Rockwell Automation 1738-AENTR User Manual

User Manual
POINT I/O and ArmorPOINT I/O 2 Port EtherNet/IP Adapters
Catalog Numbers
1734-AENTR, 1738-AENTR, Series A
Important User Information
IMPORTANT
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/ important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
) describes some
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Rockwell Automation, POINT I/O, ArmorPOINT I/O, RSLo gix, RSLinx, RSL ogix 5000, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Preface

Read this preface to familiarize yourself with the rest of the manual. It provides information concerning:
who should use this manual
the purpose of this manual
related documentation
conventions used in this manual

Who Should Use this Manual

Purpose of this Manual

Use this manual if you are responsible for designing, installing, programming, or
troubleshooting control systems that use Series A 1734 POINT I/O
1738 ArmorPOINT I/O
2 Port EtherNet/IP Adapter Modules.
or
This manual is a reference guide for the 1734-AENTR, 1738-AENTR Series A POINT I/O™ 2 Port EtherNet/IP and ArmorPOINT I/O 2 Port EtherNet/IP Adapters, communications adapters for POINT I/O modules. It describes the procedures you use to install, wire, configure, troubleshoot, and use these modules.
ATTENTION: You must use series C POINT I/O modules with the adapter. Series A or B POINT I/O modules do not work with the adapter.
Related Documentation
The following documents contain additional information concerning Rockwell Automation products. To obtain a copy, contact your local Rockwell Automation office or distributor
For Information About See This Publication Publication Number
1734-series I/O modules and compatible control platforms. POINT I/O Selection Guide 1734-SG001 Using EtherNet/IP for industrial control EtherNet/IP Design Considerations Reference Manual ENET-RM002 ControlLogix Ethernet communication interface modules ControlLogix EtherNet/IP Bridge Module Installation Instructions 1756-IN019
EtherNet/IP Modules in Logix5000 Control Systems User Manual ENET-UM001 ControlLogix chassis and power supplies installation ControlLogix Chassis and Power Supplies Installation Instructions 1756-IN005 ControlLogix systems ControlLogix System User Manual 1756-UM001 RSLinx RSLinx Classic Getting Results Guide LINX-GR001 1734-AENTR adapter installation POINT I/O 2 Port EtherNet/IP Adapter Installation Instructions 1734-IN040 1738-AENTR adapter installation ArmorPoint I/O 2-Port EtherNet/IP Adapter Installation Instructions 1738-IN028 Installing an EtherNet/IP network EtherNet/IP Media Planning and Installation Manual ODVA
Rockwell Automation Publication 1734-UM014B-EN-P - May 2013 i

Common Techniques Used in this Manual

The following conventions are used throughout this manual:
Bulleted lists such as this one provide information, not procedural steps.
Numbered lists provide sequential steps or hierarchical information.
Italic type is used for emphasis.
Rockwell Software products contain extensive tutorials and help screens. We recommend that you use these tutorials and help screens to learn about the products.
For more information about Rockwell Software products, visit the Rockwell Software website at
http://www.rockwellautomation.com/software/.
ii Rockwell Automation Publication 1734-UM014B-EN-P - May 2013
About the Adapters
Table of Contents
Preface
Who Should Use this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i
Purpose of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i
Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i
Common Techniques Used in this Manual. . . . . . . . . . . . . . . . . . . . . . . . . . ii
Chapter 1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Important Adapter Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
About the POINT I/O and ArmorPOINT I/O
2 Port Adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Set the Chassis Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Adapter Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Empty Slots and RIUP Situations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Power Up a System for the First Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Adapter Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
What the Adapter Does . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Hardware/Software Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Use of the Common Industrial Protocol (CIP) . . . . . . . . . . . . . . . . . . . . . . . 5
Understand the Producer/Consumer Model . . . . . . . . . . . . . . . . . . . . . . . . . 5
Specify the Requested Packet Interval (RPI) . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Support of Rack-optimized and Direct Connections . . . . . . . . . . . . . . . . . . 6
Mixing Rack-optimized and Direct Connections. . . . . . . . . . . . . . . . . . 7
Chapter Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chapter 2
Install Your Adapter
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Identify Adapter Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Mount the I/O Adapter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Mount the POINT I/O Adapter on a DIN Rail. . . . . . . . . . . . . . . . . 11
Mount the ArmorPOINT I/O Adapter and Base on a Wall or Panel
12
Install the POINT I/O Adapter Module . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Install the ArmorPOINT I/O Adapter Module. . . . . . . . . . . . . . . . . . . . . 14
Wire the POINT I/O Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Wire the ArmorPOINT I/O Adapter. . . . . . . . . . . . . . . . . . . . . . . . . . 15
Chapter Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Chapter 3
Configure the Adapter for Your EtherNet/IP Network
Rockwell Automation Publication 1734-UM014B-EN-P - August 2013 iii
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Configuration Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Table of Contents
Set the Network Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Use the Rockwell BootP/DHCP Utility. . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Use DHCP Software to Configure Your Adapter . . . . . . . . . . . . . . . . . . . 26
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Set Up the Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Create the Example Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Configure the I/O. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Add the POINT I/O Adapter to the I/O Configuration. . . . . . . . . . . . . 33
Add the Relay Output Module 36
Add the Digital Output Module 38
Edit the Controller Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Create the Ladder Program. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Download the Program to the Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Verify the Module Chassis Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Configure the Adapter with Fixed IP Address. . . . . . . . . . . . . . . . . . . . . . . 45
Recover From an Overloaded Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Gateway Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Subnet Mask . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Set the Network Address for POINT I/O Adapter . . . . . . . . . . . . . . 21
Set the Network Address for ArmorPOINT I/O Adapter. . . . . . . . 22
Save the Relation List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Add the Local EtherNet/IP Bridge to the I/O Configuration. . . . . 30
Add the POINT I/O Modules to the I/O Configuration . . . . . . . . 35
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
iv Rockwell Automation Publication 1734-UM014B-EN-P - August 2013
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Set Up the Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Set Up the POINT I/O Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Create the Example Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Configure the I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Add the Local EtherNet/IP Bridge to the I/O Configuration. . . . . 50
Add the I/O Adapter to the I/O Configuration . . . . . . . . . . . . . . . . . 52
Add the POINT I/O Module and Configure for Rack-optimized
Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Add the POINT I/O Module and Configure For Direct Connection
58
Download the Program to the Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Verify the Module Chassis Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Access Module Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Chapter 6
Table of Contents
Troubleshoot the Adapter
EtherNet/IP I/O Adapter Specifications
Adapter Web Dialogs
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Interpret the Status Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Status Indicators for POINT I/O Adapter. . . . . . . . . . . . . . . . . . . . . . 65
Status Indicators for ArmorPOINT I/O Adapter . . . . . . . . . . . . . . . 68
Appendix A
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Appendix B
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Work with the Home Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Work with the Diagnostics Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Use the Diagnostic Overview Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Use the Network Settings Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Use the Ethernet Statistics Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Use the I/O Connections Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Use the Diagnostic Messaging Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Work with the Configuration Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Use the Identity Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Use the Network Configuration Page . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Use the Services Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Work with the Browse Chassis Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Configure the RSLinx Ethernet Communication Driver
Index
Appendix C
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Install the RSLinx Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Configure the AB_ETH Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Configure the AB_ETH/IP Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .99
Rockwell Automation Publication 1734-UM014B-EN-P - August 2013 v
Table of Contents
vi Rockwell Automation Publication 1734-UM014B-EN-P - August 2013
About the Adapters
Chapter
1

Overview

This chapter provides an overview of the Series A1734-AENTR POINT I/O and 1738-AENTR ArmorPOINT I/O EtherNet/IP adapters, their primary features, and how to use them.
You need to understand the concepts discussed in this chapter to configure your adapter and use it in an EtherNet/IP control system.
This table lists where to find specific information.
Topic Page
Important Adapter Considerations About the POINT I/O and ArmorPOINT I/O 2 Port Adapters 1 Adapter Replacement 2 Empty Slots and RIUP Situations 2 Power Up a System for the First Time 3 Adapter Features 4 Hardware/Software Compatibility 5 What the Adapter Does 4 Use of the Common Industrial Protocol (CIP) 5 Understand the Producer/Consumer Model 5 Specify the Requested Packet Interval (RPI) 6 Support of Rack-optimized and Direct Connections 6 Mixing Rack-optimized and Direct Connections 7
1

Important Adapter Considerations

Rockwell Automation Publication 1734-UM014B-EN-P - June 2013 1
Before you begin using your adapter, note the following important considerations.
ATTENTION: You must use series C POINT I/O modules with the adapter. Series A or B POINT I/O modules do not work with the adapter.
Chapter 1 About the Adapters

About the POINT I/O and ArmorPOINT I/O 2 Port Adapters

The POINT I/O and ArmorPOINT I/O adapters provide connectivity to EtherNet/IP networks for POINT I/O and ArmorPOINT I/O modules respectively.
The POINT I/O adapter is for the I/O backplane that provides connectivity through two RJ-45 connectors for 2-port pass-through support of daisy chain or ring, and the existing star and tree network topologies.
Likewise, the ArmorPOINT I/O adapter provides the same connectivity through two M12 Ethernet-keyed connectors. It ships with a terminating base for use in the last I/O module on the backplane.
Set the Chassis Size
The I/O adapters for EtherNet/IP require configuration of their chassis size before you can make any I/O connections. The factory default setting for the chassis size is one slot, which represents the adapter by itself.
You must set the chassis size to a number equaling one slot for the adapter plus one slot for each I/O module present in the backplane of the adapter.
For example, a POINT I/O system consisting of a 1734-AENTR adapter, one 1734-IB8, one 1734-OB8, and one 1734-OB8S POINT Guard I/O module uses a chassis size of 4. The adapter stores this chassis size setting in non-volatile memory.
Each time the adapter is powered up, the adapter compares the number of I/O modules present on its backplane to the chassis size value from non-volatile memory. The adapter does not allow any I/O connection until the number of I/ O modules present equals the chassis size value minus one for the adapter itself.
Adapter Replacement
Note that during a connection request from the controller, the chassis size setting is not communicated to the adapter. You must always set this chassis size using a separate operation. This includes situations when you are replacing an adapter. The adapter does not allow any I/O connections until it is configured with the appropriate chassis size and the proper number of POINT I/O or ArmorPOINT I/O modules are present.
Empty Slots and RIUP Situations
The POINT I/O system cannot detect an empty terminal base. For this reason, there are numerous situations in which you can potentially configure a system that is unusable or one that exercises unintended control.
2 Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
About the Adapters Chapter 1
In an attempt to address these situations, you must observe the following rules for I/O system construction and the
removal and reinsertion of modules.
A correct I/O system does not have any empty terminal bases.
After you cycle power, the adapter will not allow any I/O connections
until the number of modules comprising the chassis plus one for the adapter equals the stored chassis size.
– It cannot assume any safe operation until there is a match between the
number of modules indicating their presence in the chassis and what the adapter has saved in non-volatile memory because it cannot detect empty terminal bases.
– Actual module identification (such as, electronic keying) is done when
connection establishment requests are received from the controller or controllers.
A POINT I/O module removed under power does not disrupt operation
of the other I/O modules. On the other hand, ArmorPOINT I/O modules are not intended to be removed under power.
When you remove a module, the adapter detects what changed.Whenever you remove a module with an active connection from the
POINT I/O system, the adapter indicates this by flashing the POINTBus Status LED red and reports a minor recoverable fault.
If more than one contiguous module is removed under power, connections
to all modules in the contiguous missing module set are disallowed until all modules are replaced. Because the adapter cannot detect an empty base, it does not know the physical positioning of the modules until all the missing modules are replaced.
If a module separating two sets of contiguous missing modules is removed,
the two sets merge into a single set. All the modules must be replaced before connections are permitted to any module in the set.
If modules of different types are removed and returned to the wrong
locations, attempts to connect to these modules will fail during verification of the electronic ID (providing that keying has not been disabled).
If modules of the same type are removed and returned to the wrong
locations, they accept connections from the controller or controllers and reconfigure with the correct data once they pass their electronic keying check.
These removal and return situations exist whether the system is under
power or not. If the system is under power, the situation arises immediately. If the system is not under power, the situation arises in the next power cycle.
Power Up a System for the First Time
When you power the I/O for the first time, the adapter must assign slot addresses to every module in the backplane. All I/O modules ship configured at the same address.
Rockwell Automation Publication 1734-UM014B-EN-P - June 2013 3
Chapter 1 About the Adapters
L 5 5 5 5
EtherNet/IP Network
E N B T
Other Network Devices
A E N T R
POINT I/O
E N B T
ControlLogix I/O
When you first apply power, we expect that all but one module on the backplane exhibits a solid red Module Status LED.
One by one the adapter resets these modules and addresses them appropriately. The amount of time that this operation takes is proportional to the size of your I/ O system.

Adapter Features

Features of the adapters include:
Use of EtherNet/IP messages encapsulated within standard TCP/UDP/IP
protocol
Common application layer with ControlNet and DeviceNet networks
Interfacing via Category 5 rated twisted pair cable
Half/full duplex 10 Mbit or 100 Mbit operation
DIN rail mounting for 1734-AENTR adapter/Wall or panel mounting for
1738-AENTR adapter
Communication to and from other I/O modules on the same DIN rail for
1734-AENTR adapter/Communication to and from other I/O modules in the chassis for 1738-AENTR adapter
Communication supported by RSLinx software
IP address assigned via standard BootP or DHCP tools
I/O configuration via RSLogix 5000 software
No network scheduling required
No routing tables required
Support of connections from multiple controllers simultaneously
You must use RSLogix 5000 to configure these features. For more details on configuration, see Configuration Requirements
on in chapter 3.

What the Adapter Does

The I/O adapters perform the following primary tasks:
Control of real-time I/O data (also known as implicit messaging) - the
adapter serves as a bridge between I/O modules and the network
Support of messaging data for configuration and programming
information (also known as explicit messaging)
4 Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
About the Adapters Chapter 1

Hardware/Software Compatibility

Use of the Common Industrial Protocol (CIP)

The I/O adapters and the applications described in this manual are compatible with the following firmware revisions and
Contact Rockwell Automation if you need software or firmware upgrades to use this equipment
Product Firmware Revision/ Software Release
1734-AENTR; 1738-AENTR adapters 3.xx or later 1756-ENBT 2.3 or later Logix controller 11 or later RSLogix 5000 software 11 or later RSLinx software 2.3.1 or later
The adapter uses the Common Industrial Protocol (CIP). CIP is the application layer protocol specified for EtherNet/IP, the Ethernet Industrial Protocol, as well as for ControlNet and DeviceNet networks. It is a message-based protocol that implements a relative path to send a message from the producing device in a system to the consuming devices.
The producing device contains the path information that steers the message along the proper route to reach its consumers. Since the producing device holds this information, other devices along the path simply pass this information; they do not store it.
software releases.

Understand the Producer/ Consumer Model

This has the following significant benefits:
You do not need to configure routing tables in the bridging modules,
which greatly simplifies maintenance and module replacement.
You maintain full control over the route taken by each message, which
enables you to select alternative paths for the same end device.
The CIP producer and consumer networking model replaces the old source and destination (master and slave) model. The producer and consumer model reduces network traffic and increases speed of transmission. In traditional I/O systems, controllers poll input modules to obtain their input status. In the CIP system, input modules are not polled by a controller. Instead, they produce (multicast or unicast) their data either upon a change of state (COS) or periodically.
Multicast is the default mode for version 17 Logix and earlier controllers and unicast is the default for version 18 with multicast as a selectable option.
The frequency of update depends upon the options chosen during configuration and where on the network the input module resides. The input module, therefore, is a producer of input data, and the controller is a consumer of the data.
Rockwell Automation Publication 1734-UM014B-EN-P - June 2013 5
Chapter 1 About the Adapters
The controller also produces data for other controllers to consume. The produced and consumed data is accessible by multiple controllers and other devices over the EtherNet/IP network. This data exchange conforms to the producer and consumer model.

Specify the Requested Packet Interval (RPI)

Support of Rack-optimized and Direct Connections

The Requested Packet Interval or RPI is the update rate specified for a particular piece of data on the network. The RPI can be specified for the adapter and include all of the I/O modules in the I/O system (using a rack-optimized connection) or specified for a particular module (using direct connection).
When you add a module or an adapter to the I/O configuration of a controller, you must enter the RPI as a parameter. This value specifies how often to produce the data for that device. For example, if you specify an RPI of 50 ms, it means that every 50 ms the device should send its data to the controller and the controller should send the consumed (output) data to the device.
Use RPIs only for devices that exchange data. For example, a ControlLogix EtherNet/IP bridge module in the same chassis as the controller does not require an RPI, because it is not a data-producing member of the system. Its use is only as a bridge to remote racks.
The I/O adapters supports both direct and rack-optimized connections. A direct connection is a real-time data transfer link between the controller and the module occupying the slot that the configuration data references.
Direct I/O connections occur at a cyclic rate specified by the RPI during configuration. A rack-optimized connection is a grouping of data from one or more digital I/O modules into a single block of data sent over a single connection at the same data rate.
Analog, safety, and speciality modules cannot participate in the rack-optimized connection; these modules require a direct I/O connection.
Rack-optimized connections reduce the total number of connections needed to transfer data when using many digital I/O modules in a system. The following example illustrates the benefit of rack-optimized connections.
Assume you set up a system that contains eight digital I/O modules interfaced to an adapter. If you use direct connections to transfer data to each of the these I/O modules, you need eight connections to transfer all of the data, one to each of the
6 Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
About the Adapters Chapter 1
IMPORTANT
eight I/O modules. If you use a rack-optimized connection to transfer the data, you only need a single connection – the connection to the I/O adapter.
Although rack-optimized connections offer an efficient way to use resources, there are a few limitations on their use:
• You can use only rack-optimized connections to send data to and from digital I/O modules. Analog or speciality I/O requires direct connections.
• All data is sent at the same time as the RPI rate of the I/O adapters. If the update rate required for a digital module is different from the RPI of the rack-optimized connection, a direct connection to that digital I/O module is required.
See the EtherNet/IP Design Considerations Reference Manual, publicationENET-RM002
for more information on connections.
Mixing Rack-optimized and Direct Connections

Chapter Summary

You can mix communication formats for different I/O modules communicating through the same adapter. I/O modules set up to use rack optimization communicate at the rate of the RPI configured for the adapter. I/O modules configured for direct communication communicate at their own individual RPIs and ignore the rack-optimized RPI.
In this chapter, you were introduced to the features of the POINT I/O and ArmorPOINT I/O Adapters, and considerations for installation and usage.
Rockwell Automation Publication 1734-UM014B-EN-P - June 2013 7
Chapter 1 About the Adapters
Notes:
8 Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Install Your Adapter
Chapter
2

Overview

This chapter describes how to physically install the Series A POINT I/O and ArmorPOINT I/O 2 Port EtherNet/IP adapters; and how to connect the adapter to the EtherNet/IP network. The only tools you require are a flat or Phillips head screwdriver and a drill.
This table lists where to find specific information.
Topic Page
Identify Adapter Components 10 Mount the I/O Adapter 11 Mount the POINT I/O Adapter on a DIN Rail 11 Mount the ArmorPOINT I/O Adapter and Base on a Wall or Panel 12 Install the POINT I/O Adapter Module 13 Install the ArmorPOINT I/O Adapter Module 13 Wire the POINT I/O Adapter 14 Wire the ArmorPOINT I/O Adapter 15
ATTENTION: You must use series C POINT I/O modules with the adapter. Series A or B POINT I/O modules do not work with the adapter.
Rockwell Automation Publication 1734-UM014B-EN-P - June 2013 9
Chapter 2 Install Your Adapter
1734-AENTR
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Power
POINT I O
02
0
2
Link 2
Activity/
Status
3
4
5
6
7
Link 1
Activity/
Status
44849
Status indicators
RTB removal handle
Removable Terminal Block (RTB)
DIN rail locking screw (orange)
Ethernet network RJ-45 connectors
Network address thumbwheel
1738-AENTR
EtherNet I/P
Adapter Status
Network Activity
Network Status
PointBus Status
System Power
Adapter Power
conformance tested
PWR
IP ADDRESS
Link 2 Activity/ Status
Link 1 Activity/ Status
44830
M12 connectors
Mini Style 4-Pin in Male Connector
Network address switches
Status indicators

Identify Adapter Components

Use the figures to identify the external features of your I/O adapters.
Physical Features of the 1734-AENTR Adapters
Physical Features of the 1738-AENTR Adapters
10 Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Install Your Adapter Chapter 2
1734-AENTR
Module Status
Network Activity
Network Status
Point Bus Status
System Powe
r
Field Powe
r
POINT I O
75.30 (2.96)
74.00 (2.91)
132.72 (5.23)
52.23 (2.06)
35.55 (1.40)
A
B
45174
A = DIN rail B = Secure DIN rail approximately every 200 mm (7.8 in.)
Mount the I/O Adapter
Use the following procedures to mount the I/O adapters on a new system before you install any I/O modules.
Mount a 1734-FPD module in the slot next to the I/O adapter when applying field power. You can also use the 24V DC to power the adapter to supply field power, where no FPD is necessary. Refer to Point I/O Field Potential Distribution Module Installation Instructions, publication 1734-IN059
for more
information.
Mount the POINT I/O Adapter on a DIN Rail
Position the I/O adapters vertically above the DIN rail.
1. Make sure the DIN rail locking screw (orange) is in horizontal position.
2. Position the adapter vertically above an IEC standard (35 x 7.5 x 1 mm)
top-hat DIN rail at a slight angle (DIN rail: Allen-Bradley part number
199-DR1; 46277-3).
3. Press down firmly to install the adapter on the DIN rail, noting that the
locking mechanism locks the adapter to the DIN rail.
4. Set the network address thumbwheel switches to the desired value.Set the network address thumbwheel switches to the desired value. See Set the
Network Address in chapter 3 for more details on setting the IP address.
Rockwell Automation Publication 1734-UM014B-EN-P - June 2013 11
Chapter 2 Install Your Adapter
IMPORTANT
45175
5. Slide the safety end cap up to remove it, exposing the backplane and power interconnections.
WARNING: If you connect or disconnect the Ethernet cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Mount the ArmorPOINT I/O Adapter and Base on a Wall or Panel
To mount the ArmorPOINT I/O adapter on a wall or panel, use the screw holes provided in the adapter module
The ArmorPOINT I/O adapter must be mounted on a grounded metal mounting plate or other conductive surface.
.
Refer to the drilling dimensions illustration for the ArmorPOINT I/O adapter with I/O bases to guide you in mounting the adapter and I/O bases.
Drilling Dimensions
46.25mm (1.82in)
56.00mm (2.20in)
102.0mm (4.01in)
51.90mm (2.04in)
20.10mm (0.79in)
51.90mm (2.04in)
20.10mm (0.79in)
51.90mm (2.04in)
Install the mounting base as follows:
1. Lay out the required points as shown in the drilling dimension drawing.
2. Drill the necessary holes for #8 (M4) machine or self-tapping screws.
3. Mount the adapter using #8 (M4) screws.
4. Ground the system using the ground lug connection in the I/O base. The
ground lug connection is also a mounting hole.
5. Mount the terminating base that was shipped with the adapter as the last base in the backplane instead of the base that was shipped with the I/O module.
6. Set the network address thumbwheel switches to the desired value. See Set
the Network Address in chapter 3 for more information on setting the IP
address.
12 Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Terminating Base
43787
Mounting hole
Latching mechanism release
Ground connection
Keyswitch
Latching mechanism hole
Install Your Adapter Chapter 2

Install the POINT I/O Adapter Module

To install the adapter on the DIN rail prior to installing other base units:
ATTENTION: Allow 25.4 mm (1.0 in.) of space between adjacent equipment for adequate ventilation.
1. Position the adapter vertically above the DIN rail.
2. Press down firmly to install the adapter on the DIN rail, noting that a
locking mechanism locks the adapter to the DIN rail.
3. Set the network address on the network address thumbwheel.
4. Slide the safety end cap up to remove it, exposing the backplane and power
interconnections
ATTENTION: Do not discard the end cap. Use this end cap to cover the exposed interconnections on the last mounting base on the DIN rail. Failure to do so could result in equipment damage or injury from electric shock.
.
Rockwell Automation Publication 1734-UM014B-EN-P - June 2013 13
Chapter 2 Install Your Adapter
NC
C
V
NC
Chas Gnd
C
V
NC = No Connection Chas Gnd = Chassis Ground C = Common V = Supply
0
4
2
6
Chas Gnd
12/24V DC
This DC supply connects to the internal power bus.
1
5
3
7
V DC

Install the ArmorPOINT I/O Adapter Module

To install the ArmorPOINT I/O adapter module:
1. Using a bladed screwdriver, rotate the keyswitch on the mounting base clockwise until the appropriate number for the I/O module you are installing aligns with the notch in the base.
Refer to the installation instructions for each module to determine what this number must be. See Related Documentation
on page i for a list of
these installation instructions.
2. Position the module vertically above the mounting base. The module bridges two bases.
3. Push the module down until it engages the latching mechanism. You hear a clicking sound when the module is properly engaged. The locking mechanism locks the module to the base.
Wire the POINT I/O Adapter
Refer to the following illustration to wire the adapter.
14 Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
ATT ENTI ON: Do not connect 120/240V AC power to the V DC supply.
ATT ENTI ON: Do not wire more than two conductors on any single
terminal.
ATTENTION: Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP67 requirements.
Install Your Adapter Chapter 2
IMPORTANT
(view into connector) Pin 1 - Tx + Pin 2 - Rx + Pin 3 - Tx ­Pin 4 - Rx -
M12 Female In Connector
43765
43587
Mini Style 4-Pin in Male Connector
(view into connector) Pin 1 - User Power + Pin 2 - Adapter Power + Pin 3 - Adapter Power ­Pin 4 - User Power -
Wire the ArmorPOINT I/O Adapter
Wire the EtherNet/IP and auxiliary power connectors on the adapter as shown.
EtherNet/IP Connectors

Chapter Summary

Auxiliary Power Connector
(1)
Analog modules have earth grounded metal rings. This should be considered when choosing shielded cables and grounding techniques.
In this chapter, you learned how to install and wire your POINT I/O or ArmorPOINT adapter module. The following chapter describes how to configure your POINT I/O or ArmorPOINT I/O adapter module to communicate on the EtherNet/IP network by providing an IP address, gateway address, and Subnet mask.
Rockwell Automation Publication 1734-UM014B-EN-P - June 2013 15
(1) Auxiliary power cable: standard cordset (single-ended), for example Allen-Bradley part number 889N-F4AFC-6F or 889N-R4AFC­6F; or standard patchcord (double-ended), for example, Allen-Bradley part number 889N-F4AFNU-6F or 889N-F4AFNV-6F. Refer to publication M117-CA001A-EN-P
for more information.
Chapter 2 Install Your Adapter
Notes:
16 Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Chapter
Configure the Adapter for Your EtherNet/ IP Network
3

Overview

Before using your adapter in an EtherNet/IP network, you need to configure it with an IP address, subnet mask, and optional Gateway address. This chapter describes these configuration requirements and the procedures for providing them. Here are ways you can do this:
Use the Rockwell BootP/DHCP utility, version 2.3 or later, that ships
with RSLogix 5000 or RSLinx software. – You can also use this utility to reconfigure a device with an IP address
you must change.
Use a
Use the Network Address thumbwheel switches.
Have your network administrator configure the adapter via the network
See the table for a list of where to find information in this chapter.
Topic Page
Configuration Requirements 18 IP Address 18 Gateway Address 19 Subnet Mask 20 Set the Network Address 21 Set the Network Address for POINT I/O Adapter 21 Set the Network Address for ArmorPOINT I/O Adapter 22 Use the Rockwell BootP/DHCP Utility 22 Save the Relation List 25 Use DHCP Software to Configure Your Adapter 26
third party DHCP server.
DHCP server.
Rockwell Automation Publication 1734-UM014B-EN-P - June 2013 17
Chapter 3 Configure the Adapter for Your EtherNet/IP Network
Class A
Class B
Class C
Network ID
Host ID
Host ID
Host ID
0 0
0 10
0 110
78
15 16
31
31
3123 24
Network ID
Network ID
EXAMPLE

Configuration Requirements

Before you can use your adapter, you must configure its IP address, its subnet mask, and, optionally, a gateway address. You can use the Rockwell BootP utility, version 2.3 or later, to perform the
configuration. You can also use a DHCP
server or the network address switches to configure these parameters.
ATTENTION: You must use series C POINT I/O modules with the adapter. Series A or B POINT I/O modules do not work with the adapter.
If you need to reset the adapter to factory defaults, see Work with the
Configuration Pages in Appendix B.
IP Address
The IP address identifies each node on the IP network (or system of connected networks). Each TCP/IP node on a network (including the adapter) must have a unique IP address.
The IP address is 32 bits long and has a Network ID part and Host ID part. Networks are classified A, B, C, (or other). The class of the network determines how an IP address is formatted
.
You can distinguish the class of the IP address from the first integer in its dotted­decimal IP address as follows:
Range of first integer Class Range of first integer Class
0 1…127 A 192…223 C 128…191 B 224… 255 other
Each node on the same physical network must have an IP address of the same class and must have the same network ID. Each node on the same network must have a different Host ID thus giving it a unique IP address.
IP addresses are written as four decimal integers (0…255) separated by periods where each integer gives the value of one byte of the IP address
.
For example, the 32-bit IP address:
10000000 00000001 00000000 00000001 is written as
128.1.0.1
18 Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Configure the Adapter for Your EtherNet/IP Network Chapter 3
Network 1
Network 2
128.1.0.1
128.2.0.1 128.2.0.2 128.2.0.3
128.1.0.2
A
B
G
C
Gateway Address
This section applies to multi-network systems. If you have a single network system, refer to the next section.
The Gateway Address is the default address of a network. It provides a single domain name and point of entry to the site. Gateways connect individual physical networks into a system of networks.
When a node needs to communicate with a node on another network, a gateway transfers the data between the two networks. The figure shows gateway G connecting Network 1 with Network 2.
When host B with IP address 128.2.0.1 communicates with host C, it knows from C’s IP address that C is on the same network. in an Ethernet environment, B can then resolve C’s IP address into a hardware address (MAC address) and communicate with C directly.
When host B communicates with host A, it knows from A’s IP address that A is on another network (the network IDs are different). In order to send data to A, B must use the IP address of the gateway connecting the two networks. In this example, the gateway’s IP address on Network 2 is 128.2.0.3.
The gateway has two IP addresses (128.1.0.2 and 128.2.0.3). The first must be used by hosts on Network 1 and the second must be used by hosts on Network 2. To be usable, a gateway of a host must be addressed using a network ID matching its own.
Rockwell Automation Publication 1734-UM014B-EN-P - June 2013 19
Chapter 3 Configure the Adapter for Your EtherNet/IP Network
EXAMPLE
These two bits of the Host ID are used to extend the netdwork ID.
Network 1
Network 2.1
Network 2.2
A
BC
DE
128.1.0.2
128.1.0.1
128.2.64.3
128.2.128.2
128.2.64.1 128.2.64.2
128.2.128.3
128.2.128.1
G2
G
Subnet Mask
The subnet mask is used for splitting IP networks into a series of subgroups, or subnets. The mask is a binary pattern that is matched up with the IP address to turn part of the Host ID address field into a field for subnets
Two bits of the Class B host ID are used to extend the network ID. Each unique combination of bits in the part of the Host ID where subnet mask bits are 1 specifies a different physical network.
.
Take Network 2 (a Class B network) in the previous example and add another physical network. Selecting the following subnet mask would add two additional network ID bits, allowing for four physical networks: 11111111 11111111 11
000000 00000000 = 255.255.192.0
The new configuration is:
A second network with Hosts D and E was added. Gateway G2 connects Network 2.1 with Network 2.2.
Hosts D and E will use Gateway G2 to communicate with hosts not on Network 2.2.
Hosts B and C will use Gateway G to communicate with hosts not on Network 2.1.
20 Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
When B is communicating with D, G (the configured Gateway for B) will route the data from B to D through G2.
Configure the Adapter for Your EtherNet/IP Network Chapter 3
44848
Network address thumbwheel Press either the + or - buttons to change the number and assign the IP address.
02
0
1734-AENTR
Module Status
Network Activity
Network Status
Point Bus Status
System Power
Field Power
POINT I O
Link 1 Activity/ Status
Link 2 Activity/ Status
IP ADDRESS

Set the Network Address

The adapters ship DHCP-enabled and with the switches set to 999. To change the network address, do the following.
Set the Network Address for POINT I/O Adapter
Use the thumbwheel switches located on the adapter. Press either the + or -
buttons to change the number.
Use a Dynamic Host Configuration Protocol (DHCP) server, such as
Rockwell Automation BootP/DHCP.
Retrieve the IP address from non-volatile memory.
The adapter reads the thumbwheel switches first to determine if the switches are set to a valid number. You set the node address by using the 3-position thumbwheel switch. Press the + or - buttons to change the number. Valid settings range from 001…254.
When you use the thumbwheel to assign an address and set it to 001, the adapter gateway address is set to 0.0.0.0. and the subnet mask is 255.255.255.0 . When you use the thumbwheel to assign an address and set it between 002...254, the adapter gateway address is set to 192.168.1.1.
The adapter does not have a host name assigned, or use any Domain Name System when using the thumbwheel settings.
If DHCP is not enabled, the adapter uses the IP address, along with other TCP configurable parameters, stored in non-volatile memory.
Rockwell Automation Publication 1734-UM014B-EN-P - June 2013 21
Chapter 3 Configure the Adapter for Your EtherNet/IP Network
44831
This example shows the network address set at 163.
Set the Network Address for ArmorPOINT I/O Adapter
Adjust the switches in front of the module
Use a Dynamic Host Configuration Protocol (DHCP) server such as
Rockwell Automation BootP/DHCP
Retrieve the IP address from non-volatile memory
The adapter reads the switches first to determine if the switches are set to a valid number. Set the network address by adjusting the three switches on the front of the adapter.
Network Address Example
Use a small blade screwdriver to rotate the switches. Line up the small notch on the switch with the number setting you wish to use. Valid settings range from 001254.

Use the Rockwell BootP/ DHCP Utility

When you use the switches to assign an address and set it to 001, the adapter gateway address is set to 0.0.0.0. and the subnet mask is 255.255.255.0 . When you use the switches to assign an address and set it to a valid number between
002...254, the adapter gateway address is set to 192.168.1.1.
If the switches are set to an invalid number (for example, 000 or a value greater than 254 excluding 888), the adapter checks to see if DHCP is enabled. If DHCP is enabled, the adapter requests an address from a DHCP server. The DHCP server also assigns other Transport Control Protocol (TCP) parameters.
If DHCP is not enabled, the adapter uses the IP address, along with other TCP configurable parameters, stored in non-volatile memory.
The Rockwell BootP/DHCP utility is a standalone program that incorporates the functionality of standard BootP software with a user friendly graphical interface. It is located in the Utils directory on the RSLogix5000 software installation CD. The adapter must have DHCP enabled (factory default and the network address switches set to an invalid value) to use the utility.
22 Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Loading...
+ 82 hidden pages