POINT I/O and ArmorPOINT I/O 2 Port EtherNet/IP
Adapters
Catalog Numbers
1734-AENTR, 1738-AENTR, Series A
Important User Information
IMPORTANT
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1
your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from
the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous
environment, which may lead to personal injury or death, property damage, or economic loss.
available from
) describes some
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death,
property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the
consequence
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
surfaces may reach dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Rockwell Automation, POINT I/O, ArmorPOINT I/O, RSLo gix, RSLinx, RSL ogix 5000, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Preface
Read this preface to familiarize yourself with the rest of the manual. It provides
information concerning:
• who should use this manual
• the purpose of this manual
• related documentation
• conventions used in this manual
Who Should Use this
Manual
Purpose of this Manual
Use this manual if you are responsible for designing, installing, programming, or
™
troubleshooting control systems that use Series A 1734 POINT I/O
™
1738 ArmorPOINT I/O
2 Port EtherNet/IP Adapter Modules.
or
This manual is a reference guide for the 1734-AENTR, 1738-AENTR Series A
POINT I/O™ 2 Port EtherNet/IP and ArmorPOINT I/O 2 Port EtherNet/IP
Adapters, communications adapters for POINT I/O modules. It describes the
procedures you use to install, wire, configure, troubleshoot, and use these
modules.
ATTENTION: You must use series C POINT I/O modules with the
adapter. Series A or B POINT I/O modules do not work with the adapter.
Related Documentation
The following documents contain additional information concerning Rockwell
Automation products. To obtain a copy, contact your local Rockwell Automation
office or distributor
For Information AboutSee This PublicationPublication Number
1734-series I/O modules and compatible control platforms.POINT I/O™ Selection Guide1734-SG001
Using EtherNet/IP for industrial controlEtherNet/IP Design Considerations Reference ManualENET-RM002
ControlLogix Ethernet communication interface modulesControlLogix EtherNet/IP Bridge Module Installation Instructions1756-IN019
EtherNet/IP Modules in Logix5000 Control Systems User ManualENET-UM001
ControlLogix chassis and power supplies installationControlLogix Chassis and Power Supplies Installation Instructions1756-IN005
ControlLogix systemsControlLogix System User Manual1756-UM001
RSLinxRSLinx Classic Getting Results GuideLINX-GR001
1734-AENTR adapter installationPOINT I/O 2 Port EtherNet/IP Adapter Installation Instructions1734-IN040
1738-AENTR adapter installationArmorPoint I/O 2-Port EtherNet/IP Adapter Installation Instructions 1738-IN028
Installing an EtherNet/IP networkEtherNet/IP Media Planning and Installation ManualODVA
Rockwell Automation Publication 1734-UM014B-EN-P - May 2013i
Common Techniques Used
in this Manual
The following conventions are used throughout this manual:
• Bulleted lists such as this one provide information, not procedural steps.
• Numbered lists provide sequential steps or hierarchical information.
• Italic type is used for emphasis.
Rockwell Software products contain extensive tutorials and help screens. We
recommend that you use these tutorials and help screens to learn about the
products.
For more information about Rockwell Software products, visit the Rockwell
Software website at
http://www.rockwellautomation.com/software/.
iiRockwell Automation Publication 1734-UM014B-EN-P - May 2013
About the Adapters
Table of Contents
Preface
Who Should Use this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i
Rockwell Automation Publication 1734-UM014B-EN-P - August 2013v
Table of Contents
viRockwell Automation Publication 1734-UM014B-EN-P - August 2013
About the Adapters
Chapter
1
Overview
This chapter provides an overview of the Series A1734-AENTR POINT I/O
and 1738-AENTR ArmorPOINT I/O EtherNet/IP adapters, their primary
features, and how to use them.
You need to understand the concepts discussed in this chapter to configure your
adapter and use it in an EtherNet/IP control system.
This table lists where to find specific information.
TopicPage
Important Adapter Considerations
About the POINT I/O and ArmorPOINT I/O 2 Port Adapters1
Adapter Replacement2
Empty Slots and RIUP Situations2
Power Up a System for the First Time3
Adapter Features4
Hardware/Software Compatibility5
What the Adapter Does4
Use of the Common Industrial Protocol (CIP)5
Understand the Producer/Consumer Model5
Specify the Requested Packet Interval (RPI)6
Support of Rack-optimized and Direct Connections6
Mixing Rack-optimized and Direct Connections7
1
Important Adapter
Considerations
Rockwell Automation Publication 1734-UM014B-EN-P - June 20131
Before you begin using your adapter, note the following important
considerations.
ATTENTION: You must use series C POINT I/O modules with the
adapter. Series A or B POINT I/O modules do not work with the adapter.
Chapter 1 About the Adapters
About the POINT I/O and
ArmorPOINT I/O
2 Port Adapters
The POINT I/O and ArmorPOINT I/O adapters provide connectivity to
EtherNet/IP networks for POINT I/O and ArmorPOINT I/O modules
respectively.
The POINT I/O adapter is for the I/O backplane that provides connectivity
through two RJ-45 connectors for 2-port pass-through support of daisy chain or
ring, and the existing star and tree network topologies.
Likewise, the ArmorPOINT I/O adapter provides the same connectivity
through two M12 Ethernet-keyed connectors. It ships with a terminating base for
use in the last I/O module on the backplane.
Set the Chassis Size
The I/O adapters for EtherNet/IP require configuration of theirchassis size
before you can make any I/O connections. The factory default setting for the
chassis size is one slot, which represents the adapter by itself.
You must set the chassis size to a number equaling one slot for the adapter plus
one slot for each I/O module present in the backplane of the adapter.
For example, a POINT I/O system consisting of a 1734-AENTR adapter, one
1734-IB8, one 1734-OB8, and one 1734-OB8S POINT Guard I/O module uses
a chassis size of 4. The adapter stores this chassis size setting in non-volatile
memory.
Each time the adapter is powered up, the adapter compares the number of I/O
modules present on its backplane to the chassis size value from non-volatile
memory. The adapter does not allow any I/O connection until the number of I/
O modules present equals the chassis size value minus one for the adapter itself.
Adapter Replacement
Note that during a connection request from the controller, the chassis size setting
is not communicated to the adapter. You must always set this chassis size using a
separate operation. This includes situations when you are replacing an adapter.
The adapter does not allow any I/O connections until it is configured with the
appropriate chassis size and the proper number of POINT I/O or
ArmorPOINT I/O modules are present.
Empty Slots and RIUP Situations
The POINT I/O system cannot detect an empty terminal base. For this reason,
there are numerous situations in which you can potentially configure a system
that is unusable or one that exercises unintended control.
2Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
About the Adapters Chapter 1
In an attempt to address these situations, you must observe the following rules for
I/O system construction and the
removal andreinsertion of modules.
• A correct I/O system does not have any empty terminal bases.
• After you cycle power, the adapter will not allow any I/O connections
until the number of modules comprising the chassis plus one for the
adapter equalsthe stored chassis size.
– It cannot assume any safe operation until there is a match between the
number of modules indicating their presence in the chassis and what the
adapter has saved in non-volatile memory because it cannot detect
empty terminal bases.
– Actual module identification (such as, electronic keying) is done when
connection establishment requests are received from the controller or
controllers.
• A POINT I/O module removed under power does not disrupt operation
of the other I/O modules. On the other hand, ArmorPOINT I/O
modules are not intended to be removed under power.
– When you remove a module, the adapter detects what changed.
– Whenever you remove a module with an active connection from the
POINT I/O system, the adapter indicates this by flashing the
POINTBus Status LED red and reports a minor recoverable fault.
• If more than one contiguous module is removed under power, connections
to all modules in the contiguous missing module set are disallowed until all
modules are replaced. Because the adapter cannot detect an empty base, it
does not know the physical positioning of the modules until all the missing
modules are replaced.
• If a module separating two sets of contiguous missing modules is removed,
the two sets merge into a single set. All the modules must be replaced
before connections are permitted to any module in the set.
• If modules of different types are removed and returned to the wrong
locations, attempts to connect to these modules will fail during verification
of the electronic ID (providing that keying has not been disabled).
• If modules of the same type are removed and returned to the wrong
locations, they accept connections from the controller or controllers and
reconfigure with the correct data once they pass their electronic keying
check.
• These removal and return situations exist whether the system is under
power or not. If the system is under power, the situation arises immediately.
If the system is not under power, the situation arises in the next power
cycle.
Power Up a System for the First Time
When you power the I/O for the first time, the adapter must assign slot addresses
to every module in the backplane. All I/O modules ship configured at the same
address.
Rockwell Automation Publication 1734-UM014B-EN-P - June 20133
Chapter 1 About the Adapters
L
5
5
5
5
EtherNet/IP Network
E
N
B
T
Other
Network
Devices
A
E
N
T
R
POINT
I/O
E
N
B
T
ControlLogix
I/O
When you first apply power, we expect that all but one module on the backplane
exhibits a solid red Module Status LED.
One by one the adapter resets these modules and addresses them appropriately.
The amount of time that this operation takes is proportional to the size of your I/
O system.
Adapter Features
Features of the adapters include:
• Use of EtherNet/IP messages encapsulated within standard TCP/UDP/IP
protocol
• Common application layer with ControlNet and DeviceNet networks
• Interfacing via Category 5 rated twisted pair cable
• Half/full duplex 10 Mbit or 100 Mbit operation
• DIN rail mounting for 1734-AENTR adapter/Wall or panel mounting for
1738-AENTR adapter
• Communication to and from other I/O modules on the same DIN rail for
1734-AENTR adapter/Communication to and from other I/O modules
in the chassis for 1738-AENTR adapter
• Communication supported by RSLinx software
• IP address assigned via standard BootP or DHCP tools
• I/O configuration via RSLogix 5000 software
• No network scheduling required
• No routing tables required
• Support of connections from multiple controllers simultaneously
You must use RSLogix 5000 to configure these features. For more details on
configuration, see Configuration Requirements
on in chapter 3.
What the Adapter Does
The I/O adapters perform the following primary tasks:
• Control of real-time I/O data (also known as implicit messaging) - the
adapter serves as a bridge between I/O modules and the network
• Support of messaging data for configuration and programming
information (also known as explicit messaging)
4Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
About the Adapters Chapter 1
Hardware/Software
Compatibility
Use of the Common
Industrial Protocol (CIP)
The I/O adapters and the applications described in this manual are compatible
with the following firmware revisions and
Contact Rockwell Automation if you need software or firmware upgrades to use
this equipment
ProductFirmware Revision/ Software Release
1734-AENTR; 1738-AENTR adapters3.xx or later
1756-ENBT2.3 or later
Logix controller11 or later
RSLogix 5000 software11 or later
RSLinx software2.3.1 or later
The adapter uses the Common Industrial Protocol (CIP). CIP is the application
layer protocol specified for EtherNet/IP, the Ethernet Industrial Protocol, as well
as for ControlNet and DeviceNet networks. It is a message-based protocol that
implements a relative path to send a message from the producing device in a
system to the consuming devices.
The producing device contains the path information that steers the message along
the proper route to reach its consumers. Since the producing device holds this
information, other devices along the path simply pass this information; they do
not store it.
software releases.
Understand the Producer/
Consumer Model
This has the following significant benefits:
• You do not need to configure routing tables in the bridging modules,
which greatly simplifies maintenance and module replacement.
• You maintain full control over the route taken by each message, which
enables you to select alternative paths for the same end device.
The CIP producer and consumer networking model replaces the old source and
destination (master and slave) model. The producer and consumer model reduces
network traffic and increases speed of transmission. In traditional I/O systems,
controllers poll input modules to obtain their input status. In the CIP system,
input modules are not polled by a controller. Instead, they produce (multicast or
unicast) their data either upon a change of state (COS) or periodically.
Multicast is the default mode for version 17 Logix and earlier controllers and
unicast is the default for version 18 with multicast as a selectable option.
The frequency of update depends upon the options chosen during configuration
and where on the network the input module resides. The input module,
therefore, is a producer of input data, and the controller is a consumer of the data.
Rockwell Automation Publication 1734-UM014B-EN-P - June 20135
Chapter 1 About the Adapters
The controller also produces data for other controllers to consume. The
produced and consumed data is accessible by multiple controllers and other
devices over the EtherNet/IP network. This data exchange conforms to the
producer and consumer model.
Specify the Requested
Packet Interval (RPI)
Support of Rack-optimized
and Direct Connections
The Requested Packet Interval or RPI is the update rate specified for a particular
piece of data on the network. The RPI can be specified for the adapter and
include all of the I/O modules in the I/O system (using a rack-optimized
connection) or specified for a particular module (using direct connection).
When you add a module or an adapter to the I/O configuration of a controller,
you must enter the RPI as a parameter. This value specifies how often to produce
the data for that device. For example, if you specify an RPI of 50 ms, it means that
every 50 ms the device should send its data to the controller and the controller
should send the consumed (output) data to the device.
Use RPIs only for devices that exchange data. For example, a ControlLogix
EtherNet/IP bridge module in the same chassis as the controller does not require
an RPI, because it is not a data-producing member of the system. Its use is only as
a bridge to remote racks.
The I/O adapters supports both direct andrack-optimized connections. A direct
connection is a real-time data transfer link between the controller and the module
occupying the slot that the configuration data references.
Direct I/O connections occur at a cyclic rate specified by the RPI during
configuration. A rack-optimized connection is a grouping of data from one or
more digital I/O modules into a single block of data sent over a single connection
at the same data rate.
Analog, safety, and speciality modules cannot participate in the rack-optimized
connection; these modules require a direct I/O connection.
Rack-optimized connections reduce the total number of connections needed to
transfer data when using many digital I/O modules in a system. The following
example illustrates the benefit of rack-optimized connections.
Assume you set up a system that contains eight digital I/O modules interfaced to
an adapter. If you use direct connections to transfer data to each of the these I/O
modules, you need eight connections to transfer all of the data, one to each of the
6Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
About the Adapters Chapter 1
IMPORTANT
eight I/O modules. If you use a rack-optimized connection to transfer the data,
you only need a single connection – the connection to the I/O adapter.
Although rack-optimized connections offer an efficient way to use
resources, there are a few limitations on their use:
• You can use only rack-optimized connections to send data to and
from digital I/O modules. Analog or speciality I/O requires direct
connections.
• All data is sent at the same time as the RPI rate of the I/O adapters.
If the update rate required for a digital module is different from the
RPI of the rack-optimized connection, a direct connection to that
digital I/O module is required.
See the EtherNet/IP Design Considerations Reference Manual,
publicationENET-RM002
for more information on connections.
Mixing Rack-optimized and Direct Connections
Chapter Summary
You can mix communication formats for different I/O modules communicating
through the same adapter. I/O modules set up to use rack optimization
communicate at the rate of the RPI configured for the adapter. I/O modules
configured for direct communication communicate at their own individual RPIs
and ignore the rack-optimized RPI.
In this chapter, you were introduced to the features of the POINT I/O and
ArmorPOINT I/O Adapters, and considerations for installation and usage.
Rockwell Automation Publication 1734-UM014B-EN-P - June 20137
Chapter 1 About the Adapters
Notes:
8Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Install Your Adapter
Chapter
2
Overview
This chapter describes how to physically install the Series A POINT I/O and
ArmorPOINT I/O 2 Port EtherNet/IP adapters; and how to connect the
adapter to the EtherNet/IP network. The only tools you require are a flat or
Phillips head screwdriver and a drill.
This table lists where to find specific information.
TopicPage
Identify Adapter Components10
Mount the I/O Adapter11
Mount the POINT I/O Adapter on a DIN Rail11
Mount the ArmorPOINT I/O Adapter and Base on a Wall or Panel12
Install the POINT I/O Adapter Module13
Install the ArmorPOINT I/O Adapter Module13
Wire the POINT I/O Adapter14
Wire the ArmorPOINT I/O Adapter15
ATTENTION: You must use series C POINT I/O modules with the
adapter. Series A or B POINT I/O modules do not work with the adapter.
Rockwell Automation Publication 1734-UM014B-EN-P - June 20139
Chapter 2 Install Your Adapter
1734-AENTR
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Power
POINT I O
02
0
2
Link 2
Activity/
Status
3
4
5
6
7
Link 1
Activity/
Status
44849
Status indicators
RTB removal handle
Removable Terminal
Block (RTB)
DIN rail locking screw
(orange)
Ethernet network
RJ-45 connectors
Network
address
thumbwheel
1738-AENTR
EtherNet I/P
Adapter
Status
Network
Activity
Network
Status
PointBus
Status
System
Power
Adapter
Power
conformance tested
™
PWR
IP ADDRESS
Link 2
Activity/
Status
Link 1
Activity/
Status
44830
M12 connectors
Mini Style 4-Pin
in Male
Connector
Network address
switches
Status indicators
Identify Adapter
Components
Use the figures to identify the external features of your I/O adapters.
Physical Features of the 1734-AENTR Adapters
Physical Features of the 1738-AENTR Adapters
10Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Install Your Adapter Chapter 2
1734-AENTR
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Powe
r
Field
Powe
r
POINT I O
75.30
(2.96)
74.00
(2.91)
132.72
(5.23)
52.23
(2.06)
35.55
(1.40)
A
B
45174
A = DIN rail
B = Secure DIN rail approximately every 200 mm (7.8 in.)
Mount the I/O Adapter
Use the following procedures to mount the I/O adapters on a new system before
you install any I/O modules.
Mount a 1734-FPD module in the slot next to the I/O adapter when applying
field power. You can also use the 24V DC to power the adapter to supply field
power, where no FPD is necessary. Refer to Point I/O Field Potential
Distribution Module Installation Instructions, publication 1734-IN059
for more
information.
Mount the POINT I/O Adapter on a DIN Rail
Position the I/O adapters vertically above the DIN rail.
1. Make sure the DIN rail locking screw (orange) is in horizontal position.
2. Position the adapter vertically above an IEC standard (35 x 7.5 x 1 mm)
top-hat DIN rail at a slight angle (DIN rail: Allen-Bradley part number
199-DR1; 46277-3).
3. Press down firmly to install the adapter on the DIN rail, noting that the
locking mechanism locks the adapter to the DIN rail.
4. Set the network address thumbwheel switches to the desired value.Set the
network address thumbwheel switches to the desired value. See Set the
Network Address in chapter 3 for more details on setting the IP address.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201311
Chapter 2 Install Your Adapter
IMPORTANT
45175
5. Slide the safety end cap up to remove it, exposing the backplane and power
interconnections.
WARNING: If you connect or disconnect the Ethernet cable with power
applied to this module or any device on the network, an electrical arc
can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous
before proceeding.
Mount the ArmorPOINT I/O Adapter and Base on a Wall or Panel
To mount the ArmorPOINT I/O adapter on a wall or panel, use the screw holes
provided in the adapter module
The ArmorPOINT I/O adapter must be mounted on a grounded
metal mounting plate or other conductive surface.
.
Refer to the drilling dimensions illustration for the ArmorPOINT I/O adapter
with I/O bases to guide you in mounting the adapter and I/O bases.
Drilling Dimensions
46.25mm
(1.82in)
56.00mm
(2.20in)
102.0mm
(4.01in)
51.90mm
(2.04in)
20.10mm
(0.79in)
51.90mm
(2.04in)
20.10mm
(0.79in)
51.90mm
(2.04in)
Install the mounting base as follows:
1. Lay out the required points as shown in the drilling dimension drawing.
2. Drill the necessary holes for #8 (M4) machine or self-tapping screws.
3. Mount the adapter using #8 (M4) screws.
4. Ground the system using the ground lug connection in the I/O base. The
ground lug connection is also a mounting hole.
5. Mount the terminating base that was shipped with the adapter as the last
base in the backplane instead of the base that was shipped with the
I/O module.
6. Set the network address thumbwheel switches to the desired value. See Set
the Network Address in chapter 3 for more information on setting the IP
address.
12Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Terminating Base
43787
Mounting hole
Latching mechanism release
Ground connection
Keyswitch
Latching
mechanism hole
Install Your Adapter Chapter 2
Install the POINT I/O
Adapter Module
To install the adapter on the DIN rail prior to installing other base units:
ATTENTION: Allow 25.4 mm (1.0 in.) of space between adjacent
equipment for adequate ventilation.
1. Position the adapter vertically above the DIN rail.
2. Press down firmly to install the adapter on the DIN rail, noting that a
locking mechanism locks the adapter to the DIN rail.
3. Set the network address on the network address thumbwheel.
4. Slide the safety end cap up to remove it, exposing the backplane and power
interconnections
ATTENTION: Do not discard the end cap. Use this end cap to cover the
exposed interconnections on the last mounting base on the DIN rail.
Failure to do so could result in equipment damage or injury from electric
shock.
.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201313
Chapter 2 Install Your Adapter
NC
C
V
NC
Chas
Gnd
C
V
NC = No Connection
Chas Gnd = Chassis Ground
C = Common
V = Supply
0
4
2
6
Chas
Gnd
12/24V DC
This DC supply connects
to the internal power bus.
1
5
3
7
V DC
Install the ArmorPOINT I/O
Adapter Module
To install the ArmorPOINT I/O adapter module:
1. Using a bladed screwdriver, rotate the keyswitch on the mounting base
clockwise until the appropriate number for the I/O module you are
installing aligns with the notch in the base.
Refer to the installation instructions for each module to determine what
this number must be. See Related Documentation
on page i for a list of
these installation instructions.
2. Position the module vertically above the mounting base.
The module bridges two bases.
3. Push the module down until it engages the latching mechanism.
You hear a clicking sound when the module is properly engaged. The
locking mechanism locks the module to the base.
Wire the POINT I/O Adapter
Refer to the following illustration to wire the adapter.
14Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
ATT ENTI ON: Do not connect 120/240V AC power to the V DC supply.
ATT ENTI ON: Do not wire more than two conductors on any single
terminal.
ATTENTION: Make sure all connectors and caps are securely tightened
to properly seal the connections against leaks and maintain IP67
requirements.
(view into connector)
Pin 1 - User Power +
Pin 2 - Adapter Power +
Pin 3 - Adapter Power Pin 4 - User Power -
Wire the ArmorPOINT I/O Adapter
Wire the EtherNet/IP and auxiliary power connectors on the adapter as shown.
EtherNet/IP Connectors
Chapter Summary
Auxiliary Power Connector
(1)
Analog modules have earth grounded metal rings. This should be
considered when choosing shielded cables and grounding techniques.
In this chapter, you learned how to install and wire your POINT I/O or
ArmorPOINT adapter module. The following chapter describes how to
configure your POINT I/O or ArmorPOINT I/O adapter module to
communicate on the EtherNet/IP network by providing an IP address, gateway
address, and Subnet mask.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201315
(1) Auxiliary power cable: standard cordset (single-ended), for example Allen-Bradley part number 889N-F4AFC-6F or 889N-R4AFC6F; or standard patchcord (double-ended), for example, Allen-Bradley part number 889N-F4AFNU-6F or 889N-F4AFNV-6F. Refer to
publication M117-CA001A-EN-P
for more information.
Chapter 2 Install Your Adapter
Notes:
16Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Chapter
Configure the Adapter for Your EtherNet/
IP Network
3
Overview
Before using your adapter in an EtherNet/IP network, you need to configure it
with an IP address, subnet mask, and optional Gateway address. This chapter
describes these configuration requirements and the procedures for providing
them. Here are ways you can do this:
• Use the Rockwell BootP/DHCP utility, version 2.3 or later, that ships
with RSLogix 5000 or RSLinx software.
– You can also use this utility to reconfigure a device with an IP address
you must change.
• Use a
• Use the Network Address thumbwheel switches.
• Have your network administrator configure the adapter via the network
See the table for a list of where to find information in this chapter.
TopicPage
Configuration Requirements18
IP Address18
Gateway Address19
Subnet Mask20
Set the Network Address21
Set the Network Address for POINT I/O Adapter21
Set the Network Address for ArmorPOINT I/O Adapter22
Use the Rockwell BootP/DHCP Utility22
Save the Relation List25
Use DHCP Software to Configure Your Adapter26
third party DHCP server.
DHCP server.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201317
Chapter 3 Configure the Adapter for Your EtherNet/IP Network
Class A
Class B
Class C
Network ID
Host ID
Host ID
Host ID
0
0
0
10
0
110
78
15 16
31
31
3123 24
Network ID
Network ID
EXAMPLE
Configuration
Requirements
Before you can use your adapter, you must configure its IP address, its subnet
mask, and, optionally, a gateway address. You can use the Rockwell BootP utility,
version 2.3 or later, to perform the
configuration. You can also use a DHCP
server or the network address switches to configure these parameters.
ATTENTION: You must use series C POINT I/O modules with the
adapter. Series A or B POINT I/O modules do not work with the adapter.
If you need to reset the adapter to factory defaults, see Work with the
Configuration Pages in Appendix B.
IP Address
The IP address identifies each node on the IP network (or system of connected
networks). Each TCP/IP node on a network (including the adapter) must have a
unique IP address.
The IP address is 32 bits long and has a Network ID part and Host ID part.
Networks are classified A, B, C, (or other). The class of the network determines
how an IP address is formatted
.
You can distinguish the class of the IP address from the first integer in its dotteddecimal IP address as follows:
Range of first integerClassRange of first integerClass
0 1…127A192…223C
128…191B224… 255other
Each node on the same physical network must have an IP address of the same
class and must have the same network ID. Each node on the same network must
have a different Host ID thus giving it a unique IP address.
IP addresses are written as four decimal integers (0…255) separated by periods
where each integer gives the value of one byte of the IP address
.
For example, the 32-bit IP address:
10000000 00000001 00000000 00000001 is written as
128.1.0.1
18Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Configure the Adapter for Your EtherNet/IP Network Chapter 3
Network 1
Network 2
128.1.0.1
128.2.0.1128.2.0.2128.2.0.3
128.1.0.2
A
B
G
C
Gateway Address
This section applies to multi-network systems. If you have a single network
system, refer to the next section.
The Gateway Address is the default address of a network. It provides a single
domain name and point of entry to the site. Gateways connect individual physical
networks into a system of networks.
When a node needs to communicate with a node on another network, a gateway
transfers the data between the two networks. The figure shows gateway G
connecting Network 1 with Network 2.
When host B with IP address 128.2.0.1 communicates with host C, it knows
from C’s IP address that C is on the same network. in an Ethernet environment, B
can then resolve C’s IP address into a hardware address (MAC address) and
communicate with C directly.
When host B communicates with host A, it knows from A’s IP address that A is
on another network (the network IDs are different). In order to send data to A, B
must use the IP address of the gateway connecting the two networks. In this
example, the gateway’s IP address on Network 2 is 128.2.0.3.
The gateway has two IP addresses (128.1.0.2 and 128.2.0.3). The first must be
used by hosts on Network 1 and the second must be used by hosts on Network 2.
To be usable, a gateway of a host must be addressed using a network ID matching
its own.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201319
Chapter 3 Configure the Adapter for Your EtherNet/IP Network
EXAMPLE
These two bits of the Host ID are used to
extend the netdwork ID.
Network 1
Network 2.1
Network 2.2
A
BC
DE
128.1.0.2
128.1.0.1
128.2.64.3
128.2.128.2
128.2.64.1128.2.64.2
128.2.128.3
128.2.128.1
G2
G
Subnet Mask
The subnet mask is used for splitting IP networks into a series of subgroups, or
subnets. The mask is a binary pattern that is matched up with the IP address to
turn part of the Host ID address field into a field for subnets
Two bits of the Class B host ID are used to extend the network ID. Each unique
combination of bits in the part of the Host ID where subnet mask bits are 1
specifies a different physical network.
.
Take Network 2 (a Class B network) in the previous
example and add another physical network. Selecting the
following subnet mask would add two additional
network ID bits, allowing for four physical networks:
11111111 11111111 11
000000 00000000 = 255.255.192.0
The new configuration is:
A second network with Hosts D and E was added. Gateway G2 connects
Network 2.1 with Network 2.2.
Hosts D and E will use Gateway G2 to communicate with hosts not on
Network 2.2.
Hosts B and C will use Gateway G to communicate with hosts not on
Network 2.1.
20Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
When B is communicating with D, G (the configured Gateway for B) will route
the data from B to D through G2.
Configure the Adapter for Your EtherNet/IP Network Chapter 3
44848
Network address thumbwheel
Press either the + or - buttons
to change the number and
assign the IP address.
02
0
1734-AENTR
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Power
POINT I O
Link 1
Activity/
Status
Link 2
Activity/
Status
IP ADDRESS
Set the Network Address
The adapters ship DHCP-enabled and with the switches set to 999. To change
the network address, do the following.
Set the Network Address for POINT I/O Adapter
• Use the thumbwheel switches located on the adapter. Press either the + or -
buttons to change the number.
• Use a Dynamic Host Configuration Protocol (DHCP) server, such as
Rockwell Automation BootP/DHCP.
• Retrieve the IP address from non-volatile memory.
The adapter reads the thumbwheel switches first to determine if the switches are
set to a valid number. You set the node address by using the 3-position
thumbwheel switch. Press the + or - buttons to change the number. Valid settings
range from 001…254.
When you use the thumbwheel to assign an address and set it to 001, the adapter
gateway address is set to 0.0.0.0. and the subnet mask is 255.255.255.0 . When
you use the thumbwheel to assign an address and set it between 002...254, the
adapter gateway address is set to 192.168.1.1.
The adapter does not have a host name assigned, or use any Domain Name
System when using the thumbwheel settings.
If DHCP is not enabled, the adapter uses the IP address, along with other TCP
configurable parameters, stored in non-volatile memory.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201321
Chapter 3 Configure the Adapter for Your EtherNet/IP Network
44831
This example shows the network address
set at 163.
Set the Network Address for ArmorPOINT I/O Adapter
• Adjust the switches in front of the module
• Use a Dynamic Host Configuration Protocol (DHCP) server such as
Rockwell Automation BootP/DHCP
• Retrieve the IP address from non-volatile memory
The adapter reads the switches first to determine if the switches are set to a valid
number. Set the network address by adjusting the three switches on the front of
the adapter.
Network Address Example
Use a small blade screwdriver to rotate the switches. Line up the small notch on
the switch with the number setting you wish to use. Valid settings range from
001…254.
Use the Rockwell BootP/
DHCP Utility
When you use the switches to assign an address and set it to 001, the adapter
gateway address is set to 0.0.0.0. and the subnet mask is 255.255.255.0 . When
you use the switches to assign an address and set it to a valid number between
002...254, the adapter gateway address is set to 192.168.1.1.
If the switches are set to an invalid number (for example, 000 or a value greater
than 254 excluding 888), the adapter checks to see if DHCP is enabled. If DHCP
is enabled, the adapter requests an address from a DHCP server. The DHCP
server also assigns other Transport Control Protocol (TCP) parameters.
If DHCP is not enabled, the adapter uses the IP address, along with other TCP
configurable parameters, stored in non-volatile memory.
The Rockwell BootP/DHCP utility is a standalone program that incorporates
the functionality of standard BootP software with a user friendly graphical
interface. It is located in the Utils directory on the RSLogix5000 software
installation CD. The adapter must have DHCP enabled (factory default and the
network address switches set to an invalid value) to use the utility.
22Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Configure the Adapter for Your EtherNet/IP Network Chapter 3
To configure your adapter using the BootP utility, perform the following steps:
1. Run the BootP software.
In the BOOTP Request History panel you see the hardware addresses of
devices issuing BootP requests.
2. Double-click the hardware address of the device you want to configure.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201323
Chapter 3 Configure the Adapter for Your EtherNet/IP Network
The New Entry dialog appears with the device’s Ethernet Address (MAC).
3. Enter the IP Address you want to assign to the device and click OK. The
device is added to the Relation List, displaying the Ethernet Address
(MAC) and corresponding IP Address, Hostname, and Description (if
applicable).
When the address displays in the IP Address column in the Request History
section, the IP address assignment has been made.
4. To make this configuration static in the device, highlight the device in the
Relation List panel, and click the Disable BOOTP/DHCP button.
When power is cycled to the device, it uses the configuration saved in nonvolatile memory and will not issue a DHCP request.
5. To enable DHCP for a device with DHCP disabled, highlight the device
in the Relation List, and click the Enable DHCP button.
You must have an entry for the device in the Relation List panel to reenable DHCP.
24Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Configure the Adapter for Your EtherNet/IP Network Chapter 3
Save the Relation List
You can save the Relation List for later use. To save the Relation List, perform the
following steps:
1. Select Save As... from the File menu.
The Save As dialog appears.
2. Select the folder where you want to save the Relation List.
3. Enter a File name for the Relation List, for example, control system
configuration, and click Save.
You can leave the Save as type at the default setting: Bootp Config Files
(*.bpc).
You now have the option to open the file containing the Relation List at a
later session.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201325
Chapter 3 Configure the Adapter for Your EtherNet/IP Network
Use DHCP Software to
Configure Your Adapter
DHCP (Dynamic Host Configuration Protocol) software automatically assigns
IP addresses to client stations logging onto a TCP/IP network.
DHCP is based on BootP and maintains some backward compatibility. The main
difference is that BootP was designed for manual configuration, while DHCP
allows for dynamic allocation of network addresses and configurations to newly
attached devices.
Be cautious about using DHCP software to configure your adapter. A DHCP
server typically assigns a finite lease time to the offered IP address.
When 50% of the leased time has expired, the adapter attempts to renew its IP
address with the DHCP server.
The possibility exists that the adapter will be assigned a different IP address,
which would cause the adapter to cease communicating with the ControlLogix
controller. See Configure the Adapter with Fixed IP Address
more details on how to configure an adapter with a fixed IP address.
ATT ENTI ON: To avoid unintended control or loss of control, the
I/O adapter must be assigned a fixed IP address. A dynamically
provided IP address should be used only at initial configuration. If a
DHCP server is used, it must be configured to assign the same IP
address to your adapter.
Failure to observe this precaution may result in unintended machine
motion or loss of process control.
in Chapter 4 for
Chapter Summary
This chapter provided instructions on how to configure POINT and
ArmorPOINT Adapter modules through the RSLogix 5000 software and
included information on configuration requirements and setting the network
address.
26Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Chapter
4
Configure the Adapter for Direct Connection
in RSLogix 5000 Software
Overview
In this example, a ControlLogix controller communicates with I/O modules via
the adapter using a direct connection.
The adapter makes a direct connection to each of the modules referenced by the
data. The modules presented in this chapter use RSLogix 5000 software, revision
11 and above.
ATTENTION: You must use series C POINT I/O modules with the adapter.
Series A or B POINT I/O modules do not work with the adapter.
TopicPage
Set Up the Hardware 27
Create the Example Application 29
Configure the I/O 30
Add the Local EtherNet/IP Bridge to the I/O Configuration 30
Add the POINT I/O Adapter to the I/O Configuration 33
Add the POINT I/O Modules to the I/O Configuration 35
Edit the Controller Tags 40
Create the Ladder Program 41
Download the Program to the Controller 41
Verify the Module Chassis Size 42
Configure the Adapter with Fixed IP Address 45
Recover From an Overloaded Adapter 46
Set Up the Hardware
Rockwell Automation Publication 1734-UM014B-EN-P - June 201327
In this example, a ControlLogix chassis contains the L63 controller in slot 1 and a
1756-ENBT bridge module in slot 3. The 1734-AENTR adapter is mounted on
a DIN rail in slot 0, with a 1734-OW2/C relay output module in slot 1, a 1734OV4E/C sink output module in slot 2, and a power supply (not shown).
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software
45176
To work along with this example, set up your system as shown in the figure.
Slot 0 1 2 3
1734-AENTR
10.88.70.2
Link 1
Activity/
Status
POINT I/O
Local
chassis
L63
controller (slot 1)
Data
1756-ENBT
10.88.70.4 (slot 3)
Link 2
Activity/
Status
Slot 0 1 2 3 4
Switch
10.88.70.26
Programming
terminal
• In the example application, we assume that the L63 controller and 1756-
ENBT module (firmware revision 2.3, or later) are in the slots shown in
the figure.
• Verify the IP addresses for your programming terminal, 1756-ENBT
module, and adapter.
• Verify the position (slot) of the I/O modules on the DIN rail.
• Verify that you connected all wiring and cabling properly.
• Be sure you configured your communication driver (for example,
AB_ETH-1 or AB-ETHIP-1) in RSLinx software, as described in
Appendix of this manual.
28Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Configure the Adapter for Direct Connection in RSLogix 5000 Software Chapter 4
Create the Example
Application
Perform the following steps to create the example application:
1. Start RSLogix 5000 Enterprise Series software to open the RSLogix 5000
main dialog.
2. From the File menu, select New.
3. The New Controller dialog opens.
4. Enter an appropriate Name for the Controller, for example,
POINT_IO_Controller.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201329
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software
IMPORTANT
5. Select the correct Version, Chassis Type, and Slot number of the L63
controller, and the folder where you want to save the RSLogix 5000 file
(Create In). The Description is optional.
RSLogix 5000 software version 18 lets you enable redundancy. To use
redundancy in your system, check the Redundancy Enabled checkbox
when using the said version or later.
6. Click OK.
Configure the I/O
You now add the POINT I/O modules to the controller’s I/O configuration
performing these procedures:
• Add the local 1756-ENBT module to the I/O configuration.
• Add the 1734-AENTR adapter as a child of the 1756-ENBT module on
the Ethernet network.
• Add the POINT I/O modules as children of the AENTR adapter.
Click the Help button on the configuration dialogs shown in this
section if you need assistance in selecting and setting the
parameters.
.
Add the Local EtherNet/IP Bridge to the I/O Configuration
1. Select the I/O Configuration folder in the project dialog, and click the
right mouse button. A menu opens.
2. Choose New Module.
30Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Configure the Adapter for Direct Connection in RSLogix 5000 Software Chapter 4
The Select Module dialog opens.
3. Expand the Communications tree as in the following dialog.
4. Select the 1756-ENBT EtherNet/IP Bridge and click OK.
The Select Major Revision dialog opens.
5. Select the number for Major Revision and click OK.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201331
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software
The New Module dialog opens.
6. Enter values for Name, IP Address, Slot, Electronic Keying, and Revision,
noting that we used the following values:
NameLocal_ENBT
IP Address10.88.70.4
Slot3
Electronic KeyingCompatible Keying
Revision3.1
7. Click OK to accept the configuration.
The Module Properties dialog opens.
32Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Configure the Adapter for Direct Connection in RSLogix 5000 Software Chapter 4
Add the POINT I/O Adapter
to the I/O Configuration
Next, you must add the adapter as a child of the local 1756-ENBT module.
1. In the Project dialog, right-click the local 1756-ENBT module under the
I/O Configuration folder, and select New Module from the dialog.
The Select Module dialog opens.
2. Expand the Communications tree.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201333
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software
IMPORTANT
3. Select your adapter from the list, and click OK, noting that we entered
these values on the General Tab of the New Module dialog.
NamePOINT_IO_Adapter
IP Address10.88.70.2
The Slot field appears grey because the slot is automatically 0 for
the 1734-AENTR adapter.
The New Module dialog opens.
.
4. Click Change...
The Module Definition dialog opens.
5. Choose values for Connection, Chassis Size, Electronic Keying and
Revision, noting that we used the following values:
34Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Configure the Adapter for Direct Connection in RSLogix 5000 Software Chapter 4
IMPORTANT
The chassis size value equals 1 for the adapter plus the number of I/O
modules installed (physically present on the I/O backplane).
Connection choices are the following:
• None – the adapter only makes a direct connection to each of the
modules referenced by the data.
• Rack optimization – digital I/O data is collected into a rack image. This
rack image does not include analog or specialty I/O modules.
• Listen only - rack optimization – read or verify input data only, but does
not control the modules. When you have multiple controllers, one
controller is used to control and the other controllers are used to
monitor. When the owning controller of rack-optimized connection
closes the connection, the Listen-Only data will also stop.
6. Choose None as Connection, because we are only making direct
connections, then click OK. There is no need to have a rack-optimized
connection if all I/O connections to the POINT I/O modules are directly
connected.
A dialog box opens.
The requested packet interval (RPI) is disabled because you have chosen
None as the Connection.
7. Click OK to accept the configuration.
The name of your adapter appears in the Ethernet folder.
Add the POINT I/O Modules to the I/O Configuration
You now add POINT I/O modules to the I/O Configuration List under the
adapter.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201335
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software
TIP
In this example, you add a 1734-OW2 relay output and a 1734-OV4E sink
output modules with standard configurations. Use these steps as a guide when
configuring different I/O modules for your system.
This example application uses I/O module default
configurations. For more information, refer to the
POINT I/O Selection Guide, publication
Add the Relay Output Module
1. Right-click the name of the remote adapter under the I/O Configuration
folder and select New Module.
The Select Module dialog opens.
1734-SG001.
2. Expand the Digital tree.
3. Select the 1734-OW2 relay output module from the list and click OK.
36Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Configure the Adapter for Direct Connection in RSLogix 5000 Software Chapter 4
IMPORTANT
The New Module dialog opens.
4. Enter values for Name and Slot, noting that we used the following values.
NamePOINT_Relay_Output
Slot1
5. Choose Connection.
The RPI is selectable since it is a direct connection.
6. Enter 50 for requested packet interval (RPI) to set how often you exchange
data with the I/O adapters.
To avoid overloading the I/O adapters, we recommend that RPI be no
less than 10 ms for rack connections and 50 ms for direct
connections.
7. Click OK to save the configuration.
The relay output module appears under Ethernet.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201337
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software
Add the Digital Output Module
1. Right-click the name of the I/O adapter and select New Module.
The Select Module dialog opens.
Expand the Digital tree
.
2. Select the 1734-OV4E digital output module from the list.
38Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Configure the Adapter for Direct Connection in RSLogix 5000 Software Chapter 4
3. Click OK.
The New Module dialog opens.
Enter values for Name and Slot, noting we used the following.
NamePOINT_Digital_Output
Slot2
4. On the Connection tab, enter 10 ms as the RPI for the 1734-OV4E
module.
5. Click OK.
The I/O Configuration in the Project dialog should look similar to the
following
Rockwell Automation Publication 1734-UM014B-EN-P - June 201339
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software
Tags created by the system
Enter the new tag here
Edit the Controller Tags
When you add modules to the I/O configuration the system creates tags for those
modules to use in the application program.
For the example application you need to add one more controller tag.
1. Double-click the Controller Tags folder in the project dialog.
The Controller Tags dialog opens. You see the tags created for the 1734AENTR adapter and its digital I/O modules.
40Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
2. Click the Edit Tags tab at the bottom of the Controller Tags dialog.
3. Create the following tag:
TagTyp e
Parts_CountCounter
4. Close the Controller Tags dialog.
Configure the Adapter for Direct Connection in RSLogix 5000 Software Chapter 4
Create the Ladder Program
Create the example ladder program to test the I/O.
1. Under the Main Program folder, double-click Main Routine.
2. Enter the following ladder program using the tags previously created.
Download the Program to
the Controller
3. Save the program.
Follow this procedure to download the program you just saved to the
ControlLogix controller.
1. From the main menu, choose Communications>Who-Active.
The Who Active dialog opens.
2. Navigate to select the slot where the controller is located in the chassis.
3. Choose Set Project Path.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201341
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software
4. Choose Download.
The Download dialog opens with a reminder of the following.
• The controller is in Remote Run mode.
• The mode changes to Remote Program prior to download.
5. From the Download dialog, choose Download
The RSLogix 5000 software dialog opens.
Verify the Module Chassis
Size
6. Notice that the 1756-ENBT Bridge is now online.
If yellow triangles are present, see the following section.
You have now built the I/O tree in the RSLogix 5000 software, and the
RSLogix 5000 software used the chassis size from the 1734-AENTR General tab.
Now you need to download this new chassis size value into the 1734-AENTR
adapter hardware. This procedure synchronizes the chassis size value from the
RSLogix 5000 software into the 1734-AENTR adapter hardware.
1. Verify that the RSLogix 5000 software is online.
2. In the Project dialog, right-click the 1734-AENTR adapter under I/O
Configuration.
42Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Configure the Adapter for Direct Connection in RSLogix 5000 Software Chapter 4
Value from
Module Properties
General Tab
Value currently
stored in 1734AENTR
adapter
3. Select Properties.
4. Click the Connection tab.
The Module Fault error code displays.
5. Click the Chassis Size tab.
6. Click Set Chassis Size in Module.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201343
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software
7. Read and acknowledge the warning dialog.
8. Click OK to continue.
Notice the chassis size stored in the module has been changed to 3.
At this point, your POINTBus status LED should be solid green. All the
yellow triangles in your I/O configuration should be gone.
9. Click OK.
44Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Configure the Adapter for Direct Connection in RSLogix 5000 Software Chapter 4
Configure the Adapter with
Fixed IP Address
To configure the adapter with a fixed IP address to prevent the adapter from
ceasing to communicate with the ControlLogix controller:
1. All controllers with I/O connections to the AENTR and/or the modules
in its backplane need to be in program mode.
2. In the Module Properties dialog, click the Port Configuration tab.
3. Unselect the Enable DHCP box.
4. Click the Set button.
5. Read and acknowledge the warning.
6. Click OK.
7. Click the Refresh button to verify the changes.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201345
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software
Recover From an
Overloaded Adapter
Each I/O connection established with the I/O adapter consumes a portion of
microprocessor bandwidth. The amount of bandwidth used by a connection
depends on several variables, such as the requested packet interval (RPI), number
of I/O modules involved in the connection, and rate of change of the I/O.
The AENTR adapter continuously monitors this bandwidth and rejects requests
for new I/O connections when there is insufficient bandwidth available to
support the new connection.
The condition where the I/O adapters cannot support the connection due to a
limit of the bandwidth of the microprocessor is shown on the Connection tab of
the Module Properties dialog.
If you encounter this condition, the only action you can take is to alter the
existing connections to reduce the amount of microprocessor bandwidth
consumed. The most likely fixes for this condition include the following:
• Increase the RPI.
• Decrease the number of connections.
• Remove modules from the rack-optimized I/O connection.
• Remove the rack-optimized connection if there are no modules
participating in it.
Chapter Summary
46Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
This chapter provided instructions on how to configure the POINT I/O
Adapter for Direct Connection through the the RSLogix 5000 software. It
included information about setting up the hardware and configuring the I/O,
adding the adapter to the configuration, and configuring the adapter with a fixed
IP address.
Chapter
5
Configure the Adapter for Direct Connection
and Rack Optimization in RSLogix 5000
Software
Overview
This chapter guides you through the steps required to configure your AENTR
adapter with both direct and rack-optimized I/O connections using
RSLogix 5000 software.
You can mix I/O connection formats for different I/O modules communicating
through the same adapter. I/O modules set up to use rack optimization
communicate at the rate of the RPI configured for the adapter.
I/O modules controlled by a direct I/O connection communicate at their own set
RPI. The RPI of the rack-optimized I/O connection has no bearing on the direct
I/O connections. The modules presented in this chapter have a configuration
using RSLogix 5000 software, revision 11. The chapter contains the following
main sections
TopicPage
Set Up the Hardware 48
Create the Example Application49
Configure the I/O Modules50
Add the Local EtherNet/IP Bridge to the I/O Configuration50
Add the I/O Adapter to the I/O Configuration52
Add the POINT I/O Module and Configure for Rack-optimized Connection56
Add the POINT I/O Module and Configure For Direct Connection58
Download the Program to the Controller60
Verify the Module Chassis Size61
Access Module Data 64
.
ATTENTION: You must use series C POINT I/O modules with the
adapter. Series A or B POINT I/O modules do not work with the adapter.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201347
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
45176
Set Up the Hardware
The following section describe how to set up the I/O Hardware.
Set Up the POINT I/O Hardware
In this example, a ControlLogix chassis contains the L63 controller in slot 1 and a
1756-ENBT bridge module in slot 3. In this example, we mounted the
1734-AENTR adapter on a DIN rail in slot 0, with a 1734-OW2/C relay output
module in slot 1, a 1734-OV4E/C sink output module in slot 3, and two other
POINT I/O modules which will not be controlled by this Logix controller in
slots 2 and 4.
1734-AENTR
Local
chassis
Slot 0 1 2 3
L63
controller (slot 1)
10.88.70.2
Data
1756-ENBT
10.88.70.4 (slot 3)
Switch
Link 1
Activity/
Status
Link 2
Activity/
Status
Slot 0 1 2 3 4
POINT I/O
10.88.70.26
Programming
terminal
To work along with this example, set up your system as shown in the figure.
• Note that in the example application, the Logix controller and 1756-
ENBT module (firmware revision 2.3 or later) we assume are in the slots
shown in the figure.
• Verify the IP addresses for your programming terminal, 1756-ENBT
module, and I/O adapter.
• Verify the position (slot) of the I/O modules on the DIN rail.
• Verify that you properly connected all wiring and cabling.
• Make sure you configured your communication driver (such as AB_ETH-
1 or AB-ETHIP-1) in the RSLinx software. SeeConfigure the RSLinx
Ethernet Communication Driver on page93.
48Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Chapter 5
Create the Example
Application
Perform the following steps to create the example application:
1. Start the RSLogix 5000 Enterprise Series software.
The RSLogix 5000 software main dialog opens.
2. From the File menu, select New.
3. The New Controller dialog opens.
4. Enter an appropriate Name for the Controller, for example,
POINT_IO_Controller.
5. Select the following:
– Revision
– Chassis Type
– Slot number
– Description (optional)
6. Complete the Create In entry by selecting the folder where you want to
save the file.
7. To use redundancy in your system, select the Redundancy Enabled
checkbox.
RSLogix 5000 software, revision 11 and later includes enable redundancy.
This example does not use redundancy.
8. Click OK.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201349
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
IMPORTANT
Configure the I/O Modules
You now add the I/O modules to the controller I/O configuration. To do this,
first add the local 1756-ENBT module to the I/O configuration. Next, add the I/
O adapter as a child of the 1756-ENBT module, and then add the I/O modules
as children of the adapter.
Click the Help button on the configuration dialog shown in this section if
you need assistance in selecting and setting the parameters.
Add the Local EtherNet/IP Bridge to the I/O Configuration
1. Right-click the I/O Configuration folder in the project dialog and select
New Module...
2. The Select Module dialog opens.
50Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Chapter 5
3. Expand the Communications tree, as in the following dialog and select the
1756-ENBT EtherNet/IP Bridge.
4. Click OK.
The Select Major Revision dialog opens.
5. Select the value for Major Revision and click OK.
The Module Properties dialog opens.
6. Enter values for Name, IP Address, Slot, Electronic Keying, and Revision,
noting we used the following values:
NameLocal_ENB
IP Address10.88.70.4
Slot3
Electronic KeyingCompatible Module
Revision3.1
Rockwell Automation Publication 1734-UM014B-EN-P - June 201351
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
7. Click OK to accept the configuration.
Add the I/O Adapter to the I/O Configuration
Next, you must add the I/O adapter as a child of the local 1756-ENBT module.
1. In the Project dialog, right-click the local 1756-ENBT module under the
I/O Configuration folder, and select New Module from the dialog.
The Select Module dialog opens.
52Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Chapter 5
IMPORTANT
2. Expand the Communications tree and select the 1734-AENTR Ethernet
Adapter from the list.
3. Click OK.
The New Module dialog opens.
4. Enter values for Name and IP Address, noting we used the following
values.
NamePOINT_IO_Adapter
IP Address10.88.70.2
The Slot field appears grey because the slot is automatically 0 for
the I/O adapter.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201353
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
IMPORTANT
5. On the General tab, click Change...
The Module Definition dialog opens.
6. Enter values for Connection, Chassis Size, Electronic Keying, and
Revision.
The chassis size equals 1 for the adapter plus the number of I/O
modules installed (physically present on the I/O backplane).
Connection choices include:
• None – the adapter makes a direct connection to each of the modules
referenced by the data.
• Rack optimization– digital I/O data is collected into a rack image. This
does not include analog or specialty I/O modules.
• Listen only - rack optimization– read or verify data only, but does not
control the modules. When you have multiple controllers - one controller
is used to control and the other controllers are used to monitor.
7. Choose Rack Optimization from the Connection drop-down list, because
we are making a mixed connection that includes both a direct connection
and rack-optimized connection.
8. Click OK.
54Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Chapter 5
IMPORTANT
The New Module properties dialog opens.
9. Verify that the requested packet interval (RPI) is appropriate for your
system. You use this value for the rack-optimized connection to the I/O
modules.
To avoid overloading the adapter, we recommend that you set RPI no
less than 10 ms for rack connections and 50 ms for direct connections.
10. Click OK. The name of the adapter appears in the I/O tree.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201355
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
Add the POINT I/O Module and Configure for Rack-optimized
Connection
1. Right-click the POINT I/O Chassis in the I/O Configuration folder and
select New Module
The Select Module dialog opens.
…
2. Expand the Digital tree.
3. Select the 1734-OW2 relay output module from the list and click OK.
56Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Chapter 5
IMPORTANT
TheNew Module dialog opens.
4. Click Change... and then enter values for Name and Slot, noting we used
the following values.
NamePOINT_Relay_Output
Slot1
5. Note that the requested packet interval (RPI) is the same as was chosen by
the adapter. You use this value for the rack-optimized connection to the I/
O modules.
To avoid overloading the adapter, we recommend that you set RPI no
less than 10 ms for rack connections and 50 ms for direct connections.
6. Click OK to accept the configuration.
The name of the OW2 appears indented under the local 1734-AENTR in
the I/O Configuration folder.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201357
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
IMPORTANT
Add the POINT I/O Module and Configure For Direct Connection
1. Right-click the POINT I/O Chassis in the I/O Configuration folder, and
select New Module
The Select Module dialog opens.
.
If you exceed the adapter chassis size trying to add more modules
than you configured, the New Module selection appears dim and is
disabled. Increase the adapter chassis size to add more I/O modules.
2. Expand the Digital tree.
58Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Chapter 5
3. Choose the 1734-OV4E/C module and click OK.
The New Module dialog opens.
.
4. From the New Module dialog, complete the following:
– Enter a value for Name.
– Enter a value for Slot.
– Click Change to modify the module definition values.
The Module Definition dialog opens.
5. For Connection, select Data.
This configures the controller to make a Direct I/O Connection to the
module.
6. Click OK.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201359
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
7. From the New Module dialog , click the Connection tab.
The New Module dialog opens.
8. From the New Module dialog, enter 50 for the Requested Packet Interval
(RPI).
Download the Program to
the Controller
9. Keep the following unchecked.
a. Inhibit Module
b. Major Fault on Controller If Connection fails While in Run Mode
10. Click OK.
11. Choose File → Save and enter the name and location of the file.
Follow this procedure to download the program we just saved to the
ControlLogix controller.
1. From the main menu, choose Communications>Who Active.
2. From the Who Active dialog, navigate to select the slot where the
controller is located in the chassis.
60Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Chapter 5
3. Click Set Project Path.
4. Click Download.
The Download dialog opens.
5. From the Download dialog, click Download.
The Downloading dialog displays the download progress.
Verify the Module
Chassis Size
Notice that the 1756-ENBT Bridge is now online.
If yellow triangles are present, see the following section.
You have now built the I/O tree and the RSLogix 5000 software uses the chassis
size from the General tab of the adapter for the rack-optimized I/O connection.
Now you need to configure this new chassis size value into the adapter nonvolatile memory. This procedure synchronizes the chassis size value from the
RSLogix 5000 software into the adapter hardware. You must be online to
perform this procedure.
1. Verify that the RSLogix 5000 software is online.
2. Right-click the name of the adapter under I/O Configuration in the
Project dialog.
3. Select Properties.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201361
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
4. Click the Connection tab.
The Module Fault error code displays at the bottom of the
Connectiontab.
5. Click the Chassis Size tab.
6. Click Set Chassis Size in Module.
62Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Chapter 5
7. Read and acknowledge the warning dialog.
8. Click OK to continue.
9. Notice the chassis size in the module is modified to 5.
10. Click OK.
At this point, your POINTBus status LED should be solid green. All the
yellow triangles in your I/O configuration should be gone.
11. Click OK to close the dialog.
12. Click File → Save to save the project.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201363
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
Access Module Data
Use the following information to use the I/O adapter data in the ladder logic
program:
• POINT_IO_Adapter — the name you gave to your EtherNet adapter
• # — slot number of POINT I/O module
• C — configuration, I = input, O = output
Use the controller tags in your ladder program to read input data or write output
data.
• For ControlLogix controller information, refer to ControlLogix System
User Manual, publication 1756-UM001
• Slot Status Bits: The Slot Status bits display the connection status for each
of the POINT I/O modules that use a rack-optimized connection.
– Bit 0 is reserved for the adapter and always reports a value of 1.
– Each of the other bits (1 to 63) correspond to a POINT I/O module
that you install in the POINT I/O backplane.
– In this example, we configured the 1734-AENTR adapter for both
rack-optimized and direct connections.
The slot status bits indicate that we installed the module in slot 2 with it
operating correctly:
.
0 = module participating with no errors and
1 = module not participating or connection error (typically, module
removed/missing)
64Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Troubleshoot the Adapter
44848
Link 1 activity/ status
Link 2 activity/ status
System power
Field power
Module status
Network activity
Network status
POINTBus status
Chapter
6
Overview
Interpret the Status
Indicators
This chapter describes the different status indicators available in the 1734
POINT I/O and 1738 ArmorPOINT I/O EtherNet/IP adapters and how to
interpret these indicators to help troubleshoot the modules.
The following table lists where to find specific information
TopicPage
Interpret the Status Indicators
65
Status Indicators for POINT I/O Adapter65
Status Indicators for ArmorPOINT I/O Adapter68
Read this chapter to learn about what the LED status indicators mean for the
POINT I/O and ArmorPOINT I/O EtherNet/IP adapters.
Status Indicators for POINT I/O Adapter
The following describes the status indicators on the 1734-AENTR.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201365
Solid redUnrecoverable fault, may require device replacement.
Network statusOffDevice is not online
Flashing greenDevice is online but has no CIP connections in the established state.
Solid greenDevice online and has CIP connections in the established state.
Flashing redOne or more CIP connections in timed-out state.
Solid redDuplicate IP address detected.
Flashing red/greenModule self-test
Network ActivityOffNo link established with Port 1 or Port 2.
Solid greenLink established with Port 1 and/or Port 2 @ 100 Mbps.
Flashing greenTransmit or receive activity present on Port 1 and/or Port 2 @ 100 Mbps.
Solid yellowLink established with Port 1 and/or Port 2 @ 10 Mbps.
Flashing yellowTransmit or receive activity present on Port 1 and/or Port 2 @ 10 Mbps.
Link 1 or Link 2 Activity /
Status
POINTBus statusOffDevice is not online.
OffNo link established.
Solid greenLink established @ 100 Mbps.
Flashing greenTransmit or receive activity present on indicated port @ 100 Mbps.
Solid yellowLink established @ 10 Mbps.
Flashing yellowTransmit or receive activity present on indicated port @ 10 Mbps.
Flashing greenDevice is online but has no connections in the established state.
Solid greenAdapter online with connections established.
Flashing redRecoverable fault occurred:
- Device not powered - check module status indicator.
Check for I/O module failure and controller operation.
Verify IP address setting and correct, as needed.
Link established with Port 1 and Port 2.
One port @ 100 Mbps and the other port @ 10 Mbps.
Transmit or receive activity present on Port 1 and/or Port 2.
One port @ 100 Mbps and the other port @ 10 Mbps.
Device has not completed Dup_MAC_ID test.
Device not powered - check module status indicator.
Firmware (NVS) update in progress.
• At cycle power, the number of expected modules does not equal
the number of modules present.
• A module is missing.
• Node fault (I/O connection timeout) occurred.
Solid redUnrecoverable fault occurred - POINTBus is off.
Flashing red/greenLED powerup test is in progress.
66Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Troubleshoot the Adapter Chapter 6
Status Indicators for 1734-AENTR Adapter
StatusDescription
System powerOffNot active. Adapter power is off, or there is a DC-DC converter problem.
Solid greenSystem power is on. DC-DC converter output is active (5V).
Field powerOffNot active. Adapter power is off.
Solid greenPower is on. 24V input is present.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201367
Chapter 6 Troubleshoot the Adapter
44830
Link 1 activity/status indicator
Link 2 activity/status indicator
Adapter status indicator
Network activity indicator
Network status indicator
System power indicator
Adapter power indicator
POINTBus status indicator
Status Indicators for ArmorPOINT I/O Adapter
The following describes the status indicators on the 1738-AENTR.
This module has the following indicators:
• Adapter, Network, and POINTBus status indicators for
EtherNet/IP
• Adapter and System power indicators
• Network activity indicator
EtherNet I/P
PWR
IP ADDRESS
Link 1
Activity/
Status
Link 2
Activity/
Status
Status Indicators for 1738-AENTR Adapter
StatusDescription
Adapter statusOffNo power applied to device
GreenDevice operating normally
Flashing red/greenDevice is in self-test
Flashing redRecoverable fault.
RedUnrecoverable fault
-Firmware (NVS) update.
-Address switches changed.
-Self-test failure (Flash checksum failure at power up,
RAM test failure or EEPRO< checksum failure at cycle power).
-Firmware fatal error.
1738-AENTR
Adapter
Status
Network
Activity
Network
Status
PointBus
Status
System
Power
Adapter
Power
conformance tested
™
68Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Troubleshoot the Adapter Chapter 6
Status Indicators for 1738-AENTR Adapter
StatusDescription
Network activityOffNo link established with Port 1 or Port 2.
GreenLink established with Port 1 and/or Port 2 at 100 Mbps.
Flashing greenTransmit or receive activity present on Port 1 and/or Port 2 at 100 Mbps.
YellowLink established with Port 1 and/or Port 2 at 10 Mbps.
Flashing yellowTransmit or receive activity present Port 1 and/or Port 2 at 10 Mbps.
Network statusOffDevice not initialized. Device does not have an IP address.
GreenCIP connections present. Device online and has an IP address, and CIP connections
Flashing greenNo CIP connections present. Device has an IP address, but no CIP connections are
Flashing red/greenDevice is in self-test.
Flashing redOne or more CIP connections have timed out.
System powerOffNot active; adapter power is off, or DC-DC converter problem is present.
GreenSystem power is on; DC-DC converter output is active (5V).
Adapter powerOffNot active; adapter power is off
GreenPower is on; 24V input is present.
POINTBus statusOffDevice is not online.
GreenDevice is online and has connections in the established state.
Flashing greenDevice is online but has no connections in the established state.
Flashing red/greenLED cycle power test present.
Flashing redCommunication faulted device - the device has detected a network access error
RedUnrecoverable fault has occurred:
Link 1 or Link 2 activity/status OffNo link established.
GreenLink established at 100 Mbps
Flashing greenTransmit or receive activity present at 100 Mbps.
YellowLink established at 10 Mbps.
Flashing yellowTransmit or receive activity present at 10 Mbps.
Link established with Port 1 and Port 2.
One port at 100 Mbps and one port at 10 Mbps
Transmit or receive activity present on Port 1 and/or Port 2.
One port at 100 Mbps and one port at 10 Mbps.
are established.
established.
- Device has not completed Dup_MAC_ID test.
- Device not powered - check Adapter Status indicator
Firmware (NVS) update in progress.
and is in communication faulted state.
Device has received and accepted an Identify Communication Faulted Request long protocol message
- POINTBus is off.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201369
Chapter 6 Troubleshoot the Adapter
Notes:
70Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Appendix
EtherNet/IP I/O Adapter Specifications
A
Specifications
Following are specifications for the POINT I/O and ArmorPOINT I/O
modules
General Specifications – POINT I/O and ArmorPOINT I/O 2 Port EtherNet/IP
Adapters 1734-AENTR, 1738-AENTR
SpecificationDescription
Module locationStarter module - left side of the 1734 system
LED IndicatorsAdapter status - green/red
Input voltage ratings, nom24V DC
Input voltage range10…28.8V DC
Inrush current, max6 A for 10 ms
Power consumption, max10.4 W @ 28.8V DC
Power dissipation, max6.3 W @ 28.8V DC
Thermal dissipation, max21.5 BTU/hr. @ 28.8V DC
POINTBus output current,
max
Input overvoltage protectionReverse polarity protected
Isolation voltage50V (continuous), Basic Insulation Type
Field side power, max24V DC (+ 20% = 28.8V DC) @ 400 mA
Fieldbus power current, max 10 A
Fieldbus power range10…28.8V DC
InterruptionOutput voltage will stay within specifications when input drops out
Wiring category
(1)
Network status - green/red
POINTBus status - green/red
Network activity - green
System power (POINTBus 5V power) - green
Field power (24V from field supply) - green
Link activity status - green/yellow
0.8 A @ 5V DC ± 5% (4.75…5.25)
Tested at 1250V rms for 60s
for 10 ms at 10V with maximum load
1 – on power ports
2 – on communications ports
(1) Use this conductor category information for planning conductor routing. Refer to publication 1770-IN041,
Industrial Automation Wiring and Grounding Guidelines.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201371
Appendix A EtherNet/IP I/O Adapter Specifications
Specifications – POINT I/O 2 Port EtherNet/IP Adapter 1734-AENTR
SpecificationDescription
Expansion I/O capacity
• Maximum of 63 modules
• Maximum of 5 Rack Optimized connections (for digital modules
only)
• Maximum of 20 Direct connections
• POINT I/O 1734-AENTR backplane current output= 0.8 A
maximum. The actual number of modules varies. Add up the
current requirements of the modules you want to use to make
sure they do not exceed the amperage limit of 0.8 A for the 1734AENTR.
• Backplane current is extended beyond 1.0 A with a 1734-EP24DC
Backplane Extension Power Supply. Add multiple 1734-EP24DC
modules to reach the 63 module maximum.
Cat. No.POINTBus Current Requirements
1734-IB275 mA
1734-IB475 mA
1734-IB875 mA
1734-IV275 mA
1734-IV475 mA
1734-OB275 mA
1734-OB475 mA
1734-OB875 mA
1734-OB2E75 mA
1734-OB2EP75 mA
1734-OB4E75 mA
1734-OB8E75 mA
1734-OV2E75 mA
1734-OV4E75 mA
1734-OW2 80 mA
1734-OX2100 mA
1734-IE2C75 mA
1734-OE2C75 mA
1734-IE2V75 mA
1734-OE2V75 mA
1734-IA275 mA
1734-IM275 mA
1734-OA275 mA
1734-IJ2160 mA
1734-IK2160 mA
1734-IR2220 mA
1734-IT2I175 mA
1734-SSI110 mA
1734-VHSC5180 mA
1734-VHSC24180 mA
1734-232ASC75 mA
1734-485ASC75 mA
1734-ARM75 mA
1734-IB4D50 mA
1734-IV875 mA
1734-OV8E75 mA
1734-OW480 mA
1734-IE4C75 mA
1734-IE8C75 mA
72Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
EtherNet/IP I/O Adapter Specifications Appendix A
Specifications – POINT I/O 2 Port EtherNet/IP Adapter 1734-AENTR
SpecificationDescription
Expansion I/O capacity1734-OE4C75 mA
Ethernet
communication rate
Module locationStarter module - left side of the 1734 system
Dimensions (HxWxD),
approx.
Weight, approx.280 g (9.87 oz)
Enclosure type ratingNon (open style)
Terminal base screw
torque
Conductors#22…#14 AWG (0.324...2.08)
Wire size1.2 mm (3/4 in.) insulation, max
North American temp
code
IEC temp codeT4
1734-IA475 mA
1734-IM475 mA
1734-OA475 mA
1734-IR2E75 mA
1734-8CFG100 mA
10/100 Mbps, half or full-duplex
76.2 x 73.0 x 133.4
(3.0 x 2.87 x 5.25)
0.8 Nm (7 in.-lb)
solid or stranded wire rated at 75 °C or higher
T4
Rockwell Automation Publication 1734-UM014B-EN-P - June 201373
Appendix A EtherNet/IP I/O Adapter Specifications
Specifications – AmorPOINT I/O 2 Port EtherNet/IP Adapter 1738-AENTR
SpecificationDescription
Expansion I/O capacity
Dimensions (HxWxD),
approx.
Weight, approx.330 g (11.64 oz)
Enclosure type ratingMeets IP65, IP66, IP67 (when marked)
Mounting base screw
torque
Wire size1.2 mm (3/4 in.) insulation, max
• Maximum of 63 modules
• Maximum of 5 Rack Optimized connections (for digital modules
only)
• Maximum of 20 Direct connections
• 1738-AENTR backplane current output =0.8 A. The actual number
of modules varies. Add up the current requirements of the
modules you want to use to make sure they do not exceed the
amperage limit of 0.8 A.
• Backplane current is extended beyond 1.0 A with a 1738-EP24DC
Backplane Extension Power Supply. Add multiple 1738-EP24DC
modules to reach the 63 module maximum.
Cat. No.POINTBus Current Requirements
1738-IB2M1275 mA
1738-IB4xxx75 mA
1738-IB8xxx75 mA
1738-IV4xxx75 mA
1738-IV8xxx75 mA
1738-OB2EM1275 mA
1738-OB2EPM1275 mA
1738-OB4Exxx75 mA
1738-OB8Exxx75 mA
1738-OB16xxx150 mA
1738-OV4EM1275 mA
1738-OW4xxx 90 mA
1738-IE2CM12 75 mA
1738-OE2CM1275 mA
1738-IE4Cxxx75 mA
1738-OE4Cxxx75 mA
1738-IE2VM12 75 mA
1738-OE2VM12 75 mA
1738-IA2xxx 75 mA
1738-OA2xxx 75 mA
1738-IJM23160 mA
1738-SSIM23110 mA
1738-IR2M12 220 mA
1738-IT2IM12 175 mA
1738-VHSC24M23 180 mA
1738-232ASCM1275 mA
1738-485ASCM1275 mA
1738-IB4Dxxx50 mA
1738-IB16Dxxx75 mA
1738-8CFGxxx100 mA
76.2 x 73.0 x 133.4 mm
(3.0 x 2.87 x 5.25 in.)
#8 screw, 0.845 Nm (7.5 in-lbs) in aluminum
1.81 Nm (16 in-lbs) in steel
74Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz – 1734AENTR
±4 kV at 5 kHz on power ports
±2 kV at 5 kHz on communication ports
±3 kV at 5 kHz on communication ports – 1734-AENTR
IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±2 kV line-earth(CM) on unshielded communications ports (tested as
balanced circuits)
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Rockwell Automation Publication 1734-UM014B-EN-P - June 201375
Appendix A EtherNet/IP I/O Adapter Specifications
Certifications
Certifications (when
product is marked)
c-UL-us
Value
(1)
1734-AENTR only
UL Listed Industrial Control Equipment, certified for US and
Canada. See UL File E65584
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous
Locations, certified for U.S. and Canada. See UL File E194810.
CE
European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
Ex
1734-AENTR only
European Union 94/9/EC ATEX Directive, compliant with:
EN 60079-15; Potentially Explosive Atmospheres, Protection
"n" (Zone 2)
EtherNet/IP
(1) See the Product Certification link at http://www.rockwellautomation.com/products/certification/ for
Declaration of Conformity, Certificates, and other certification details.
ODVA conformance tested to EtherNet/IP specifications
76Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Adapter Web Dialogs
Appendix
B
Overview
The Web dialog of the I/O adapter offers extensive internal and network
diagnostics. To view the Web dialogs, enter the IP address of the I/O adapters
into your browser
For Information AboutPage
Work with the Home Page77
Work with the Diagnostics Pages79
Use the Diagnostic Overview Page79
Use the Network Settings Page81
Use the Ethernet Statistics Page82
Use the I/O Connections Page83
Use the Diagnostic Messaging Page84
Work with the Configuration Pages85
Use the Identity Page86
Use the Network Configuration Page87
Use the Services Page89
Work with the Browse Chassis Page89
.
Work with the Home Page
Rockwell Automation Publication 1734-UM014B-EN-P - June 201377
Use the adapter diagnostics home page to access other adapter diagnostics web
pages and see the following information.
• Host Name
• Module Description
• Module Location
• IP Address
• Ethernet Address (MAC)
• DHCP Enabled
• Product Revision
• Serial Number
• Status
• Auto Negotiate
• Media Speed
• Half or Full Duplex
Chapter B Adapter Web Dialogs
IMPORTANT
Enter the adapter IP address
to see the home page.
Click Expand to show
options.
To display and work with the adapter diagnostics home page, follow these
procedures.
Make sure that your PC Internet LAN setting and your TCP/IP
settings are configured to access the subnet on which your
adapter communicates.
1. From your web browser, enter the adapter IP address to see the Home page.
2. From the Home page, click Expand to show options, or minimize to see
Diagnostics, Configuration, and Browse Chassis options without the
expansion.
3. From the Home page, complete one of these, as desired.
• Click one of the following to access www.ab.com
.
– Allen-Bradley logo at the top of the page
– Visit
78Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
ab.com for additional information statement under Resources
Adapter Web Dialogs Chapter B
Type a refresh rate.
Click tabs to see
the corresponding
page.
Click from this
panel to see the
corresponding
page.
• Click Rockwell Automation at the top right to go to
www.rockwellautomation.com
.
• Click the following to see additional diagnostics web pages.
– Diagnostics - Diagnostic overview, Network Settings,
To work with the Diagnostics options, follow these procedures.
1. From the Home page, click Diagnostics or Expand to see the following
diagnostics options from the panel at the left.
• Diagnostic overview
• Network settings
• Ethernet statistics
• I/O connections
• Diagnostic messaging
2. In the Refresh Rate field, you can type a refresh rate, noting that the default
rate is 15 seconds.
3. From the panel at the left or tabs at the top of the page, click one of the
diagnostics options to see the corresponding page
.
Use the Diagnostic Overview Page
To use the Diagnostic Overview page for general diagnostics information, follow
this procedure.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201379
Chapter B Adapter Web Dialogs
1. Click Diagnostic Overview from the tab at the top of the page or panel on
the left.
The Diagnostic Overview page opens.
2. From the Diagnostic Overview page, view the following:
• Ethernet Link Status
– Media Speed
– Half or Full Duplex
– Autonegotiate Status
• System Resource Utilitization
– CPU Utilization
– Module Uptime
• CIP Connection Statics
– Current CIP MSG Connections
– CIP MSG Connection Limit
– Max Msg Connections Obser ved
– Current CIP I/O Connections
– CIP I/O Connection Limit
– Max I/O Connections Observed
– Conn Opens
– Open Errors
80Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Adapter Web Dialogs Chapter B
– Conn Closes
– Close Errors
– Conn Timeout
– Status
• Module Settings
– Chassis Size
– Switches
Use the Network Settings Page
To use the Network Settings page for network related information, follow this
procedure.
1. Click Network Settings from the tab at the top of the page or panel on the
left.
This opens the Network Settings page.
2. From the Network Settings page, view the following:
• Network Interface
– Ethernet Address (MAC)
– IP Address
– Subnet Mask
– Default Gateway
– Primary Name Server
– Secondary Name Server
– Default Domain Name
Rockwell Automation Publication 1734-UM014B-EN-P - June 201381
Chapter B Adapter Web Dialogs
– Host Name
– Name Resolution
• Ethernet Interface Configuration
– How the Network Configuration was obtained - Static or Dynamic
• Ethernet Link
– Media Speed
– Half or Full Duplex
– Autonegotiate Status
Use the Ethernet Statistics Page
To use the Ethernet Statistics page for information about the Ethernet link and
interface and media counters, use this procedure.
1. Click Ethernet Statistics from the tab at the top of the page or panel on the
left.
The Ethernet Statistics page opens.
2. From the Ethernet Statistics page, view the following:
• Ethernet Link
– Media Speed, Half or Full Duplex, Autonegotiate Status
82Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
• Interface Counters
The value for Slot shows
the slot number of the I/O
module this connection is
controlling.
The top value in this column representing Lost shows
the number of packets from the missing source.
– In Octets, In UCast Packets, In NUcast Packets,
In Discards, In Errors, In Unknown Protos,
Out Octets, Out Ucast Packets, Out NUcast Packets,
Out Discards, Out Errors
• Media Counters
– Alignment Errors
– FCS Errors
– Single Collisions
– Multiple Collisions
– SQE Test Errors
– Deferred Transmissions
– Late Collisions
– Excessive Collisions
– MAC Transmit Errors
– Carrier Sense Errors
– Frame Too Long
– MAC Receive Errors
Adapter Web Dialogs Chapter B
Use the I/O Connections Page
To use the I/O Connections page for CIP I/O (Class 1) connection information,
follow this procedure.
1. Click I/O Connections from the tab at the top of the page or panel on the
left.
The I/O Connections page opens.
2. From the I/O Connections page, view the following:
Rockwell Automation Publication 1734-UM014B-EN-P - June 201383
Chapter B Adapter Web Dialogs
• Connection Number
• Upt ime
• Receive and Transmit (Rcv/Xmt)
• Connection ID
• Source IP Address with an indication of the following:
– (O) for originator
– (T) for target
• Destination IP Address
• Multicast Address
• Requested Packet Interval (RPI)
• Lost/Slot that shows the number of lost packets and the slot number for
the connection, with a slot value of 0 indicating that this is a rackoptimized connection
• Size of data in bytes
Use the Diagnostic Messaging Page
To use the Diagnostic Messaging page to execute explicit, unconnected message
services, use this procedure.
1. Click Diagnostic Messaging from the tab at the top of the page or panel on
the left.
The Diagnostic Messaging page opens.
2. From the Diagnostic Messaging page, enter the following:
• Service – choose either Get Attribute Single or Get Attributes All
• I/O Module Slot Position (0 to 63 decimal)
• Class (decimal)
• Instance (decimal)
84Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Adapter Web Dialogs Chapter B
IMPORTANT
IMPORTANT
• Attribute (decimal)
• Timeout
3. From the Diagnostic Messaging page, click Submit to see values similar to
that shown.
Work with the
Configuration Pages
To wo rk wi th th eConfiguration pages, follow these procedures.
The values on these pages are in non-volatile memory. Changes to
these parameters do not take effect until you reset or cycle power
through the I/O adapters.
If you set the value of the I/O adapters switch to 888and then
power cycle the module, the following occurs:
· The DHCP Enabled function is enabled (set to True).
· The Ethernet link is negotiated automatically. The Auto Negotiate
function is set to True.
· The web server is enabled. The Disabled Web Server function is
disabled.
· The Ethernet port are disabled. Both ports are re-enabled once the
switches are returned to their previous value and power is cycled.
· The password for this page resets to the factory default whih is
"password".
Note the value of the switches before you enter the 888 value
because you must return the adapter to those values once this
process is complete.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201385
Chapter B Adapter Web Dialogs
1. From the Home page, click Configuration or Expand to see the
Configuration options, if needed.
2. From the Configuration page, click one of the following:
• Identity
• Network
• Services
A login dialog opens as shown. The dialog may vary in appearance
depending on your operating system and browser.
3. From the user name and password dialog, enter values, noting the
following:
• The values for user name and password are case sensitive.
• The default user name is admin.
• The default password is "password".
4. Click OK to log in. After you log in, you can go to any of the
Configuration pages without having to log in again.
5. Refer to the section of this manual that corresponds to the section you
clicked:
• Identity
• Network Configuration
• Services
Use the Identity Page
To use the Identity page to make entries for the host name, module description,
module location, and chassis size, use this procedure.
1. Click Identity from the tab at the top of the page or panel on the left.
86Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Adapter Web Dialogs Chapter B
The Identity page opens
2. From the Identity page, complete entries for the following, noting that the
description and location help you identify where modules are in the
facility:
• Host Name – the name a Domain Name Server uses to resolve this
adapter’s IP address
• Module Description
• Module Location
• Chassis Size - the value that shows the number of I/O modules plus the
adapter. This value must match the number of I/O modules plus 1 for
the adapter before any I/O connections are allowed.
3. Click Apply Changes to save the modified values.
Use the Network Configuration Page
To use the Network Configuration page to make entries for enabling or disabling
DHCP and setting TCP/IP parameters and Ethernet link operation, follow this
procedure.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201387
Chapter B Adapter Web Dialogs
1. Click Network from the tab at the top of the page or panel on the left. The
Network Configuration page opens.
2. From the Network Configuration page, complete these entries, noting that
values for Network Interface are disabled when DHCP is
Dynamic DHCP and port speed and duplex mode are disabled when
Autonegotiate Speed and Duplex is selected.
• For Initial Network Configuration:
– Ethernet Interface Configuration
- Static
- Dynamic DHCP
• For Network Interface, select from these choices:
– IP Address
– Subnet Mask
– Gateway Address
– Primary Name Server
– Secondary Name Server
– Domain Name
• For Ethernet Link, select from these choices:
– Autonegotiate Status
- Autonegotiate Speed and Duplex
- Force Speed and Duplex
– Select Port Speed - 10 megabits, 100 megabits
– Select Duplex Mode - Half Duplex, Full Duplex
88Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Adapter Web Dialogs Chapter B
3. From the Network Configuration page, click Apply Changes to save the
modified values.
Use the Services Page
To use the Services page to change the password for the Configuration web page
or disable the web server, complete these procedures.
1. Click Services from the tab at the top of the page or panel on the left.
The Services page opens.
Work with the Browse
Chassis Page
2. From the Services page, make these entries.
• Click in the Enable box to change whether the web server runs after the
module is reset.
• Change the password by typing the new value for New Password and
Confirm Password, noting the following:
– The entry is case sensitive.
– The default value is the word password.
3. Click Apply Changes.
Use the Browse Chassis page for the following:
• See what modules are present on the system.
• Run a query from slot 1 to slot 63.
• Display the modules found based on the query.
• Provide an easy way to see which modules the adapter recognizes on
your system.
To work with the Browse Chassis page, follow these procedures.
Rockwell Automation Publication 1734-UM014B-EN-P - June 201389
Chapter B Adapter Web Dialogs
Check Increase timeout to increase time of the browse query
and the time the modules get to respond to the query. This is
useful when browsing a busy system.
Before the query completes,
this note about the disabled
module hyperlinks appears.
Before the query completes,
module hyperlinks are inactive.
Before the query finds the module,
the Requesting... message appears.
If there is no response to the query,
the Module not found message
appears.
1. From the Home page, click Browse Chassis.
2. From the Browse Chassis page, leave the Display compact check box
unchecked, unless you want to decrease the font size, to make the full page
easier to read after the query.
3. Check the Increase timeout check box to increase the time of the browse
query and time the modules get to respond to the query.
This function is useful when you are browsing a busy system.
4. Click Start to run the query. A Browser Chassis page opens.
Note that module hyperlinks are inactive before the query completes or is
cancelled.
90Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Adapter Web Dialogs Chapter B
Click a module hyperlink to
view information about the
module
After completing a query, here is how a typical Browse Chassis page looks
with the module hyperlinks active and the Display compact check box
unselected.
5. To view information about a particular module, click the corresponding
Module Description hyperlink.
The 1734 Module Information page opens showing this information
about the module:
• Product Name
• Ve n d o r
• Product Type
• Product Code
• Module Revision
• Serial Number
• Status
Rockwell Automation Publication 1734-UM014B-EN-P - June 201391
Chapter B Adapter Web Dialogs
Notes:
92Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.