Pilz PNOZ s3 Data Sheet

Page 1
E-STOP relays, safety gate monitors
InputInput
A1 A2 S21 S22
=
Power
Reset/
Start
S34
S11 S12
=
Y32
K1
K2
13
23
24
14
Interface
expansion
unit
Up to PL e of EN ISO 13849-1
PNOZ s3
Gertebild
][Bildunterschrift_NOT_Sch.tuer_Licht
Approvals
PNOZ s3
Unit features
Gertemerkmale
Positive-guided relay outputs:
– 2 safety contacts (N/O), instanta-
neous
1 semiconductor outputConnection options for:
– E-STOP pushbutton – Safety gate limit switch – Reset button – Light barriers – PSEN
A connector can be used to con-
nect 1 PNOZsigma contact ex­pander module
Operating modes can be set via ro-
tary switch
LED indicator for:
– Supply voltage – Input status, channel 1 – Input status, channel 2 – Switch status channel 1/2 – Reset circuit – Error
Plug-in connection terminals (either
spring-loaded terminal or screw terminal)
Unit description
Bestimmung/Gertebeschreibung NOT-AUS, Schutzt, Lichtschr_PNOZ
The safety relay meets the require­ments of EN 60947-5-1, EN 60204-1 and VDE 0113-1 and may be used in applications with
E-STOP pushbuttonsSafety gates Light beam devices
Safety features
][Sicherheitseigenscha ften Schaltgerät_allgem einer Teil
The relay meets the following safety requirements:
The circuit is redundant with built-in
self-monitoring.
The safety function remains effec-
tive in the case of a component fail­ure.
The correct opening and closing of
the safety function relays is tested automatically in each on-off cycle.
Sicherheitseigenschaften Zusatz - Sicherung DC_PNOZ
The unit has an electronic fuse.
Zulassungen
Block diagram
Blockschaltbild
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
1001969-EN-04-2011-09
Page 2
E-STOP relays, safety gate monitors
POWER
Input
Output safe
Reset/Start
t1 t2
t1
t2
t2
t1
t1 t2
1 2
ab
3
Out semi
t1
t2
t2
t1
ab
t4
t2
t2
ab
t1
t1
t3
4
t3
R
lmax
Rl / km
I
max
=
Up to PL e of EN ISO 13849-1
PNOZ s3
Function description
][Funktionen_ein_zweikan alig_ohne Quer
Single-channel operation: no re-
dundancy in the input circuit, earth faults in the reset circuit and input circuit are detected.
Dual-channel operation without de-
tection of shorts across contacts: redundant input circuit, detects – earth faults in the reset and input
circuit,
– short circuits in the input circuit
and, with a monitored reset, in the reset circuit too.
][Funktionen_zweikanalig_mit Quer
Dual-channel operation with detec-
tion of shorts across contacts: re­dundant input circuit, detects – earth faults in the reset and input
circuit,
Timing diagram
– short circuits in the input circuit
and, with a monitored reset, in the reset circuit too,
– shorts between contacts in the
input circuit.
][Funktionen_auto_manu_Start
Automatic reset: Unit is active once
the input circuit has been closed.
Manual reset: Unit is active once
the input circuit is closed and then the reset circuit is closed.
][Funktionen_berStart_fall_Flanke
Monitored reset with falling edge:
Unit is active once – the input circuit is closed and
then the reset circuit is closed and opened again.
– the reset circuit is closed and
then opened again once the in­put circuit is closed.
][Funktionen_berStart_steig_Flanke
][Zeitdiagramm_PNOZs_auto_manu_ueber1_ueber2_Semi
Monitored reset with rising edge:
Unit is active once the input circuit is closed and once the reset circuit is closed after the waiting period has elapsed (see technical details).
][Funktionen_Start_Anlauftest
Reset with start-up test: The unit
checks whether safety gates that are closed are opened and then closed again when supply voltage is applied.
][Funktionen_Kontaktvervielfachung_PNOZsigma
Increase in the number of available
instantaneous safety contacts by connecting contact expander mod­ules or external contactors/relays; A connector can be used to con­nect 1 PNOZsigma contact ex­pander module.
Key
Power: Supply voltage Reset/Start: Reset circuit S12-S34Input: Input circuits S11-S12,S 21-
S22
Output safe: Safety contacts 13-14,
23-24
Out semi: Semiconductor
outputY32
: Automatic reset : Manual reset : Monitored reset with rising edge: Monitored reset with falling edgea: Input circuit closes before reset
circuit
b: Reset circuit closes before input
circuit
Wiring
][Verdrahtung_Si_unverz
Please note:
Information given in the “Technical
details” must be followed.
R
Outputs 13-14, 23-24 are safety
contacts.
To prevent contact welding, a fuse
should be connected before the output contacts (see technical de­tails).
Calculation of the max. cable runs
in the input circuit:
l
max
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
Use copper wire that can withstand
Sufficient fuse protection must be
= max. overall cable resist-
lmax
ance (see technical details)
/km = cable resistance/km
R
l
60/75 °C.
provided on all output contacts with capacitive and inductive loads.
: Switch-on delay
t
1
: Delay-on de-energisation
t
2
: Waiting period
t
3
: Waiting period reset circuit was
t
4
closed
1001969-EN-04-2011-09Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-2
Page 3
E-STOP relays, safety gate monitors
A1
L+
A2
L-
S1
S11
S22
S12
S1
S11
S12 S22
S1
S22
S21
S12
S11
S1
S22
S11 S12
S1
S2
S11
S12 S22
S1
S2
S12
S11
S22
S21
S12 S22
24 V DC
A2
GND
Up to PL e of EN ISO 13849-1
PNOZ s3
Preparing for operation
Betriebsbereitschaft herstellen PNOZs
Supply voltage
Supply voltage AC DC
Input circuit
Input circuit Single-channel Dual-channel E-STOP
without detection of shorts across con­tacts
E-STOP with detection of shorts across contacts
Safety gate without detection of shorts across con­tacts
Safety gate with detection of shorts across contacts
Light beam device or safety switch with detection of shorts across contacts via ESPE
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
1001969-EN-04-2011-09
Page 4
E-STOP relays, safety gate monitors
S12
S34
K5
K6
K5
L1 N
K6
S12
13 (23)
S34
14 (24)
S12
S34
S3
K5
K6
K5
L1
K6
S12 S34
S3
N
13 (23) 14 (24)
Y32
PLC Input
*
Up to PL e of EN ISO 13849-1
PNOZ s3
Reset circuit/feedback loop
Reset circuit/feedback loop Reset circuit Feedback circuit Automatic reset
Manual/monitored reset
Semiconductor output
*Connect together the 0V connections on all the external power supplies
Key
S1/S2 E-STOP/safety gate switch
S3 Reset button
Switch operated
Gate open
Gate closed
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
1001969-EN-04-2011-09Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-4
Page 5
E-STOP relays, safety gate monitors
120 (4.72")
* 100 (3,94")
98 (3.86")
17,5
(0.69")
Up to PL e of EN ISO 13849-1
PNOZ s3
Terminal configuration
Klemmenbelegung
Installation
][Montage_PNOZsigma
Install base unit without contact ex­pander module:
Ensure that the plug terminator is
inserted at the side of the unit.
Connect base unit and PNOZsigma contact expander module:
Remove the plug terminator at the
side of the base unit and at the con­tact expander module.
Connect the base unit and the con-
tact expander module to the sup­plied connector before mounting the units to the DIN rail.
Installation in control cabinet
The safety relay should be installed
in a control cabinet with a protec­tion type of at least IP54.
Use the notch on the rear of the unit
to attach it to a DIN rail (35 mm).
When installed vertically: Secure
the unit by using a fixing element (e.g. retaining brakket or end angle).
Push the unit upwards or down-
wards before lifting it from the DIN rail.
Dimensions
Abmessungen
*with spring-loaded terminals
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
1001969-EN-04-2011-09
Page 6
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ s3
Notice
][WICHTIG_PDB_al t
This data sheet is only intended for use during configuration. For installation and operation, please refer to the op­erating instructions supplied with the unit.
Service life graph
Lebensdauerkurve_Rela is_Text vor Kurv e
The service life graphs indicate the number of cycles from which failures due to wear must be expected. The wear is mainly caused by the electrical load; the mechanical load is negligible.
Lebensdauerkurve_Relais_Text nach Kurve_SIF Bsp
Example
Inductive load: 0,2 AUtilisation category: AC15Contact service life: 2,000,000 cy-
cles Provided the application requires few­er than 2,000,000 cycles, the PFH val­ue (see technical details) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provided on all output contacts. With capacitive loads, any power surges that occur must be noted. With contactors, use freewheel diodes for spark suppres­sion.
Lebensdauerkurve
Technical details PNOZsigma
Technical details
Electrical data
Supply voltage Supply voltage U Voltage tolerance -15 %/+10 % Power consumption at U Residual ripple DC 20 % Voltage and current at Input circuit DC: 24.0 V 50.0 mA Reset circuit DC: 24.0 V 50.0 mA Feedback loop DC: 24.0 V 50.0 mA Number of output contacts Safety contacts (S) instantaneous: 2
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
DC 24 V
B
DC 2.5 W
B
1001969-EN-04-2011-09Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-6
Page 7
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ s3
Electrical data
Utilisation category in accordance with EN 60947-4-1 Safety contacts: AC1 at 240 V I
Safety contacts: DC1 at 24 V I
Utilisation category in accordance with EN 60947-5-1 Safety contacts: AC15 at 230 V I Safety contacts: DC13 at 24 V (6 cycles/min) I Conventional thermal current 6.0 A Contact material AgCuNi + 0.2 µm Au External contact fuse protection (I Blow-out fuse, quick Safety contacts: 10 A Blow-out fuse, slow Safety contacts: 6 A Circuit breaker 24 VAC/DC, characteristic B/C Safety contacts: 6 A Semiconductor outputs (short circuit proof) 24.0 V DC, 20 mA Max. overall cable resistance R input circuits, reset circuits single-channel at U dual-channel without detect. of shorts across contacts at U dual-channel with detect. of shorts across contacts at U Min. input resistance when switching on 110 Ohm
Safety-related characteristic data
PL in accordance with EN ISO 13849-1: 2006 PL e (Cat. 4) Category in accordance with EN 954-1 Cat. 4 SIL CL in accordance with EN IEC 62061 SIL CL 3 PFH in accordance with EN IEC 62061 2.31E-09 SIL in accordance with IEC 61511 SIL 3 PFD in accordance with IEC 61511 2.03E-06 T
[year] in accordance with EN ISO 13849-1: 2006 20
M
Times
Switch-on delay with automatic reset typ. 170 ms with automatic reset max. 300 ms with automatic reset after power on typ. 350 ms with automatic reset after power on max. 600 ms with manual reset typ. 40 ms on monitored reset with rising edge typ. 35 ms on monitored reset with rising edge max. 50 ms on monitored reset with falling edge typ. 55 ms on monitored reset with falling edge max. 70 ms Delay-on de-energisation with E-STOP typ. 10 ms with E-STOP max. 20 ms with power failure typ. 40 ms with power failure max. 60 ms Recovery time at max. switching frequency 1/s after E-STOP 100 ms after power failure 100 ms Waiting period with a monitored reset with rising edge 120 ms with falling edge 250 ms Min. start pulse duration with a monitored reset with rising edge 30 ms with falling edge 100 ms
DC 30 Ohm
B
= 1 kA) to EN 60947-5-1
K
lmax
DC 60 Ohm
B
DC 30 Ohm
B
: 0.01 A , I
min
: 1500 VA
P
max
: 0.01 A , I
min
P
: 150 W
max
: 5.0 A
max
: 5.0 A
max
max
max
: 6.0 A
: 6.0 A
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
1001969-EN-04-2011-09
Page 8
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ s3
Times
Simultaneity, channel 1 and 2 Supply interruption before de-energisation 20 ms
Environmental data
EMC EN 60947-5-1, EN 61000-6-2, EN 61000-6-4 Vibration to EN 60068-2-6 Frequency 10 - 55 Hz Amplitude 0.35 mm Climatic suitability EN 60068-2-78 Airgap creepage in accordance with EN 60947-1 Pollution degree 2 Overvoltage category III / II Rated insulation voltage 250 V Rated impulse withstand voltage 4.00 kV Ambient temperature -10 - 55 °C Storage temperature -40 - 85 °C Protection type Mounting (e.g. cabinet) IP54 Housing IP40 Terminals IP20
Mechanical data
Housing material Housing PC Front PC Cross section of external conductors with screw terminals 1 core flexible 0.25 - 2.50 mm² , 24 - 12 AWG No. 750103 2 core, same cross section, flexible: with crimp connectors, without insulating sleeve 0.25 - 1.00 mm² , 24 - 16 AWG No. 750103 without crimp connectors or with TWIN crimp connectors 0.20 - 1.50 mm² , 24 - 16 AWG No. 750103 Torque setting with screw terminals 0.50 Nm No. 750103 Cross section of external conductors with spring-loaded termi­nals: Flexible with/without crimp connectors Spring-loaded terminals: Terminal points per connection 2 No. 751103 Stripping length 9 mm No. 751103 Dimensions Height 102.0 mm No. 751103
Width 17.5 mm Depth 120.0 mm Weight 140 g
Technische Daten_Satz No .
No. stands for order number.
0.20 - 2.50 mm² , 24 - 12 AWG No. 751103
96.0 mm No. 750103
Si-Kennzahlen_Zusatz_Relais_Lebensdauer_PDB
It is essential to consider the relay's service life graphs. The relay outputs' safety-related characteristic data is only valid if the values in the service life graphs are met.
The PFH value depends on the switch­ing frequency and the load on the relay output. If the service life graphs are not acces­sible, the stated PFH value can be
used irrespective of the switching fre­quency and the load, as the PFH value already considers the relay's B10d val­ue as well as the failure rates of the other components.
Si_Kennzahlen_Erläute rung_1
All the units used within a safety function must be considered when calculating the safety characteristic data.
Si_Kennzahlen_Erläuterung_2
INFORMATION
A safety function's SIL/PL values are not identical to the SIL/PL values of the units that are used and may be dif­ferent. We recommend that you use
Technische Daten_Satz Normen
the PAScal software tool to calculate the safety function's SIL/PL values.
1001969-EN-04-2011-09Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
-8
Page 9
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ s3
The standards current on 2006-04 apply.
Bestelldaten
Order reference
Type Features Terminals Order no.
PNOZ s3 24 VDC With screw terminals 750 103 PNOZ s3 C 24 VDC With spring-loaded terminals 751 103
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
1001969-EN-04-2011-09