Controller 3-13
1764-24BWA Wiring Diagram with Sourcing Inputs
Input Terminals
+24V
POWER
OUT
COM
Output Terminals
L2
(Lo)
120/240
COM 0
VAC
DC
IN 1
IN 0IN 2
VAC
NEUT
EARTH
GND
IN 3IN 4IN 6
COM 1
+DC
VAC/
VAC/
VDC 1
VDC 0
DC
OUT 1OUT 0
-DC
VAC/
VDC 2
IN 5
OUT 2
COM 2
IN 7IN 8
VAC/
VDC 3
OUT 3
DC
VAC/
VDC 4
IN 9
OUT 4
IN 11
IN 10
CRCR
OUT 6
VAC/
VDC 5
OUT 10OUT 8OUT 7OUT 5
OUT 11OUT 9
(Hi)
L1
CRCRCRCR
Publication 1764-UM001B-EN-P - April 2002
Page 64
3-14 Wiring Your Controller
1764-28BXB Wiring Diagram with Sinking Inputs
Input Terminals
-DC
+DC
NOT
USEDDCCOM 0
NOT
IN 0IN 2
USED
“NOT USED” terminals are not intended for use as connection points.
IN 3IN 4IN 6
IN 1
DC
COM 1
IN 5
DC
COM 2
IN 7IN 8
IN 9
IN 10
Output Terminals (FET Outputs Are Sourcing Only)
-DC
CR
IN 13
IN 11
IN 12
CRCR
-DC
+DC
IN 15
IN 14
Publication 1764-UM001B-EN-P - April 2002
+DC
+24v
COM
VDC 0
EARTH
GND
VAC/
VAC/
VDC 1
OUT 1OUT 0
CRCRCR
OUT 2
OUT 3VDC 2
OUT 5
OUT 4
OUT 6
OUT 7
COM 2
VDC
VAC/
VDC 3
OUT 8
VAC/
VDC 4
OUT 10OUT 9
OUT 11
Page 65
Wiring Your Controller 3-15
1764-28BXB Wiring Diagram with Sourcing Outputs
Input Terminals
+DC
-DC
NOT
USEDDCCOM 0
NOT
IN 0IN 2
USED
“NOT USED” terminals are not intended for use as connection points.
IN 3IN 4IN 6
IN 1
DC
COM 1
IN 5
DC
COM 2
IN 7IN 8
IN 9
IN 10
Output Terminals (FET Outputs Are Sourcing Only)
-DC
CR
IN 13
IN 11IN 15
IN 14
IN 12
CRCR
+DC
-DC
+DC
+24V
COM
EARTH
GND
VAC/
VDC 0
VAC/
VDC 1
OUT 1OUT 0
CRCRCR
OUT 2
OUT 3VDC 2
OUT 5
OUT 4
OUT 6
Publication 1764-UM001B-EN-P - April 2002
OUT 7
COM 2
VDC
VAC/
VDC 3
OUT 8
VAC/
VDC 4
OUT 10OUT 9
OUT 11
Page 66
3-16 Wiring Your Controller
Controller I/O Wiring
Minimizing Electrical Noise
Because of the variety of applications and environments where
controllers are installed and operating, it is impossible to ensure that
all environmental noise will be removed by input filters. To help
reduce the effects of environmental noise, install the MicroLogix 1500
system in a properly rated (i.e. NEMA) enclosure. Make sure that the
MicroLogix 1500 system is properly grounded.
A system may malfunction may occur due to a change in the
operating environment after a period of time. We recommend
periodically checking system operation, particularly when new
machinery or other noise sources are installed near the Micrologix
1500 system.
Transistor Output Transient Pulses
ATTENTION
!
A brief transient current pulse may flow through
transistor outputs if the external supply voltage is
suddenly applied at the V dc and V dc com terminals
(e.g. via the master control relay). It is a fast
rate-of-change of voltage at the terminals that causes
the pulse. This condition is inherent in transistor
outputs and is common to solid state devices. The
transient pulses may occur regardless of whether the
controller is powered or running.
Publication 1764-UM001B-EN-P - April 2002
The transient energy is dissipated in the load, and the pulse duration
is longer for loads with high impedance. The graph below illustrates
the relation between pulse duration and load current. Power-up
transients will not exceed the times shown in the graph. For most
applications the pulse energy is not sufficient to energize the load.
To reduce the possibility of inadvertent operation of devices
connected to transistor outputs, consider adding an external resistor in
parallel to the load to increase the on-state load current. The duration
of the transient pulse is reduced when the on-state load current is
increased or the load impedance is decreased.
Page 67
1.0
Wiring Your Controller 3-17
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
Transient Pulse Duration as a
Function of Load Current
Time - Duration of Transient (ms)
0.1
0.0
10009008007006005004003002001001
On-State Load Current (mA)
Publication 1764-UM001B-EN-P - April 2002
Page 68
3-18 Wiring Your Controller
Publication 1764-UM001B-EN-P - April 2002
Page 69
Chapter
4
Communication Connections
This chapter describes how to set up communications for your control
system. The method you use and cabling required depend on your
application. This chapter also describes how the controller establishes
communication with the appropriate network. Topics include:
• Default Communication Configuration
• Communications Toggle Push Button
• Connecting to the RS-232 Port
• Connecting to a DH-485 Network
• Connecting to DeviceNet
• Connecting to Ethernet
Default Communication
Configuration
ATTENTION
All devices communicating within a network, must
use the same protocol.
!
The MicroLogix 1500 has the following default communication
configuration.
• The controller is powered-up for the first time.
• The communications toggle push button specifies
default communications (the DCOMM LED is on).
• An OS upgrade is completed.
For more information about communications, see Understanding
Communication Protocols on page E-1.
The Communications Toggle Push Button is located on the processor.
You must remove processor door or DAT to access the
Communications Toggle Push Button.
Use the Communications Toggle Push Button to change from the
user-defined communication configuration to the default
communications configuration and back. The Default
Communications (DCOMM) LED operates to show when the
controller is in the default communications mode (settings shown on
page 4-1).
Publication 1764-UM001B-EN-P - April 2002
TIP
COMMS
DC INPUTS
24V SINK/SOURCE
DC/RELAY OUT
24V SOURCE
The Communication Toggle Push Button must be
pressed and held for two seconds to activate.
The Communication Toggle Push Button only affects
the communication configuration of Channel 0.
Page 71
Communication Connections 4-3
Connecting to the RS-232
Port
DF1 Full-Duplex Communication Parameters
When a communication channel is configured for DF1 Full-Duplex,
the following parameters can be changed.
(Message) Detect
ACK Timeout1 to 65535 counts (20 ms increments)50 counts
NAK retries0 to 2553 retries
ENQ retries0 to 2553 retries
Stop Bitsnot a setting, always 11
0 to 254 decimal1
no
handshaking
enabled, disabledenabled
handshaking
Making a DF1 Full-Duplex Point-to-Point Connection
You can connect the MicroLogix 1500 programmable controller to
your personal computer using a serial cable from your personal
computer’s serial port to the controller, as shown in the illustrations
below.
ATTENTION
!
Chassis ground, internal 24V ground, user 24V dc
ground, and RS-232 ground are internally connected.
You must connect the chassis ground terminal screw
to ground prior to connecting any devices. It is
important that you understand your personal
computer’s grounding system before connecting to
the controller. An optical isolator, such as the
1761-NET-AIC, is recommended between the
controller and your personal computer when using
Channel 0. An isolator is not required when using
Channel 1 (1764-LRP).
Publication 1764-UM001B-EN-P - April 2002
Page 72
4-4 Communication Connections
Channel 0
We recommend using an Advanced Interface Converter (AIC+),
catalog number 1761-NET-AIC, or similar optical isolator, as shown
below. See page 4-16 for specific AIC+ cabling information.
1761-CBL-AM00
TX
TX PWR
TERM
A
B
COM
SHLD
CHS GND
TX
DC SOURCE
CABLE
EXTERNAL
or 1761-CBL-HM02
24V dc
MicroLogix 1500 provides power
to the AIC+ or an external power
supply may be used.
Channel 1
MicroLogix 1500 with 1764-LSP
or 1764-LRP processor
1747-CP3 or 1761-CBL-AC00
Personal Computer
MicroLogix
1500 Controller
with 1764-LRP
processor
Publication 1764-UM001B-EN-P - April 2002
Personal Computer
1747-CP3
Page 73
Personal
Computer
Using a Modem
You can use modems to connect a personal computer to one
MicroLogix 1500 controller (using DF1 Full-Duplex protocol), or to
multiple controllers (using DF1 Half-Duplex protocol), or Modbus
Slave RTU protocol, as shown in the following illustration. Do not use
DH-485 protocol through modems under any circumstance. (See
Using Modems with MicroLogix 1500 Programmable Controllers on
page E-3 for information on types of modems you can use with the
MicroLogix controllers.)
Modem Cable
(straight-through)
Modem
Communication Connections 4-5
MicroLogix1500
Controller with
1764-LRP
Processor
Protocol
DF1 Full-Duplex protocol (to 1 controller)
DF1 Half-Duplex Slave protocol (to multiple controllers when a
DF1 Half-Duplex Master is present)
Isolated Modem Connection
We recommend using an AIC+, catalog number 1761-NET-AIC, as
your optical isolator for Channel 0. See page 4-16 for specific AIC+
cabling information. Using an AIC+ to isolate the modem is illustrated
below:
1761-CBL-AM00
or 1761-CBL-HM02
User supplied modem cable
24V dc
MicroLogix 1500 provides power to the AIC+ or
an external power supply may be used.
Modem
MicroLogix 1500 with 1764-LSP
or 1764-LRP processor
Modem
Publication 1764-UM001B-EN-P - April 2002
Page 74
4-6 Communication Connections
Constructing Your Own Modem Cable
If you construct your own modem cable, the maximum cable length is
15.24 m (50 ft) with a 25-pin or 9-pin connector. Refer to the following
typical pinout for constructing a straight-through cable:
pins 4 and 6
are internally
connected for
1764-LRP only
If you construct your own null modem cable, the maximum cable
length is 15.24m (50 ft) with a 25-pin or 9-pin connector. Refer to the
following typical pinout:
Baud Rate300, 600, 1200, 2400, 4800, 9600, 19.2K, 38.4K
Paritynone, even
Source ID (Node Address)0 to 254 decimal
Control Lineno handshaking, handshaking
Error DetectionCRC, BCC
EOT Suppressionenabled, disabled
When EOT Suppression is enabled, the slave does not respond when polled if no message is queued. This
saves modem transmission power and time when there is no message to transmit.
Communication Connections 4-7
Duplicate Packet (Message)
Detect
Poll Timeout (x20 ms)0 to 65535 (can be set in 20 ms increments)
RTS Off Delay (x20 ms)0 to 65535 (can be set in 20 ms increments)
RTS Send Delay (x20 ms)0 to 65535 (can be set in 20 ms increments)
Message Retries0 to 255
Pre Transmit Delay
(x1 ms)
enabled, disabled
Detects and eliminates duplicate responses to a message. Duplicate packets may be sent under noisy
communication conditions if the sender’s Message Retries are not set to 0.
Poll Timeout only applies when a slave device initiates a MSG instruction. It is the amount of time that the
slave device waits for a poll from the master device. If the slave device does not receive a poll within the
Poll Timeout, a MSG instruction error is generated, and the ladder program needs to requeue the MSG
instruction. If you are using a MSG instruction, it is recommended that a Poll Timeout value of zero not be
used. Poll Timeout is disabled when set to zero.
Specifies the delay time between when the last serial character is sent to the modem and when RTS is
deactivated. Gives the modem extra time to transmit the last character of a packet.
Specifies the time delay between setting RTS until checking for the CTS response. For use with modems
that are not ready to respond with CTS immediately upon receipt of RTS.
Specifies the number of times a slave device attempts to resend a message packet when it does not
receive an ACK from the master device. For use in noisy environments where message packets may
become corrupted in transmission.
0 to 65535 (can be set in 1 ms increments)
• When the Control Line is set to
Required for 1761-NET-AIC physical Half-Duplex networks. The 1761-NET-AIC needs delay time to
change from transmit to receive mode.
• When the Control Line is set to
receiving the last character of a packet and the RTS assertion.
no handshaking
DF1 Half-Duplex Modem
, this is the delay time before transmission.
, this is the minimum time delay between
Publication 1764-UM001B-EN-P - April 2002
Page 76
4-8 Communication Connections
DF1 Half-Duplex Master-Slave Network
Use this diagram for DF1 Half-Duplex Master-Slave protocol without
hardware handshaking.
SLC 5/03 (DF1 Master)
CH0
1761-CBL-AP00 or
AIC+
MicroLogix 1500 (DF1 Slave)
1761-CBL-PM02
straight 9-25 pin cable
AIC+
radio modem
or lease line
radio modem
or lease line
CH0 to port 1 or port 2
1761-CBL-AM00 or
1761-CBL-HM02
1761-CBL-AP00 or
1761-CBL-PM02
MicroLogix 1500 (DF1 Slave)
CH0
1761-CBL-AM00 or
1761-CBL-HM02
AIC+
straight 9-25
pin cable
MicroLogix 1500 (DF1 Slave)
CH0 to port 1 or port 2
1761-CBL-AM00 or
1761-CBL-HM02
AIC+
1761-CBL-AP00 or
1761-CBL-PM02
REFERENCE: AIC+ Port Identification
Port 3: RS-485
Port 1: DB-9 RS-232
Publication 1764-UM001B-EN-P - April 2002
Port 2: mini-DIN 8 RS-232
Page 77
Rockwell Software RSLinx 2.0 (or
higher), SLC 5/03, SLC 5/04, and
SLC 5/05, or PLC-5 processors
configured for DF1 Half-Duplex
Master.
Communication Connections 4-9
DF1 Half-Duplex Network (Using PC and Modems)
DF1 Half-Duplex Protocol
Modem
TERM
A
B
COM
SHLD
CHS GND
TX
TX
TX PWR
DC SOURCE
CABLE
EXTERNAL
MicroLogix
1000 (Slave)
TERM
A
B
COM
SHLD
CHS GND
TX
TX
TX PWR
DC SOURCE
CABLE
EXTERNAL
MicroLogix
1200 (Slave)
TERM
A
B
COM
SHLD
CHS GND
TX
TX
TX PWR
DC SOURCE
CABLE
EXTERNAL
MicroLogix 1500 with
1764-LSP or 1764-LRP
Processor (Slave)
SLC 5/03 (Slave)
MicroLogix 1500 with
1764-LRP Processor (Slave)
Publication 1764-UM001B-EN-P - April 2002
Page 78
4-10 Communication Connections
Connecting to a DH-485
Network
connection from port 1 or port 2
to MicroLogix Channel 1
1761-CBL-AP00
or 1761-CBL-PM02
AIC+
TERM
A
B
COM
SHLD
CHS GND
TX
TX PWR
EXTERNAL
24V dc
(user supply
needed if not
connected to
a controller)
1747-CP3
or 1761-CBL-AC00
AIC+
TERM
A
B
COM
SHLD
CHS GND
TX
TX PWR
The following network diagrams provide examples of how to connect
MicroLogix 1500 controllers to the DH-485 network using the
Advanced Interface Converter (AIC+, catalog number 1761-NET-AIC).
For more information on the AIC+, see the Advanced Interface Converter and DeviceNet Interface Installation Instructions,
Publication 1761-5.11.
DH-485 Network with a MicroLogix 1500 Controller
MicroLogix 1500
1761-CBL-AM00
or 1761-CBL-HM02
EXTERNAL
connection from port 1 or port 2
to MicroLogix Channel 0
1761-CBL-AP00
or 1761-CBL-PM02
Personal Computer
PC to port 1
or port 2
24V dc
(user supply needed if not
connected to a controller)
REFERENCE: AIC+ Port Identification
TERM
A
B
COM
SHLD
Port 2: mini-DIN 8 RS-232
Port 3: RS-485
Port 1: DB-9 RS-232
CHS GND
TX
TX PWR
EXTERNAL
AIC+
24V dc
(user supplied)
1761-CBL-AP00
or 1761-CBL-PM02
TERM
A
B
COM
SHLD
CHS GND
TX
TX
TX PWR
DC SOURCE
CABLE
EXTERNAL
1747-CP3
or 1761-CBL-AC00
Publication 1764-UM001B-EN-P - April 2002
Page 79
Typical 3-Node Network (Channel 0 Connection)
AIC
PanelView 550
A-B
Communication Connections 4-11
PanelView
RJ45 port
1761-CBL-AS09
or 1761-CBL-AS03
TERM
A
B
COM
SHLD
CHS GND
TX
TX
TX PWR
DC SOURCE
CABLE
EXTERNAL
1747-CP3 or
1761-CBL-AC00
Typical 3-Node Network (Channel 1 Connection)
A-B
A-B
1761-CBL-AS09
or 1761-CBL-AS03
1747-CP3 or
1761-CBL-AC00
RJ45 port
TERM
TERM
A
A
B
B
COM
COM
SHLD
SHLD
CHS GND
CHS GND
TX
TX
TX
TX
1747-CP3 or
TXPWR
TX PWR
DC SOURCE
DC SOURCE
CABLE
CABLE
EXTERNAL
EXTERNAL
1761-CBL-AC00
1761-CBL-AM00
or 1761-CBL-HM02
PanelView
PanelView
PanelView 550
MicroLogix 1500 with
1764-LRP Processor
MicroLogix 1500 with
1764-LSP or 1764-LRP
Processor
Networked Operator Interface Device and MicroLogix Controllers
AIC+
TERM
A
B
COM
SHLD
CHS GND
TX
TX
TX PWR
DC SOURCE
CABLE
EXTERNAL
SLC 5/04
DH-485 Network
AIC+AIC+AIC+
TERM
A
B
COM
SHLD
CHS GND
TX
TX
TX PWR
DC SOURCE
CABLE
EXTERNAL
MicroLogix 1000
TERM
A
B
COM
SHLD
CHS GND
TX
TX
TX PWR
DC SOURCE
CABLE
EXTERNAL
MicroLogix 1200
TERM
A
B
COM
SHLD
CHS GND
TX
TX
TX PWR
DC SOURCE
CABLE
EXTERNAL
MicroLogix 1500
+
TERM
A
B
A-B
COM
SHLD
CHS GND
TX
TX
TX PWR
DC SOURCE
CABLE
EXTERNAL
PanelView
PanelView 550
AIC+
TERM
A
B
COM
SHLD
CHS GND
TX
TX
TX PWR
DC SOURCE
CABLE
EXTERNAL
Personal
Computer
Publication 1764-UM001B-EN-P - April 2002
Page 80
4-12 Communication Connections
DH-485 Configuration Parameters
When MicroLogix communications are configured for DH-485, the
following parameters can be changed:
The communication cable consists of a number of cable segments
daisy-chained together. The total length of the cable segments cannot
exceed 1219 m (4000 ft). However, two segments can be used to
extend the DH-485 network to 2438m (8000 ft). For additional
information on connections using the AIC+, refer to the Advanced Interface Converter (AIC+) User Manual, publication 1761-6.4.
Publication 1764-UM001B-EN-P - April 2002
Page 81
Communication Connections 4-13
Communication Cable Connection to the DH-485 Connector
TIP
A daisy-chained network is recommended.
We do not recommend the following:
Belden #3106A or #9842
Connector
Connector
Incorrect
Connector
Single Cable Connection
When connecting a single cable to the DH-485 connector, use the
following diagram.
Orange with White Stripes
White with Orange Stripes
Shrink Tubing Recommended
Blue (#3106A) or
Blue with White
Stripes (#9842)
6 Termination
5 A
4 B
3 Common
2 Shield
1 Chassis Ground
Drain/Shield
Publication 1764-UM001B-EN-P - April 2002
Page 82
4-14 Communication Connections
Multiple Cable Connection
When connecting multiple cables to the DH-485 connector, use the
following diagram.
to Previous Device
to Next Device
Table 4.6 Connections using Belden #3106A Cable
For this Wire/PairConnect this WireTo this Terminal
For this Wire/PairConnect this WireTo this Terminal
Shield/DrainNon-jacketedTerminal 2 - Shield
Blue/WhiteWhite with Blue StripeCut back - no
connection
Blue with White StripeTerminal 3 -
(Common)
White/OrangeWhite with Orange
Stripe
Orange with White
Stripe
(1) To prevent confusion when installing the communication cable, cut back the white with blue stripe wire
immediately after the insulation jacket is removed. This wire is not used by DH-485.
Terminal 4 - (Data B)
Terminal 5 - (Data A)
(1)
Grounding and Terminating the DH-485 Network
Only one connector at the end of the link must have Terminals 1 and
2 jumpered together. This provides an earth ground connection for
the shield of the communication cable. Both ends of the network must
have Terminals 5 and 6 jumpered together, as shown below. This
connects the termination impedance (of 120Ω) that is built into each
AIC+ as required by the DH-485 specification.
Publication 1764-UM001B-EN-P - April 2002
Page 83
End-of-Line Termination
Communication Connections 4-15
Jumper
Belden #3106A or #9842 Cable
1219 m (4000 ft) Maximum
Jumper
Jumper
Connecting the AIC+
The AIC+, catalog number 1761-NET-AIC, enables MicroLogix
controllers to connect to a DH-485 network when they are configured
for DH-485 protocol. The AIC+ has two isolated RS-232 ports and one
RS-485 port. When two MicroLogix controllers are closely positioned,
you can connect a controller to each of the RS-232 ports on the AIC+.
The AIC+ can also be used as an RS-232 isolator, providing an
isolation barrier between the controllers communications port and any
equipment connected to it (i.e. personal computer, modem, etc.)
The following figure shows the connections and specifications of the
AIC+.
(cable = port 2 power source, external =
external power source connected to item 5)
5Terminals for external 24V dc power supply
and chassis ground
3
2
1
5
4
For additional information on connecting the AIC+, refer to the
Advanced Interface Converter (AIC+) User Manual, publication
1761-6.4.
Publication 1764-UM001B-EN-P - April 2002
Page 84
4-16 Communication Connections
Cable Selection Guide
1761-CBL-AP00
1761-CBL-PM02
CableLengthConnections fromto AIC+ External Power
Supply
(1)
1761-CBL-AP00
1761-CBL-PM02
45cm (17.7 in)
2m (6.5 ft)
Required
1764-LRP processor, channel 1port 2yesexternal
SLC 5/03 or SLC 5/04 processors, channel 0port 2yesexternal
MicroLogix 1000 or 1500port 1yesexternal
PanelView 550 through NULL modem adapterport 2yesexternal
DTAM Plus / DTAM Microport 2yesexternal
PC COM portport 2yesexternal
(1) External power supply required unless the AIC+ is powered by the device connected to port 2, then the selection switch should be set to
1761-CBL-AM00
CableLengthConnections fromto
AIC+
External Power
Supply Required
1761-CBL-HM02
cable
Power Selection
(1)
Switch Setting
.
Power
Selection
Switch
(1)
Setting
(1)
1761-CBL-AM00
1761-CBL-HM02
(1) External power supply required unless the AIC+ is powered by the device connected to port 2, then the selection switch should be set to
45cm (17.7 in)
2m (6.5 ft)
MicroLogix 1000 or 1500port 2nocable
to port 2 on another AIC+port 2yesexternal
cable
.
Publication 1764-UM001B-EN-P - April 2002
Page 85
1761-CBL-AC00
Communication Connections 4-17
1747-CP3
CableLengthConnections fromto AIC+External Power
Supply Required
1747-CP3
1761-CBL-AC00
3m (9.8 ft)
45cm (17.7 in)
1764-LRP processor, channel 1port 1yesexternal
SLC 5/03 or SLC 5/04 processor, channel 0port 1yesexternal
PC COM portport 1yesexternal
PanelView 550 through NULL modem adapter port 1yesexternal
DTAM Plus / DTAM Micro™port 1yesexternal
Port 1 on another AIC+port 1yesexternal
(1) External power supply required unless the AIC+ is powered by the device connected to port 2, then the selection switch should be set to
user supplied cable
CableLengthConnections fromto
AIC+
straight
—modem or other communication deviceport 1yesexternal
External Power
Supply Required
(1)
9-25 pin
(1) External power supply required unless the AIC+ is powered by the device connected to port 2, then the selection switch should be set to
9-Pin D-Shell8-Pin Mini Din
9RI24V1
8CTSGND2
7RTSRTS3
6DSRRXD4
5GNDDCD5
4DTRCTS6
Controller
7
8
6
3
4
5
12
Publication 1764-UM001B-EN-P - April 2002
3TXDTXD7
2RXDGND8
1DCD
Page 87
Communication Connections 4-19
Recommended User-Supplied Components
The components in Table 4.8 can be purchased from your local
electronics supplier.
Table 4.8 User Supplied Components
ComponentRecommended Model
external power supply and chassis
power supply rated for 20.4-28.8V dc
ground
NULL modem adapterstandard AT
straight 9-25 pin RS-232 cablesee table below for port information if making own
cables
Port 1Port 2Port 3
6
7
8
9
DB-9 RS-232
1
2
3
4
5
(2) The 8-pin mini-DIN connector is not commercially available.
8-pin mini-DIN
3
4
(2)
876
5
2
1
RS-485 connector
6
5
4
3
2
1
Table 4.9 AIC+ Terminals
PinPort 1: DB-9 RS-232
Port 2
(2)
Port 3: RS-485
Connector
1received line signal
24V dcchassis ground
detector (DCD)
2received data (RxD)ground (GND)cable shield
3transmitted data (TxD)request to send (RTS) signal ground
4
DTE ready (DTR)
(1)
received data (RxD)DH-485 data B
5signal common (GND)received line signal detector (DCD) DH-485 data A
6
DCE ready (DSR)
(2)
clear to send (CTS)termination
7request to send (RTS)transmitted data (TxD)not applicable
8clear to send (CTS)ground (GND)not applicable
9not applicablenot applicablenot applicable
(1) On port 1, pin 4 is electronically jumpered to pin 6. Whenever the AIC+ is powered on, pin 4 will match the state
of pin 6.
(2) An 8-pin mini DIN connector is used for making connections to port 2. This connector is not commercially
available.
Publication 1764-UM001B-EN-P - April 2002
Page 88
4-20 Communication Connections
Safety Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B,
C, D or non-hazardous locations only.
.
WARNING
EXPLOSION HAZARD
This product must be installed in an enclosure. All
cables connected to the product must remain in the
enclosure or be protected by conduit or other means.
!
See Safety Considerations on page 2-3 for additional information.
Installing and Attaching the AIC+
1. Take care when installing the AIC+ in an enclosure so that the
cable connecting the MicroLogix 1500 controller to the AIC+
does not interfere with the enclosure door.
2. Carefully plug the terminal block into the RS-485 port on the
AIC+ you are putting on the network. Allow enough cable slack
to prevent stress on the plug.
3. Provide strain relief for the Belden cable after it is wired to the
terminal block. This guards against breakage of the Belden cable
wires.
Publication 1764-UM001B-EN-P - April 2002
Powering the AIC+
In normal operation with a MicroLogix programmable controller
connected to port 2 of the AIC+, the controller powers the AIC+. Any
AIC+ not connected to a MicroLogix controller requires a 24V dc
power source. The AIC+ requires 120 mA at 24V dc.
If both the controller and external power are connected to the AIC+,
the power selection switch determines what device powers the AIC+.
ATTENTION
If you use an external power supply, it must be 24V
dc. Permanent damage results if higher voltage is
used.
!
Page 89
Communication Connections 4-21
Set the DC Power Source selector switch to EXTERNAL before
connecting the power supply to the AIC+. The following illustration
shows where to connect external power for the AIC+.
24VDC
Bottom View
DC
NEUT
CHS
GND
ATTENTION
Always connect the CHS GND (chassis ground)
terminal to the nearest earth ground. This connection
must be made whether or not an external 24V dc
supply is used.
!
Power Options
Below are two options for powering the AIC+:
• Use the 24V dc user power supply built into the MicroLogix
1500 controller. The AIC+ is powered through a hard-wired
connection using a communication cable (1761-CBL-HM02, or
equivalent) connected to port 2.
• Use an external DC power supply with the following
specifications:
– operating voltage: 24V dc +20% or -15%
– output current: 150 mA minimum
– rated NEC Class 2
Make a hard-wired connection from the external supply to the
screw terminals on the bottom of the AIC+.
ATTENTION
If you use an external power supply, it must be 24V
dc. Permanent damage results if miswired with the
wrong power source.
!
Publication 1764-UM001B-EN-P - April 2002
Page 90
4-22 Communication Connections
Connecting to DeviceNet
You can connect a MicroLogix 1500 using DF1 Full-Duplex protocol to
a DeviceNet network using the DeviceNet Interface (DNI), catalog
number 1761-NET-DNI. For additional information on using the DNI,
refer to the DeviceNet Interface User Manual, publication 1761-6.5.
The following figure shows the external wiring connections of the
DNI.
V–
CAN_L
NET
SHIELD
CAN_H
NODE
DANGER
GND
V+
TX/RX
MOD
RS-232 (Port 2)
DeviceNet Node (Port 1)
(Replacement connector
part no. 1761-RPL-0000)
Use this write-on
area to mark the
DeviceNet node
address.
Cable Selection Guide
1761-CBL-AM00
CableLengthConnections fromto DNI
1761-CBL-AM00
1761-CBL-HM02
1761-CBL-AP00
45 cm (17.7 in)
2m (6.5 ft)
MicroLogix 1000port 2
MicroLogix 1500port 2
CableLengthConnections fromto DNI
1761-CBL-AP00
1761-CBL-PM02
45 cm (17.7 in)
2m (6.5 ft)
SLC 5/03 or SLC 5/04 processors,
channel 0
PC COM portport 2
1764-LRP processor, channel 1port 2
1761-CBL-HM02
1761-CBL-PM02
port 2
Publication 1764-UM001B-EN-P - April 2002
Page 91
Communication Connections 4-23
Connecting to Ethernet
You can connect a MicroLogix 1500 to an Ethernet network using the
Ethernet Interface (ENI), catalog number 1761-NET-ENI. For additional
information on using the ENI, refer to the Ethernet Interface User Manual, publication 1761-UM006. The following figure shows the
external wiring connections of the ENI.
ETHERNET
RS232
FAULT
NET
Ethernet Port (ENI Port 1)
IP
EXTERNAL
CABLE
TX/RX
TX/RX
PWR
RS-232 Mini-DIN (ENI Port 2)
Ethernet Connections
The Ethernet connector, port 1, is an RJ45, 10Base-T connector. The
pin-out for the connector is shown below:
PinPin Name
1Tx+
2Tx3Rx+
4not used by 10Base-T
5not used by 10Base-T
6Rx7not used by 10Base-T
8not used by 10Base-T
When to use straight-through and cross-over cable:
• ENI Ethernet port to 10Base-T Ethernet switch cables utilize a
straight-through pin-out (1-1, 2-2, 3-3, 6-6).
• Direct point-to-point 10Base-T cables connecting the ENI
Ethernet port directly to another ENI Ethernet port (or a
computer 10Base-T port) require a cross-over pin-out (1-3, 2-6,
3-1, 6-2).
Publication 1764-UM001B-EN-P - April 2002
Page 92
4-24 Communication Connections
RS-232 Connections
Port 2 of the ENI is an 8-pin mini-DIN RS-232 port that provides
connection to DF1 compatible RS-232 devices. The connector pin
assignments are shown below.
The table below describes the RS-232 compatible cables.
Publication 1764-UM001B-EN-P - April 2002
ENI Connected to:Catalog NumberUse Cable
MicroLogix (all series)
1761-CBL-AM00
1761-CBL-HM02
SLC 5/03, SLC 5/04, or
SLC 5/05 Channel 01761-CBL-AP00
1761-CBL-PM02
PLC-5
1761-CBL-AP00
1761-CBL-PM02
Mini DIN to Mini DIN
45 cm (17.7 in)
2m (6.5 ft.)
Mini DIN to D-Shell
45 cm (17.7 in)
2m (6.5 ft.)
Mini DIN to D-Shell
45 cm (17.7 in)
2m (6.5 ft.)
Page 93
Chapter
Using Trim Pots and the Data Access Tool
(DAT)
5
Trim Pot Operation
The processor has two trimming potentiometers (trim pots) which
allow modification of data within the controller. Adjustments to the
trim pots change the value in the corresponding Trim Pot Information
(TPI) register. The data value of each trim pot can be used throughout
the control program as timer, counter, or analog presets depending
upon the requirements of the application.
The trim pots are located below the mode switch under the left access
door of the processor.
Trim Pot 0
Trim Pot 1
REM
RUN PROG
Use a small flathead screwdriver to turn the trim pots. Adjusting their
value causes data to change within a range of 0 to 250 (fully
clockwise). The maximum rotation of each trim pot is three-quarters,
as shown below. Trim pot stability over time and temperature is
typically ±2 counts.
Minimum
(fully counterclockwise)
Trim pot data is updated continuously whenever the controller is
powered-up.
1Publication 1764-UM001B-EN-P - April 2002
Maximum
(fully clockwise)
Page 94
5-2 Using Trim Pots and the Data Access Tool (DAT)
Trim Pot Information Function File
The composition of the Trim Pot Information (TPI) Function File is
described in the MicroLogix 1200 and MicroLogix 1500 Instruction Set Reference Manual, publication 1762-RM001.
Error Conditions
If the controller detects a problem/error with either trim pot, the last
values read remain in the data location, and an error code is put in the
error code byte of the TPI file for whichever trim pot had the
problem. Once the problem/error is corrected, the error code is
cleared. The error codes are described in the MicroLogix 1200 and MicroLogix 1500 Instruction Set Reference Manual, publication
1762-RM001.
Data Access Tool (DAT)
The DAT is a convenient and simple tool that provides an interface for
editing and monitoring data. The DAT has five primary features:
• provides direct access to 48 bit elements
• provides direct access to 48 integer elements
• provides two function keys
• displays controller faults
• allows removal/insertion under power
DAT Keypad and Indicator Light Functions
The DAT has a digital display, 6 keys, an up/down key, and 7
indicator lights. Their functions are described in the table on page 5-3.
PROTECTED
Publication 1764-UM001B-EN-P - April 2002
BIT
F1
INT
F2
ESC
ENTER
Page 95
Using Trim Pots and the Data Access Tool (DAT) 5-3
FeatureFunction
Digital DisplayDisplays address elements, data values, faults and errors.
Up/Down KeySelects element numbers and change data values. The up/down key scrolls when held.
F1 Key and Indicator LightControls the F1 status bit. When the F1 key is pressed or latched, the F1 indicator LED is lit.
F2 Key and Indicator LightControls the F2 status bit. When the F2 key is pressed or latched, the F2 indicator LED is lit.
ESC KeyCancels a current operation.
BIT Key and Indicator LightPressing the BIT key puts the DAT in bit mode. The bit indicator light is on when the DAT is in bit
mode.
INT Key and Indicator LightPressing the INT key puts the DAT in integer mode. The integer indicator light is on when the DAT
is in integer mode.
ENTER KeyPress to select the flashing element number or enter data value.
PROTECTED Indicator LightIndicates element data cannot be changed using the DAT (element is read-only).
TIP
The F1, F2, ESC, BIT, INT, and ENTER keys do not
repeat when held. Holding down any one of these
keys results in only one key press. The Up/Down
arrow key is the only key that repeats when held.
Power-Up Operation
The DAT receives power when it is plugged into the controller. Upon
power-up, the DAT performs a self-test.
If the test fails, the DAT displays an error code, all indicator lights are
deactivated, and the DAT does not respond to any key presses. See
DAT Error Codes on page 5-10.
PROTECTED
F1
BIT
INT
F2
ESC
ENTER
After a successful self-test, the DAT reads the DAT function file to
determine its configuration.
Publication 1764-UM001B-EN-P - April 2002
Page 96
5-4 Using Trim Pots and the Data Access Tool (DAT)
DAT Function File
DAT configuration is stored in the processor in a specialized
configuration file called the DAT Function File. The DAT Function
File, which is part of the user’s control program, is described in the
MicroLogix 1200 and MicroLogix 1500 Instruction Set Reference
Manual, publication 1762-RM001.
Following a successful power-up sequence, the DAT enters the bit
monitoring mode.
PROTECTED
-
ff
o
00
0
F1
BIT
INT
F2
ESC
ENTER
Power Save Timeout (PST) Parameter
The power save timeout turns off the DAT display after keypad
activity has stopped for a user-defined period of time. The power-save
(DAT:0.PST) value is set in the DAT Function File. The valid range is 0
to 255 minutes. The power-save feature can be disabled by setting the
PST value to 0, which keeps the display on continuously. The default
value is 0.
In power-save mode, a dash flashes in the left-most segment of the
display. Press any key (except F1 or F2) to return the DAT to its
previous mode. If F1 or F2 is pressed, the DAT will change the value
of the F1 or F2 status bits, but the display remains in power-save
mode.
Publication 1764-UM001B-EN-P - April 2002
Page 97
Using Trim Pots and the Data Access Tool (DAT) 5-5
Understanding the DAT Display
When the DAT enters either the bit or integer mode, the element
number and its data are displayed, as shown below. The element
number is either the integer or bit location.
Bit Mode DisplayInteger Mode Display
PROTECTED
276
3
F2
INT
integer data
• -32,768 to 32,767
• – – – (undefined)
ENTER
8
ESC
00
F1
BIT
bit element
number
• 0 to 47
PROTECTED
ff
o
F2
INT
bit data
• OFF - 0
• ON - 1
• – – – (undefined)
-
0
ESC
ENTER
21
F1
BIT
integer
element
number
• 0 to 47
-
If the displayed element is defined in the controller’s data file, and is
not protected, the element number flashes, indicating that it can be
modified. If the displayed element is protected, the PROTECTED
indicator light illuminates, and the element number does not flash,
indicating that the element cannot be modified.
If the element is undefined, the data field displays three dashes. The
element number does not flash because the element does not exist.
PROTECTED
INT
---
F2
ESC
ENTER
Publication 1764-UM001B-EN-P - April 2002
50
F1
BIT
Page 98
5-6 Using Trim Pots and the Data Access Tool (DAT)
Entering Bit Mode
Bit mode allows you to view and modify up to 48 contiguous bit
locations in the controller. The DAT enters the bit mode automatically
following a successful power-up. The bit mode can also be selected
by pressing the BIT key. If the bit mode was previously active, the
DAT displays the last bit element monitored. If the integer mode was
active, the DAT displays the first bit element in the data file. However,
there may be a brief delay while the DAT requests information from
the controller. During the delay, the working screen will display. See
Working Screen Operation on page 5-7.
Entering Integer Mode
Integer mode allows you to view and modify up to 48 contiguous
16-bit integer data locations in the controller. To initiate integer mode,
press the INT key. If the integer mode was previously active, the DAT
displays the last integer element monitored. If the bit mode was
active, the DAT displays the first integer element in the data file.
However, there may be a brief delay while the DAT requests
information from the controller. If there is a delay, the working screen
is displayed. See Working Screen Operation on page 5-7.
Monitoring and Editing
1. Press the INT or BIT key to enter the desired mode. The element
number flashes (if not protected).
2. Use the up/down key to scroll and select an element (to scroll
rapidly, hold the up/down key).
3. Press ENTER to edit the element. The element number becomes
steady and the data flashes if it is not protected.
4. Use the up/down key to change the data. Bit values toggle
between “ON” and “OFF”. Integer values increment or
decrement. Holding down the up/down key causes the integer
value to increment or decrement quickly.
TIP
If the data is protected or undefined, pressing
the up/down key scrolls to the next element in
the list.
Publication 1764-UM001B-EN-P - April 2002
Page 99
Using Trim Pots and the Data Access Tool (DAT) 5-7
5. Press ENTER to load the new data. Press ESC or INT/BIT to
discard the new data.
F1 and F2 Functions
The function keys, F1 and F2, correspond to bits and can be used
throughout the control program as desired. They have no effect on bit
or integer monitoring.
Each key has two corresponding bits in the DAT function file. The bits
within the DAT function file are shown in the table below.
KeyBitsAddressData FormatTypeUser Program
Access
F1 KeyPressedDAT:0/F1PBinaryStatusRead/Write
LatchedDAT:0/F1LBinaryStatusRead/Write
F2 KeyPressedDAT:0/F2PBinaryStatusRead/Write
LatchedDAT:0/F2LBinaryStatusRead/Write
F1 or F2 Key Pressed
The pressed bits (DAT:0/F1P and DAT:0/F2P) function as
push-buttons and provide the current state of either the F1 or F2 key
on the keypad. When the F1 or F2 key is pressed, the DAT sets (1) the
corresponding pressed key bit. When the F1 or F2 key is not pressed,
the DAT clears (0) the corresponding pressed key bit.
F1 or F2 Key Latched
The latched bits (DAT:0/F1L and DAT:0/F2L) function as latched
push-buttons and provide latched/toggle key functionality. When the
F1 or F2 key is pressed, the DAT sets (1) the corresponding latched
key bit within the DAT Function File. When the F1 or F2 key is
pressed a second time, the DAT clears (0) the corresponding latched
key bit.
Working Screen Operation
Because the DAT is a communications device, its performance is
affected by the scan time of the controller. Depending on the user
program, if a long scan time is encountered and the DAT waits for
information from the controller, a working screen is displayed. The
Publication 1764-UM001B-EN-P - April 2002
Page 100
5-8 Using Trim Pots and the Data Access Tool (DAT)
working screen consists of three dashes that move across the display
from left to right. While the working screen is displayed, key presses
are not recognized. Once the DAT receives data from the controller, it
returns to its normal mode of operation.
If you encounter excessive working screen conditions, you can
minimize the effect by adding an SVC instruction to the control
program. Refer to the MicroLogix 1200 and MicroLogix 1500 Programmable Controllers Instruction Set Reference Manual,
publication 1762-RM001, for information on the SVC instruction.
Non-Existent Elements
When the DAT determines that an element number does not exist in
the controller, the element value displays as three dashes.
If the protection bit for an element is undefined, the DAT will assume
that the element is unprotected.
Controller Faults
The DAT checks for controller faults every 10 seconds. When the DAT
detects a controller fault, the display shows “FL” in the element
number field and the value of the controller’s major fault word (S2:6)
is displayed in the value field, as shown below.
PROTECTED
TIP
lf
F1
BIT
If an element value is being modified when the
fault is detected, the fault is stored until the
modification is accepted or discarded. Then, the
fault will be displayed.
0002H
F2
INT
ESC
ENTER
Publication 1764-UM001B-EN-P - April 2002
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.