Pilz PNOZ X10 Data Sheet

E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X10
Gertebild
][Bildunterschrift_NOT_Sch.tuer_Licht
Approvals
PNOZ X10
SÜDDEUTSCHLAND
Unit features
Gertemerkmale
` Positive-guided relay outputs:
– 6 safety contacts (N/O), instanta-
neous
– 4 auxiliary contacts (N/C), in-
stantaneous
` Connection options for:
– E-STOP pushbutton – Safety gate limit switch – Reset button – Light barriers
` LED indicator for:
– Switch status channel 1/2 – Supply voltage
` See order reference for unit types
Unit description
Bestimmung/Gertebesc hreibung NOT-AUS , Schutzt, Lichtsc hr_PNOZ
The safety relay meets the require­ments of EN 60947-5-1, EN 60204-1 and VDE 0113-1 and may be used in applications with
` E-STOP pushbuttons ` Safety gates ` Light beam devices
Safety features
][Sicherheitseigenscha ften Schaltgerät_allgem einer Teil
The relay meets the following safety requirements:
` The circuit is redundant with built-in
self-monitoring.
` The safety function remains effec-
tive in the case of a component fail­ure.
` The correct opening and closing of
the safety function relays is tested automatically in each on-off cycle.
Sicherheitseigenschaften Zusatz - AC/DC-Gerte_PNOZ
` The tranformer is short circuit-
proof. An electronic fuse is used on a DC supply.
Zulassungen
Block diagram
~
Power
=
S11 S12A1 A2
Feed-
back
Y1 Y2
S21 S22
InputInput
Blockschaltbild
K1
K2
K3
13 23
3343536371819101
14 24
3444546472829202
Y3
Input
S33 S34
Reset/
Start
S37
Reset/
Start
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-038-2010-08
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X10
Function description
][Funktionen_einkanalig_nur_24_V_ACDC
` Single-channel operation (only with
24 VAC/DC): no redundancy in
U
B
the input circuit, earth faults in the reset and input circuit are detected.
][Funktionen_zweikanalig_ohne_quer
` Dual-channel operation without de-
tection of shorts across contacts: redundant input circuit, detects – earth faults in the reset and input
circuit,
– short circuits in the input circuit
and, with a monitored reset, in the reset circuit too.
Timing diagram
1 2
POWER
Reset/Start
Input
Output safe
][Funktionen_zweikanalig_mit_quer_manu
` Dual-channel operation with detec-
tion of shorts across contacts: re­dundant input circuit, detects – earth faults in the reset and input
circuit,
– short circuits and shorts be-
tween contacts in the input cir­cuit.
][Funktionen_autoStart
` Automatic start: Unit is active once
the input circuit has been closed.
][Funktionen_manuStart
` Manual reset: Unit is active once
the input circuit is closed and then the reset circuit is closed.
][Funktionen_berStart_allg
` M on it or ed re se t: Un i t i s ac ti ve on c e
][Zeitdiagramm_auto_manu_ueber1_aux
ab
– the input circuit is closed and
then the reset circuit is closed and opened again.
– the reset circuit is closed and
then opened again once the in­put circuit is closed.
][Funktionen_Kontaktvervielfachung
` Increase in the number of available
instantaneous safety contacts by connecting contact expansion modules or external contactors.
ab
3
Output aux.
t1 t2
t1 t2
Key
` Power: Supply voltage ` Reset/Start: Reset circuit S33(S12)-
S34
` Input: Input circuits S12-Y3, S21-
S22
` Output safe: Safety contacts 13-14,
23-24, 33-34, 43-44, 53-54, 63-64
Wiring
][Verdrahtung_Si_Hi_unverz
Please note:
` Information given in the “Technical
details” must be followed.
` Outputs 13-14, 23-24, 33-34, 43-
44, 53-54, 63-64 are safety con­tacts, outputs 71-72, 81-82, 91-92, 01-02 are auxiliary contacts (e.g. for display).
` To prevent contact welding, a fuse
should be connected before the output contacts (see technical de­tails).
` Calculation of the max. cabling runs
in the input circuit:
l
max
t1
t1
t2
t2
` Output aux: Auxiliary contacts 71-
72, 81-82, 91-92, 01-02
` c: Automatic reset ` d: Manual reset ` e: Monitored reset ` a: Input circuit closes before reset
circuit
R
lmax
=
I
max
Rl / km
R
= max. overall cable resist-
lmax
ance (see technical details)
/km = cable resistance/km
R
l
` Use copper wire that can withstand
60/75 °C.
` Sufficient fuse protection must be
provided on all output contacts with capacitive and inductive loads.
t1
t2
t
3
t2
t1
` b: Reset circuit closes before input
circuit
: Switch-on delay
` t
1
: Delay-on de-energisation
` t
2
` t
: Recovery time
3
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-038-2010-08Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-2
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X10
Preparing for operation
Betriebsbereitschaft her stellen
` Supply voltage
Supply voltage AC DC
A1
A2
L1
N
PE
` Input circuit
Input circuit Single-channel Dual-channel E-STOP
without detection of shorts across con­tacts
E-STOP with detection of shorts across contacts
S12 Y3
S12 S11 S21
S22
S1
S21 S22
S11 Y3
A1
A2
S11 S21 S22
S12
S11
S12
Y3
L+
L-
S1
S1
Safety gate without detection of shorts across con­tacts
Safety gate with detection of shorts across contacts
S12 Y3
S12 S11 S21
S22
S1
S21 S22
S11 Y3
S11
S12
Y3
S11 S12 S22 S21
S1
S1
S2
S2
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-038-2010-08
Loading...
+ 5 hidden pages