Mitsubishi SEZ-KA35VA, SEZ-KA50VA, SEZ-KA60VA, SEZ-KA71VA Service Manual

0 (0)

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS

September 2006

No.OC321

REVISED EDITION-B

TECHNICAL & SERVICE MANUAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

 

 

 

 

 

 

[Model names]

 

[Service Ref.]

SEZ-KA35VA

 

SEZ-KA35VA.TH

SEZ-KA50VA

 

SEZ-KA50VA.TH

SEZ-KA60VA

 

SEZ-KA60VA.TH

SEZ-KA71VA

 

SEZ-KA71VA.TH

Revision:

•RoHS PARTS LIST is added in REVISED EDITION-B. •Some descriptions have been modified.

•Please void OC321 REVISED EDITION-A.

Note:

This manual describes only service data of the indoor

units.When servicing outdoor units, please refer to the service manual No.OC322, OC323 together with this manual.

RoHS compliant products have <G> mark on the spec name plate.

For servicing of RoHS compliant products, refer to the RoHS Parts List.

CONTENTS

1. PART NAMES AND FUNCTIONS ······

2. SPECIFICATIONS·············

3. OUTLINES AND DIMENSIONS·······

Model name

4. WIRING DIAGRAM·············

indication

5.REFRIGERANT SYSTEM DIAGRAM······

6.TROUBLESHOOTING···········

 

7. DISASSEMBLY PROCEDURE········

INDOOR UNIT

8. PARTS LIST················

9.RoHS PARTS LIST·············

10.OPTIONAL PARTS·············

TEMP. ON/OFF

WIRED REMOTE CONTROLLER

1 PART NAMES AND FUNCTIONS

Indoor Unit

SEZ-KA35VA.TH

SEZ-KA50VA.TH

SEZ-KA60VA.TH

SEZ-KA71VA.TH

Air outlet

Air outlet duct flange

inlet

(Selecting the either back side or bottom side)

Wired remote controller

Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.

Operation buttons

Set Temperature buttons

 

 

 

Down

 

 

 

Up

 

 

 

Timer Menu button

 

 

 

(Monitor/Set button)

 

 

 

Mode button (Return button)

 

 

 

 

 

TEMP.

 

Set Time buttons

 

 

 

Back

 

MENU

ON/OFF

Ahead

BACK

MONITOR/SET

DAY

 

Timer On/Off button

PAR-21MAA

CLOCK

 

(Set Day button)

 

 

 

Opening the

 

 

 

door

 

 

 

 

 

Start/Stop button

 

 

Fan Speed button

 

 

Filter

button

 

 

(<return sign> button)

 

ON/OFF

Test Run button

 

 

 

 

 

 

Service button (Clear button)

 

FILTER

 

 

 

CHECK

TEST

 

 

OPERATION

 

Airflow Up/Down button

CLEAR

 

 

 

 

 

Louver button

 

 

(

 

Operation button)

 

 

 

 

To preceding operation

 

 

 

 

number

 

 

Ventilation button

 

 

(

Operation button)

 

 

 

 

To next operation number

2

Display

For purposes of this explanation, all parts of the display are shown as lit. During actual operation, only the relevant items will be lit.

Identifies the current operation

Shows the operating mode, etc.

*Multilanguage display is supported.

“Centrally Controlled” indicator

Indicates that operation of the remote controller has been prohibited by a master controller.

“Timer Is Off” indicator

Indicates that the timer is off.

Temperature Setting

Shows the target temperature.

Day-of-Week

Shows the current day of the week.

Time/Timer Display

Shows the current time, unless the simple or Auto Off timer is set.

If the simple or Auto Off timer is set, shows the time remaining.

TIME SUN MON TUE WED THU FRI SAT

TIMER

Hr

ON

AFTER

AFTER

OFF

ERROR CODE

 

FUNCTION

˚F˚C

 

FILTER

˚F˚C

 

 

WEEKLY

ONLY1Hr.

 

SIMPLE

 

AUTO OFF

Up/Down Air Direction indicator

The indicator shows the direction of the outcoming airflow.

“One Hour Only” indicator

Displayed if the airflow is set to Low and downward during COOL or DRY mode. (Operation varies according to model.)

The indicator goes off after one hour, at which time the airflow direction also changes.

Room Temperature display

Shows the room temperature.

Louver display

Indicates the action of the swing louver. Does not appear if the louver is stationary.

(Power On indicator)

Indicates that the power is on.

“Sensor” indication

Displayed when the remote controller sensor is used.

“Locked” indicator

Indicates that remote controller buttons have been locked.

“Clean The Filter” indicator

Comes on when it is time to clean the filter.

Timer indicators

The indicator comes on if the corresponding timer is set.

Fan Speed indicator

Shows the selected fan speed.

Ventilation indicator

Appears when the unit is running in Ventilation mode.

Caution

Only the Power on indicator lights when the unit is stopped and power supplied to the unit.

If you press a button for a feature that is not installed in the indoor unit, the remote controller will display the “Not Available” message.

If you are using the remote controller to operate multiple indoor units, this message will appear only if the feature is not present at the parent unit.

When power is turned ON for the first time, it is normal that “PLEASE WAIT” is displayed on the room temperature indication (For max. 2minutes). Please wait until this “PLEASE WAIT” indication disappears then start the operation.

3

2 SPECIFICATIONS

 

 

Indoor model

 

 

Function

 

 

Power supply

Capacity Air flow (High/Low)

Electrical

data

Power outlet

Auxiliary heater

 

 

Running current 1

 

 

Power input Rated frequency

 

 

Fan motor current 1

Fan

motor

Model

Winding

 

 

 

 

resistance (at20:)

 

 

Dimensions WoHoD

 

 

Weight

 

 

Air direction

remarks

Sound level (High/Low)

Fan speed (High/Low)

 

 

Special

Fan speed regulator

External satatic pressure

 

 

Thermistor TH1 (at 25:)

Thermistor TH2 (at 25:)

Thermistor TH5 (at 25:)

 

SEZ-KA35VA.TH

SEZ-KA50VA.TH

 

Cooling

Heating

Cooling

Heating

 

 

Single phase

Single phase

 

 

230V, 50Hz

230V, 50Hz

K /h

 

780/600

1020/720

A

 

10

 

20

A

 

0.40

 

0.55

W

 

60

 

80

A(kW)

 

 

A

 

0.22

 

0.27

 

 

PK6V19-EF

PK6V32-EF

 

WHT-BLK : 257 BLK-BLU : 20

WHT-BLK : 166

BLK-BLU : 52

"

BLU-YLW : 27 YLW-BRN : 14

BLU-YLW : 19

YLW-BRN : 8

 

BRN-RED : 51(at 26:)

BRN-RED : 40(at 26:)

mm

1100o270o700

1100o270o700

kg

 

33.5

 

33.5

 

 

1

 

1

dB(A)

 

35/30

 

39/31

rpm

 

770/630

840/640

 

 

3

 

3

Pa

Std : 30 Max : 50

Std : 30 Max : 50

k"

 

10

 

10

k"

 

10

 

10

k"

 

10

 

10

NOTE : Test conditions are based on ISO 5151

Cooling : Indoor

D.B. 27: W.B. 19:

Outdoor D.B. 35: W.B. 24:

Heating : Indoor

D.B. 20: W.B. 15:

Outdoor D.B. 7: W.B. 6: Refrigerant piping length (one way): 5m

1 Measured under rated operating frequency.

Specifications and rating conditions of main electric parts

INDOOR UNIT

Item

Model

SEZ-KA35VA.TH SEZ-KA50VA.TH SEZ-KA60VA.TH SEZ-KA71VA.TH

 

 

 

Indoor fan capacitor

(C1)

SEZ-KA35/50VA.TH : 2.5+ 440V SEZ-KA60VA.TH : 3.0+ 440V SEZ-KA71VA.TH : 4.0+ 440V

Fuse

(FUSE)

250V 6.3A

Varistor

(ZNR)

ERZV10D471

Terminal block

(TB)

TO OUTDOOR UNIT : 3P TO WIRED REMOTE CONTROLLER : 2P

Indoor fan motor thermal fuse

141:i3:

4

 

 

Indoor model

 

 

Function

 

 

Power supply

Capacity Air flow (High/Low)

Electrical

data

Power outlet

Auxiliary heater

 

 

Running current 1

 

 

Power input Rated frequency

 

 

Fan motor current 1

Fan

motor

Model

Winding

 

 

 

 

resistance

 

 

Dimensions WoHoD

 

 

Weight

 

 

Air direction

remarks

Sound level(High/Low)

Fan speed(High/Low)

 

 

 

 

Fan speed regulator

Special

External satatic pressure

Thermistor TH2 (at 25:)

 

 

Thermistor TH1 (at 25:)

Thermistor TH5 (at 25:)

 

SEZ-KA60VA.TH

SEZ-KA71VA.TH

 

Cooling

Heating

Cooling

 

Heating

 

 

 

Single phase

Single phase

 

230V, 50Hz

230V, 50Hz

K /h

1200/720

1200/720

A

 

20

 

20

A

 

0.65

 

0.60

W

 

100

 

130

A(kW)

 

 

A

 

0.39

 

0.51

 

PK6V50-EF

PK4V60-EA

 

WHT-BLK : 103

BLK-BLU : 57

WHT-BLK : 108

 

BLK-BLU : 29

"

BLU-YLW : 15

YLW-BRN : 7

BLU-YLW : 26

 

YLW-BRN : 14

 

BRN-RED : 29 (at 26:)

BRN-RED : 34 (at 26:)

mm

1100o270o700

1100o270o700

kg

 

33.5

 

35

 

 

1

 

1

dB(A)

43/32

43/32

rpm

890/660

1050/690

 

 

3

 

3

Pa

Std : 30 Max : 50

Std : 30 Max : 50

k"

 

10

 

10

k"

 

10

 

10

k"

 

10

 

10

NOTE : Test conditions are based on ISO 5151

Cooling : Indoor

D.B. 27: W.B. 19:

Outdoor D.B. 35: W.B. 24:

Heating : Indoor

D.B. 20: W.B. 15:

Outdoor D.B. 7: W.B. 6: Refrigerant piping length (one way): 5m

1 Measured under rated operating frequency.

5

Mitsubishi SEZ-KA35VA, SEZ-KA50VA, SEZ-KA60VA, SEZ-KA71VA Service Manual

NOISE CRITERION CURVES

<50Hz>

SEZ-KA35VA.TH

NOTCH SPL(dB) LINE

 

 

 

 

 

 

 

High

35

 

 

 

 

 

 

 

 

Low

30

 

 

90

 

 

 

 

 

 

 

 

bar)

80

 

 

 

 

 

 

 

 

= 0.0002

70

 

 

 

 

 

 

 

 

dB

 

 

 

 

 

 

 

NC-70

 

 

 

 

 

 

 

 

dB (0

60

 

 

 

 

 

 

 

 

LEVEL,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-60

 

 

 

 

 

 

 

 

 

PRESSURE

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-50

40

 

 

 

 

 

 

 

 

SOUND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-40

 

 

 

 

 

 

 

 

 

BAND

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-30

 

 

 

 

 

 

 

 

 

OCTAVE

20

APPROXIMATE

 

 

 

 

 

 

 

TERESHOLD OF

 

 

 

 

 

 

 

HEARING FOR

 

 

 

 

 

NC-20

 

 

CONTINUOUS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOISE

 

 

 

 

 

 

 

 

10

63

125

250

500

1000

2000

4000

8000

 

 

BAND CENTER FREQUENCIES, Hz

<50Hz>

SEZ-KA50VA.TH

NOTCH SPL(dB) LINE

 

 

 

 

 

 

 

High

39

 

 

 

 

 

 

 

 

Low

31

 

 

90

 

 

 

 

 

 

 

 

bar)

80

 

 

 

 

 

 

 

 

= 0.0002

70

 

 

 

 

 

 

 

 

dB

 

 

 

 

 

 

 

NC-70

 

 

 

 

 

 

 

 

dB (0

60

 

 

 

 

 

 

 

 

LEVEL,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-60

 

 

 

 

 

 

 

 

 

PRESSURE

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-50

40

 

 

 

 

 

 

 

 

SOUND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-40

 

 

 

 

 

 

 

 

 

BAND

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-30

 

 

 

 

 

 

 

 

 

OCTAVE

20

APPROXIMATE

 

 

 

 

 

 

 

TERESHOLD OF

 

 

 

 

 

 

 

HEARING FOR

 

 

 

 

 

NC-20

 

 

CONTINUOUS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOISE

 

 

 

 

 

 

 

 

10

63

125

250

500

1000

2000

4000

8000

 

 

BAND CENTER FREQUENCIES, Hz

SEZ-KA60VA.TH

 

 

 

<50Hz>

 

 

 

NOTCH

SPL(dB)

LINE

 

 

SEZ-KA71VA.TH

 

 

High

43

 

 

 

 

 

Low

32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90

 

 

 

 

 

 

 

 

 

 

bar)

80

 

 

 

 

 

 

 

 

 

UNIT

= 0.0002

70

 

 

 

 

 

 

 

NC-70

 

 

dB (0 dB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

External static

 

LEVEL,

 

 

 

 

 

 

 

NC-60

1.5m

 

 

 

 

 

 

 

 

pressure 30Pa

 

 

 

 

 

 

 

 

 

 

PRESSURE

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-50

 

 

SOUND

40

 

 

 

 

 

 

 

 

 

MICROPHONE

 

 

 

 

 

 

 

 

NC-40

 

 

BAND

 

 

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OCTAVE

 

 

 

 

 

 

 

 

NC-30

 

 

20

HEARING FOR

 

 

 

 

 

 

 

 

 

APPROXIMATE

 

 

 

 

 

 

 

 

 

 

TERESHOLD OF

 

 

 

 

 

 

 

 

 

 

CONTINUOUS

 

 

 

 

 

NC-20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOISE

 

 

 

 

 

 

 

 

 

 

10

63

125

250

500

1000

2000

4000

8000

 

 

 

 

 

 

BAND CENTER FREQUENCIES, Hz

NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound may be bigger than displayed level under actual installation condition by surrounding echoes. The sound level can be higher by about 2 dB than the displayed level during cooling and heating operation.

6

INDOOR FAN PERFORMANCE AND CORRECTED AIR FLOW

SEZ-KA35VA.TH

Fan Performance

Recommended range

80

pressure(Pa) 60 staticExternal 0.1mmAq)= (1Pa

40

20

0

5

7

10

15

20

25

 

Air flow (K/X)

Correction factor

Correction factor

Corrected Air flow

Capacity

Cooling

Input

 

1.1

1.0

0.9

0.8

5

10

15

20

25

Air flow (K/X)

Heating

1.3

1.2

1.1

1.0

0.9

0.8

5

10

15

20

25

Air flow (K/X)

SEZ-KA50VA.TH

Fan Performance

Recommended range

80

pressure(Pa) 60 staticExternal 0.1mmAq)= (1Pa

40

20

0

5

10

15

20

25

 

Air flow (K/X)

 

 

Corrected Airflow

 

 

Capacity

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

Input

 

1.1

 

 

 

 

 

 

 

 

factor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Correction

0.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

 

 

 

10

15

20

25

 

5

 

 

 

 

Air flow (K/X)

 

 

 

 

 

1.2

Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

factor

1.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Correction

0.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

 

 

 

10

15

20

25

 

5

Air flow (K/X)

7

INDOOR FAN PERFORMANCE AND CORRECTED AIR FLOW

SEZ-KA60VA.TH

Fan Performance

Recommended range

80

pressure(Pa) 60 staticExternal 0.1mmAq)= (1Pa

40

20

0

5

10

15

20

25

 

Air flow (K/X)

Correction factor

Correction factor

Corrected Air flow

Capacity

Cooling

Input

 

1.1

1.0

0.9

0.8

10

15

20

25

30

Air flow (K/X)

Heating

1.3

1.2

1.1

1.0

0.9

10

15

20

25

30

Air flow (K/X)

SEZ-KA71VA.TH

Fan Performance

Recommended range

80

pressure(Pa) 60 staticExternal 0.1mmAq)= (1Pa

40

20

0

5

10

15

20

25

 

Air flow (K/X)

Correction factor

Correction factor

Corrected Air flow

Capacity

Cooling

Input

 

1.1

1.0

0.9

0.8

10

15

20

25

30

Air flow (K/X)

Heating

1.3

1.2

1.1

1.0

0.9

10

15

20

25

30

Air flow (K/X)

8

3 OUTLINES AND DIMENSIONS

SEZ-KA35VA.TH SEZ-KA50VA.TH SEZ-KA60VA.TH SEZ-KA71VA.TH

Air inlet (rear side) dimensions

 

 

42

930

 

 

 

(Inlet size)

240

120

 

 

 

12.5

77.5 100

7x100=700

 

29

955

 

 

24-{2.9 holes

In case of bottom side suction, mount the PLATE (A) on the rear side.

After installation, remove the transportation support PLATE (B).

215

(Inlet size)

25

 

PLATE (B) x 2

5027

1016

150

450

 

Air inlet

 

Electrical parts box

 

(rear side)

 

 

 

w Select the either

77

150

 

back side or bottom side.

 

 

 

 

50

Unit : mm

Air inlet (bottom side) dimensions

PLATE (A)

240

120

930

215

(Inletsize)

 

51

 

 

 

 

(Inlet size)

 

 

12.5

39 77.5 100

7x100=700

25

 

 

 

 

 

 

955

 

 

1000

680

350

Suspension bolt pitch

 

 

38

50

 

 

60

 

 

 

(10)

Suspension bolt M10 or 3/8 (procure locally)

 

 

 

 

 

 

 

 

24-{2.9 holes

 

 

 

 

 

 

600

 

 

 

 

 

 

 

700

 

Access door

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Service space

 

 

 

 

 

 

 

 

 

(It is necessary to maintain a working

 

 

 

 

 

 

service area from the ceiling.)

 

 

40

100

7x100=700

 

 

 

 

 

 

 

50

 

880

Air outlet duct flange

 

 

 

 

 

 

9 x 2-{2.9 holes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air outlet

 

 

 

 

 

 

 

 

 

1070

 

 

 

 

 

 

 

 

 

Suspension bolt pitch

more

 

 

 

 

Refrigerent pipe (gas)

 

 

 

 

 

 

 

 

 

 

 

(1070)

 

 

 

 

Refrigerent pipe (liquid)

 

 

or

 

 

 

 

 

 

 

 

(10)

50

 

 

 

 

(Suspension bolt pitch)

20

 

 

 

Terminal block

 

 

 

25

32.5

 

Wiring entry

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

Electrical parts box

170

100

 

 

 

 

 

 

270

 

 

 

 

 

 

 

75

 

 

 

 

1100

Air inlet

Access door

(bottom side)

 

w Select the either back side or bottom side.

2x2-{2.9 holes

Air outlet duct flange

Models

SEZ-KA35VA

SEZ-KA50VA

SEZ-KA60VA

SEZ-KA71VA

108

25

Electrical parts box

94

80

Drain plug R1 (male)

 

350

 

 

Refrigerent pipe

Refrigerent pipe

(liquid)

(gas)

{6.35mm

{9.52mm

flared connection

flared connection

1/4F

 

3/8F

{6.35mm

{12.7mm

flared connection

flared connection

1/4F

 

1/2F

{6.35mm

{15.88mm

flared connection

flared connection

1/4F

 

5/8F

{9.52mm

{15.88mm

flared connection

flared connection

3/8F

 

5/8F

9

4 WIRING DIAGRAM

SEZ-KA35VA.TH

SEZ-KA50VA.TH

SEZ-KA60VA.TH

SEZ-KA71VA.TH

MF

WHT

ORN

RED

BLK

YLW

BLU

BRN

 

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

ORN

 

 

 

YLW

BLU

 

 

C1

RED

 

<fig:w1>

MODELS

SW2

BLK

BLU

BRN

WHT

RED

WHT

 

RED

BLU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KA35

ON

 

 

 

WHT

 

 

RED

 

 

 

ORN

 

OFF

1 2

3 4

5 6

1

3

1

3

 

 

 

(POWER)

 

1 2 3 4 5

7 (FAN)

(POWER

 

 

 

 

 

FAN

 

 

BOARD)

 

 

 

CND

 

 

 

 

 

 

 

 

 

 

 

 

KA50

ON

 

 

 

 

 

 

CNDK

 

 

 

 

 

OFF

 

 

 

 

 

 

FUSE

 

 

 

 

 

 

1 2 3 4 5

 

 

 

 

 

 

 

 

 

 

 

 

KA60

ON

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

1 2 3 4 5

 

 

 

 

 

 

ZNR

 

 

 

 

 

 

ON

X6

X5

X4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KA71

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

1 2 3 4 5

X6

X5

X4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SWE

SW3

 

 

 

 

 

 

 

 

 

 

 

 

ON

ON

 

 

 

 

LED3

 

 

 

 

 

 

OFF

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 2 3 4 5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW2

CN2L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLK

RED

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(2 PHASE) (INTAKE)

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN29

CN20

 

1 2 3 4 5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN32

CN51

CN41

CN90

 

 

 

1

2

1

2

 

 

 

 

 

 

 

 

 

See fig:w1

TH5 TH1

[LEGEND]

SYMBOL

NAME

SYMBOL

NAME

P.B

INDOOR POWER BOARD

C1

CAPACITOR(FAN MOTOR)

I.B

INDOOR CONTROLLER BOARD

MF

FAN MOTOR

 

CN2L

CONNECTOR(LOSSNAY)

TB4

TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE)

 

CN32

CONNECTOR(REMOTE SWITCH)

 

TERMINAL BLOCK(REMOTE CONTROLLER

 

CN41

CONNECTOR(HA TERMINAL-A)

TB15

TRANSMISSION LINE)

 

 

 

 

 

 

 

 

CN51

CENTRALLY CONTROL

TH1

ROOM TEMP.THERMISTOR

 

CN90

CONNECTOR(WIRELESS)

(0°C/15kΩ ,25°C/5.4kΩ DETECT)

 

 

 

FUSE

FUSE(T6.3AL250V)

TH2

PIPE TEMP.THERMISTOR/LIQUID

 

LED1

POWER SUPPLY(I.B)

(0°C/15kΩ ,25°C/5.4kΩ DETECT)

 

 

 

LED2

POWER SUPPLY(I.B)

TH5

COND./EVA.TEMP.THERMISTOR

 

 

 

(0°C/15kΩ ,25°C/5.4kΩ DETECT)

 

LED3

TRANSMISSION(INDOOR-OUTDOOR)

 

 

 

SW2

SWITCH(CAPACITY CODE)

 

 

 

SW3

SWITCH(MODE SELECTION)

 

 

 

SWE

SWITCH(EMERGENCY OPERATION)

 

 

 

 

 

 

 

 

X4

RELAY(FAN MOTOR LL)

 

 

 

 

 

 

 

 

X5

RELAY(FAN MOTOR Lo)

 

 

 

X6

RELAY(FAN MOTOR Hi)

 

 

 

ZNR

VARISTOR

 

 

TB4

 

 

 

 

 

S1

 

 

 

 

 

 

 

 

S2

TO OUTDOOR

 

 

 

 

 

S3

 

 

 

 

 

UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P.B

 

 

 

 

 

 

1 2

3

AC220-240V

 

 

 

 

 

 

 

 

CNSK(RED)

 

ORN

BLU

I.B

 

 

 

 

 

1

3

 

 

 

 

 

TRANS

 

BLU

 

 

 

 

 

 

 

(CONTROL)

 

 

 

 

 

 

CN3C

 

 

 

 

 

 

 

 

 

 

 

 

1

2

DC13.1V

 

 

 

 

 

 

 

 

CN2S(WHT)

 

 

WHT

 

1

BLK

 

 

 

 

(POWER

 

WHT

 

 

 

 

BOARD)

2

 

 

 

 

CN2D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LED1

 

 

 

 

 

LED2

 

 

 

 

 

 

 

WHT

BLU

 

 

 

 

 

(LIQUID)

(REMOCON)

 

 

 

CN21

CN22

 

 

 

 

1

2

1

2

 

 

 

 

 

 

 

BLU

BLU

 

 

 

 

 

 

 

 

 

TB15

 

 

 

 

 

 

 

 

1

TO MA-REMOTE

 

 

 

 

 

 

TH2

 

 

 

2 }CONTROLLERDC8.7-13V

NOTES: 1.Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.

2.Indoor and outdoor connecting wires are made with polarities,make

wiring matching terminal numbers(S1,S2,S3).

 

 

 

 

 

 

 

3.Symbols used in wiring diagram above are,

:Connector,

:Terminal(block).

4.Since the indoor fan motor(MF) is connected with 50Hz power,

 

 

 

if 60Hz power is used, change the wiring connection shown in

 

 

 

fig:w2.

 

<fig:w2>

 

 

 

 

 

 

 

 

Indoor Fan Motor(MF)

 

 

 

50

 

YELLOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

for 60Hz

BLUE

 

 

60

 

 

BLUE

 

 

 

 

 

wFor details on how to operate self-diagnosis, refer to the technical manuals etc.

10