LG LB-H2460CL, LB-G3060CL, LB-H1860CL, LB-G3660CL Installation Manual

0 (0)

CEILING DUCT TYPE AIR CONDITIONERS

INSTALLATION INSTRUCTIONS

 

<![if ! IE]>

<![endif]>ENGLISH

 

• Please read this instruction sheet completely before installing the product.

• When the power cord is wanted to replace, replacement work shall be performed by authorized

 

personnel only.

 

• Installation work must be performed in accordance with national wiring standards by authorized

 

personnel only.

 

 

 

Indoor Unit

 

 

 

Air outlet vents

Air filters

 

(Optional)

 

Air intake vents

 

 

 

Remote Controller

 

Outdoor Unit

 

 

 

Air Intake

Connecting Wire

 

(side, rear)

Power Wire

 

 

 

Air Outlet

 

Air Intake

Vents

Connection Tube

 

(side, rear)

 

 

Drain Hose

 

 

Air outlet

 

 

 

Control

 

 

cover

 

 

Connecting

 

 

wire

 

 

Connection Tube

 

 

Drain hose

 

 

 

P/No.: 3828A20168R

OUT-LINE OF INSTALLATION

1.The following should be always observed for safety ...............................

3

 

 

 

 

 

 

 

 

Installation works

 

 

 

Installation Parts

 

Required tools

 

 

 

 

 

 

 

 

2. Installation of Indoor, Outdoor unit

 

 

 

 

1) Selection of the best

 

 

 

Four Type “A” screws

 

Level

 

location............................

4

 

 

Connecting cable

 

 

Screw driver

 

2) Indoor unit installation....

5

 

 

 

 

 

Electric drill

 

 

 

 

 

 

 

 

Hole core drill (ø 70mm)

 

3. Connecting Pipes to the Indoor Unit

 

 

 

 

1) Preparation of Piping...

12

 

 

Pipes: Gas side .....

1/2", 5/8", 3/4"

 

Flaring Tools set

 

 

 

 

 

Liquid side .............

1/4", 3/8", 1/2"

 

 

 

Insulated drain hose

Insulation materials

4.Connecting Pipes to the Outdoor Unit

1) Connecting the pipes to

Additional Drain hose

 

 

 

the Outdoor Unit ..........

14

(Inner Dia...............

25mm)

 

5.

Checking the Drainage ..............................................................................

 

 

14

6.

Connecting Cables between Indoor Unit and Outdoor Unit

 

1)

Connecting cables to the

 

Screw driver

 

 

 

Indoor Unit ...................

15

 

 

 

2)

Clamping of cables ......

15

 

 

 

3)

Connecting cables to the

 

 

 

 

 

Outdoor Unit ................

16

 

 

 

4)

Form the pipings ..........

17

 

 

 

7.

Air Purging of the Connecting Pipes and the Indoor Unit ....................

18

 

 

 

 

 

Hexagonal Wrench (4mm/5mm)

 

 

 

 

 

Gas-leak Detector

 

8.

Group Control ............................................................................................

 

 

 

19

9.

Two Thermistor System

............................................................................

 

19

10. E.S.P (External Static Pressure) Setting................................................

20

11. How to set E.S.P?. ...................................................................................

 

 

21

2

 

1. The following should be always observed for safety

 

 

<![if ! IE]>

<![endif]>ENGLISH

 

 

 

 

 

• Please report to or take consent by the supply authority before connecting to the system.

 

• Be sure to read "THE FOLLOWING SHOULD BE ALWAYS OBSERVED FOR SAFETY" before

 

 

installing the air conditioner.

 

• Be sure to observe the cautions specified here as they include important items related to safety.

 

• The indications and meanings are as follows.

 

 

 

 

 

 

 

 

 

 

 

WARNING

Could lead to death, serious injury, etc.

 

 

 

 

 

 

 

CAUTION

Could lead to serious injury in particular environments when operated incorrectly.

 

 

 

 

 

 

 

After reading this manual, be sure to keep it together with the owner's manual in an accessible place.

WARNING

Do not install it yourself (customer).

Incomplete installation could cause injury due to fire, electric shock, the unit falling or a leakage of water. Consult the dealer from whom you purchased the unit or special installer.

Install the unit securely in a place which can bear the weight of the unit.

When installed in an insufficient strong place, the unit could fall causing injured.

Use the specified wires to connect the indoor and the outdoor units securely and attach the wires firmly to the terminal board connecting sections so the stress of the wires is not applied to the sections.

• Incomplete connecting and fixing could cause fire.

Check that the refrigerant gas do not leak after installation is completed.

Perform the installation securely referring to the installation manual.

Incomplete installation could cause a personal injury due to fire, electric shock, the unit falling or a leakage of water.

Perform electrical work according to the installation manual and be sure to use an exclusive circuit.

If the capacity of the power circuit is insufficient or there is incomplete electrical work, it could result in a fire or an electric shock.

Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely.

If the electrical part cover if the indoor unit and/or the service panel if the outdoor unit are not attached securely, it could result in a fire or electric shock due to dust, water, etc.

Be sure to use the part provided or specified parts for the installation work.

The use of defective parts could cause an injury or leakage of water due to a fire, electric shock, the unit falling, etc.

CAUTION

Perform the drainage/piping work securely according to the installation manual.

If there is a defect in the drainage/piping work, water could drop from the unit and household goods could be wet and damaged.

Do not install the electric heater (18~42K)

Electric heater may cause deformation or fire of blower and housing which were made of plastic.

Do not install the unit in a place where an inflammable gas leaks.

If gas leaks and accumulates in the area surrounding the unit, it could cause an explosion.

3

2.Installation of Indoor, Outdoor Unit

1.Selection of the best location

1) Indoor unit

Top view

 

 

 

 

 

 

Inspection hole

 

 

 

 

 

 

(600X600)

 

 

 

 

 

 

Select location

(unit: mm)

 

 

 

 

 

 

Control box

Install the air conditioner in the location that

 

 

 

 

 

 

 

 

 

 

 

satisfies the following conditions.

 

 

 

 

 

 

 

 

 

 

 

• The place shall easily bear a load exceeding

 

 

600

 

 

<![if ! IE]>

<![endif]>1000

 

 

 

 

 

 

 

 

 

 

four times the indoor unit’s weight.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• The place shall be able to inspect the unit as

 

 

 

 

 

 

 

Front

the figure.

 

 

 

 

 

 

 

 

 

 

 

• The place where the unit shall be leveled.

Front view

 

 

 

 

 

 

 

 

 

• The place shall allow easy water

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

drainage.(Suitable dimension “H” is necessary

 

 

 

 

 

 

 

 

 

 

 

to get a slope to drain as figure.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• The place shall easily connect with the

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

outdoor unit.

 

 

 

 

 

 

 

 

 

 

 

The place where the unit is not affected by an electrical noise.

The place where air circulation in the room will be good .

There should not be any heat source or steam near the unit

600

2) Outdoor unit

 

Sunroof

 

• If an awning is built over the unit to prevent

 

 

direct sunlight or rain exposure, be careful

More

 

that heat radiation from the condenser is not

30cm

 

 

restricted.

 

 

 

• There should not be any animals or plants

 

 

 

which could be affected by hot air

Fence

 

 

discharged.

 

 

 

 

 

• Ensure the spaces indicated by arrows from

or

 

More than

obstacles

the wall, ceiling, fence or other obstacles.

30cm

 

 

 

More than

3) Piping length and the elevation

 

 

70cm

 

 

 

 

Pipe Size

Length A(m)

Elevation B(m)

*Additional

Capacity

(Diameter: Ø)

refrigerant

 

 

 

 

 

Gas

Liquid

Standard

Max.

Standard

Max.

(g/m)

18K BTU/h

5/8"

1/4"

7.5

50

5

30

30

24K BTU/h

5/8"

1/4"

7.5

50

5

30

35

30K BTU/h(1ø )

5/8"

1/4"

7.5

50

5

30

45

36K BTU/h(3ø )

5/8"

1/4"

7.5

50

5

30

45

36K BTU/h(1ø )

5/8"

1/4"

7.5

50

5

30

60

42K BTU/h(1ø )

3/4"

3/8"

7.5

50

5

30

55

42K BTU/h(3ø )

3/4"

3/8"

7.5

50

5

30

50

If 18K Model is installed at a distance of 15m, 225g of refrigerant should be added (15-7.5) x 30g = 225g

Capacity is based on standard length and maximun allowance length is on the basis of reliability.

Improper refrigerant charge may result in abnormal cycle.

Indoor unit

A

B

Outdoor unit

4

2. Indoor unit installation

 

 

 

 

Installation of Unit

 

 

 

 

 

 

 

Install the unit above the ceiling correctly.

 

<![if ! IE]>

<![endif]>ENGLISH

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

CASE 1

 

 

 

 

 

 

 

 

B

 

POSITION OF SUSPENSION BOLT

 

 

 

 

 

-canvas between the unit and

 

<![if ! IE]>

<![endif]>C E

 

 

 

unnecessary vibration.

 

 

 

 

 

 

 

 

 

 

 

Accessory at air return hole.

 

<![if ! IE]>

<![endif]>D

 

 

 

 

 

 

 

(Unit:mm)

 

 

 

 

 

 

 

 

(G)

<![if ! IE]>

<![endif]>F

Dimension

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity

A

B

C

D

E

F

(G)

H

I

 

 

 

 

 

 

 

 

 

 

 

 

 

18K BTU/h

932

880

355

45.5

450

30

87

750

163

 

 

24K BTU/h

<![if ! IE]>

<![endif]>I

<![if ! IE]>

<![endif]>mm

30K BTU/h

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36K BTU/h

1232 1180

355

45.5

450

30

87

830

186

 

<![if ! IE]>

<![endif]>1-3

42K BTU/h

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Drainage hole

 

CASE 2

 

 

 

leaning to a drainage hole

M10 Nut

X 4

 

M10 SP. washer X 4

(Local

for easy water drainage.

M10 washer

X 4

supply)

 

 

 

POSITION OF CONSOLE BOLT

M10 washer

X 4

(Local

 

M10 SP. washer X 4

 

supply)

the unit will be leveled and

M10 Nut

X 4

 

the weight of the unit.

 

 

 

the unit can withstand its

 

 

 

service can be easily

 

 

 

5

Select and mark the position for fixing bolts.

Drill the hole for set anchor on the face of ceiling.

Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling.

Mount the suspension bolts to the set anchor firmly.

Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers.

CAUTION

prevent

Old building

 

New building

1

Set anchor

2

Plate washer

3

Spring washer

4

Nut

 

5 Suspension

 

bolts

 

• Local supply

 

Set anchor

 

Plate washer

- M10

Spring washer

- M10

Nut

 

- W3/8 or M10

Suspension bolt

- W3/8 or M10

6

LG LB-H2460CL, LB-G3060CL, LB-H1860CL, LB-G3660CL Installation Manual

 

CAUTION

<![if ! IE]>

<![endif]>ENGLISH

1.

Install declination of the indoor unit is very important for the drain of the duct type air

 

 

conditioner.

 

2.

Minimum thickness of the insulation for the connecting pipe shall be 5mm.

 

Front of view

The unit must be horizontal or declined to the drain hose connected when finished installation.

 

 

Ceiling

 

 

 

<![if ! IE]>

<![endif]>1~3mm

 

CORRECT

Drainage hole

INCORRECT

Drainage hole

 

 

CAUTION FOR GRADIENT OF UNIT AND DRAIN PIPING

Lay the drain hose with a downward inclination so water will drain out.

Always lay the drain with downward inclination (1/50 to 1/100).

Prevent any upward flow or reverse flow in any part.

5mm or thicker formed thermal insulator shall always be provided for the drain pipe.

 

Thermal insulator

 

(Local supply)

 

Drainage pipe

Unit

(Local supply)

 

Make sure to be closed.

Drainage hole

• Upward routing not allowed

CORRECT

INCORRECT

Applied U-Trap Dimension

Install the P-Trap (or U-Trap) to prevent a water leakage caused by the blocking of intake air filter.

A

70mm

 

B

2C

 

 

C

2 x SP

B

SP = External Pressure

 

(mmAq)

C

Ex) External Pressure

U-Trap

 

= 10mmAq

 

A

70mm

A

 

B

40mm

 

 

C

20mm

 

7