Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1
available from your local Rockwell Automation sales office or online at
http://www.ab.com/manuals/gi) describes some important differ enc es
between solid state equipment and hard-wired electromechanical devices.
Because of this difference, and also because of the wide variety of uses for
solid state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is
acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for
indirect or consequential damages resulting from the use or application of
this equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with
any particular installation, Rockwell Automation, Inc. cannot assume
responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to
use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without
written permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual, when necessary we use notes to make you aware of
safety considerations
.
WARNING
IMPORTANT
ATTENTION
BURN HAZARD
Identifies information about practices or circumstances
that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property
damage, or economic loss.
Identifies information that is critical for successful
application and understanding of the product.
Identifies information about practices or circumstances
that can lead to personal injury or death, property
damage, or economic loss. Attentions help you:
• identify a hazard
• avoid a hazard
• recognize the consequence
Labels may be located on or inside the equipment (e.g.,
drive or motor) to alert people that dangerous voltage may
be present.
Labels may be located on or inside the equipment (e.g.,
drive or motor) to alert people that surfaces may be
dangerous temperatures.
Preface
Purpose of This Manual
This manual describes how to install, configure, and operate your
ArmorPoint I/O™ DeviceNet™ Adapters, catalog numbers
1738-ADN12, -ADN18, -ADN18P, and -ADNX.
See the following sections:Page:
Who Should Use This ManualP-2
What the Manual ContainsP-2
Related TermsP-3
Related Products and DocumentationP-5
Guidelines for Using Your AdapterP-6
Conventions Used in This ManualP-6
IMPORTANT
In this manual, we use ArmorPoint DeviceNet
adapters to refer to all the 1738 DeviceNet adapter
modules (1738-ADN12, -ADN18, -ADN18P, and
-ADNX). We use the specific catalog number (e.g.,
1738-ADNX) to refer to a specific module.
In the rest of this manual (except Chapter 4), we
refer to the ArmorPoint I/O DeviceNet adapters as
the adapters.
Who Should Use
This Manual
In Chapter 4, we refer to the ArmorPoint I/O
DeviceNet adapter as the scanner because the
chapter describes how to configure the adapter on
the subnet.
You must be able to use RSNetWorx for DeviceNet™ software or a
similar configuration software to configure your adapter.
In this manual, we assume you know how to configure an ada pte r. If
you do not, refer to your software user manuals or online help before
attempting to use these adapters.
We also assume you are familiar with the ArmorPoint I/O product
line, including other fieldbus interfaces, I/O modules, and power
supplies. If you are not familiar with these components, you can read
some of the ArmorPoint I/O documents listed in the Related Products
and Documentation section.
1Publication 1738-UM001A-EN-P - February 2005
Preface 2
What the Manual Contains
This manual contains the following sections:
Chapter 1 - Install the ArmorPoint DeviceNet Adapters
Description of how to install and wire the adapter
Chapter 3 - Use Auto Start Mode
Description of how to use the Auto
Start Mode on your adapter to quickly
get your system up and running
Chapter 2 - What Is the ArmorPoint DeviceNet Adapter?
Overview of the adapter’s features and functionality
1738-ADN12
DeviceNet Out
DeviceNet In
Adapter
Status
DeviceNet
Status
PointBus
X1
Status
X10
PWR
Or
System
Power
R
Adapter
Power
Chapter 4 - Configure the
DeviceNet Scanner Subnet
Description of how to configure your
adapter on the subnet
Chapter 5 - Add the ArmorPoint
DeviceNet Adapter to the DeviceNet
Scanner’s Scanlist
Description of how to configure the
DeviceNet adapter and how to add it to the
scanlist
Appendix B - Quick Start
Learning how to use the 1738-ADN12
with a ControlLogix system on DeviceNet
Chapter 6 - Troubleshoot the
ArmorPoint DeviceNet Adapter
Description of how to use the status
indicators and how to troubleshoot your
adapter
Appendix C - 1738-ADNX Rules and Guidelines
Rules and guidelines regarding how to use the
1738-ADNX
Appendix A - Specifications
Listing of the ArmorPoint adapters’
specifications
Appendix D - Default Data Maps
Listing of the default data maps for
1738 ArmorPoint I/O modules
Publication 1738-UM001A-EN-P - February 2005
Preface 3
Related Terms
This manual uses the following terms:
Term:Definition:
AdapterThe adapter interfaces between DeviceNet devices and
ArmorPoint I/O modules. ArmorPoint I/O DeviceNet adapters
include the 1738-ADN12, -ADN18, -ADN18P, and -ADNX.
Auto Catalog ReplaceThe ArmorPoint I/O DeviceNet adapter supports the swapping
of two identical modules connected to the adapter . That is, if a
1738-IB4M12 is in slot 3 and another 1738-IB4M12 is in slot 7,
the two modules can be removed from the ArmorPoint system
and the slot 3 module placed into slot 7, and vice-versa. When
Automatic Device Replacement (ADR) is active, the swapped
modules will be reconfigured to match the previous module in
their new slot. When ADR is not active, the configuration
parameters will not be modified, the swapped modules must
have identical configuration and values for their EDS file
parameters.
Auto Device Replacement
(ADR)
This refers to the ADR feature of a ControlLogix System on
DeviceNet. With ADR active, any device on the DeviceNet link
may be removed and replaced with an out-of-the-box
checkmark compliant DeviceNet device. The ADR feature will
result in downloading the values of the configuration
parameters of the EDS file of the removed device to the new
device.
Auto Start ModeA feature that lets the ArmorPoint I/O system get “up and
running” without the prerequisite to configure any of the EDS
parameters for the PointBus
Using Auto Start Mode will result in a scan list within the
adapter that stores the modules identity information.
AutobaudA feature in devices (e.g., ArmorPoint I/O modules) on the
DeviceNet network that causes them to listen to
communications on the network and set their own baudrate to
match the network rate.
BackplaneThe PointBus that consists of ArmorPoint I/O modules
connected to the ArmorPoint DeviceNet adapter.
BaudrateRate of communications between devices on the DeviceNet
network. Backplane baudrate is used for the 1738-ADN12,
-ADN18, and -ADN18P. Subnet baudrate is used for the
1738-ADNX.
Change of State (COS)DeviceNet communications method in which the adapter
sends data based on detection of any changed value within
the input data. Data is independently received based on a
change of state from the sender . Data in both directions can be
acknowledged or unacknowledged depending on the run-time
configuration of the system.
CommissioningThe period in time associated with post startup activities.
Commissioning implies that the system has been validated
and all configuration parameters are correct, all modules are
in good operating condition, and the adapter scanlist is
complete.
ControlFlash™Utility software you can use to update the adapter’s firmware
with the most current boot and application code.
™ or ArmorPoint I/O modules.
Publication 1738-UM001A-EN-P - February 2005
Preface 4
Term:Definition:
CyclicDeviceNet communications method in which the adapter
sends data cyclically based on a configured time value. Data is
independently received cyclically from the sender . Data in both
directions can be acknowledged or unacknowledged
depending on the run time configuration of the system.
MACIDMedia Access Control Identifier (DeviceNet network address).
MasterA DeviceNet network device (e.g., 1771-SDN) that initiates
communication with DeviceNet slave devices (e.g.,
ArmorPoint I/O modules) to retrieve data. The master only
receives unprompted data when the slave is enabled for COS
and there is a change in the device’s operating state.
Max Backplane MACIDThe 1738-ADNX has a unique attribute, Max(imum)
Backplane MACID. This value represents the highest node
address of a module residing on the backplane. This value
must be greater than or equal to the right most backplane
ArmorPoint I/O module, but must be less than that of any
non-backplane Subnet module.
OfflineState of the adapter when it is not powered or maintaining
normal communication exchanges with other DeviceNet
devices.
OnlineState of the adapter when it is powered and maintaining
normal communication exchanges with other DeviceNet
devices.
PointBusThe ArmorPoint I/O backplane PointBus maintains all
DeviceNet network protocol but also offers configuration
capabilities.
PolledDeviceNet communications method in which a module sends
data in response to received data.
Primary NetworkThe primary DeviceNet network is defined as the DeviceNet
link that provides the direct connection between the
ArmorPoint DeviceNet adapter and a DeviceNet scanner.
RSNetWorx for DeviceNetConfiguration software for the adapter and Subnet modules.
Publication 1738-UM001A-EN-P - February 2005
ScanlistThe list of Subnet modules connected to the adapter. When
ADR is active, the scanlist stores the configured values of
each of the Subnet modules’ configurable parameters. When
ADR is not active, the scanlist stores only the module identity
information.
ScannerOperating state of the ArmorPoint DeviceNet adapter when it
retrieves I/O data from Subnet modules.
SlaveA DeviceNet network device that cannot initiate
communication (except when configured with COS enabled)
but responds to a DeviceNet master device.
StrobeAdapter sends data in response to the strobe command. The
single bit allocated to the adapter in the strobe message is not
used. If the configured size of the input data (sent from the
adapter) is greater than 8 bytes, the strobe connection
establishment will fail. In this case, the input size must be
reconfigure to 8 bytes or less.
Term:Definition:
Subnet1738-ADNX only.
The Subnet DeviceNet network is defined as the DeviceNet
link that provides the expansion of the PointBus to let the
1738-ADNX use its lower connector to add an additional 500
meters and up to 63 nodes. These nodes will be bridged
through the 1738-ADNX up to the primary network. Note that
backplane modules are also part of the Subnet.
Preface 5
Related Products and
The following table lists related ArmorPoint I/O products and
documentation:
ArmorPoint PROFIBUS Adapter User Manual1738-UM002
ArmorPoint ControlNet Adapter Installation Instructions
1738-ACNR
ArmorPoint ControlNet Adapter User Manual1738-UM003
ArmorPoint EtherNet/IP Adapter Installation Instructions
1738-AENT
ArmorPoint EtherNet/IP Adapter User Manual1738-UM004
ArmorPoint Extension Units Installation Instructions1738-EXT1, -EXT31738-IN018
ArmorPoint Field Potential Distributor Installation Instructions1738-FPD1738-IN019
ArmorPoint I/O 24V dc Expansion Power Supply Installation Instructions1738-EP24DC1738-IN020
DeviceNet Media Design & Installation GuideN/ADNET-UM072
Industrial Automation Wiring and Grounding Installation InstructionsN/A1770-4.1
Publication 1738-UM001A-EN-P - February 2005
1738-IN015
1738-IN016
1738-IN017
Preface 6
If you need more information on these products, contact your local
Rockwell Automation/Allen-Bradley distributor, integrator or sales
office for assistance. For more information on the documentation,
refer to the Allen-Bradley Publication Index, publication SD499.
Guidelines for Using
Your Adapter
Conventions Used In
This Manual
Remember the following operational guidelines when using your
ArmorPoint DeviceNet adapter.
• Do not leave spaces in the I/O. Instea d, instal l all ArmorPoint
I/O modules adjacent to each other.
• Populate every position on the mounting base.
• ArmorPoint does not support removal and insertion under
power (RIUP). When an I/O module is removed, the IP67 seal is
broken and the backplane bus is interrupted.
• Use Allen-Bradley terminal markers to identify your ArmorPoint
I/O modules.
For more information on the Allen-Bradley terminal marking
kits, see the documents list on page
The following conventions are used thro ughout this manual:
• bullet lists (such as this one) provide information, not
procedural steps
• numbered lists provide sequential steps
• text written like this identifies screen, menu, toolbar names, field
names, buttons, and check boxes on screens
• a menu item in this format File>Save identifies the submenu item
after the caret (>) that is accessed from the main menu (name
before the caret)
• pictures of symbols and/or scre ens represent th e actual symbols
you see or the screens you use
Preface-5.
Publication 1738-UM001A-EN-P - February 2005
Install the ArmorPoint
DeviceNet Adapters
What Is the ArmorPoint
DeviceNet Adapter?
Table Of Contents
Chapter 1
Mount the Adapter and I/O Base. . . . . . . . . . . . . . . . . . . . 1-1
This chapter describes how to install and wire your adapter.
See the following sections:Page:
Mount the Adapter and I/O Base1-1
Set the Node Address1-2
Wire the DeviceNet Adapters1-3
Chapter Summary and What’s Next1-4
Mount the Adapter and
I/O Base
Adapter
4.02 in.
102 mm
To mount the ArmorPoint adapter on a wall or panel, use the screw
holes provided in the adapter.
A mounting illustration for the ArmorPoint adapter with I/O bases is
shown below.
47.2 mm
1.81 in.
46 mm
50 mm
22 mm
50 mm
22 mm
Install the mounting base as follows:
1. Lay out the required points as shown in the drilling dimension
drawing.
50 mm
43769
2. Drill the necessary holes for #8 (M4) machine or self-tapping
screws.
3. Mount the adapter and I/O bases using #8 (M4) screws.
4. Ground the system using the ground lug connection in the I/O
base. (The ground lug connection is also a mounting hole.)
1Publication 1738-UM001A-EN-P - February 2005
1-2 Install the ArmorPoint DeviceNet Adapters
5. Mount the terminating base that was shipped with the adapter as
the last base in the backplane instead of the base that was
shipped with the I/O module.
Terminating base
Mounting hole
Ground connection
Set the Node Address
Latching mechanism holes
43787
Valid node addresses are 00 through 63.
Set the node address using either the rotary switches, RSNetWorx for
DeviceNet, DeviceNetManager, or another software configuration
tool. Setting the switches at any number from 64 through 99 lets the
software have address control.
Each module is shipped with the switches set for node address 63.
Remove the caps on the front of the module to access the switches
(refer to the X10 and X1 on the front of the module). The two
switches are:
• X10 (most significant digit) - left side of module
• X1 (least significant digit) - right side of module
This example shows the
node address set at 63.
31433-M
Publication 1738-UM001A-EN-P - February 2005
To reset the node addre ss, use a sma ll blade screwdriv er to rotate the
switches. Line up the small notch on the switch with the number
setting you wish to use and then cycle power.
Install the ArmorPoint DeviceNet Adapters 1-3
M
The rotary switches are read periodically. If the switches have been
changed since the last time they were read and th ey no longer match
the on line address, a minor fault will occur, which is indicated by a
flashing red Adapter Status LED. Settings of 64 through 99 cause the
module to use the last valid node address stored internally
. For
example, the last setting internal ly was 40. If a change is made to 68,
and then you power up, the address will default to 40.
The module is equipped with AutoBaud detect. AutoBaud lets the
module read the settings already in use on your DeviceNet network
and automatically adjusts to follow those settings.
Wire the
DeviceNet Adapters
Following are wiring instructions for the ArmorPoint DeviceNet
adapters.
(view into connector)
Pin 1 - User Power +
Pin 2 - Adapter Power +
Adapter/Subnet + (1738-ADNX only)
Pin 3 - Adapter Power -
43587
Pin 4 - User Power -
Adapter/Subnet - (1738-ADNX only)
Chapter Summary and
What’s Next
ATTENTION
Make sure all connectors and caps are securely
tightened to properly seal the connections against
leaks and maintain IP67 requirements.
In this chapter , you learned how to install and wire your DeviceNet
adapter. Move to chapter 2 to learn about the ArmorPoint DeviceNet
adapters.
Publication 1738-UM001A-EN-P - February 2005
Chapter
2
What Is the ArmorPoint DeviceNet Adapter?
This chapter describes the ArmorPoint I/O DeviceNet adapter,
including descriptions of the adapter’s features and functionality.
See the following sections:Page:
Use the Adapter2-2
Understand the DeviceNet Network and Subnet2-6
Adapter Features2-8
Communicate Through the Adapter2-18
Communicate With I/O Modules2-23
Use Diagnostic Tables2-24
Chapter Summary and What’s Next2-26
1Publication 1738-UM001A-EN-P - Februa ry 2005
2-2 What Is the ArmorPoint DeviceNet Adapter?
Use the Adapter
The adapter resides on the primary DeviceNet network and the
Subnet simultaneously.
The adapter interfaces between DeviceNet devices and ArmorPoint
I/O modules. The graphic below shows the adapter on the DeviceNet
network and PointBus.
ControlLogix chassis
IMPORTANT
The PointBus maintains all DeviceNet network
protocol but also offers configuration capab ilities.
computer with PLC
programming software
ControlNet network
1784-PCD
PCMCIA card
computer with
RSNetWorx for
DeviceNet software
DeviceNet network
See page 2-19 for an
explanation of the number
sequence.
ArmorPoint I/O modules
1738-ADN12 adapter
Subnet (1738-ADNX only)
DeviceNet Out
DeviceNet In
8
x10
PWR
1738-IB8M12
1738-ADN12
0
0
2
2
8
6
6
4
4
x1
Adapter
Status
DeviceNet
Status
PointBus
Status
System
Power
Adapter
Power
24V dc In
02
13
46
57
MOD
NET
02
13
0
1
2
3
4
5
6
7
1738-OB8EM12
24V dc Out
MOD
NET
0
1
43852
2
3
4
6
4
5
7
5
6
7
After you have installed your adapter into a ArmorPoint I/O system,
you must perform the following tasks:
1. Set Subnet/Backplane Baudrate
2. Set Subnet/Backplane I/O Module Addresses
3. Configure the Subnet I/O
4. Configure the Primary Device Net Network
The steps mentioned above are explained briefly here and then in
greater detail throughout this manual. Y ou must complete the steps for
the adapter to work with DeviceNet masters (e.g., 1756-DNB) on the
primary network and Subnet modules.
Publication 1738-UM001A-EN-P - February 2005
What Is the ArmorPoint DeviceNet Adapter? 2-3
1. Set Subnet/Backplane Baudrate
The adapter and Subnet/Backplane modules must use the same
baudrate to communicate with each other. Use one or both of the
following to set a Subnet/Backplane baudrate.
• Enable or disable the Backplane Autobaud feature for
ArmorPoint I/O modules. ArmorPoint I/O modules have
Autobaud enabled as the default- See page
• Set the adapter baudrate for the Subnet. The default for the
1738-ADN12, -ADN18, and -ADN18P is 1Mbaud. The default for
the 1738-ADNX is 125Kbaud - See page
You set the backplane baudrate for the 1738-ADN12, -ADN18,
and -ADN18P. You set the Subnet baudrate for the 1738-ADNX.
2-12.
2-9.
2. Set Subnet/Backplane I/O Module Addresses
Once the adapter and ArmorPoint I/O modules are communicating at
the same rate on the backplane, you must make sure all modules use
a valid MACID.
Set the Auto Address feature for ArmorPoint I/O modules - See
page 2-13.
For the 1738-ADNX, a DeviceNet configuration tool, such as
RSNetW orx for DeviceNet, may be required to set the node addre ss. (if
node address switches are not present on the Subnet device).
3. Configure the Subnet I/O
In the first two steps, you set a consistent communication rate and
made sure each module uses valid addresse s for communication. Next
you must configure the PointBus (e.g., set scan list).
You can configure the PointBus using one of two methods:
• Auto Start Mode (ASM) or
• Manually
For more information on configuring the PointBus, see Chapter 3 for
ASM or see Chapter 4 for manual configuration.
Publication 1738-UM001A-EN-P - Februa ry 2005
2-4 What Is the ArmorPoint DeviceNet Adapter?
4. Configure the Primary DeviceNet Network
Finally, you must configure the adapter for communication with a
master (e.g., 1756-DNB).
For more information on configuring the Devic eNet network, see
Chapter 5, Add the ArmorPoint DeviceNet Adapter to the DeviceNet
Scanner’s Scanlist.
You must understand all of the adapter’s features to effectively use it
in your ArmorPoint I/O system. Keep these four steps in mind as you
read this manual:
1. Set Subnet/Backplane Baudrate
2. Set Subnet/Backplane I/O Module Addresses
3. Configure the Subnet I/O
4. Configure the Primary Device Net Network
Publication 1738-UM001A-EN-P - February 2005
What Is the ArmorPoint DeviceNet Adapter? 2-5
Remove and Reinsert Modules on the Backplane
Removal and Insertion Under Power (RIUP) is not recommended in a
ArmorPoint System because of the following reasons.
• Removing a module breaks the IP 67 seal.
• Removing a module breaks the backp lan e bu s. Mod ule s to the
right of the removed module will be ‘lost’ to the adapter. Also,
the terminating resistor will be removed, causing system
uncertainty.
• Inserting a module under power may cause the adjacent module
to reset due to the addition of a large capacitive load on the
power bus.
IMPORTANT
If the module is removed wh ile it is under power, all
the modules to the right of the removed module will
disconnect from the PointBus and field power until
the module is reinstalled.
If you must remove and reinsert modules, we recommend the
following:
• Do not move I/O modules to different locations on the
mounting base after they have been installed and configured.
• If adjacent modules (i.e., 2 or more) are remo ved from the
backplane, replace all of them before attempting to operate the
ArmorPoint I/O system. Input data will hold last state until all
previously removed modules are replaced.
– If adjacent modules are removed and all but one is returned,
the adapter cannot verify the location of the returned
modules. For example, if modules are removed from node s 3
and 4 and only the module from node 4 is returned, the
adapter cannot verify the location. In this case, the adapter
alerts you via a flashing red PointBus status LED that it cannot
verify the presence of modules in the affected locations. I/O
data will not be exchanged with this node until both modules
have been reinserted.
– If modules of different types are removed and returned to
the wrong locations, the adapter identifies the returned
modules and alerts you (via RSNetWorx for DeviceNet) that
the error has occurred and must be corrected.
Publication 1738-UM001A-EN-P - Februa ry 2005
2-6 What Is the ArmorPoint DeviceNet Adapter?
– If modules of the same type are removed and returned to the
wrong locations, the adapter identifies the returned modules,
updates their MACIDs, and continues operation.
IMPORTANT
IMPORTANT
The removal and return scenario ex ists whether the
system is under power or not. If the system is under
power, the scenario arises immediately. If the system
is not under power, the scenario arises in the next
power cycle.
Also, the example above shows removal of two
adjacent modules. The scenario described exists
anytime 2 or more adjacent modules are removed
and all are not returned.
Care must be taken when replacing backplane I/O
modules. Each I/O module stores its configuration
parameters in internal non-volatile memory. You
must either enable ADR for all modules or manually
configure each module in a non-manufacturing
environment when the module is being replaced or
placed on the network for the first time. Failure to do
so could result in inadvertent control attributed to
different configuration settings.
Understand the DeviceNet
Network and Subnet
DeviceNet Network
Your adapter serves as a slave to DeviceNet masters. The adapter
receives data from and returns data to the master through the
following I/O connections:
• Change of State (COS)
• Cyclic
• Polled
• Strobe
Publication 1738-UM001A-EN-P - February 2005
What Is the ArmorPoint DeviceNet Adapter? 2-7
1
Backplane/Subnet Network
On the Backplane/Subnet, your adapter acts as a scanner and is the
master of the Subnet modules. The adapter performs the following
functions:
• Exchanges I/O data with devices on the Backplane/Subnet
• Collects I/O data from the Backplane/Subnet and sends it to
devices on the DeviceNet network (e.g., scanners or controllers)
• Supplies power to the backplane I/O modules (See Appendix A
for power supply rules regarding I/O modules power
requirements.)
Data Collection
The adapter collects I/O data from up to 63 modules via the
Backplane/Subnet. The I/O modules appear on the primary
DeviceNet network as a single node, though, and require only one
DeviceNet node address.
IMPORTANT
If Automatic Device Replacement (ADR) is enabled
on the adapter, you can only connect up to 62
modules via the Subnet.
For more information on ADR, see page 2-15.
Module Power
The adapter supplies 5V logic power to ArmorPoint I/O modules by
converting 24V dc field power to PointBus 5V power.
You can connect up to 63 I/O modules to each adapter and you can
power the backplane I/O modules from the adapter (with a maximum
of 10A of field power). You may use the integrated, isolated 24V dc
expansion power unit (1738-EP24DC) to power additional I/O
modules, as shown below.
738-ADN12 adapter
1738-OB8EM12
1738-IB8M12
1738-ADN12
24V dc In
02
System
Power
Adapter
Power
13
46
57
02
13
MOD
NET
0
1
2
4
3
4
5
5
6
7
DeviceNet Out
Adapter
Status
DeviceNet In
DeviceNet
Status
PointBus
Status
0
0
2
2
8
8
6
6
4
4
x1
x10
PWR
24V dc Out
02
MOD
13
NET
0
1
2
46
3
6
4
5
7
57
6
7
ArmorPoint I/O
modules
1738-OB8EM12
1738-IB8M12
24V dc Out
24V dc In
02
MOD
13
MOD
NET
NET
0
1
2
4
3
6
4
5
7
5
6
7
1738-EP24DC
expansion power unit
1738-IB8M12
24V dc Power Supply
24V dc In
02
MOD
13
NET
0
0
1
1
2
2
46
3
3
4
4
5
5
57
6
6
7
7
ArmorPoint I/O
modules
1738-OB8EM12
1738-EP24DC
24V dc Out
02
MOD
13
NET
0
1
SYSTEM
2
POWER
FIELD
3
4
6
POWER
P
A
O
U
W
X
E
R
4
5
7
5
6
7
02
13
46
57
1738-OB8EM12
1738-IB8M12
24V dc Out
24V dc In
MOD
NET
0
1
2
3
4
5
6
7
02
13
4
5
02
MOD
13
NET
0
1
2
3
6
4
5
7
6
7
1738-IB8M12
24V dc In
46
57
MOD
NET
0
1
2
3
4
5
6
7
1738-OB8EM12
02
13
4
5
24V dc Out
02
MOD
13
NET
0
1
2
3
6
4
5
7
6
7
24V dc In
46
57
24V dc Out
02
MOD
13
MOD
NET
NET
0
0
1
1
2
2
3
4
3
6
4
4
5
5
7
5
6
6
7
7
1738-OB8EM12
1738-IB8M12
43851
For more information on the 1738-EP24DC expansion power unit, see
the ArmorPoint I/O 24V dc Expansion Power Supply Installation
Instructions, publication 1738-IN020.
Publication 1738-UM001A-EN-P - Februa ry 2005
2-8 What Is the ArmorPoint DeviceNet Adapter?
Adapter Features
Your adapter uses the following features on both the DeviceNet
network and the PointBus:
• Self-Test
• Field Upgradable Firmware
• Fully Configurable Software
• Connections
• Baudrates
Self-Test
When power is applied to the adapter, the adapter performs a
self-test. The adapter tests various internal and programmatic
memories and checks the status indicators (LEDs).
Field Upgradable Firmware
You can update the adapter’s firmware with the ControlFlash Utility
software. This feature lets you always use the most current firm ware.
Fully Software Configurable
The adapter is fully software configurable using RSNetWorx for
DeviceNet. You must configure the adapter to be used with a
DeviceNet master (e.g., 1756-DNB) and separately to be used with
Subnet devices.
For more information on how to configure your adapter to use with a
DeviceNet master, see Chapter 5, Add the ArmorPoint DeviceNet
Adapter to the DeviceNet Scanner’s Scanlist.
For more information on how to configure your adapter to use with
Subnet modules, see Chapter 4, Configure the DeviceNet Scanner
Subnet.
Connections
Y o ur adapter supports the following connections on both the primary
DeviceNet network and Subnet:
• I/O connections:
– Polled
– Strobe
– Cyclic
– COS
• Explicit connections
Publication 1738-UM001A-EN-P - February 2005
What Is the ArmorPoint DeviceNet Adapter? 2-9
You can use I/O mapping to determine the data contained in each
connection.
The adapter supports Master/Slave connection types on the DeviceNet
network. On the Subnet, the adapter functions as a scanner device,
exchanging data with I/O modules.
Baudrates
Choose baudrates for the adapter in the RSNetWorx for DeviceNet
software. The adapter supports these rates:
• 125Kbaud
• 250Kbaud
• 500Kbaud
• Autobaud - The adapter detects the primary DeviceNet network
baudrate and automatically sets its own baudrate to match
the network.
• For the 1738-ADN12, -ADN18, and -ADN18P, the Po intBus can
be configured to operate at 1Mbaud (1000Kbaud).
• For the 1738-ADNX, the Subnet can be configured to operate at
125K, 250K, and 500K baud only.
Auto Start Mode
Auto Start Mode lets you easily get your adapter installed and
operating. In this mode, the adapter’s configurable features operate as
they were most recently configured. For example, if Autobaud on
DeviceNet was enabled in the adapter’s last configuration, it will be
enabled when Auto Start Mode is used.
For a more detailed explanation of how to use Auto Start Mode, see
Chapter 3.
Publication 1738-UM001A-EN-P - Februa ry 2005
2-10 What Is the ArmorPoint DeviceNet Adapter?
Auto Catalog Replace
Auto Catalog Replace corrects errors that might occur when backplane
modules of the same type are removed and replaced in the wrong
location. If modules of the same ty pe are removed and returned to th e
wrong locations, the adapter identifies the returned modules, updates
their MAC IDs, and continues operation.
IMPORTANT
If modules of different types are removed and
returned to the wrong locations, the adapter
identifies the returned modules and alerts you (via
RSNetWorx for DeviceNet, the Node Status Table,
and the Faulted Node Table) that the error has
occurred and must be corrected.
EDS parameter Backplane Baudrate is accessible from the primary
DeviceNet and sets a specific baudrate for all backplane I/O modules.
Set this parameter in RSNetWorx for DeviceNet to one of the
following baudrates:
• 125 Kbaud
• 250 Kbaud
• 500 Kbaud
• 1 Mbaud (available for all the ArmorPoint DeviceNet adapters
except the 1738-ADNX)
Publication 1738-UM001A-EN-P - February 2005
When you download this parameter , the adapter sends a command to
reset all present I/O modules on the backplane to the new baudrate.
If additional modules are connected to the adapter, you must
download the Backplane/Subnet Baudrate to make sure the new
modules use the same rate as the others.
What Is the ArmorPoint DeviceNet Adapter? 2-11
The baudrate may not take effect until power is recycled or the I/O
modules are reset.
IMPORTANT
Changes to the Backplane/Subnet Baudrate
parameter only take effect if they are downloaded on
an individual basis. (For example, if you change the
Backplane/Subnet Baudrate and download the
changes with additional changes to other features,
the Backplane/Subnet Baudrate remains at the
previous setting.)
Also, this parameter should be set to ‘Do Nothing’
when you download all parameters or when
Automatic Device Replacement is enabled for
the adapter.
If you want to set an I/O module to use a specific
baudrate (i.e., 125, 250, 500), you must first disable
Backplane Autobaud for that module.
Backplane/Subnet Baudrate performs the following functions:
• Sets the adapter’s Subnet baudrate
• Sends a message to all connected backplane I/O modules. If an
I/O module is set to autobaud, it receives the message but
ignores the new baudrate.
Publication 1738-UM001A-EN-P - Februa ry 2005
2-12 What Is the ArmorPoint DeviceNet Adapter?
Backplane Autobaud
The adapter itself never autobauds on the Subnet. Backplane
Autobaud automatically enables or disables Autobaud for all I/O
modules currently attached to the backplane. The adapter does not set
a specific rate though (as with Backplane Baudrate).
If you enable Backplane Autobaud in the adapter or the EDS
parameter access that you set from the primary DeviceNet, the adapter
only enables the Autobaud in all backplane I/O modules. When the
modules listen to communications on the DeviceNet network, they
detect the rate of communication and auto matically set their own
baudrates to match the network rate.
The module does not automatically detect the backplane baudrate
until power is cycled or the module is reset.
TIP
Autobaud, when enabled, is useful if you swap
ArmorPoint I/O modules between networks that are
operating at different baudrates.
Enable Backplane Baudrate in RSNetWorx for DeviceNet.
IMPORTANT
Changes to the Backplane Autobaud parameter only
take effect if they are downloaded on an individual
basis. (For example, if you enable the Backplane
Autobaud setting and download the change with
additional changes to other features, the Backplane
Baudrate remains disabled.)
This parameter should be set to ‘Do Nothing’ when
you download all parameters or when Automatic
Device Replacement is enabled for the adapter.
If you want to set an I/O module to use a specific
baudrate (i.e., 125, 250, 500), you must first disable
Autobaud for that module.
Publication 1738-UM001A-EN-P - February 2005
What Is the ArmorPoint DeviceNet Adapter? 2-13
Auto Address
The EDS parameter Auto Address is available from the primary
DeviceNet and lets the user sequentially order the node ad dresses of
backplane I/O modules. This parameter is not a mode but occurs on a
single occurrence only. The node address sele cte d is assigned to the
module closest to the adapter. The next closest module is assi gned the
next numerically higher value. The numbering pattern continues for
all connected backplane I/O modules.
Enable this parameter in the RSNetWorx for DeviceNet software.
IMPORTANT
Changes to the Auto Address parameter only take
effect if they are downloaded on an individual basis.
(For example, if you enable the Auto Address and
download the changes with additional changes to
other features, the node addresses of the I/O
modules remains disabled.)
This parameter should be set to ‘Do Nothing’ when
you download all parameters or when Automatic
Device Replacement is enabled for the adapter.
Physical List Acquire Status
The adapter maintains a physical list that indicates the order of the
node addresses of all ArmorPoint I/O modules present on the
backplane. Physical List Acquire Status shows the status of this
physical list acquire process.
The adapter requires that each backplane I/O module has a MACID
greater than that of its neighbor to its immediate left. The list is
created when power is applied to the adapter and each time a module
is inserted on the backplane.
The valid values are:
• Idle
• Busy
• Auto Start Mode
Publication 1738-UM001A-EN-P - Februa ry 2005
2-14 What Is the ArmorPoint DeviceNet Adapter?
Cycling Node Status
Using the Cycling Node Status parameter, you can easily determine
the status of any ArmorPoint I/O modules with which the adapter is
experiencing problems. A corresponding text string appears, including
the MAC ID, and a description of the status code reported in the Node
Status Table. For more information on the Node Status Table,
see page 2-24.
For the connection sizes mentioned below, the I/O connection sizes
on DeviceNet are dependent on the scanlist configuration on the
backplane.
Poll/COS Connection Consume Size
Poll/COS Connection Consume Size shows the size (number of data
bytes) consumed by the poll/COS (Instance 2) I/O connection on the
primary DeviceNet.
Poll Connection Produce Size
Poll Connection Produce Size shows the size (number of data bytes)
produced by the polled (Instance 2) I/O connection on the primary
DeviceNet.
COS/Cyclic Connection Produce Size
COS Produce Size shows the size (number of data bytes) prod uced by
the Change of State I/O connection on the primary DeviceNet.
Strobe Connection Produce Size
The Strobe Produce Size shows the size (number of data bytes)
produced by the Strobe I/O connection on the primary DeviceNet.
Publication 1738-UM001A-EN-P - February 2005
Loading...
+ 104 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.