Mitsubishi SEZ-A12AR.TH, SEZ-A18AR.TH, SEZ-A24AR.TH Service Manual

0 (0)

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS

No. OC303

TECHNICAL & SERVICE MANUAL

 

 

Ceiling Concealed

R410A

 

 

Series SEZ

 

Indoor unit

 

 

 

[Model names]

[Service Ref.]

SEZ-A12AR

SEZ-A12AR.TH

SEZ-A18AR

SEZ-A18AR.TH

SEZ-A24AR

SEZ-A24AR.TH

•This manual does not cover the following outdoor units. When servicing them, please refer to the service manual No.OC304 and this manual in a set.

CONTENTS

1. PART NAMES AND FUNCTIONS ······

2. SPECIFICATIONS·············

3. OUTLINES AND DIMENSIONS·······

Model name

4. WIRING DIAGRAM·············

indication

5.REFRIGERANT SYSTEM DIAGRAM ······

6.TROUBLESHOOTING···········

 

 

 

7. DISASSEMBLY PROCEDURE········

INDOOR UNIT

8. PARTS LIST················

 

 

 

9. OPTIONAL PARTS ·············

CENTRALLY CONTROLLED

1Hr.

 

 

ON OFF

˚C

 

CHECK

CLOCK

 

 

 

 

FILTER

 

˚C

 

CHECK MODE

 

 

TEST RUN

 

STAND BY

ERROR CODE

NOT AVAILABLE FUNCTION

 

DEFROST

 

TEMP.

 

ON/OFF

 

WIRED REMOTE CONTROLLER

1 PART NAMES AND FUNCTIONS

Indoor Unit

SEZ-A12AR.TH

SEZ-A18AR.TH

SEZ-A24AR.TH

Air outlet

Air outlet duct flange

inlet

(Selecting the either back side or bottom side)

Wired remote controller

On the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.

Operation buttons

 

 

TEMP. ADJUSTMENT button

 

 

TIME SETTING button

 

 

 

 

 

 

 

 

 

 

 

This sets the room temperature. The

 

 

This sets the current time, start time

 

 

temperature setting can be performed

 

 

and stop time.

 

 

in 1: units

 

 

 

 

 

 

 

 

 

 

 

Setting range

 

 

 

 

 

 

Cooling 19: to 30:

 

 

 

 

 

 

Heating 17: to 28:

 

 

 

 

 

 

 

 

 

 

 

TIMER button

This switches between continuous operation and the timer operation.

OPERATION SWITCH button

Press this button to switch the cooling, electronic dry (dehumidify), automatic and heating modes.

 

CENTRALLY CONTROLLED

1Hr.

 

 

 

ON OFF

 

˚C

 

CHECK

CLOCK

 

 

 

 

 

 

 

 

 

 

FILTER

 

˚C

 

 

CHECK MODE

STAND BY

ERROR CODE

 

TEST RUN

 

NOT AVAILABLE

FUNCTION

DEFROST

 

 

 

 

TEMP.

 

 

ON/OFF

FILTER

CHECK TEST

PAR-20MAA

TIMER SET

FAN SPEED button

This sets the ventilation fan speed.

ON/OFF button

This switches between the operation and stop modes each time it is pressed. The lamp on this button lights during operation.

AIR DIRECTION button

This adjusts the vertical angle of the ventilation.

(Not available for this model.)

FILTER button

This resets the filter service indication display

LOUVER button

This switch the horizontal fan motion ON and OFF.

(Not available for this model.)

VENTILATION button

This sets the ventilation fan speed.

(Not available for this model.)

CHECK-TEST RUN button

Only press this button to perform an inspection check or test operation. Do not use it for normal operation.

2

Display

CENTRALLY CONTROLLED display

This indicates when the unit is controlled by optional features such as central control type remote controller.

TIMER display

This indicates when the continuous operation and time operation modes are set.

It also display the time for the timer operation at the same time as when it is set.

OPERATION MODE display

This indicates the operation mode.

STANDBY display

The [STANDBY] symbol is only displayed from the time the heating operation starts unit the heated air begins to blow.

DEFROST display

This indicates when the defrost operation is performed.

CLOCK display

 

In this display example on the bot-

 

tom left, a condition where all dis-

 

 

The current time , start time and stop

 

play lamps light is shown for expla-

time can be displayed in ten second

 

nation purposes although this differs

intervals by pressing the time switch

 

from actual operation.

button. The start time or stop time is

 

 

 

 

 

always displayed during the timer

 

 

 

 

operation.

 

 

 

 

 

 

AIR DIRECTION display

 

 

 

 

 

 

 

 

This displays the air direction.

 

 

 

 

 

 

 

 

(Not available for this model.)

 

 

 

 

 

 

 

AIR SPEED display

 

 

 

 

 

 

CENTRALLY CONTROLLED

1Hr.

 

 

 

ON OFF

 

˚C

 

CHECK

CLOCK

 

 

 

 

 

 

 

 

 

 

FILTER

 

˚C

 

 

CHECK MODE

STAND BY

ERROR CODE

 

TEST RUN

 

NOT AVAILABLE

FUNCTION

DEFROST

 

 

 

 

TEMP.

 

 

ON/OFF

FILTER

CHECK TEST

PAR-20MAA

TIMER SET

The selected fan speed is displayed.

ROOM TEMPERATURE display

The temperature of the suction air is displayed during operation. The display range is 8°C to 39°C. The display flashes 8°C when the actual temperature is less than 8°C and flashes 39°C when the actual temperature is greater than 39°C.

Operation lamp

This lamp lights during operation, goes off when the unit stops and flashes when a malfunction occurs.

CHECK MODE

display

TEST RUN

This display lights in the check mode or when a test operation is performed.

CHECK display

 

 

 

 

 

 

SET TEMPERATURE display

 

POWER display

This indicates when a malfunction

 

 

 

 

has occurred in the unit which should

 

This displays the selected setting

 

This lamp lights when electricity is

be checked.

 

 

 

temperature.

 

supplied to the unit.

 

 

 

 

 

 

 

 

Caution

FILTER display

This lamp lights when the filter need to be cleaned.

Only the Power display lights when the unit is stopped and power supplied to the unit.

When the central control remote control unit, which is sold separately, is used the ON-OFF button, operation switch button and TEMP. adjustment button do not operate.

“NOT AVAILABLE” is displayed when the Air speed button are pressed.This indicates that this room unit is not equipped with the fan direction adjustment function and the louver function.

When power is turned ON for the first time, it is normal that “H0” is displayed on the room temperature indication (For max. 2minutes). Please wait until this “H0” indication disappear then start the operation.

3

2 SPECIFICATIONS

 

 

Indoor model

 

SEZ-A12AR.TH

 

 

Function

 

 

Cooling

Heating

 

 

Power supply

 

Single phase

 

 

 

230V, 50Hz

 

 

 

 

 

Capacity Air flow (High/Low)

 

K /h

780/600

 

 

Power outlet

 

A

10

 

Electrical

data

Running current 1

A

0.21

 

Power input Rated frequency

W

33

 

 

 

 

 

 

Auxiliary heater

 

A(kW)

 

 

 

Power factor 1

 

%

94

95

 

 

Fan motor current

1

A

0.21

 

Fan

motor

Model

 

"

PK6V19-EF

 

 

BLU-YLW : 26.5

YLW-BRN : 13.2

 

 

Winding

 

 

WHT-BLK : 251.4

BLK-BLU : 19.9

 

 

 

 

 

 

 

 

resistance (at20:)

 

 

BRN-RED : 50.0

 

 

 

 

 

 

 

Dimensions WoHoD

mm

1100o270o700

 

 

Weight

 

kg

33.5

 

remarks

Air direction

 

 

1

 

Sound level (High/Low)

dB(A)

35/30

 

 

 

 

Fan speed (High/Low)

rpm

770/630

Special

Fan speed regulator

 

3

 

Thermistor RT11 (at 25:)

k"

10

 

 

 

 

 

 

Thermistor RT12 (at 25:)

k"

10

 

 

 

Thermistor RT13 (at 25:)

k"

10

 

 

 

Remote controller model

 

PAR-20MAA

NOTE : Test conditions are based on ISO 5151

 

 

 

Cooling : Indoor

D.B. 27: W.B. 19:

 

 

 

Outdoor D.B. 35: W.B. 24:

 

 

 

Heating : Indoor

D.B. 20: W.B. 5:

 

 

 

Outdoor D.B. 7: W.B. 6:

 

Refrigerant piping length (one way): 5m

1 Measured under rated operating frequency.

SEZ-A18AR.TH

Cooling

Heating

Single phase

230V, 50Hz

1020/720

20

 

0.27

49

 

 

97

98

0.27

PK6V32-EF

WHT-BLK : 161.9

BLK-BLU : 50.3

BLU-YLW : 18.7 YLW-BRN : 8.0

BRN-RED : 39.2

1100o270o700

33.5

1

39/31

840/640

3

10

10

10 PAR-20MAA

Specifications and rating conditions of main electric parts

INDOOR UNIT

Item

Model

SEZ-A12AR.TH SEZ-A18AR.TH SEZ-A24AR.TH

 

 

 

Indoor fan capacitor

(C1)

SEZ-A12/18AR.TH : 2.5+ 440V SEZ-A24AR.TH : 3.0+ 440V

Fuse

(FUSE)

250V 3.15A

Varistor

(ZNR1)

ERZV10D471

Terminal block

(TB)

POWER SUPPLY : 3P TO OUTDOOR UNIT : 4P

Contactor

(52C)

G4A-1A-E-PS 12V DC

Indoor fan motor thermal fuse

145:i2:

4

 

 

Indoor model

 

 

Function

 

 

Power supply

Capacity Air flow (High/Low)

 

 

Power outlet

Electrical

data

Running current 1

Power input Rated frequency

 

 

 

 

Auxiliary heater

 

 

Power factor 1

 

 

Fan motor current 1

Fan

motor

Model

Winding

 

 

 

 

resistance (at20:)

 

 

Dimensions WoHoD

 

 

Weight

remarks

Air direction

Sound level(High/Low)

 

 

 

 

Fan speed(High/Low)

Special

Fan speed regulator

 

Thermistor RT11 (at 25:)

Thermistor RT12 (at 25:)

Thermistor RT13 (at 25:) Remote controller model

 

SEZ-A24AR.TH

 

Cooling

Heating

 

 

Single phase

 

 

230V, 50Hz

K /h

 

1200/720

A

 

20

A

 

0.34

W

 

64

A(kW)

 

%

98

98

A

 

0.34

 

 

PK6V50-EF

 

WHT-BLK : 101.1 BLK-BLU : 56.1

"BLU-YLW : 14.7 YLW-BRN : 6.7

 

BRN-RED : 28.2

mm

1100o270o700

kg

33.5

 

1

dB(A)

43/32

rpm

890/660

 

3

k"

10

k"

10

k"

10

 

PAR-20MAA

NOTE : Test conditions are based on ISO 5151

Cooling : Indoor

D.B. 27: W.B. 19:

Outdoor D.B. 35: W.B. 24:

Heating : Indoor

D.B. 20: W.B. 15:

Outdoor D.B. 7: W.B. 6: Refrigerant piping length (one way): 5m

1 Measured under rated operating frequency.

5

Mitsubishi SEZ-A12AR.TH, SEZ-A18AR.TH, SEZ-A24AR.TH Service Manual

NOISE CRITERION CURVES

<50Hz>

SEZ-A12AR.TH

NOTCH SPL(dB) LINE

 

 

 

 

 

 

 

Hi

35

 

 

 

 

 

 

 

 

Lo

30

 

 

90

 

 

 

 

 

 

 

 

bar)

80

 

 

 

 

 

 

 

 

= 0.0002

70

 

 

 

 

 

 

 

 

dB (0 dB

 

 

 

 

 

 

 

NC-70

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

LEVEL,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-60

 

 

 

 

 

 

 

 

 

PRESSURE

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-50

40

 

 

 

 

 

 

 

 

SOUND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-40

 

 

 

 

 

 

 

 

 

BAND

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-30

 

 

 

 

 

 

 

 

 

OCTAVE

20

APPROXIMATE

 

 

 

 

 

 

 

TERESHOLD OF

 

 

 

 

 

 

 

HEARING FOR

 

 

 

 

 

NC-20

 

 

CONTINUOUS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOISE

 

 

 

 

 

 

 

 

10

63

125

250

500

1000

2000

4000

8000

 

 

BAND CENTER FREQUENCIES, Hz

<50Hz>

SEZ-A18AR.TH

NOTCH SPL(dB) LINE

 

 

 

 

 

 

 

Hi

39

 

 

 

 

 

 

 

 

Lo

31

 

 

90

 

 

 

 

 

 

 

 

bar)

80

 

 

 

 

 

 

 

 

= 0.0002

70

 

 

 

 

 

 

 

 

dB (0 dB

 

 

 

 

 

 

 

NC-70

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

LEVEL,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-60

 

 

 

 

 

 

 

 

 

PRESSURE

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-50

40

 

 

 

 

 

 

 

 

SOUND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-40

 

 

 

 

 

 

 

 

 

BAND

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-30

 

 

 

 

 

 

 

 

 

OCTAVE

20

APPROXIMATE

 

 

 

 

 

 

 

TERESHOLD OF

 

 

 

 

 

 

 

HEARING FOR

 

 

 

 

 

NC-20

 

 

CONTINUOUS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOISE

 

 

 

 

 

 

 

 

10

63

125

250

500

1000

2000

4000

8000

 

 

BAND CENTER FREQUENCIES, Hz

<50Hz>

SEZ-A24AR.TH

NOTCH SPL(dB) LINE

 

 

 

 

 

 

 

Hi

43

 

 

 

 

 

 

 

 

 

 

Lo

32

 

 

 

 

90

 

 

 

 

 

 

 

 

 

 

bar)

80

 

 

 

 

 

 

 

 

 

UNIT

= 0.0002

70

 

 

 

 

 

 

 

 

 

 

dB(0dB

 

 

 

 

 

 

 

NC-70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEVEL,

60

 

 

 

 

 

 

 

NC-60

External static

1.5m

 

 

 

 

 

 

 

 

pressure 30Pa

 

 

 

 

 

 

 

 

 

 

PRESSURE

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-50

 

 

SOUND

40

 

 

 

 

 

 

 

 

 

MICROPHONE

 

 

 

 

 

 

 

 

NC-40

 

 

BAND

 

 

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OCTAVE

 

 

 

 

 

 

 

 

NC-30

 

 

20

HEARING FOR

 

 

 

 

 

 

 

 

 

APPROXIMATE

 

 

 

 

 

 

 

 

 

 

TERESHOLD OF

 

 

 

 

 

 

 

 

 

 

CONTINUOUS

 

 

 

 

 

NC-20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOISE

 

 

 

 

 

 

 

 

 

 

10

63

125

250

500

1000

2000

4000

8000

 

 

 

 

 

 

BAND CENTER FREQUENCIES, Hz

NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound may be bigger than displayed level under actual installation condition by surrounding echoes. The sound level can be higher by about 2 dB than the displayed level during cooling and heating operation.

6

3 OUTLINES AND DIMENSIONS

SEZ-A12AR.TH SEZ-A18AR.TH SEZ-A24AR.TH

Unit : mm

Air inlet (rear side) dimensions

In case of bottom side suction,

 

mount the PLATE (A) on the rear side.

 

 

42

930

 

 

 

(Inlet size)

240

120

 

 

 

12.5

77.5 100

7o100=700

 

29

955

 

 

 

 

 

24-[2.9 holes

 

 

5027

1016

50

1000

680 38

pitch

Suspensionbolt

 

350

 

 

60

50

 

 

(10)

40

100

50

 

Air inlet (rear side)

wSelect the either

back side or bottom side.

7o100=700

880

9o2-[2.9 holes

Air outlet

After installation, remove the

transportation support PLATE (B).

 

215

(Inlet size)

 

 

25

 

 

 

PLATE (B) o2

 

 

 

 

 

51

150

450

240

120

 

 

 

Electrical parts box

12.5

 

77

 

 

 

150

 

 

 

 

 

 

600

 

700

 

Access door

 

 

 

 

Service space

 

 

(It is necessary to

 

 

maintain a working

 

 

service area from

 

 

the ceiling.)

 

Air outlet duct flange

 

 

Air inlet (bottom side) dimensions

PLATE (A)

 

930

215

size)(Inlet

 

(Inlet size)

 

 

3977.5 100

7o100=700

25

 

 

 

 

955

 

 

24-[2.9 holes

1070

Suspension bolt pitch

Refrigerent pipe (gas)

Suspension bolt

 

more

M10 or 3/8

(1070)

(procure locally)

or

 

(Suspension bolt pitch)

 

20

 

 

30

Electrical parts box

 

270

1100

 

Air inlet

Access door

(bottom side)

w Select the either back side or bottom side.

 

(10)

50

25

32.5

20

170

100

 

75

 

108

 

 

2o2-[2.9 holes

94

Air outlet duct flange

25

80

350

Refrigerent pipe (liquid)

Terminal

block

Wiring entry

Electrical parts box

Drain plug R1 male

Models

SEZ-A12AR

SEZ-A18AR

SEZ-A24AR

Refrigerent pipe

Refrigerent pipe

(liquid)

(gas)

[6.35mm

[9.52mm

flared connection

flared connection

1/4F

3/8F

[6.35mm

[12.7mm

flared connection

flared connection

1/4F

1/2F

[6.35mm

[15.88mm

flared connection

flared connection

1/4F

5/8F

7

50 YELLOW
60 BLUE
fig: *1

4 WIRING DIAGRAM

SEZ-A12AR.TH

SEZ-A18AR.TH

SEZ-A24AR.TH

CIRCUIT BREAKER

TB

 

 

L

w WHT

 

 

N

w BLU

 

 

 

GRN/YLW

POWER SUPPLY

 

~/N

 

 

 

220-240V 220V

 

50Hz

60Hz

 

 

 

TB

12VDC

3

w RED

FOR A12

 

 

 

(1:1 SYSTEM) 220-240V~

2

w WHT

TO OUTDOOR

 

N

w BLU

 

 

 

UNIT

 

 

 

CONNECTING

 

 

GRN/YLW

 

 

 

FOR A18/24 (1:1 SYSTEM)

 

 

OR MULTI SYSTEM

 

 

 

12V DC 3

 

 

TO OUTDOOR

2

 

 

UNIT

 

 

 

CONNECTING

N

 

 

[LEGEND]

 

SYMBOL

NAME

I.B

INDOOR CONTROLLER

 

BOARD

C1

FAN MOTOR CAPACITOR

FUSE

FUSE(3.15A)

X2,X4,X5 RELAY(FAN MOTOR)

ZNR1

VARISTOR

52C

COMPRESSOR CONTACTOR

I.B

 

 

5

CND(POWER)

52C

 

CN29

2

 

 

3

RED

 

4

 

(2 PHASE)

1

 

 

1

 

 

 

 

BLK

RT13

 

 

 

 

 

FUSE

CN21

 

 

 

 

 

w

2

 

 

 

 

 

(LIQUID)

 

 

 

 

 

 

 

1

 

 

 

 

 

3

 

WHT

 

 

 

 

 

 

 

CN20

RT12

 

 

 

 

 

 

ZNR1

2

 

 

 

 

 

 

(INTAKE)

1

 

 

 

 

 

 

 

RED

RT11

 

 

 

 

 

 

 

 

 

 

 

 

TRANS

 

 

 

 

 

 

FAN1

DC13.1V

 

 

 

 

 

 

(FAN)

 

 

 

 

 

 

WHT

7

WHT

X2

 

 

 

 

 

BLK

 

 

 

 

 

 

5

 

 

 

 

 

 

BLU

 

X2

 

 

 

 

 

3

 

X4

 

 

 

 

 

 

 

 

 

 

 

 

YLW

BLU 1

 

 

 

 

 

MF

FAN2(FAN)

X4

 

 

 

 

BRN

 

X5

 

CN22

 

 

5 WHT

X5

 

 

 

RED

3

 

 

 

(REMOCON)

 

 

ORN

C1

 

 

BLU

 

 

1

 

 

 

 

 

 

 

 

1

2

 

 

 

 

 

 

 

 

 

 

 

TRANSMISSION WIRE

TB 2

BLU

 

 

 

 

 

 

DC12V

 

 

 

 

 

 

 

 

1

BLU

 

 

 

 

 

 

R.B

 

 

 

 

 

 

 

CN2

2

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

TB

 

 

 

 

SYMBOL

 

NAME

 

The 12V DC is NOT always against the ground.

MF

FAN MOTOR

 

 

Terminal 3 has 12V DC against terminal N.

 

ROOM TEMPERATURE

RT11

However, between 3 and 2, these terminals are

THERMISTOR

 

 

 

NOT electrically insulated by the transformer or

RT12

PIPE TEMPERATURE

 

THERMISTOR / LIQUID

other device.

 

 

 

 

 

RT13

CONDENSER / EVAPORATOR

 

 

 

 

 

TEMPERATURE THERMISTOR

 

 

 

 

 

 

 

 

 

 

 

TB

TERMINAL BLOCK

 

 

 

 

 

 

R.B

REMOTE CONTROLLER

 

 

 

 

 

BOARD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

1.Since the indoor fan motor(MF) is connected with 50Hz power,if 60Hz power is used, change the wiring connection showing fig: *1

Indoor Fan Motor(MF) for 60Hz

BLUE

2.About the outdoor side electric wiring refer to the outdoor unit electlic wiring diagram for servicing. 3.Use copper conductors only. (For field wiring)

4.Symbols below indicate.

: Terminal block : Connector

How to remove the terminals shown at " w " mark.

" w " shows the terminals with a lock mechanism, so they cannot be removed when you pull the lead wire. Be sure to pull the wire by pushing the locking lever (projected part) of the terminal with a finger.

sleeve 1Slide the sleeve.

2Pull the wire while pushing the locking lever.

locking lever

8