Rockwell Automation 1738-ADNX User Manual

ArmorPoint I/O DeviceNet Adapters
1738-ADN12, 1738-ADN18, 1738-ADN18P, 1738-ADNX
User Manual

Important User Information

SHOCK HAZARD
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.ab.com/manuals/gi) describes some important differ enc es between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual, when necessary we use notes to make you aware of safety considerations
.
WARNING
IMPORTANT
ATTENTION
BURN HAZARD
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you:
identify a hazard
avoid a hazard
recognize the consequence
Labels may be located on or inside the equipment (e.g., drive or motor) to alert people that dangerous voltage may be present.
Labels may be located on or inside the equipment (e.g., drive or motor) to alert people that surfaces may be dangerous temperatures.

Preface

Purpose of This Manual

This manual describes how to install, configure, and operate your ArmorPoint I/O™ DeviceNet™ Adapters, catalog numbers 1738-ADN12, -ADN18, -ADN18P, and -ADNX.
See the following sections: Page:
Who Should Use This Manual P-2 What the Manual Contains P-2 Related Terms P-3 Related Products and Documentation P-5 Guidelines for Using Your Adapter P-6 Conventions Used in This Manual P-6
IMPORTANT
In this manual, we use ArmorPoint DeviceNet adapters to refer to all the 1738 DeviceNet adapter modules (1738-ADN12, -ADN18, -ADN18P, and
-ADNX). We use the specific catalog number (e.g., 1738-ADNX) to refer to a specific module.
In the rest of this manual (except Chapter 4), we refer to the ArmorPoint I/O DeviceNet adapters as the adapters.

Who Should Use This Manual

In Chapter 4, we refer to the ArmorPoint I/O DeviceNet adapter as the scanner because the chapter describes how to configure the adapter on the subnet.
You must be able to use RSNetWorx for DeviceNet™ software or a similar configuration software to configure your adapter.
In this manual, we assume you know how to configure an ada pte r. If you do not, refer to your software user manuals or online help before attempting to use these adapters.
We also assume you are familiar with the ArmorPoint I/O product line, including other fieldbus interfaces, I/O modules, and power supplies. If you are not familiar with these components, you can read some of the ArmorPoint I/O documents listed in the Related Products and Documentation section.
1 Publication 1738-UM001A-EN-P - February 2005
Preface 2

What the Manual Contains

This manual contains the following sections:
Chapter 1 - Install the ArmorPoint DeviceNet Adapters
Description of how to install and wire the adapter
Chapter 3 - Use Auto Start Mode
Description of how to use the Auto Start Mode on your adapter to quickly get your system up and running
Chapter 2 - What Is the ArmorPoint DeviceNet Adapter?
Overview of the adapter’s features and functionality
1738-ADN12
DeviceNet Out DeviceNet In
Adapter Status DeviceNet Status PointBus
X1
Status
X10
PWR
Or
System Power
R
Adapter Power
Chapter 4 - Configure the DeviceNet Scanner Subnet
Description of how to configure your adapter on the subnet
Chapter 5 - Add the ArmorPoint DeviceNet Adapter to the DeviceNet Scanner’s Scanlist
Description of how to configure the DeviceNet adapter and how to add it to the scanlist
Appendix B - Quick Start
Learning how to use the 1738-ADN12 with a ControlLogix system on DeviceNet
Chapter 6 - Troubleshoot the ArmorPoint DeviceNet Adapter
Description of how to use the status indicators and how to troubleshoot your adapter
Appendix C - 1738-ADNX Rules and Guidelines
Rules and guidelines regarding how to use the 1738-ADNX
Appendix A - Specifications
Listing of the ArmorPoint adapters’ specifications
Appendix D - Default Data Maps
Listing of the default data maps for 1738 ArmorPoint I/O modules
Publication 1738-UM001A-EN-P - February 2005
Preface 3

Related Terms

This manual uses the following terms:
Term: Definition:
Adapter The adapter interfaces between DeviceNet devices and
ArmorPoint I/O modules. ArmorPoint I/O DeviceNet adapters include the 1738-ADN12, -ADN18, -ADN18P, and -ADNX.
Auto Catalog Replace The ArmorPoint I/O DeviceNet adapter supports the swapping
of two identical modules connected to the adapter . That is, if a 1738-IB4M12 is in slot 3 and another 1738-IB4M12 is in slot 7, the two modules can be removed from the ArmorPoint system and the slot 3 module placed into slot 7, and vice-versa. When Automatic Device Replacement (ADR) is active, the swapped modules will be reconfigured to match the previous module in their new slot. When ADR is not active, the configuration parameters will not be modified, the swapped modules must have identical configuration and values for their EDS file parameters.
Auto Device Replacement (ADR)
This refers to the ADR feature of a ControlLogix System on DeviceNet. With ADR active, any device on the DeviceNet link may be removed and replaced with an out-of-the-box checkmark compliant DeviceNet device. The ADR feature will result in downloading the values of the configuration parameters of the EDS file of the removed device to the new device.
Auto Start Mode A feature that lets the ArmorPoint I/O system get “up and
running” without the prerequisite to configure any of the EDS parameters for the PointBus Using Auto Start Mode will result in a scan list within the adapter that stores the modules identity information.
Autobaud A feature in devices (e.g., ArmorPoint I/O modules) on the
DeviceNet network that causes them to listen to communications on the network and set their own baudrate to match the network rate.
Backplane The PointBus that consists of ArmorPoint I/O modules
connected to the ArmorPoint DeviceNet adapter.
Baudrate Rate of communications between devices on the DeviceNet
network. Backplane baudrate is used for the 1738-ADN12,
-ADN18, and -ADN18P. Subnet baudrate is used for the 1738-ADNX.
Change of State (COS) DeviceNet communications method in which the adapter
sends data based on detection of any changed value within the input data. Data is independently received based on a change of state from the sender . Data in both directions can be acknowledged or unacknowledged depending on the run-time configuration of the system.
Commissioning The period in time associated with post startup activities.
Commissioning implies that the system has been validated and all configuration parameters are correct, all modules are in good operating condition, and the adapter scanlist is complete.
ControlFlash™ Utility software you can use to update the adapter’s firmware
with the most current boot and application code.
or ArmorPoint I/O modules.
Publication 1738-UM001A-EN-P - February 2005
Preface 4
Term: Definition:
Cyclic DeviceNet communications method in which the adapter
sends data cyclically based on a configured time value. Data is independently received cyclically from the sender . Data in both directions can be acknowledged or unacknowledged
depending on the run time configuration of the system. MACID Media Access Control Identifier (DeviceNet network address). Master A DeviceNet network device (e.g., 1771-SDN) that initiates
communication with DeviceNet slave devices (e.g.,
ArmorPoint I/O modules) to retrieve data. The master only
receives unprompted data when the slave is enabled for COS
and there is a change in the device’s operating state. Max Backplane MACID The 1738-ADNX has a unique attribute, Max(imum)
Backplane MACID. This value represents the highest node
address of a module residing on the backplane. This value
must be greater than or equal to the right most backplane
ArmorPoint I/O module, but must be less than that of any
non-backplane Subnet module. Offline State of the adapter when it is not powered or maintaining
normal communication exchanges with other DeviceNet
devices. Online State of the adapter when it is powered and maintaining
normal communication exchanges with other DeviceNet
devices. PointBus The ArmorPoint I/O backplane PointBus maintains all
DeviceNet network protocol but also offers configuration
capabilities. Polled DeviceNet communications method in which a module sends
data in response to received data. Primary Network The primary DeviceNet network is defined as the DeviceNet
link that provides the direct connection between the
ArmorPoint DeviceNet adapter and a DeviceNet scanner. RSNetWorx for DeviceNet Configuration software for the adapter and Subnet modules.
Publication 1738-UM001A-EN-P - February 2005
Scanlist The list of Subnet modules connected to the adapter. When
ADR is active, the scanlist stores the configured values of
each of the Subnet modules’ configurable parameters. When
ADR is not active, the scanlist stores only the module identity
information. Scanner Operating state of the ArmorPoint DeviceNet adapter when it
retrieves I/O data from Subnet modules. Slave A DeviceNet network device that cannot initiate
communication (except when configured with COS enabled)
but responds to a DeviceNet master device. Strobe Adapter sends data in response to the strobe command. The
single bit allocated to the adapter in the strobe message is not
used. If the configured size of the input data (sent from the
adapter) is greater than 8 bytes, the strobe connection
establishment will fail. In this case, the input size must be
reconfigure to 8 bytes or less.
Term: Definition:
Subnet 1738-ADNX only.
The Subnet DeviceNet network is defined as the DeviceNet
link that provides the expansion of the PointBus to let the
1738-ADNX use its lower connector to add an additional 500
meters and up to 63 nodes. These nodes will be bridged
through the 1738-ADNX up to the primary network. Note that
backplane modules are also part of the Subnet.
Preface 5
Related Products and
The following table lists related ArmorPoint I/O products and documentation:
Documentation
Description Cat. No. Publication
ArmorPoint 24V dc Output Modules Installation Instructions 1738-OB2E, -OB2EP, -OB4E, -OV4E, -OB8E 1738-IN001 ArmorPoint 24V dc Input Modules Installation Instructions 1738-IB2, IB4, -IV4, -IB8, -IV8 1738-IN002 ArmorPoint 24V dc Analog Input Modules Installation Instructions 1738-IE2C, -IE2V 1738-IN003 ArmorPoint 24V dc Analog Output Modules Installation Instructions 1738-OE2C, -OE2V 1738-IN004 ArmorPoint RTD and Thermocouple Modules Installation Instructions 1738-IR2, -IT2I 1738-IN005 ArmorPoint AC Input Modules Installation Instructions 1738-IA2M12AC3, -IA2M12AC4 1738-IN006 ArmorPoint AC Output Module Installation Instructions 1738-OA2M12AC3 1738-IN007 ArmorPoint Relay Output Modules Installation Instructions 1738-OW4M12, -OW4M12AC 1738-IN008 ArmorPoint RS232 ASCII Module Installation Instructions 1738-232ASCM12 1738-IN009 ArmorPoint RS485 ASCII Module Installation Instructions 1738-485ASCM12 1738-IN010 ArmorPoint 24V dc VHSC Module Installation Instructions 1738-VHSC24M23 1738-IN011 ArmorPoint 5V dc Incremental Encoder Module Installation Instructions 1738-IJM23 1738-IN012 ArmorPoint SSI Module Installation Instructions 1738-SSIM23 1738-IN013 ArmorPoint DeviceNet Adapters Installation Instructions 1738-ADN12, -ADN18, -ADN18P, -ADNX 1738-IN014 ArmorPoint PROFIBUS Adapter Installation Instructions
1738-APB
ArmorPoint PROFIBUS Adapter User Manual 1738-UM002 ArmorPoint ControlNet Adapter Installation Instructions
1738-ACNR
ArmorPoint ControlNet Adapter User Manual 1738-UM003 ArmorPoint EtherNet/IP Adapter Installation Instructions
1738-AENT
ArmorPoint EtherNet/IP Adapter User Manual 1738-UM004 ArmorPoint Extension Units Installation Instructions 1738-EXT1, -EXT3 1738-IN018 ArmorPoint Field Potential Distributor Installation Instructions 1738-FPD 1738-IN019 ArmorPoint I/O 24V dc Expansion Power Supply Installation Instructions 1738-EP24DC 1738-IN020 DeviceNet Media Design & Installation Guide N/A DNET-UM072 Industrial Automation Wiring and Grounding Installation Instructions N/A 1770-4.1
Publication 1738-UM001A-EN-P - February 2005
1738-IN015
1738-IN016
1738-IN017
Preface 6
If you need more information on these products, contact your local Rockwell Automation/Allen-Bradley distributor, integrator or sales office for assistance. For more information on the documentation, refer to the Allen-Bradley Publication Index, publication SD499.

Guidelines for Using Your Adapter

Conventions Used In This Manual

Remember the following operational guidelines when using your ArmorPoint DeviceNet adapter.
Do not leave spaces in the I/O. Instea d, instal l all ArmorPoint I/O modules adjacent to each other.
Populate every position on the mounting base.
ArmorPoint does not support removal and insertion under
power (RIUP). When an I/O module is removed, the IP67 seal is broken and the backplane bus is interrupted.
Use Allen-Bradley terminal markers to identify your ArmorPoint I/O modules.
For more information on the Allen-Bradley terminal marking kits, see the documents list on page
The following conventions are used thro ughout this manual:
bullet lists (such as this one) provide information, not procedural steps
numbered lists provide sequential steps
text written like this identifies screen, menu, toolbar names, field
names, buttons, and check boxes on screens
a menu item in this format File>Save identifies the submenu item after the caret (>) that is accessed from the main menu (name before the caret)
pictures of symbols and/or scre ens represent th e actual symbols you see or the screens you use
Preface-5.
Publication 1738-UM001A-EN-P - February 2005
Install the ArmorPoint DeviceNet Adapters
What Is the ArmorPoint DeviceNet Adapter?

Table Of Contents

Chapter 1
Mount the Adapter and I/O Base. . . . . . . . . . . . . . . . . . . . 1-1
Set the Node Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Wire the DeviceNet Adapters. . . . . . . . . . . . . . . . . . . . . . . 1-3
1738-ADN12 and 1738-ADNX. . . . . . . . . . . . . . . . . . . . 1-3
1738-ADN18 and 1738-ADN18P . . . . . . . . . . . . . . . . . . 1-3
1738 ArmorPoint DeviceNet Auxiliary Power . . . . . . . . 1-4
Chapter Summary and What’s Next . . . . . . . . . . . . . . . . . . 1-4
Chapter 2
Use the Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Set Subnet/Backplane Baudrate . . . . . . . . . . . . . . . . . . 2-3
Set Subnet/Backplane I/O Module Addresses . . . . . . . . 2-3
Configure the Subnet I/O. . . . . . . . . . . . . . . . . . . . . . . 2-3
Configure the Primary DeviceNet Network . . . . . . . . . . 2-4
Remove and Reinsert Modules on the Backplane . . . . . 2-5
Understand the DeviceNet Network and Subnet. . . . . . . . . 2-6
DeviceNet Network . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Backplane/Subnet Network . . . . . . . . . . . . . . . . . . . . . 2-7
Adapter Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Communicate Through the Adapter . . . . . . . . . . . . . . . . . . 2-18
Map the Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18
Overview of the Communication Process . . . . . . . . . . . 2-19
Image Table Mapping . . . . . . . . . . . . . . . . . . . . . . . . . 2-20
Communicate With I/O Modules . . . . . . . . . . . . . . . . . . . . 2-23
Use Diagnostic Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-24
Chapter Summary and What’s Next . . . . . . . . . . . . . . . . . . 2-26
Chapter 3
Use Auto Start Mode
i Publication 1738-UM001A-EN-P - February 2005
Why Use Auto Start Mode? . . . . . . . . . . . . . . . . . . . . . . . . 3-2
What Does Auto Start Mode Do?. . . . . . . . . . . . . . . . . . 3-2
How Is I/O Data Mapped Using Auto Start Mode?. . . . . 3-3
Requirement To Using Auto Start Mode . . . . . . . . . . . . 3-4
Install the I/O Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Remove the Module From the Mounting Base. . . . . . . . 3-5
Use RSNetWorx for DeviceNet. . . . . . . . . . . . . . . . . . . . . . 3-5
Begin Auto Start Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Use Custom Configuration. . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Chapter Summary and What’s Next . . . . . . . . . . . . . . . . . . 3-10
ii
Configure the DeviceNet Scanner Subnet
Add the ArmorPoint DeviceNet Adapter to the DeviceNet Scanner’s Scanlist
Troubleshoot the ArmorPoint DeviceNet Adapter
Chapter 4
Configuration Overview . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Add the Scanner To Your Network. . . . . . . . . . . . . . . . 4-2
Add I/O Modules To Your Network . . . . . . . . . . . . . . . 4-3
Set the Scanner’s Parameters. . . . . . . . . . . . . . . . . . . . . 4-3
Go On Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Chapter Summary and What’s Next . . . . . . . . . . . . . . . . . . 4-8
Chapter 5
Configuration Overview . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Add the Adapter to Your Network . . . . . . . . . . . . . . . . 5-2
Set the Adapter’s Parameters. . . . . . . . . . . . . . . . . . . . . 5-3
Go On Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
Chapter 6
Use the Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Guidelines for Using Your Adapter . . . . . . . . . . . . . . . . . . 6-3
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Specifications
Quick Start For the 1738-ADNX
Rules and Guidelines For the 1738-ADNX
Appendix A
Appendix B
What’s In This Appendix? . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Assumptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Review of the 1738-ADNX Rules and the MACID Parameter B-9
Review of Auto Start Mode. . . . . . . . . . . . . . . . . . . . . B-11
Browse the Subnet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-15
Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . B-19
Navigate Between Networks. . . . . . . . . . . . . . . . . . . . B-24
Appendix C
Publication 1738-UM001A-EN-P - February 2005
Default Data Maps
iii
Appendix D
1738-IA2 Input Module . . . . . . . . . . . . . . . . . . . . . . . . D-2
1738-IB2 Sink Input Module. . . . . . . . . . . . . . . . . . . . . D-2
1738-IB4 Sink Input Module. . . . . . . . . . . . . . . . . . . . . D-2
1738-IB8 Sink Input Module. . . . . . . . . . . . . . . . . . . . . D-3
1738-IV4 Source Input Module . . . . . . . . . . . . . . . . . . . D-3
1738-IV8 Source Input Module . . . . . . . . . . . . . . . . . . . D-3
1738-OA2 Output Module . . . . . . . . . . . . . . . . . . . . . . D-4
1738-OB2E Electronically Protected Output Module . . . D-4
1738-OB2EP Protected Output Module . . . . . . . . . . . . . D-4
1738-OB4E Electronically Protected Output Module . . . D-5
1738-OB8E Electronically Protected Output Module . . . D-5
1738-OV4E Protected Sink Output Module . . . . . . . . . . D-6
1738-OW4 Relay Sink/Source Output Module . . . . . . . . D-6
1738-IE2C Analog Current Input Module. . . . . . . . . . . . D-7
1738-IE2V Analog Input Module. . . . . . . . . . . . . . . . . . D-8
1738-OE2C Analog Current Output Module. . . . . . . . . . D-9
1738-OE2V Analog Output Module. . . . . . . . . . . . . . . . D-9
1738-IJ Encoder/Counter Module . . . . . . . . . . . . . . . . D-10
1738-IR2 RTD Input Module. . . . . . . . . . . . . . . . . . . . D-10
1738-IT2I Isolated Thermocouple Input Module . . . . . D-11
1738-VHSC 24V dc High Speed Counter Module . . . . . D-12
1738-SSI Synchronous Serial Interface Absolute
Encoder Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-12
1738-232ASC ASCII Module . . . . . . . . . . . . . . . . . . . . D-13
1738-485ASC ASCII Module . . . . . . . . . . . . . . . . . . . . D-13
Publication 1738-UM001A-EN-P - February 2005
iv
Publication 1738-UM001A-EN-P - February 2005
Chapter
1.9 in.
2.0 in.
0.87 in.
2.0 in.
0.87 in.
2.0 in.
Drilling Dimension Drawing
1

Install the ArmorPoint DeviceNet Adapters

This chapter describes how to install and wire your adapter.
See the following sections: Page:
Mount the Adapter and I/O Base 1-1 Set the Node Address 1-2 Wire the DeviceNet Adapters 1-3 Chapter Summary and What’s Next 1-4

Mount the Adapter and I/O Base

Adapter
4.02 in. 102 mm
To mount the ArmorPoint adapter on a wall or panel, use the screw holes provided in the adapter.
A mounting illustration for the ArmorPoint adapter with I/O bases is shown below.
47.2 mm
1.81 in. 46 mm
50 mm
22 mm
50 mm
22 mm
Install the mounting base as follows:
1. Lay out the required points as shown in the drilling dimension drawing.
50 mm
43769
2. Drill the necessary holes for #8 (M4) machine or self-tapping screws.
3. Mount the adapter and I/O bases using #8 (M4) screws.
4. Ground the system using the ground lug connection in the I/O
base. (The ground lug connection is also a mounting hole.)
1 Publication 1738-UM001A-EN-P - February 2005
1-2 Install the ArmorPoint DeviceNet Adapters
5. Mount the terminating base that was shipped with the adapter as the last base in the backplane instead of the base that was shipped with the I/O module.
Terminating base
Mounting hole Ground connection

Set the Node Address

Latching mechanism holes
43787
Valid node addresses are 00 through 63.
Set the node address using either the rotary switches, RSNetWorx for DeviceNet, DeviceNetManager, or another software configuration tool. Setting the switches at any number from 64 through 99 lets the software have address control.
Each module is shipped with the switches set for node address 63. Remove the caps on the front of the module to access the switches (refer to the X10 and X1 on the front of the module). The two switches are:
X10 (most significant digit) - left side of module
X1 (least significant digit) - right side of module
This example shows the node address set at 63.
31433-M
Publication 1738-UM001A-EN-P - February 2005
To reset the node addre ss, use a sma ll blade screwdriv er to rotate the switches. Line up the small notch on the switch with the number setting you wish to use and then cycle power.
Install the ArmorPoint DeviceNet Adapters 1-3
M
The rotary switches are read periodically. If the switches have been changed since the last time they were read and th ey no longer match the on line address, a minor fault will occur, which is indicated by a flashing red Adapter Status LED. Settings of 64 through 99 cause the module to use the last valid node address stored internally
. For example, the last setting internal ly was 40. If a change is made to 68, and then you power up, the address will default to 40.
The module is equipped with AutoBaud detect. AutoBaud lets the module read the settings already in use on your DeviceNet network and automatically adjusts to follow those settings.

Wire the DeviceNet Adapters

Following are wiring instructions for the ArmorPoint DeviceNet adapters.
1738-ADN12 and 1738-ADNX
ale In Connector Female Out Connector (1738-ADN12)
(Subnet Out - 1738-ADNX only)
(view into connector) Pin 1 - Drain Pin 2 - +V Pin 3 - -V Pin 4 - CAN_High
43763
Pin 5 - CAN_Low
43764
1738-ADN18 and 1738-ADN18P
Male In Connector Female Out Connector (1738-ADN18P only)
43746
(view into connector) Pin 1 - Drain Pin 2 - +V Pin 3 - -V Pin 4 - CAN_High Pin 5 - CAN_Low
43749
Publication 1738-UM001A-EN-P - February 2005
1-4 Install the ArmorPoint DeviceNet Adapters
1738 ArmorPoint DeviceNet Auxiliary Power
Male In Connector
(view into connector) Pin 1 - User Power + Pin 2 - Adapter Power +
Adapter/Subnet + (1738-ADNX only)
Pin 3 - Adapter Power -
43587
Pin 4 - User Power -
Adapter/Subnet - (1738-ADNX only)

Chapter Summary and What’s Next

ATTENTION
Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP67 requirements.
In this chapter , you learned how to install and wire your DeviceNet adapter. Move to chapter 2 to learn about the ArmorPoint DeviceNet adapters.
Publication 1738-UM001A-EN-P - February 2005
Chapter
2

What Is the ArmorPoint DeviceNet Adapter?

This chapter describes the ArmorPoint I/O DeviceNet adapter, including descriptions of the adapter’s features and functionality.
See the following sections: Page:
Use the Adapter 2-2 Understand the DeviceNet Network and Subnet 2-6 Adapter Features 2-8 Communicate Through the Adapter 2-18 Communicate With I/O Modules 2-23 Use Diagnostic Tables 2-24 Chapter Summary and What’s Next 2-26
1 Publication 1738-UM001A-EN-P - Februa ry 2005
2-2 What Is the ArmorPoint DeviceNet Adapter?

Use the Adapter

The adapter resides on the primary DeviceNet network and the Subnet simultaneously.
The adapter interfaces between DeviceNet devices and ArmorPoint I/O modules. The graphic below shows the adapter on the DeviceNet network and PointBus.
ControlLogix chassis
IMPORTANT
The PointBus maintains all DeviceNet network protocol but also offers configuration capab ilities.
computer with PLC programming software
ControlNet network
1784-PCD PCMCIA card
computer with RSNetWorx for DeviceNet software
DeviceNet network
See page 2-19 for an explanation of the number sequence.
ArmorPoint I/O modules
1738-ADN12 adapter
Subnet (1738-ADNX only)
DeviceNet Out
DeviceNet In
8
x10
PWR
1738-IB8M12
1738-ADN12
0
0
2
2
8
6
6
4
4
x1
Adapter Status DeviceNet Status PointBus Status
System Power
Adapter Power
24V dc In
02
13
46
57
MOD
NET
02
13
0
1 2
3 4 5
6 7
1738-OB8EM12
24V dc Out
MOD
NET
0 1
43852
2 3
4
6
4 5
7
5
6 7
After you have installed your adapter into a ArmorPoint I/O system, you must perform the following tasks:
1. Set Subnet/Backplane Baudrate
2. Set Subnet/Backplane I/O Module Addresses
3. Configure the Subnet I/O
4. Configure the Primary Device Net Network
The steps mentioned above are explained briefly here and then in greater detail throughout this manual. Y ou must complete the steps for the adapter to work with DeviceNet masters (e.g., 1756-DNB) on the primary network and Subnet modules.
Publication 1738-UM001A-EN-P - February 2005
What Is the ArmorPoint DeviceNet Adapter? 2-3
1. Set Subnet/Backplane Baudrate
The adapter and Subnet/Backplane modules must use the same baudrate to communicate with each other. Use one or both of the following to set a Subnet/Backplane baudrate.
Enable or disable the Backplane Autobaud feature for ArmorPoint I/O modules. ArmorPoint I/O modules have Autobaud enabled as the default- See page
Set the adapter baudrate for the Subnet. The default for the 1738-ADN12, -ADN18, and -ADN18P is 1Mbaud. The default for the 1738-ADNX is 125Kbaud - See page
You set the backplane baudrate for the 1738-ADN12, -ADN18, and -ADN18P. You set the Subnet baudrate for the 1738-ADNX.
2-12.
2-9.
2. Set Subnet/Backplane I/O Module Addresses
Once the adapter and ArmorPoint I/O modules are communicating at the same rate on the backplane, you must make sure all modules use a valid MACID.
Set the Auto Address feature for ArmorPoint I/O modules - See page 2-13.
For the 1738-ADNX, a DeviceNet configuration tool, such as RSNetW orx for DeviceNet, may be required to set the node addre ss. (if node address switches are not present on the Subnet device).
3. Configure the Subnet I/O
In the first two steps, you set a consistent communication rate and made sure each module uses valid addresse s for communication. Next you must configure the PointBus (e.g., set scan list).
You can configure the PointBus using one of two methods:
Auto Start Mode (ASM) or
Manually
For more information on configuring the PointBus, see Chapter 3 for ASM or see Chapter 4 for manual configuration.
Publication 1738-UM001A-EN-P - Februa ry 2005
2-4 What Is the ArmorPoint DeviceNet Adapter?
4. Configure the Primary DeviceNet Network
Finally, you must configure the adapter for communication with a master (e.g., 1756-DNB).
For more information on configuring the Devic eNet network, see Chapter 5, Add the ArmorPoint DeviceNet Adapter to the DeviceNet Scanner’s Scanlist.
You must understand all of the adapter’s features to effectively use it in your ArmorPoint I/O system. Keep these four steps in mind as you read this manual:
1. Set Subnet/Backplane Baudrate
2. Set Subnet/Backplane I/O Module Addresses
3. Configure the Subnet I/O
4. Configure the Primary Device Net Network
Publication 1738-UM001A-EN-P - February 2005
What Is the ArmorPoint DeviceNet Adapter? 2-5
Remove and Reinsert Modules on the Backplane
Removal and Insertion Under Power (RIUP) is not recommended in a ArmorPoint System because of the following reasons.
Removing a module breaks the IP 67 seal.
Removing a module breaks the backp lan e bu s. Mod ule s to the
right of the removed module will be ‘lost’ to the adapter. Also, the terminating resistor will be removed, causing system uncertainty.
Inserting a module under power may cause the adjacent module to reset due to the addition of a large capacitive load on the power bus.
IMPORTANT
If the module is removed wh ile it is under power, all the modules to the right of the removed module will disconnect from the PointBus and field power until the module is reinstalled.
If you must remove and reinsert modules, we recommend the following:
Do not move I/O modules to different locations on the mounting base after they have been installed and configured.
If adjacent modules (i.e., 2 or more) are remo ved from the backplane, replace all of them before attempting to operate the ArmorPoint I/O system. Input data will hold last state until all previously removed modules are replaced.
– If adjacent modules are removed and all but one is returned,
the adapter cannot verify the location of the returned modules. For example, if modules are removed from node s 3 and 4 and only the module from node 4 is returned, the adapter cannot verify the location. In this case, the adapter alerts you via a flashing red PointBus status LED that it cannot verify the presence of modules in the affected locations. I/O data will not be exchanged with this node until both modules have been reinserted.
– If modules of different types are removed and returned to
the wrong locations, the adapter identifies the returned modules and alerts you (via RSNetWorx for DeviceNet) that the error has occurred and must be corrected.
Publication 1738-UM001A-EN-P - Februa ry 2005
2-6 What Is the ArmorPoint DeviceNet Adapter?
– If modules of the same type are removed and returned to the
wrong locations, the adapter identifies the returned modules, updates their MACIDs, and continues operation.
IMPORTANT
IMPORTANT
The removal and return scenario ex ists whether the system is under power or not. If the system is under power, the scenario arises immediately. If the system is not under power, the scenario arises in the next power cycle.
Also, the example above shows removal of two adjacent modules. The scenario described exists anytime 2 or more adjacent modules are removed and all are not returned.
Care must be taken when replacing backplane I/O modules. Each I/O module stores its configuration parameters in internal non-volatile memory. You must either enable ADR for all modules or manually configure each module in a non-manufacturing environment when the module is being replaced or placed on the network for the first time. Failure to do so could result in inadvertent control attributed to different configuration settings.

Understand the DeviceNet Network and Subnet

DeviceNet Network
Your adapter serves as a slave to DeviceNet masters. The adapter receives data from and returns data to the master through the following I/O connections:
Change of State (COS)
Cyclic
Polled
Strobe
Publication 1738-UM001A-EN-P - February 2005
What Is the ArmorPoint DeviceNet Adapter? 2-7
1
Backplane/Subnet Network
On the Backplane/Subnet, your adapter acts as a scanner and is the master of the Subnet modules. The adapter performs the following functions:
Exchanges I/O data with devices on the Backplane/Subnet
Collects I/O data from the Backplane/Subnet and sends it to
devices on the DeviceNet network (e.g., scanners or controllers)
Supplies power to the backplane I/O modules (See Appendix A for power supply rules regarding I/O modules power requirements.)
Data Collection
The adapter collects I/O data from up to 63 modules via the Backplane/Subnet. The I/O modules appear on the primary DeviceNet network as a single node, though, and require only one DeviceNet node address.
IMPORTANT
If Automatic Device Replacement (ADR) is enabled on the adapter, you can only connect up to 62 modules via the Subnet.
For more information on ADR, see page 2-15.
Module Power
The adapter supplies 5V logic power to ArmorPoint I/O modules by converting 24V dc field power to PointBus 5V power.
You can connect up to 63 I/O modules to each adapter and you can power the backplane I/O modules from the adapter (with a maximum of 10A of field power). You may use the integrated, isolated 24V dc expansion power unit (1738-EP24DC) to power additional I/O modules, as shown below.
738-ADN12 adapter
1738-OB8EM12
1738-IB8M12
1738-ADN12
24V dc In
02
System Power Adapter Power
13
46
57
02
13
MOD
NET
0
1 2
4
3 4 5
5 6 7
DeviceNet Out
Adapter Status
DeviceNet In
DeviceNet Status PointBus Status
0
0
2
2
8
8
6
6
4
4
x1
x10
PWR
24V dc Out
02
MOD
13
NET
0 1 2
46
3
6
4 5
7
57 6 7
ArmorPoint I/O modules
1738-OB8EM12
1738-IB8M12
24V dc Out
24V dc In
02
MOD
13
MOD
NET
NET
0
1 2
4
3
6 4 5
7
5 6 7
1738-EP24DC expansion power unit
1738-IB8M12
24V dc Power Supply
24V dc In
02
MOD
13
NET
0
0 1
1
2
2
46
3
3
4
4 5
5
57
6
6
7
7
ArmorPoint I/O modules
1738-OB8EM12
1738-EP24DC
24V dc Out
02
MOD
13
NET
0 1
SYSTEM
2
POWER FIELD
3
4
6
POWER
P
A
O
U
W
X
E R
4 5
7
5
6 7
02
13
46
57
1738-OB8EM12
1738-IB8M12
24V dc Out
24V dc In
MOD
NET
0
1 2
3 4 5
6 7
02
13
4
5
02
MOD
13
NET
0 1 2 3
6
4 5
7
6 7
1738-IB8M12
24V dc In
46
57
MOD
NET
0
1 2
3 4 5
6 7
1738-OB8EM12
02
13
4
5
24V dc Out
02
MOD
13
NET
0 1 2 3
6
4 5
7
6 7
24V dc In
46
57
24V dc Out
02
MOD
13
MOD
NET
NET
0
0 1
1
2
2
3
4
3
6
4
4 5
5
7
5
6
6
7
7
1738-OB8EM12
1738-IB8M12
43851
For more information on the 1738-EP24DC expansion power unit, see the ArmorPoint I/O 24V dc Expansion Power Supply Installation Instructions, publication 1738-IN020.
Publication 1738-UM001A-EN-P - Februa ry 2005
2-8 What Is the ArmorPoint DeviceNet Adapter?

Adapter Features

Your adapter uses the following features on both the DeviceNet network and the PointBus:
Self-Test
Field Upgradable Firmware
Fully Configurable Software
Connections
Baudrates
Self-Test
When power is applied to the adapter, the adapter performs a self-test. The adapter tests various internal and programmatic memories and checks the status indicators (LEDs).
Field Upgradable Firmware
You can update the adapter’s firmware with the ControlFlash Utility software. This feature lets you always use the most current firm ware.
Fully Software Configurable
The adapter is fully software configurable using RSNetWorx for DeviceNet. You must configure the adapter to be used with a DeviceNet master (e.g., 1756-DNB) and separately to be used with Subnet devices.
For more information on how to configure your adapter to use with a DeviceNet master, see Chapter 5, Add the ArmorPoint DeviceNet Adapter to the DeviceNet Scanner’s Scanlist.
For more information on how to configure your adapter to use with Subnet modules, see Chapter 4, Configure the DeviceNet Scanner Subnet.
Connections
Y o ur adapter supports the following connections on both the primary DeviceNet network and Subnet:
I/O connections:
PolledStrobeCyclicCOS
Explicit connections
Publication 1738-UM001A-EN-P - February 2005
What Is the ArmorPoint DeviceNet Adapter? 2-9
You can use I/O mapping to determine the data contained in each connection.
The adapter supports Master/Slave connection types on the DeviceNet network. On the Subnet, the adapter functions as a scanner device, exchanging data with I/O modules.
Baudrates
Choose baudrates for the adapter in the RSNetWorx for DeviceNet software. The adapter supports these rates:
125Kbaud
250Kbaud
500Kbaud
Autobaud - The adapter detects the primary DeviceNet network
baudrate and automatically sets its own baudrate to match the network.
For the 1738-ADN12, -ADN18, and -ADN18P, the Po intBus can be configured to operate at 1Mbaud (1000Kbaud).
For the 1738-ADNX, the Subnet can be configured to operate at 125K, 250K, and 500K baud only.
Auto Start Mode
Auto Start Mode lets you easily get your adapter installed and operating. In this mode, the adapter’s configurable features operate as they were most recently configured. For example, if Autobaud on DeviceNet was enabled in the adapter’s last configuration, it will be enabled when Auto Start Mode is used.
For a more detailed explanation of how to use Auto Start Mode, see Chapter 3.
Publication 1738-UM001A-EN-P - Februa ry 2005
2-10 What Is the ArmorPoint DeviceNet Adapter?
Auto Catalog Replace
Auto Catalog Replace corrects errors that might occur when backplane modules of the same type are removed and replaced in the wrong location. If modules of the same ty pe are removed and returned to th e wrong locations, the adapter identifies the returned modules, updates their MAC IDs, and continues operation.
IMPORTANT
If modules of different types are removed and returned to the wrong locations, the adapter identifies the returned modules and alerts you (via RSNetWorx for DeviceNet, the Node Status Table, and the Faulted Node Table) that the error has occurred and must be corrected.
Backplane (1738-ADN12, -ADN18, -ADN18P)/Subnet (1738-ADNX) Baudrate
EDS parameter Backplane Baudrate is accessible from the primary DeviceNet and sets a specific baudrate for all backplane I/O modules.
Set this parameter in RSNetWorx for DeviceNet to one of the following baudrates:
125 Kbaud
250 Kbaud
500 Kbaud
1 Mbaud (available for all the ArmorPoint DeviceNet adapters
except the 1738-ADNX)
Publication 1738-UM001A-EN-P - February 2005
When you download this parameter , the adapter sends a command to reset all present I/O modules on the backplane to the new baudrate. If additional modules are connected to the adapter, you must download the Backplane/Subnet Baudrate to make sure the new modules use the same rate as the others.
What Is the ArmorPoint DeviceNet Adapter? 2-11
The baudrate may not take effect until power is recycled or the I/O modules are reset.
IMPORTANT
Changes to the Backplane/Subnet Baudrate parameter only take effect if they are downloaded on an individual basis. (For example, if you change the Backplane/Subnet Baudrate and download the changes with additional changes to other features, the Backplane/Subnet Baudrate remains at the previous setting.)
Also, this parameter should be set to ‘Do Nothing’ when you download all parameters or when Automatic Device Replacement is enabled for the adapter.
If you want to set an I/O module to use a specific baudrate (i.e., 125, 250, 500), you must first disable Backplane Autobaud for that module.
Backplane/Subnet Baudrate performs the following functions:
Sets the adapter’s Subnet baudrate
Sends a message to all connected backplane I/O modules. If an
I/O module is set to autobaud, it receives the message but ignores the new baudrate.
Publication 1738-UM001A-EN-P - Februa ry 2005
2-12 What Is the ArmorPoint DeviceNet Adapter?
Backplane Autobaud
The adapter itself never autobauds on the Subnet. Backplane Autobaud automatically enables or disables Autobaud for all I/O modules currently attached to the backplane. The adapter does not set a specific rate though (as with Backplane Baudrate).
If you enable Backplane Autobaud in the adapter or the EDS parameter access that you set from the primary DeviceNet, the adapter only enables the Autobaud in all backplane I/O modules. When the modules listen to communications on the DeviceNet network, they detect the rate of communication and auto matically set their own baudrates to match the network rate.
The module does not automatically detect the backplane baudrate until power is cycled or the module is reset.
TIP
Autobaud, when enabled, is useful if you swap ArmorPoint I/O modules between networks that are operating at different baudrates.
Enable Backplane Baudrate in RSNetWorx for DeviceNet.
IMPORTANT
Changes to the Backplane Autobaud parameter only take effect if they are downloaded on an individual basis. (For example, if you enable the Backplane Autobaud setting and download the change with additional changes to other features, the Backplane Baudrate remains disabled.)
This parameter should be set to ‘Do Nothing’ when you download all parameters or when Automatic Device Replacement is enabled for the adapter.
If you want to set an I/O module to use a specific baudrate (i.e., 125, 250, 500), you must first disable Autobaud for that module.
Publication 1738-UM001A-EN-P - February 2005
What Is the ArmorPoint DeviceNet Adapter? 2-13
Auto Address
The EDS parameter Auto Address is available from the primary DeviceNet and lets the user sequentially order the node ad dresses of backplane I/O modules. This parameter is not a mode but occurs on a single occurrence only. The node address sele cte d is assigned to the module closest to the adapter. The next closest module is assi gned the next numerically higher value. The numbering pattern continues for all connected backplane I/O modules.
Enable this parameter in the RSNetWorx for DeviceNet software.
IMPORTANT
Changes to the Auto Address parameter only take effect if they are downloaded on an individual basis. (For example, if you enable the Auto Address and download the changes with additional changes to other features, the node addresses of the I/O modules remains disabled.)
This parameter should be set to ‘Do Nothing’ when you download all parameters or when Automatic Device Replacement is enabled for the adapter.
Physical List Acquire Status
The adapter maintains a physical list that indicates the order of the node addresses of all ArmorPoint I/O modules present on the backplane. Physical List Acquire Status shows the status of this physical list acquire process.
The adapter requires that each backplane I/O module has a MACID greater than that of its neighbor to its immediate left. The list is created when power is applied to the adapter and each time a module is inserted on the backplane.
The valid values are:
Idle
Busy
Auto Start Mode
Publication 1738-UM001A-EN-P - Februa ry 2005
2-14 What Is the ArmorPoint DeviceNet Adapter?
Cycling Node Status
Using the Cycling Node Status parameter, you can easily determine the status of any ArmorPoint I/O modules with which the adapter is experiencing problems. A corresponding text string appears, including the MAC ID, and a description of the status code reported in the Node Status Table. For more information on the Node Status Table, see page 2-24.
For the connection sizes mentioned below, the I/O connection sizes on DeviceNet are dependent on the scanlist configuration on the backplane.
Poll/COS Connection Consume Size
Poll/COS Connection Consume Size shows the size (number of data bytes) consumed by the poll/COS (Instance 2) I/O connection on the primary DeviceNet.
Poll Connection Produce Size
Poll Connection Produce Size shows the size (number of data bytes) produced by the polled (Instance 2) I/O connection on the primary DeviceNet.
COS/Cyclic Connection Produce Size
COS Produce Size shows the size (number of data bytes) prod uced by the Change of State I/O connection on the primary DeviceNet.
Strobe Connection Produce Size
The Strobe Produce Size shows the size (number of data bytes) produced by the Strobe I/O connection on the primary DeviceNet.
Publication 1738-UM001A-EN-P - February 2005
What Is the ArmorPoint DeviceNet Adapter? 2-15
Cycling I/O Mapping
Cycling I/O Mapping is an EDS parameter accessible from the primary DeviceNet that shows you how data is mapped in the adapter’s scanlist. The data, as shown below, is listed in order o f active modules in the scanlist.
The data format is NN OBBB:b-BBB:b,IDBBB:b-BBB:b, where:
NN = node number
O or I = data type (output or input)
BBB = byte number
b = bit number
D = DeviceNet connection (C [COS/cyclic], S [strobe], or P [poll])
IMPORTANT
If an I/O module’s data has multiple mappings, you must use RSNetWorx for DeviceNet to browse to the backplane to view the mappings.
Automatic Device Replacement
With Automatic Device Replacement (ADR), the adapter automatically configures a new replacement module.
IMPORTANT
The replacement module must match the original module (i.e., same vendor I.D., device type, product code, major and minor revision) for ADR to work. The parameters that must match are those selected in the electronic keying portion of the scanlist. You determine the level of electronic keying.
The backplane configuration parameters (e.g., Auto Address) should be set to ‘Do Nothing’.
Publication 1738-UM001A-EN-P - Februa ry 2005
2-16 What Is the ArmorPoint DeviceNet Adapter?
The adapter is capable of holding approximately 64K of configuration data for ArmorPoint I/O modules connected to it. The adapter sends configuration data to an I/O module each time connections are created with that module (i.e., power cycle or module insertion to backplane).
You can exchange an old module for a new one if the following conditions are met:
ADR is enabled in the adapter.
The new module matches the old one (i.e., electronic keying).
The new module is inserted in the proper location (only for
modules using the backplane).
For modules that do not use the backplane, you can exchange an old module for a new one if the following conditions are met:
The MACID equals 63.
The new module matches the electronic keying of the old
module.
Only one missing module matches th e electronic keying of the old module.
If the conditions listed above are met, the new module’s MACID is changed to the appropriate value, if necessary, and the configuration information is subsequently downloaded to the module.
Physical Ordering
When power is applied, or when an I/O module is inserted, the adapter detects the backplane I/O modules’ order, based on MACID. With Physical Ordering, the adapter detects if any ArmorPoint I/O modules connected to it are out of order. If this condition is detected, the adapter changes the MACIDs of any new modules.
IMPORTANT
The adapter’s MACID is always 0 on Subnet. The MACIDs of each attached backplane I/O module must be sequentially ordered (i.e., each module’s MACID is greater than the left adjacent module).
If any backplane I/O modules are missing when power is applied, none of the backplane modules enter run mode.
Publication 1738-UM001A-EN-P - February 2005
What Is the ArmorPoint DeviceNet Adapter? 2-17
Interscan Delay (ISD)
Interscan Delay is the time delay between consecutive I/O scans of polled devices. The default setting is 10ms. The ISD=4ms for Auto Start Mode. You can change this parameter in the Module window of the scanner in the RSNetWorx for DeviceNet software.
The scanner uses this period of time to perform non-time-critical communications on the DeviceNet network, such as communicating with RSNetWorx for DeviceNet software. Setting this parameter to a very low value increases the latency for non-time-critical scanner operations, including the time required to respond to RSLinx software and configuration functions. Setting this parameter to a very large value reduces the freshness of the I/O data being collected by the scanner and is not advisable.
Foreground to Background Poll Ratio
Foreground to Background Poll Ratio is the ratio of foreground to background polls. You can set this parameter in the Module window of the scanner in RSNetWorx for DeviceNet software.
Devices can be polled on every I/O scan (foreground) or they can be polled less frequently (background). Whether a particular device will be polled in the foreground or in the background i s determined by its Poll Rate parameter on the Edit I/O Parameters dialog box, which is accessed from the Scanlist property page.
The poll ratio sets the frequency of poll I/O messages to a device in relation to the number of I/O scans. For example, if the poll ratio is set to 5, the scanner will poll the selected devices once every six I/O scans. We recommend that you use a poll ratio of 1.
Expected Packet Rate
Expected Packet Rate is the rate at which the packets will be expected to be received by the scanner. You set this parameter in the Module window (from the Advanced button) of the scanner in RSNetWorx for DeviceNet software.
IMPORTANT
We recommend that you do not change the Expected Packet Rate unless you are instructed to do so by a Rockwell Automation technical support representative.
Publication 1738-UM001A-EN-P - Februa ry 2005
2-18 What Is the ArmorPoint DeviceNet Adapter?
Transmit Retries
Transmit Retries are the maximum number of times that the scanner will attempt to send an I/O message to a device before it times out and generates an error message. Y ou set this parameter in the Module window (from the Advanced button) of the scanner in RSNetWorx for DeviceNet software.

Communicate Through the Adapter

IMPORTANT
As described previously in this manual, the adapter resides on the DeviceNet network and the PointBus simultaneously. The adapter’s functions are as follows:
DeviceNet – adapter serves as a slave device that exchanges I/O data with another DeviceNet scanner device (e.g., 1771-SDN) via DeviceNet messages
PointBus – adapter serves as master for up to 63 I/O modules, using DeviceNet messages to consume from or produce data to each module
IMPORTANT
W e recommend that you do not change the Transmit Retries unless you are instructed to do so by a Rockwell Automation technical support representative.
.
If Automatic Device Replacement (ADR) is enabled on the adapter, you can only connect up to 62 modules via the PointBus.
Publication 1738-UM001A-EN-P - February 2005
For more information on ADR, see page 2-15.
Map the Data
Your adapter must store data temporarily before transferring it between devices. You must map data to your adapter’s memory before transferring it.
For a detailed description of the mapping process, see page 2-20.
What Is the ArmorPoint DeviceNet Adapter? 2-19
K
K
K
Overview of the Communication Process
In a typical configuration, the adapter acts as an interface between a DeviceNet scanner (e.g., 1756-DNB) and ArmorPoint I/ O mo dules. The following example graphic shows information transferred from a 1756-DNB to ArmorPoint I/O modules.
IMPORTANT
Although information is exchanged between the Logix5555 and 1756-DNB, this diagram (nor this chapter) is not designed to explain such an exchange.
Four data transfers are shown in the diagram, including:
1. Scanner to adapter
2. Adapter to I/O modules
3. I/O modules to adapter
4. Adapter to scanner
Key Points About Scanner to Adapter Transfer (Step 1 )
1. Scanner initiates transfer
2. Scanner uses DeviceNet I/O messaging to write data to adapter.
Data may contain:
device output data
configuration data
ey Points About Adapter to Output Module Transfer (Step 2)
1. Adapter initiates transfer
2. Adapter produces data for I/O module to consume.
Data may contain:
device output data
configuration data
ey Points About Input Module to Adapter Transfer (Step 3)
Adapter consumes data I/O module has produced. Data may contain:
device input data
status data
ey Points About Adapter to Scanner Transfer (Step 4)
SDN consumes I/O data produced by adapter.
1738-ADN adapter
Data may contain:
device input data
status data
computer with PLC programming software
ControlNet network
Logix5555 controller
The Logix5555 controller sits in the backp lane. The 1756-DNB contained in the controller communicates with the ArmorPoint adapter.
1784-PCD PCMCIA card
DeviceNet network
DeviceNet Out
DeviceNet In
8
PWR
1738-IB8M12
1738-ADN12
0
0
2
2
8
6
6
4
4
x1
x10
Adapter Status DeviceNet Status PointBus Status
System Power
Adapter Power
24V dc In
02
13
46
57
MOD
NET
02
13
0
1 2
3 4 5
6 7
1738-OB8EM12
24V dc Out
MOD
NET
0 1 2 3
4
6
4 5
7
5
6 7
ArmorPoint I/O modules
computer with RSNetWorx for DeviceNet software
The computers and PCMCIA card shown in the diagram are required to configure the processor, adapter, and I/O modules.
Although the PCMCIA card is used in this example, you can use other communications cards, such as PCID and KFD cards.
42409
Because the adapter simultaneously resides on the DeviceNet network and on PointBus, it serves as a slave to the processor (i.e., steps 1 and
4) and a master to the I/O modules (i.e., steps 2 and 3).
Publication 1738-UM001A-EN-P - Februa ry 2005
2-20 What Is the ArmorPoint DeviceNet Adapter?
The four data transfers are not necessarily sequential. Transfers 2 and 3 typically occur more frequently than transfers 1 and 4.
Image Table Mapping
Your adapter receives data from:
master devices (e.g., scanners) - output data is then passed to ArmorPoint I/O modules
input modules - input data is passed to the scanner
The adapter must map the data it receives to its internal memory before passing it to the appropriate device. The I/O map for a module is divided into:
read bytes - input and status bytes
write bytes - output and configuration bytes
The data is mapped by 3 buffers for input data (each representing an I/O connection on the primary DeviceNet) and 1 buffer for output data (representing data sent for Poll or COS connections on the primary DeviceNet).
The number of read bytes or write bytes can be 2 or more. The length of each I/O module's read bytes and write bytes vary in size depending on module complexity. Each I/O module suppo rts at least 1 input byte or 1 output byte. Status and configuration are optional, depending on the module.
Publication 1738-UM001A-EN-P - February 2005
What Is the ArmorPoint DeviceNet Adapter? 2-21
The following graphic shows how the adapter maps information.
DeviceNet
Scanner
DeviceNet
ArmorPoint DeviceNet Adapter
DeviceNet Poll Buffer
DeviceNet Strobe Buffer
DeviceNet COS/CYC Buffer
Subnet Modules
INPUT DATA
248 bytes
+ 2 bytes status
6 + 2 bytes
248 bytes
+ 2 bytes status
I/O MAPPING
OUTPUT DATA
Poll OR COS (inst 2)
248 + 2 bytes
Subnet DeviceNet
42406
Publication 1738-UM001A-EN-P - Februa ry 2005
2-22 What Is the ArmorPoint DeviceNet Adapter?
Byte 0
See the I/O Status Word Bit Definitions table for definitions of the first 2 bytes of each I/O message produced by the adapter on DeviceNet.
I/O Status Word Bit Definitions
Bit Operating Mode Operating Mode Description
0 0 = Run mode
1 = Idle mode
1 1 = Device failure (at least one
device failed) 2 1 = Communication failure 3 1 = Duplicate node
address failure 4 Reserved 5 Reserved 6 Reserved
Run - The adapter maps output data to each module on PointBus.
Idle - Output data with zero length is sent to I/O modules.
Device Failure - One or more of the devices in the scanlist has failed to communicate with the adapter.
Communications Failure - The adapter has entered the BUSOFF state on the Subnet. Another Subnet device is configured with the wrong baud rate.
Byte 1
7 Reserved 0 Reserved 1 Reserved 2 Reserved 3 Reserved 4 Reserved 5 Reserved 6 Reserved 7 Reserved
Duplicate Node Address Failure ­There is another node with the same address (0) as the scanner on the Subnet and the adapter has failed its Dup_MAC_ID test.
The first 2 bytes of output data on the DeviceNet network that are sent to the adapter are reserved as a command word. No bits have been defined.
Publication 1738-UM001A-EN-P - February 2005
What Is the ArmorPoint DeviceNet Adapter? 2-23

Communicate With I/O Modules

The adapter module supports multiple communication choices. These choices all use the default I/O structure previously described. The adapter’s master (e.g., 1756-DNB) makes the actual communication choice. The choices are:
Polled – Adapter sends data in response to received data.
Strobe – Adapter sends data in response to the strobe command.
The single bit allocated to the adapter in the strobe message is not used. If the configured size of the input data (sent from the adapter) is greater than 8 bytes, the strobe connection establishment will fail. In this case, the input size must be reconfigured to 8 bytes or less (only 6 bytes are I/O data because the first 2 bytes are the status word).
Change of State – Adapter sends data based on detection of any changed value within the input data. Data is independently received based on change of state from the sender. Data in both directions can be acknowledged or unacknowledged depending on the run time configuration of the system.
Cyclic – Adapter sends data cyclically based on a configured time value. Data is independently received cyclically from the sender. Data in both directions can be acknowledged or unacknowledged depending on the run time con f iguration of the system.
The adapter uses these messages to solicit data from or deliver data to each device. Data received from the devices (i.e., input data) is organized by the adapter and retransmitted to the master. Data received from the master (i.e., output data) is organized in the adapter and sent on to the I/O modules.
Publication 1738-UM001A-EN-P - Februa ry 2005
2-24 What Is the ArmorPoint DeviceNet Adapter?

Use Diagnostic Tables

The adapter maintains three diagnostic tables to manage the flow of data between a processor and a network’s devices. You can access the table over DeviceNet through the Scan Config Object (Class Code 0x90), Instance 1, via the following read-only attributes:
Faulted Node Table (Attribute 0xA) - In this 8-byte table, each bit represents a node on the backplane. For example, bit 0 in byte 0 represents MACID 0 (the adapter), while bit 0 in byte 1 represents MACID 8 and so on. If a bit is set, a correspondin g non-zero status value can be read from the Node State Table described below.
Idle Node Table (Attribute 0xB) - In this 8-byte table, each bit also represents a node on the backplane, as with the Faulted Node Table. If a bit is set in the Idle Node Table, the corresponding node is in the scanlist and currently in idle mode.
Node Status Table (Attribute 0xC) - This 64 byte table contains a status code for each possible MACID on the backplane. Non-zero values are accompanied with the respective bit in the Faulted Node Table being set.
See the table Node Status T able Numeric Code Defi nitions for an explanation of the text messages associated with the Node Status Table.
Node Status Table Numeric Code Definitions
Numeric Code: Text Message: Definition: Take this action:
70 DupMAC Failure Adapter failed Duplicate Node
Address check.
71 Scanner Cfg Error Illegal data in the scan list table. Reconfigure the scan list table and
72 Comm Failure Slave device stopped communicating. Inspect the I/O modules and
73 Wrong Device Type Device’s identity information does not
match electronic key in scan list table entry.
74 Port Overrun Error Data overrun on port detected. Modify your configuration and check for
75 Network Failure Communication has ceased on
the backplane.
76 No Msg for Scanner No direct network traffic for
scanner detected.
An I/O module has a MACID of zero. Change the module’s address.
remove any illegal data.
verify connections. Verify that the correct device is at this
node number. Make sure that the device matches the
desired electronic key (vendor, product code, product type).
invalid data. Check network communication traffic.
Inspect the I/O modules and verify connections.
No action. The scanner hears other network communication.
Publication 1738-UM001A-EN-P - February 2005
What Is the ArmorPoint DeviceNet Adapter? 2-25
Node Status Table Numeric Code Definitions
Numeric Code: Text Message: Definition: Take this action:
77 Wrong Data Size Data size expected by the device does
not match scan list entry.
78 No Such Device Slave device in scan list table does
not exist.
Reconfigure your module for correct transmit and receive data sizes.
Add the device to the network, or delete scan list entry for that device.
79 Transmit Failure Adapter has failed to transmit
a message.
Make sure that other modules exist on the backplane.
80 In Idle Mode Adapter is in IDLE mode. No action necessary.
If you want the adapter to run, put it in RUN mode.
82 Fragmentation Error Error detected in sequence of
fragmented I/O messages from device.
Check scan list table entry for slave device to make sure that input and output data lengths are correct.
Check slave device configuration.
83 Slave Init Error Slave device is returning error
Check accuracy of scan list table entry. responses when scanner attempts to communicate with it.
Check slave device configuration. Slave
device might be in another master’s
scan list.
Reboot slave device.
84 Not Yet Initialized Adapter is initializing the
No action. DeviceNet channel.
85 Rcv Buffer Overflow Data size is larger than 255 bytes. Configure the device for a smaller data
size.
86 Device Went Idle Device is producing zero length data
(idle state) while channel is in
Check device configuration and slave
node status. Run Mode.
89 ADR Failed Failure occurred when downloading
ADR data to the I/O module.
91 Port Bus Off Bus-off condition detected on
communications port.
Reconfigure the ADR download data for
the I/O module.
Check DeviceNet connections and
physical media integrity. Scanner is detecting communications
errors.
92 Port Power Off N o network power detected on
communications port.
Check system for failed slave devices or
other possible sources of network
interference.
Provide network power.
Make sure that scanner drop cable is
providing network power to adapter
communications port.
Publication 1738-UM001A-EN-P - Februa ry 2005
2-26 What Is the ArmorPoint DeviceNet Adapter?
A user program can monitor the Device Failure Bit in the I/O message(s) received from the adapter. When it has determined the bit set, you can read the Faulted Node Table and Node Status Table, using the Explicit Message Program Control Feature of the scanner device, to determine the module experiencing problems and the nature of those problems.

Chapter Summary and What’s Next

In this chapter you learned about the ArmorPoint DeviceNet adapters. Move to Chapter 3 to learn about using Auto Start Mode.
Publication 1738-UM001A-EN-P - February 2005
Chapter

Use Auto Start Mode

This chapter describes how to use the Auto Start Mode with your ArmorPoint I/O DeviceNet adapters.
See the following sections: Page:
Why Use Auto Start Mode? 3-2 Install the I/O Module 3-4 Use RSNetWorx for DeviceNet 3-5 Begin Auto Start Mode 3-7 Use Custom Configuration 3-9 Chapter Summary and What’s Next 3-10
3
1. Install the I/O Module
DeviceNet Out DeviceNet In
X10
PWR
X1
R
1738-ADN12
Adapter Status
DeviceNet Status
PointBus Status
System Power
Adapter Power
Add and Commission
Non-Backplane I/O
Modules to the Subnet
43785
This chapter assumes you already have an ArmorPoint system mounted. There are five simple steps to the Auto Start Mode:
2. Wire the DeviceNet Adapters 3. Install the I/O Module
1738-OB8EM12/A
24V dc Out
2
0
MOD
3
1
NET
0 1 2 3
6
4
43763
5. Use RSNetWorx
5. Begin Auto Start Mode4. 1738-ADNX Only
4
5
7
5
6 7
43771
for DeviceNet
1 Publication 1738-UM001A-EN-P - February 2005
3-2 Use Auto Start Mode

Why Use Auto Start Mode?

Auto Start Mode offers you a quick and easy method of getting your ArmorPoint I/O system ‘up and running’. If your ArmorPoint I/O application can use default configuration, you should use Auto Start Mode to easily begin operations.
Once your adapter is:
installed
connected to the system’s I/O modules
online (in RSNetWorx for DeviceNet)
you only need to choose the Auto Start Mode option in the adapter’s Parameters window in the RSNetW orx for DeviceNet software and the adapter begins working with a default configuration.
IMPORTANT
Although Auto Start Mode allows your adapter to operate with a default configuration, you can write a custom configuration after operation has begun.
For more information on how to write custom configuration for your adapter on DeviceNet, see Chapter 5, Add the ArmorPoint DeviceNet Adapter to the DeviceNet Scanner’s Scanlist.
What Does Auto Start Mode Do?
When using Auto Start Mode, the adapter:
1. Sets all modules on the backplane to Auto Baud
2. Reads the Subnet module’s identity information
3. Sets backplane modules’ addresses sequentially
4. Generates a scanlist for the Subnet
5. Maps I/O data, based on byte, word, double-word, or fixed
boundaries
When this sequence of events is completed, the ArmorPoint I/O modules connected to the adapter are ready to accept connections from a scanner.
Publication 1738-UM001A-EN-P - February 2005
Use Auto Start Mode 3-3
How Is I/O Data Mapped Using Auto Start Mode?
In Auto Start Mode, you can map I/O data in the adapter’s memory i n one of the following ways:
Byte Boundaries
Word Boundaries
Double Word Boundaries
Fixed Boundaries
Byte Boundaries
Each node’s I/O data is mapped in the adapter’s memory at the next available byte. This option works best in applications that use Allen-Bradley PLCs and SLCs.
Word Boundaries
Each node’s I/O data is mapped in the adapter’s memory at the next available word. This option works best in applications that use Allen-Bradley PLCs and SLCs.
Double Word Boundaries
Each node’s I/O data is mapped in the adapter’s memory at the next available double word. This option works best in applications that use Allen-Bradley Logix products.
Fixed Boundaries
The map to the fixed location is based on the node add ress. Mapping size ranges from 1 to 32 and is set using an EDS parameter. The mapping for a node with address 1 begins on byte 2. The formula for mapping is: 2+((N-1)(mapsize)), where N = node address.
Keep the following in mind when using fixed boundaries:
You specify fixed map size using EDS parameters
Data is mapped after status/channel words in I/O image,
beginning with byte 2
No data area is reserved for MACID 0 (the adapter)
Publication 1738-UM001A-EN-P - February 2005
3-4 Use Auto Start Mode
Requirement To Using Auto Start Mode
Your ArmorPoint DeviceNet adapter must be free of I/O co nnections on DeviceNet when you use Auto Start Mode. If you attempt to use Auto Start Mode after another scanner device has established I/O connections with the adapter, your attempt to use Auto Start Mode will be rejected. When the adapter is configuring itself in Auto Start Mode, no other device can establish I/O connections to the adapter.

Install the I/O Module

To install the module:
1. Using a bladed screwdriver, rotate the keyswitch on the mounting base clockwise until the correct number for the I/O module aligns with the notch in the base. (See the individual ArmorPoint I/O module installation instructions for this number.)
2. Position the module vertically above the mounting base. The module will bridge two bases.
Module will bridge two bases.
1738-OB8EM12/A
24V dc Out
0
1
2
MOD
3
NET
0 1
2 3
6
4
5
4 5
7
6 7
Publication 1738-UM001A-EN-P - February 2005
43771
3. Push the module down until it engages the latching mechanism. You will hear a clicking sound when the module is properly engaged.
The locking mechanism will lock the module to the base.
Use Auto Start Mode 3-5
Remove the Module From the Mounting Base
To remove the module from the mounting base:
1. Put a flat blade screwdriver into the slot of the orange latching mechanism.
2. Push the screwdriver toward the I/O module to disengage the latch.
The module will lift up off the base.
3. Pull the module off of the base.
For more information on installing and wiring the multiple ArmorPoint I/O modules, see the installation instructions for each catalog number.

Use RSNetWorx for DeviceNet

You must use the RSNetWorx for DeviceNet software to configure your adapter.
If you are using a 1738-ADNX adapter, make sure that you properly configure non-backplane modules for baudrate and MACID.
Follow the steps below to use Auto Start Mode.
1. Go online in the software.
IMPORTANT
A.Click on the Network
pull-down menu.
B.Choose Online.
2. Once you are online, browse for the primary network (e.g., You can use Single Pass Browse).
Auto Start Mode is only available when RSNetWorx for DeviceNet is online.
A.Click on the Network
pull-down menu.
B.Choose a Browse type.
Publication 1738-UM001A-EN-P - February 2005
3-6 Use Auto Start Mode
3. Click OK to synchronize your offline and online configuration.
The adapter appears on the screen.
4. Double click on the adapter icon.
Double click on this icon.
You can either:
Upload configuration from the device to update the software
Download configuration from the software to the device
5. Click Yes to upload configuration from the device.
Publication 1738-UM001A-EN-P - February 2005
Use Auto Start Mode 3-7

Begin Auto Start Mode

After you upload the configuration from the device to the software, begin Auto Start Mode (ASM).
1. Double click on the adapter icon to open the adapter properties window.
2. Click on the Parameters tab.
3. Click on the right side of the Auto Start Mode line so that a
menu appears.
A.Click on the
Parameters window.
B.Use the Auto Start
Mode pull-down menu to choose a mapping option. The options are described on page 3-3.
4. Download the Auto Start Mode value. Make sure you only download this single value, as shown below.
A.Choose Single Value.
After 30-40 seconds, the adapter be gins operations and uses the configuration most recently applied. During the Auto Start Mode process, the Physical List Ac qui re Status field displays the words: Auto Start Mode, but after the download is complete the field displays the word Idle.
Check for solid red indicators on all modules
Verify that all non-backplane modules have the proper baudrate
(or have autobaud enabled)
B.Download the value.
Publication 1738-UM001A-EN-P - February 2005
3-8 Use Auto Start Mode
Check that MACIDs are set to proper values
Check scanlist
browse to Subnet and view scanlist, or look at mapping textMake sure the scanlist was saved (if not, investigate why?)If you are using the 1738-ADNX adapter, check the
Max(imum) Backplane MACID parameter. It should equal the number of modules residing on the backplane.
After ASM has completed (that is, Physical List Acquire Sta tus field is Idle), verify that the operation was successful and that each I/O module was added to the adapter’s scanlist. The PointBus Status LED should be solid green. This indicates only that the adapter is able to establish I/O connections with each module in its scanlist, not that each module on the Subnet was successfully added to its scanlist.
To verify the presence of each module in the adapter’s scanlist, perform one of the following checks:
Each I/O module’s NET LED should be solid green. If the device has neither LED, use one of the following methods.
– By browsing to the Subne t and uploading the adapter’s
scanlist using RSNetW orx for DeviceNet and verifying that the device is found in the scanlist.
By repeatedly uploading the EDS parameter Cycling I/O
Mapping to verify that a mapping for the concerned module
exists. See page
2-15 for more information about this
parameter. If one of the following is observed, it is likely that one of the
Subnet modules has been addressed incorrectly or is configured to communicate at the wrong baud rate.
The adapter’s PointBus Status LED is solid or blinking red
An I/O module’s NET LED is solid red
It appears that the adapter has not saved a scanlist
Publication 1738-UM001A-EN-P - February 2005
Use Auto Start Mode 3-9
Use the following procedures to attempt to remedy a problem:
Verify tha t each non- backplane module’s address and baudrate have been set correctly.
Verify that each backplane module is configured to autobaud. The adapter’s EDS parameter Set Backplane Autobaud can be used to set each module’s autobaud parameter. It is necessary to cycle a module’s power before the autobaud parameter change takes effect. In rare situations, it may be nece ssary to download the parameter and cycle power several times before each backplane module’s autobaud parameter has been changed.
Note that if the adapter is configured to autobaud on the primary DeviceNet network, network traffic on the primary network is required before the backplane modules will attempt to communicate. For this reason, it is sometimes helpful to have RSLinx continuously browsing the primary network while attempting the ASM process and verification.

Use Custom Configuration

When it is believed that each non-backplane module is co rrectly configured and that each backplane module is able to communicate on the Subnet, the ASM process can be attempted again.
After successfully configuring your adapter with the Auto Start Mode feature, the adapter must still be added to the primary DeviceNet network scanner’s scanlist. See Chapter 5 for more information.
The Auto Start Mode is recommended to quickly and easily get your ArmorPoint I/O system ‘up and running’. But this mode does not prevent you from changing the adapter’s default configuration after system operation has begun.
For more information on how to write custom configuration for your adapter on DeviceNet, see Chapter 4, Configure the DeviceNet Scanner Subnet and Chapter 5, Add the ArmorPoint DeviceNet Adapter to the DeviceNet Scanner’s Scanlist.
IMPORTANT
The adapter’s ADR configuration for the Subnet modules is reset when you run Auto Start Mode.
Publication 1738-UM001A-EN-P - February 2005
3-10 Use Auto Start Mode

Chapter Summary and What’s Next

Auto Start Mode was discussed in this chapter. Move on to Chapter 4, Configure the DeviceNet Scanner Subnet or to Chapter 5, Add the ArmorPoint DeviceNet Adapter to the DeviceNet Scanner’s Scanlist.
Publication 1738-UM001A-EN-P - February 2005
Chapter
4

Configure the DeviceNet Scanner Subnet

This chapter describes how to custom configure your scanner for use with ArmorPoint I/O modules.
See the following sections: Page:
Configuration Overview 4-1 Add the Scanner To Your Network 4-2 Add I/O Modules To Your Network 4-3 Set the Scanner’s Parameters 4-3 Go On Line 4-8 Chapter Summary and What’s Next 4-8

Configuration Overview

Your adapter works on two networks simultaneously and must be configured for each separately. This chapter explains con figuration of the scanner for use with ArmorPoint I/O modules.
For information on how to configure the adapter for use on the DeviceNet Network see Chapter 5, Adding the DeviceNet adapters to the DeviceNet Scanner’s Scanlist.
You must use the RSNetWorx for DeviceNet software to configure your scanner. You can configure the scanner while it is:
on line
off line
This chapter shows configuration in the offline mode. Configuration screens appear the same in both modes. Note that some screen options are unavailable in offline mode. The only difference is that if you make changes off line, you must take the scanner on line before the configuration changes take effect.
IMPORTANT
1 Publication 1738-UM001A-EN-P - February 2005
Throughout most of this manual, we refer to the ArmorPoint I/O DeviceNet adapter as the adapter. The adapter also communicates with Subnet modules as a scanner. In this chapter only, the adapter is referred to as a scanner.
4-2 Configure the DeviceNet Scanner Subnet
You must follow these steps during configuration:
1. Add the scanner to your network
2. Add I/O modules to your network
3. Set the scanner’s parameters
4. Go on line
Add the Scanner To Your Network
Follow these steps:
1. Start RSNetWorx for DeviceNet.
2. Add the scanner as shown below.
1. Expand the list of communication adapters.
2. Select the 1738-ADN12 ArmorPoint Scanner.
IMPORTANT
3
The scanner appears on the network.
The scanner must always exist on the Subnet at Node 00.
Publication 1738-UM001A-EN-P - February 2005
1. Expand the Category to display the list of I/O modules.
Configure the DeviceNet Scanner Subnet 4-3
Add I/O Modules To Your Network
After you add the scanner, you must add the modules connected to the scanner on the Subnet. In the offline mode, I/O modules must be added individually. Follow these steps:
1. Add modules as shown below.
NOTE: Make sure you check under all the categories that I/O modules reside (i.e.,
General Purpose Discrete I/O, Rockwell Automation miscellaneous, and Specialty I/O).
2. Double-click the I/O module you
want to add to the network.
TIP: You can also click and drag the
module name onto the network.
We used the 1738-IB4M12,
-OB4EM12, and -IE2CM12 I/O modules in this example. Your netwo rk screen should reflect the I/O modules on your network.
Set the Scanner’s Parameters
After adding the scanner to the network, you must configure it for use with I/O modules.
IMPORTANT
This chapter shows configuration in the of f li ne mode. Changes set in this mode do not take effect until the scanner goes on line. For more information on how to go on line, see page 4-8.
1. Right-click on the scanner.
2. Click on Properties... to
configure your scanner.
1. Configure the scanner as shown below.
TIP: You can also double
click on the scanner to view the Properties window.
A window will open with a series of tabs along the top. Each tab opens to a window that provides options to write configuration for your scanner. These wind ows are sh own on the following pages.
Publication 1738-UM001A-EN-P - February 2005
4-4 Configure the DeviceNet Scanner Subnet
e s
General window
Type the scanner’s name here. Type a description here (optional).
The scanner’s address must = 0.
This window also shows the scanner’s device identity. These fields are read-only.
Device Bridging window
Use Associate File to associate this configuration file with the configuration file that configures the same 1738 ArmorPoint DeviceNet scanner (called adapter on the primary network) for communication with a master device on the primary DeviceNet network.
For more information on the need to maintain two configuration files in the same adapter and the simultaneous presence of the adapter on two networks (i.e., DeviceNet as a slave and PointBus as a master), see page 4-1.
Click OK to accept the parameters. IMPORTANT: Configuration changes mad
in offline mode do not take effect until the scanner goe on line. For more information on how the scanner goes on line, see page 4-8.
Use Clear Association to remove previously established configuration file associations that no longer apply to your scanner.
Publication 1738-UM001A-EN-P - February 2005
Module window
Set the Interscan Delay here.
Set the Foreground to Background Poll Ratio here.
Configure the DeviceNet Scanner Subnet 4-5
Click here to reset the Interscan Delay and Foreground to Background Poll Ratio back to the module default values.
Click Advanced to change the advanced module settings, as shown in the following window.
Advanced window accessed from Module window
We recommend you DO NOT change module settings unless advised to do so by a Rockwell Automation support representa tive.
Scanlist window
Add and remove I/O modules to and from the scanlist on this screen.
To set any of the parameters on this screen (e.g., Node Active) for a specific module, first add the module to the scanlist and then highlight the module to make specific changes.
Click Automap on Add so a checkmark appears to automap I/O data when adding modules.
Click Edit I/O Parameters to edit the module’s I/O parameters, as shown below.
Set the Expected Packet Rate here.
Set the number of Transmit Retries here.
Click OK to accept new settings.
Add modules to or remove modules from the scanlist.
Choose Electronic Key parameters for each module.
Edit I/O Parameters window accessed from Scanlist window
Click OK when finished.
Click on the appropriate I/O data transmission method (e.g., Polled) and make other appropriate I/O parameter changes on this screen.
Publication 1738-UM001A-EN-P - February 2005
4-6 Configure the DeviceNet Scanner Subnet
t
Input window
Use this pull-down menu to choose a Memory type.
The memory type corresponds to an I/O connections on DeviceNet.
Advanced Mapping window accessed from Input window
Set Map From parameters here.
Click Apply Mapping to apply changes and leave the screen open.
Click Close when finished.
Set Map To parameters here.
Highlight a module and click Unmap to unmap it.
Click Advanced to edit the advanced mapping parameters, as shown below.
Click Options to edit the automap options, as shown below.
Set the starting byte for I/O mapping.
Automap Options window accessed from Input window
Choose a
Data Alignmen
and click
OK.
Output window
Use this pull-down menu to choose a memory type. This corresponds to I/O on the primary DeviceNet.
Set the starting byte for I/O mapping here.
The bytes mapped last will determine sizes on the primary DeviceNet.
Highlight a module and click Unmap to unmap it.
Click Advanced to edit the advanced mapping parameters.
Click Options to edit the automap options.
Note that the Advanced Mapping and Options windows are the same for output modules as those sh own for input modules. See above for an explanation of these windows.
Publication 1738-UM001A-EN-P - February 2005
ADR window
Use this screen to choose Automatic Device Replacement options.
Configure the DeviceNet Scanner Subnet 4-7
Following are the remaining configuration windows.
You must have loaded each device into RSNetWorx for DeviceNet before you can Load Device Config using this button.
Summary window
IMPORTANT: You cannot change any
configuration parameters on this screen. It is for information purposes only. These buttons do not apply for this window but are here to maintain consistency among the windows.
This completes the configuration options. Your scanner must go on line for configuration changes to take effect.
Publication 1738-UM001A-EN-P - February 2005
4-8 Configure the DeviceNet Scanner Subnet
1. Click on Network.
2. Click on Online.
Go On Line
After you set configuration parameters, your scanner must go on line to accept the configuration changes. Follow these steps:
1. Use the Network pulldown to go on line.
The software prompts you to save your configuration changes.
Click Yes.
Select the DeviceNet network subnetwork.
This selection accesses the PointBus to configure the adapter on the DeviceNet network.
2. Choose your scanner’s network and apply the changes, as shown below.
Click OK to apply the data to your scanner.

Chapter Summary and What’s Next

Publication 1738-UM001A-EN-P - February 2005
In this chapter, you learned how to configure the scanner. Move to Chapter 5 to learn how to add the ArmorPoint DeviceNet adapter to the DeviceNet scanner’s scanlist.
Chapter
5

Add the ArmorPoint DeviceNet Adapter to the DeviceNet Scanner’s Scanlist

This chapter describes how to custom configure your adapter for use with DeviceNet devices.
See the following sections: Page:
Configuration Overview 5-1 Add the Adapter to Your Network 5-2 Set the Adapter’s Parameters 5-3 Go On Line 5-6 Chapter Summary 5-6

Configuration Overview

Your adapter works on two networks simultaneously and must be configured for each separately, which means that you will have two separate RSNetWor x for DeviceNet software files.
This chapter explains configuration of the adapter for use on the primary DeviceNet network. For information on how to configure the adapter for use on the Subnet, see Chapter 4, Configure the DeviceNet Scanner Subnet.
You must use the RSNetWorx for DeviceNet software to configure your adapter. You can configure the adapter while it is:
on line
off line
This chapter shows configuration in the offline mode. Configuration screens appear the same in both modes. Note that some screen options are unavailable in offline mode. The only difference is that if you make changes off line, you must take the adapter on line before the configuration changes take effect.
1 Publication 1738-UM001A-EN-P - February 2005
5-2 Add the ArmorPoint DeviceNet Adapter to the DeviceNet Scanner’ s Scanlist
You must follow these steps during configuration:
1. Add the adapter to your network
2. Set the adapter’s parameters
3. Add the DeviceNet adapter’s scanlist (see the Quick Start,
Appendix B)
4. Go on line
Add the Adapter to Your Network
Follow these steps:
1. Start the RSNetWorx for DeviceNet software.
1. Expand the list of communication adapters.
2. To add the adapter, you can double click on the adapter or click and drag the adapter name onto the network.
2. Add the adapter as shown below.
3
The adapter appears on the network.
Publication 1738-UM001A-EN-P - February 2005
Add the ArmorPoint DeviceNet Adapter to the DeviceNet Scanner’s Scanlist 5-3
Set the Adapter’s Parameters
After adding the adapter to the network, you must configure it for use with master DeviceNet devices.
1. Right-click on the adapter.
2. Click on Properties to
configure your adapter.
IMPORTANT
This chapter shows configuration in the offline mode. Changes set in this mode do not take effect immediately. For configuration changes to take place, you must:
go on line with your adapter
download the new configuration to your adapter
For more information on how to go on line, see page 5-6.
1. Configure the adapter as shown below.
TIP: You can also double click on the adap ter
to view the Properties menus.
General window
Type the adapter’s name here.
Ty pe a description here (optional).
Select the desired address. This address corresponds to the address switch on the adapter.
This screen shows the adapter’s device identity. These f ie lds are read-only.
You see a window with a series of tabs. Each tab opens to a window that provides options to write configuration for your adapter. The tabs are shown on the following pages.
Publication 1738-UM001A-EN-P - February 2005
5-4 Add the ArmorPoint DeviceNet Adapter to the DeviceNet Scanner’ s Scanlist
Device Bridging window
Use Associate File to associate this configuration file with the configuration file that configures the same ArmorPoint DeviceNet scanner for communication with ArmorPoint I/O modules.
For more information on the need to maintain two configuration files in the same adapter and the simultaneous presence of the adapter on two networks (i.e., DeviceNet as a slave and Subnet as a master), see page 5-1.
Use Clear Association to remove previously established configuration file associations that no longer apply to your adapter.
Parameters window
Restore all parameter default values.
For a description of a specific parameter, highlight the parameter below and click here.
Any parameter with a lock shown before it cannot be changed.
The values correspond to the I/O connection sizes from the I/O Data window. They can be uploaded from an adapter with a downloaded scanlist.
The following screens show how to change the other parameters.
AutoAddress
Enable or disable autoaddress.
Auto Start Mode
IMPORTANT: The following
configuration parameters:
Auto Start Mode
Set Backplane Baudrate
Set Backplane Autobaud
AutoAddress Backplane
Modules
should only be used when on line and should be set to Do Nothing when Download All Parameters is selected or when saving to a scanner’s ADR data.
Note: The parameters Max Backplane MACID and Fixed Map Size are found only in the 1738-ADNX Parameters window.
Backplane Baudrate
Set the backplane baudrate.
Backplane Autobaud
Configure backplane modules to autobaud.
Publication 1738-UM001A-EN-P - February 2005
AutoAddress Backplane Modules
Choose the autoaddress.
I/O Data window
Add the ArmorPoint DeviceNet Adapter to the DeviceNet Scanner’s Scanlist 5-5
The following screens show the remaining configuration windows.
Connection sizes appear only when the Subnet network file has been associated in the Device Bridging window.
These values correspond to the 4 parameters (Poll/COS Connection Consume Size, Poll
Connection Produce Size, COS Connection Produce Size, Strobe Connection Produce Size) found in the device’s Parameters
window.
EDS File window
Click here to view the EDS file. An example of the EDS file is shown below.
The window below shows an example EDS file.
This completes the configuration options. Your adapter must go on line for the configuration to take effect.
Publication 1738-UM001A-EN-P - February 2005
5-6 Add the ArmorPoint DeviceNet Adapter to the DeviceNet Scanner’ s Scanlist
Go On Line
Follow these steps for the adapter to go on line:
1. Use the Network pulldown.
1. Click on Network.
2. Click on Online.
The software prompts you to save your configuration changes.
Click Yes.
Select the DeviceNet network. This selection accesses the PointBus
to configure the adapter on the DeviceNet network.
2. Choose your adapter’s network as shown below.
Click OK to apply the data to your adapter.
To learn how to add the ArmorPoint DeviceNet adapter to the scanner’s scanlist, refer to the Quick Start section, Appendix B.

Chapter Summary

Publication 1738-UM001A-EN-P - February 2005
In this chapter, you learned how to configure the adapter.
Chapter
6

Use the Status Indicators

Troubleshoot the ArmorPoint DeviceNet Adapter

This chapter describes how to troubleshoot your adapter.
See the following sections: See page:
Use the Status Indicators 6-1 Guidelines for Using Your Adapter 6-3 Chapter Summary 6-3
You can use the status indicators to troubleshoot your adapter. The following graphic shows the adapter’s status indicators.
1738-ADN12
DeviceNet Out
DeviceNet In
X10
PWR
X1
R
Use the table below to troubleshoot your adapter
Indication Indication Probable Cause Adapter Status Off No power applied to device.
Green Device is operating normally. Flashing Red Recoverable fault.
1738-ADN12
Adapter Status
DeviceNet Status
PointBus Status
System Power
Adapter Power
Adapter Status Indicator
DeviceNet Status Indicator PointBus Status Indicator
System Power Indicator Adapter Power Indicator
43785
Red Unrecoverable fault - may require device replacement. Flashing Red/Green Device is in self-test.
1 Publication 1738-UM001A-EN-P - February 2005
6-2 Troubleshoot the ArmorPoint DeviceNet Adapter
Indication Indication Probable Cause DeviceNet Status Off Device is not on line:
Flashing Green Device is on line but has no connections in the established state. Green Device is on line and has connections in the established state. Flashing Red One or more I/O connection in timed-out state. Red Critical link failure - failed communication device. Device
PointBus Status Off Device is not on line:
Flashing Green Device is on line but has no connections in the established state. Green Device is on line and has connections in the established state. Flashing Red One or more I/O connection in timed-out state.
- Device attempting to AutoBaud
- Device has not completed dup_MAC_ID test
- Device not powered - check module status indicator.
detected error that prevents it from communicating on the network. (Possible duplicate MACID or baud rate mismatch).
- Device has not completed dup_MAC_ID test
- Device not powered - check module status indicator.
Red Critical link failure - failed communication device. Device
detected error that prevents it from communicating on the network. (Possible duplicate MACID or baud rate mismatch).
Flashing Red/Green Communication faulted device - the device has detected a
network access error and is in communication faulted state. Device has received and accepted an Identify Communication Faulted Request - long protocol message.
PointBus Status (1738-ADNX only)
Off No power applied to device.
Device not on line
Device has not completed dup_MAC_ID test. Green Subnet on line and has connections in the established state. Flashing Red Recoverable fault:
- No scanlist configured
- Problem with module in scanlist (missing, mismatch, etc.).
Red Unrecoverable fault may require device replacement
(Possible duplicate MACID or baud rate mismatch.)
System Power Off Not active - Field power is off or dc-dc-converter problem.
Green System power on - dc-dc converter active (5V).
Adapter Power Off Not active - Field power is off.
Green Power on, 24V present.
Publication 1738-UM001A-EN-P - February 2005
Troubleshoot the ArmorPoint DeviceNet Adapter 6-3

Guidelines for Using Your Adapter

Remember the following operational guidelines when using your ArmorPoint DeviceNet adapter.
Do not leave spaces in the I/O. Instead, install all ArmorPoint I/O modules adjacent to each other.
Populate every position on the mounting base.
Do not add new I/O modules to the end of the ArmorPoint I/O
system while the system is under power.
Use labels with the I/O mo dules.
Do not move I/O modules to different locations on the
mounting base after they have been installed and configured.
If adjacent modules (i.e., 2 or more) are removed, replace all of them to operate the ArmorPoint I/O system. Input data will hold last state until all previously removed module s are replaced.
Use Allen-Bradley marker cards to identify your ArmorPoint I/O modules. The cards are easily ordered from your Rockwell Automation representative under the Bulletin 1492 number.

Chapter Summary

Properly terminate the 1738-ADNX Subnet at the end s of the Subnet trunk line.
Correctly set the Max Backplane MACID (1738-ADNX only).
In this chapter you learned how to troubleshoot your adapter.
Publication 1738-UM001A-EN-P - February 2005
6-4 Troubleshoot the ArmorPoint DeviceNet Adapter
Notes:
Publication 1738-UM001A-EN-P - February 2005
Appendix
A

Specifications

Following are specifications for the 1738 ArmorPoint DeviceNet adapters.
ArmorPoint DeviceNet Adapters - 1738-ADN12, -ADN18, -ADN18P, and -ADNX
Expansion I/O Capacity DeviceNet adapter backplane current output = 1.0 A maximum. See the following list for
backplane current consumption for each ArmorPoint I/O catalog number and the current consumption for each of the ArmorPoint modules connected to the ArmorPoint DeviceNet adapter. Verify that it is below 1.0 A.
Backplane current can be extended beyond 1.0 A with a 1738-EP24DC Backplane Extension Power Supply. The 1738-EP24DC can supply up to an additional 1.3 A of backplane current.
Multiple 1738-EP24DC modules can be used to reach the maximum of 63 modules.
Cat. No. PointBus Current Requirements
1738-IB2M12 75mA 1738-IB4xxx 75mA 1738-IB8xxx 75mA 1738-IV4xxx 75mA 1738-IV8xxx 75mA 1738-OB2EM12 75mA 1738-OB2EPM12 75mA 1738-OB4Exxx 75mA 1738-OB8Exxx 75mA 1738-OV4EM12 75mA 1738-OW4xxx 90mA 1738-IE2CM12 75mA 1738-OE2CM12 75mA 1738-IE2VM12 75mA 1738-OE2VM12 75mA 1738-IA2xxx 75mA 1738-OA2xxx 75mA 1738-IJM23 160mA 1738-SSIM23 110mA 1738-IR2M12 220mA 1738-IT2IM12 175mA 1738-VHSC24M23 180mA 1738-232ASCM12 75mA 1738-485ASCM12 75mA
DeviceNet Communication Rate
DeviceNet Cable
125K bit/s (500m maximum) 250K bit/s (250m maximum) 500K bit/s (100m maximum)
Refer to publication M115-CA001 for more information
1 Publication 1738-UM001A-EN-P - Februa ry 2005
A-2 Specifications
ArmorPoint DeviceNet Adapters - 1738-ADN12, -ADN18, -ADN18P, and -ADNX DeviceNet Power Specifications
Power Supply
Note: In order to comply with CE Low Voltage Directives (LVD), you must use either a NEC Class 2, a Safety Extra Low Voltage (SELV) or a Protected Extra Low Voltage (PELV) power supply to power this adapter. A SELV supply cannot exceed 30V rms, 42.4V peak or 60V dc under normal conditions and under single fault conditions. A PELV supply has the same rating and is
connected to protected earth. Input Voltage Rating 24V dc nominal DeviceNet Input Voltage Range 11-25V dc DeviceNet specification Input Overvoltage Protection Reverse polarity protected DeviceNet Power Requirements 24V dc (+4% = 25V dc) @ 30 mA maximum
Power Supply Specifications
Power Supply
Note: In order to comply with CE Low Voltage Directives (LVD), you must use either a NEC Class
2, a Safety Extra Low Voltage (SELV) or a Protected Extra Low Voltage (PELV) power supply to
power this adapter. A SELV supply cannot exceed 30V rms, 42.4V peak or 60V dc under normal
conditions and under single fault conditions. A PELV supply has the same rating and is
connected to protected earth. Input Voltage Rating 24V dc
10-28.8V dc range Input Overvoltage Protection Reverse polarity protected Inrush Current 6 A maximum for 10 ms PointBus Output Current 1 A maximum @ 5V dc +
5% (4.75-5.25) Field Side Power Requirements, Maximum 24V dc (+20% = 28.8V dc) @ 400 mA Interruption
Output voltage will stay within specifications when input drops out for 10 ms at 10V with maximum load
General Specifications
LED Indicators
1 green/red Adapter status 1 green/red DeviceNet status 1 green/red PointBus status 1 green System Power (PointBus 5V power)
1 green Adapter Power (24V from field supply) Power Consumption, Maximum 8.1 W @ 28.8V dc Power Dissipation, Maximum 2.8 W @ 28.8V dc Thermal Dissipation, Maximum 9.5 BTU/hr. @ 28.8V dc Isolation Voltage
(continuous-voltage withstand rating) Field Power Bus
Nominal Voltage Supply Voltage Supply Current
50V rms
Tested at 1250V ac rms for 60 s
24V dc
10-28.8V dc range
10 A maximum Dimensions Inches) (Millimeters) 4.41 H x 2.83 W x 2.56 D (112 H x 72 W x 65 D) Operating Temperature IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
20 to 60°C (68 to 140°F) Storage Temperature IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
-40 to 85°C (-40 to 185°F)
Publication 1738-UM001A-EN-P - February 2005
Specifications A-3
ArmorPoint DeviceNet Adapters - 1738-ADN12, -ADN18, -ADN18P, and -ADNX General Specifications (continued)
Relative Humidity IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
5-95% non-condensing Shock IEC60068-2-27 (Test Ea, Unpackaged Shock):
Operating 30 g
Non-operating 50 g Vibration IEC60068-2-6 (Test Fc, Operating):
5 g @ 10-500 Hz ESD Immunity IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges Radiated RF Immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80%AM from 30 MHz to 2000 MHz
10V/m with 200 Hz 50% Pulse 100%AM at 900 Mhz
10V/m with 200 Hz 50% Pulse 100%AM at 1890 Mhz EFT/B Immunity IEC 61000-4-4:
±4 kV at 5 kHz on power ports
±3 kV at 5 kHz on signal ports Surge Transient Immunity IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±2 kV line-earth(CM) on shielded ports Conducted RF Immunity IEC 61000-4-6:
10Vrms with 1 kHz sine-wave 80%AM from 150 kHz to 80 MHz Emissions CSPR 11:
Group 1, Class A Enclosure Type Rating Meets IP65/66/67 (when marked) Mounting Base Screw Torque #8 screw, 7.5 in. lbs. in Aluminum, 16 in. lbs. in Steel
Wiring Category
1
1 - on power ports
1 - on communications ports Weight Imperial (Metric) 0.80 lb. (0.36 kg)
Certifications:
2
(when product is marked)
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada
2
CE
European Union 89/336/EEC EMC Directive, compliant with: EN 61000-6-4; Industrial Emissions EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity
C-Tick Australian Radiocommunications Act,
compliant with: AS/NZS CISPR 11; Industrial Emissions
ODVA ODVA conformance tested to DeviceNet specifications
1. Use this Conductor Category information for planning conductor routing. Refer to Publication 1770-4.1, Industrial Automation
Wiring and Grounding Guidelines.
2. See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Publication 1738-UM001A-EN-P - Februa ry 2005
A-4 Specifications
Notes:
Publication 1738-UM001A-EN-P - February 2005

Quick Start For the 1738-ADNX

Appendix
B

What’s In This Appendix?

In this Quick Start, you will learn how to use the 1738-ADNX with a ControlLogix system on DeviceNet. You will also use one of the 1738-ADNX’s features (Auto Start Mode) in an exercise to automatically configure devices on its Subnet
When you complete this quick start you will be familiar with:
The 1738-ADNX as an adapter on the ControlLogix primary DeviceNet network and as a scanner on the DeviceNet expansion Subnet
Configuring the 1738-ADNX with ArmorPoint I/O on its Subnet
Using and applying the correct termination of the 1738-ADNX’s
Subnet
Using the 1738-A DNX to expand the length of a DeviceNet system
Using the 1738-A DNX to implement a second baudrate for Subnet devices
For rules and guidelines regarding how to use the 1738-ADNX, see Appendix C of this manual.
.

Assumptions

1 Publication 1738-UM001A-EN-P - February 2005
A ControlLogix DeviceNet system already exists to which you ar e going to add new devices without modifying the existing system’s architecture. Y ou are going to expand the length of the system beyond its maximum specification and add new devices that can operate at a different baudrate than the existing system.
The existing system attributes include:
ControlLogix processor in a Logix chassis of 4 or more slots.
1756-ENBT (EtherNet/IP) in the Logix chassis.
Configuration to 125 Kb aud with thin trunk (max distance is
100 m (328 ft.) (ControlLogix chassis may be connected on any DeviceNet network.)
ControlLogix processor with a 1756-DNB (DeviceNet) in slot 3 (slot 3 was picked for this example. This can be any slot.)
B-2 Quick Start For the 1738-ADNX
The new Subnet system attributes include:
Most field devices are more than 100 m from the ControlLogix Processor
Previously installed and documented at 500 Kbaud
1738-ADNX with discrete inputs and outputs for several field
devices
The ability to be replicated several times in the future without changing documentation. (i.e., devices will be replicated with same attributes, node addresses, etc.)
The existing devices will be wired to ArmorPoint I/O.
NetLinx will let you configure everything from your PC, using the 1756-ENBT module and a 1756-DNB. You will be able to connect from your computer over Ethernet to the ControlLogix backplane and configure both the primary (remember the 1 73 8- ADNX will be a new node on this network) and Subnet network (the 1738-ADNX will be node 0 on this network).
When you have completed this exercise you will be able to browse through the 1738-ADNX to see its backplane, using only the RSNetWorx for DeviceNet software package.
1. Open RSNetWorx for DeviceNet by double clicking the icon on your desktop.
2. From the RSNetWorx for DeviceNet main menu select File>New.
3. Select DeviceNet configuration.
Publication 1738-UM001A-EN-P - February 2005
Quick Start For the 1738-ADNX B-3
4. Click OK.
Now that you have created a new DeviceNet project, go on line by clicking the Online icon on the toolbar.
5. A list of the available drivers in RSLinx appears. Drill down from Ethernet into your ControlLogix project through the backplane to your 1756-DNB in slot 3. Select channel A, as shown below.
Your system may not be configured as illustrated. You must pick an Ethernet driver that is configured with the address of your ControlLogix 1756-ENBT bridge module.
6. Click OK to accept the path configuration.
7. Click OK to the prompt.
The sticker on the front of your 1756-ENBT module identifies the IP address configured for your module.
Publication 1738-UM001A-EN-P - February 2005
B-4 Quick Start For the 1738-ADNX
RSNetWorx will go on line. A screen similar to the one below will appear:
Your system may not look like the above system. (You may have more nodes.) It is only important to verify that you have the 1756-DNB at node 0 and the 1738-ADNX at note 16.
8. After the browse is complete, from the RSNetWorx for DeviceNet main menu select File>Save As.
9. Type in MainNetworkADNX as the filename (use this exact name to avoid confusion later).
10. Click Save.
On the main network, the 1738-ADNX acts as an adapter.
The rotary switches on the front of the 1738-ADNX should be set to node 16.
Verify your browse reported the 1738-ADNX at node 16.
Later you will browse deeper to see the Subnet. (Note that on
the Subnet, the 1738-ADNX acts as a scanner and is always at node 0 on that network.)
11. Download a blank scanlist to the 1756-DNB. a. Y ou do not want the existing program in our Logix processors
to interfere with clearing the scanlist. T o en sure that this does not occur, use the key switch to put
all the processors in program mode then back to remote program (turn the keys right then back to the middle position).
b. Double click the 1756-DNB to bring up its properties page.
Publication 1738-UM001A-EN-P - February 2005
Quick Start For the 1738-ADNX B-5
c. Select the Scanlist tab and when prompted click Download.
12. When the download is complete, add the 1738-ADNX to the scanlist by selecting the 1738-ADNX (node 16) and clic king the single right arrow.
A warning window opens that says that the 1738-ADNX does not contain any I/O data.
At this point, RSNetWorx for DeviceNet does not know how many bytes of data are being inputted and outputted to the Subnet so it cannot fill in the values for you.
13. Press OK to close the warning window.
14. To verify that there are no data for input and outputs, click the
1738-ADNX in the Scanlist window.
Publication 1738-UM001A-EN-P - February 2005
B-6 Quick Start For the 1738-ADNX
X
15. Click Edit I/O Parameters.
Click the 1738-ADN in the Scanlist and then click Edit I/O Parameters to verify input and output bytes.
16. Verify that nothing is filled in for input and output sizes (both are zero). If you knew how much data was being produced and consumed on the Subnet, you could fill these fields in manually. Because it is easier to let RSNetWorx for DeviceNet fill in these values for us, click Cancel to close this window.
Publication 1738-UM001A-EN-P - February 2005
Quick Start For the 1738-ADNX B-7
Click the
ill
r
17. Remove the 1738-ADNX from the scanlist for now by clicking the double arrows.
double left arrow to remove the 1738-ADNX from the Scanlist. Then verify that the Scanlist is empty. Y ou w return here later after RSNetWorx fo DeviceNet knows more about the devices on the Subnet.
18. Click OK. When prompted if you want to download changes to the device, click Yes.
At this point you have a choice:
You could start another instance of RSNetWorx for DeviceNet and configure the Subnet. You would then see the 1738-ADNX at node 0 on the Subnet and add the ArmorPoint I/O to its scanlist. You would then map the data to the exact location you want it. For example, if ladder logic was already written, you could map it to an address.
If you have not written your ladder logic yet and you are not particular about the mapping, you could use the auto start feature of the 1738-ADNX to map all the devices automatically from the primary network. After the mapping is complete, look at the Subnet to verify that eve rything worked as expected.
19. Verify that the subnetwork taps are electronically isolated and have their own terminating resistors at each end.
IMPORTANT
The Subnet must always be properly terminated. In this example, there is a terminating resistor at each end of the Subnet trunk.
Publication 1738-UM001A-EN-P - February 2005
B-8 Quick Start For the 1738-ADNX
se
)
To properly terminate the 1738-ADNX when using a Subnet, refer to the illustration.
Terminator Resistor
Note that standard DeviceNet terminator resistors are shown in this illustration. Refer to the On-Machine Connectivity catalog, publication no. M115-CA001, Network Media section, for other DeviceNet connection options.
Drop
Terminator Resistor
Trunk
Main
Drop
Trunk
Subnet
DeviceNet In
Subnet Out
X10
PWR
Adapter
Terminator Resistor
If you are not going to use the Subnet, you must still terminate it!
Note that the non-terminating base is shipped with the 1738-ADNX only. The terminating base is shipped with all the other ArmorPoint DeviceNet adapters.
Do not use carbon resistors. Metal film is recommended.
1738-ADNX With Subnet (1738-ADNX Subnet Drop Off Subnet Trun k
Terminator Resistor
1738-ADNX
Adapter Status
DeviceNet Status
PointBus Status
System Power
Adapter Power
X1
I/O Base I/O Base non-terminating ba
43899
Publication 1738-UM001A-EN-P - February 2005
Continue ONLY after you have verified that the taps are terminated correctly.
20. Double click on the 1738-ADNX to open the properties window. In the next step you will download the EDS defaults to the 1738-ADNX.
Quick Start For the 1738-ADNX B-9
21. Select the Parameters tab and choose Download.
22. Verify that your window looks similar to the following window.

Review of the 1738-ADNX Rules and the MACID Parameter

To understand some of the MACID parameters, you should review some of the rules for using the 1738-ADNX.
The 1738-ADNX always has address 0 on the Subnet.
All ArmorPoint I/O backplane module MACIDs must be
numerically less than those of non-backplane Subnet modules.
Each backplane module’s MACID must be greater than that of its left neighboring module.
The 1738-ADNX has a unique attribute: Max(imum) Backplane MACID. This value represents the highest node address of a
module residing on the backplane. This value must be greater than or equal to the rightmost backplane ArmorPoint I/O module, but must be less than that of any non-backplane Subnet module. You select this value to allow for the future addition of backplane modules. The attribute’s default value is 31, representing the middle of the address range.
Publication 1738-UM001A-EN-P - February 2005
B-10 Quick Start For the 1738-ADNX
The 1738-ADNX will automatically maintain the MACIDs of the backplane modules.
Note that the assignment of the MACIDs of the non-backplane subnet modules is manual and is not performed or retained by the 1738-ADNX.
The 1738-ADNX supports 125 kb, 250 kb, and 500 kb baudrates. For this example, you are going to set the Subnet to 125 kb.
When using Auto Start Mode, the adapter:
Sets all ArmorPoint I/O modules on the backplane to Autobaud.
Reads all ArmorPoint I/O module IDs on the backplane.
Sets the ArmorPoint I/O module addresses sequentially.
Sets the Max Backplane MACID.
Generates a scanlist for the backplane.
Maps automatically I/O data, based on byte (I/O data is mapped
in the adapter’s memory at the next available byte), word (I/O data is mapped at the next available word), double-word (I/O data is mapped at the next available double word) or fixed (the data is mapped to a fixed allocation size). You will choose one of these four options from a pulldown menu later in this Quick Start.
IMPORTANT
Your 1738-ADNX DeviceNet adapter must be free of I/O connections when you use Auto Start Mode. If another scanner device has established I/O connections with the adapter (if it is mapped in another scanner’s scanlist), the attempt to use Auto Start Mode is rejected. Also, when the adapter is configuring itself in Auto Start Mode, no other device can establish I/O connections to the adapter.
When the adapter completes this sequence of events, the ArmorPoint I/O modules connected to the adapter are ready to accept connections from a scanner.
IMPORTANT
Although Auto Start Mode lets your adapter operate with a default configuration, you can choose to manually change the configuration after operation has begun or you can write a custom configuration.
Publication 1738-UM001A-EN-P - February 2005
Quick Start For the 1738-ADNX B-11
When Auto Start Mode is used, the adapter and connected I/O modules go through the following sequence of events:
Connections are established to I/O modules
The adapter makes Change of State (COS) connections if the I/O
module supports COS, if not, the connection is Polled
Data is mapped to the connections
The notes above explain parameter 1 – Max Backplane MACID. Next you will review parameter 6, Auto Start Mode and parameter 7, Fixed Map Size.
Review of Auto Start Mode
1. Select parameter 6, then click the help icon to display information about Auto Start Mode.
A window describing Auto Start Mode opens.
Publication 1738-UM001A-EN-P - February 2005
B-12 Quick Start For the 1738-ADNX
Right now, the 1738-ADNX is not in another scanner’s scanlist so you can use the Auto Start Mode feature. By using Auto Start Mode, the 1738-ADNX will map all the devices on the Su bnet and automatically adjust the value for the following parameters:
1, Max Backplane MACID
9, Poll/COS Connection Consume Size
10, Poll Connection Produce Size
11, COS Connection Produce Size, and
12, Strobe Connection Produce Size.
2. Select the pulldown box next to the Auto Start Mode parameter. Y ou can map the data using the four options discussed earlier. If you choose to use the Map Data With Fixed Map Size option, the map size is selected with parameter 7, Fixed Map Size.
3. For this example, choose Map Data To Word Boundaries as shown below:
Publication 1738-UM001A-EN-P - February 2005
Quick Start For the 1738-ADNX B-13
Notice that parameters 9, 10, 11 and 12 are still at their default of 2 bytes. These values will be filled out for you when this action is complete.
Download
parameters to the device
Monitor
icon
4. Make sure All is selected and the Monitor value then click the icon to download parameters to the device (this triggers the Auto Start Mode).
5. Click the Monitor icon and notice:
Parameter 6 has gone back to Do Nothing. The Auto Start has
begun and will not repeat unless you trigger it again later.
Parameter 8, Phys List Acqu ire Status, indicates you are in Auto
Start Mode. Give the system at least a minute or two to complete the configuration you requested then go to the next step.
Publication 1738-UM001A-EN-P - February 2005
B-14 Quick Start For the 1738-ADNX
d
6. Wait for parameter 8 to return to idle. Then click the Monitor icon to end monitoring. Notice the following:
Parameter 1 has been filled in for you. There are three ArmorPoint I/O modules in the backplane, causing the default to change from 31 to 3.
Parameter 3: Verify the Backplane Baudrate is 125 Kbaud. If it is not, you will need to find out why and make the necessary corrections.
Parameter 9, 10, 11, and 12 have been filled in for you.
Expand the column to view all the text.
Consume size is data that the adapter will consume from the scanner. These are the outputs being sent from the scanner to the ArmorPoint I/O adapter.
Produce size is data the 1738-ADNX adapter will produce for the 1756-DNB scanner. This will be discusse in more detail later in this section.
Publication 1738-UM001A-EN-P - February 2005
Note that you do not need to view the Subnet to determine where the data has been mapped. You can go back to monitor mode and view parameter 14, Cycling I/O Mapping. The help for this parameter states how to use the parameter to determine mapping.
7. Press OK to close this window.
Quick Start For the 1738-ADNX B-15
8. From the RSNetWorx for DeviceNet main menu, select
File>Save.

Browse the Subnet

IMPORTANT
Look at the Subnet at this point to make things more clear.
1. From the RSNetW orx for DeviceNet main menu, select File>New
and then select DeviceNet Configuration.
2. Click OK.
Now that you have a new DeviceNet project created.
3. Click the Online icon.
Last time you browsed to the 1756-DNB. This time you will browse a little deeper.
You must save your work before moving on.
Publication 1738-UM001A-EN-P - February 2005
B-16 Quick Start For the 1738-ADNX
Last time you browsed the main network
This time you will browse the Subnet
4. Drill down from Ethernet into your ControlLogix demo box through the backplane to your 1756-DNB in slot 3, channel A, 1738-ADNX and select DeviceNet Subnet as shown below:
5. To go on line, click OK to accept the path configuration and then OK to the prompt.
Wait for the browse to complete.
6. From the RSNetWorx for DeviceNet main menu, select File>Save As.
7. Type in SubNetADNX as the filename.
8. Click Save.
IMPORTANT
You must save your work before continuing.
Publication 1738-UM001A-EN-P - February 2005
Quick Start For the 1738-ADNX B-17
The nodes can be in any order. Verify:
o
9. Verify your screen appears as shown below.
All four are there
They have the correct node numbers
On the Subnet, the 1738-ADNX is a scanner and it is always at node 0. It is OK for some or all of the node numbers on the Subnet to be the same as devices on the primary network. Because they are two different networks, duplicate node errors will not occur. The 1738-ADNX will communicate back to the 1756-DNB scanner as a single entity (only taking up one node number on the main network).
10. Double click on the 1738-ADNX to bring up its properties page.
11. Select the Scanlist tab and when prompted select Upload.
To view the configuration you just created, upload the scanlist from the 1738-ADNX.
Make sure you click Upload! You do not want t download over the configuration you just created.
Publication 1738-UM001A-EN-P - February 2005
B-18 Quick Start For the 1738-ADNX
Verify your scanlist matches that shown below.
Notice that all the ArmorPoint I/O modules have been added
to the scanlist, as you probably expected.
You are about to look at the input and output tabs. Based on your selections earlier, all the data should be mapped to word boundaries.
Publication 1738-UM001A-EN-P - February 2005
Quick Start For the 1738-ADNX B-19
e n
Inputs and Outputs
1. Select the Input tab. A single word is 16 bits. Notice that the mapping is as expected.
The first two bytes (1 byte = 8 bits) are reserved as read only.
The first word is completely used, so the 1738-IB4M12 can map
to the beginning of the next word (byte 2, bit 0).
There is a space between the 1738-IB4M12 and the 1738-OB4EM12 because the next word does not start until byte
4.
This field describes how th data is transferred betwee the I/O modules and the adapter on the PointBus Subnet.
The current memory buffer selected is COS/Cyclic. There are also buffers for Polled and Strobed. This is how the data will be transferred to the scanner (1756-DNB in this example).
Note the mapping in the 1738-ADNX Scanner is shown in byte increments. The 1756-DNB displays in double words (4 bytes).
Use the scroll bar as needed to see all of the data.
The first 2 bytes are reserved for status.
Publication 1738-UM001A-EN-P - February 2005
B-20 Quick Start For the 1738-ADNX
Earlier view of the parameters.
Scroll down and notice that bytes 0 throug h 11 = 12 bytes total were enough for the input data.
This matches what you observed earlier on the main network:
The primary network knew you were producing 12 bytes of data.
The data mapped in the 1738-ADNX will be exchanged with the 1756-DNB scanner.
There are thre e memory buffers that the 1738-ADNX uses for input data to the scanner on Device Net. The buffers are COS/cyclic, polled, and strobed. You can map data into any of the three buffer areas on the adapter.
Currently, all of the I/O modules are mapped to the COS/cyclic buffer.
Publication 1738-UM001A-EN-P - February 2005
Quick Start For the 1738-ADNX B-21
Earlier view of the parameters.
2. Select the pulldown listbox next to the Memory label in the
middle of the window to display the three memory buffer choices.
3. Select each of the choices and view the mapping. You will see that only the COS/cyclic buffer is b ein g used (There are 2 bytes reserved for status in each buffer. These words are not for a specific module.)
4. Set the Memory selection back to COS/cyclic.
Note that for the 1738-ADNX, each line in the mapping area represents a byte of data. When you view the 1756-DNB, each line will be 4 bytes of data (double word).
Now you are ready to take a look at the output side. Based on the numbers you saw on the main network you expect to see 3 bytes (two of them are going to be reserved status words).
The primary network knew you were consuming 3 bytes of data.
Publication 1738-UM001A-EN-P - February 2005
B-22 Quick Start For the 1738-ADNX
You should still be looking at the subnet 1738-ADN X Input tab. Now select the Output tab and verify you have the following:
Notice that only the output module 1738-OB4EM12 appears.
These two say read only, but since it is an output tab, a better description is reserved for future use.
Publication 1738-UM001A-EN-P - February 2005
5. Expand the plus next to node 2.
Several revisions ago (RSNetWorx for DeviceNet V3.21) the
ability to view I/O details from the Input and Output windows was added into the software.
From the Input and Output windows, you can view detailed I/O
information for each device in the scanlist of a DeviceNet scanner.
To view the I/O details for a particular device, click the plus sign (+) located to the left of the device. If a plus sign is not displayed, there are not any I/O details for that device.
This feature is driven by each device’s EDS file.
Quick Start For the 1738-ADNX B-23
Click OK and not Cancel to close the window.
6. Select Output V alue #1 and notice the exact location of that bit is displayed. You can easily tell that Output Value #1 is in byte 2, bit 1 (see the highlighted portion of byte 2). This information will make it very easy to write your ladder logic late r.
You uploaded the scanlist and looked at the input and output data. Now you are about to save this information to your hard disk.
7. Click OK (not cancel) to close this window.
Publication 1738-UM001A-EN-P - February 2005
B-24 Quick Start For the 1738-ADNX
8. From the RSNetWorx for DeviceNet main menu, select
File>Save.
IMPORTANT
You must save your work before moving on.
Now all the information is saved in the file SubnetADNX.dnt.
Navigate Between Networks
A nice feature of RSNetWorx for DeviceNet is the easy way it lets you commission the Subnet. You can have two DeviceNet projects because there are actually two DeviceNet networks. Another nice feature of RSNetWorx for DeviceNet is the easy way it lets you navigate between two related networks rather than having to keep track of which network file goes with what.
RSNetWorx for DeviceNet provides an easy way to associate two networks that will allow quick navigation between them. You will look at that now.
1. Double click on the 1738-ADNX icon to pull up its properties page.
Publication 1738-UM001A-EN-P - February 2005
Quick Start For the 1738-ADNX B-25
2. Select the Device Bridging tab. The following window opens.
This window lets you define a file that is associated with this one through the 1738-ADNX. Once you specify the associated file, you will be able to jump to that file through a menu selection from the 1738-ADNX. The file you nee d to associate in this case is the MainNetworkADNX.dnt project file you created earlier.
3. Click the Associate File button.
4. Make sure you are looking in the Networks folder in the path
shown below.
5. Select MainNetworkADNX.dnt then the Open button. The MainNetworkADNX.dnt file will appear in the File box as shown below.
6. Click OK to close the properties window.
Publication 1738-UM001A-EN-P - February 2005
B-26 Quick Start For the 1738-ADNX
7. From the RSNetWorx for DeviceNet main menu, select
File>Save. Now you can observe how you would switch networks.
Switch Between Networks
1. Move the cursor over the 1738-ADNX in the network browse window.
2. Press the right mouse button.
3. Click Associated Network from the menu.
If prompted to save your changes, you must select Yes (you will probably not get this prompt if you saved earlier).
To get back to the main network, associate the SubnetADNX.dnt project to MainNetworkADNX.dnt using the following steps:
4. Double click on the 1738-ADNX adapter at Node 16.
5. Click the Device Bridging tab.
Publication 1738-UM001A-EN-P - February 2005
Loading...