CAUTION FOR UL/cUL REQUIREMENTS
-THE HYUNDAI HEAVY INDUSTRY N700E INVERTER UL FILE NUMBER IS E205705. CONFIRMATION OF UL LISTING CAN BE FOUND ON THE UL WEB SITE : www.ul.com
-DO NOT CONNECT OR DISCONNECT WIRING, OR PERFORM SIGNAL CHECKS WHILE THE POWER SUPPLY IS TURNED ON.
-THERE ARE LIVE PARTS INSIDE THE INVERTER. NEVER TOUCH THE PRINTED WIRING BOARD(PWB) WHILE THE POWER SUPPLY IS TURNED ON.
-[WARNING] THE BUS CAPACITOR DISCHARGE TIME IS 5 MINUTES. BEFORE STARTING WIRING OR INSPECTION, SWITCH POWER OFF, WAIT FOR MORE THAN 5 MINUTES, AND CHECK FOR RESIDUAL VOLTAGE BETWEEN TERMINAL P(+) AND N(-) WITH A METER ETC., TO AVOID HAZARD OF ELECTRICAL SHOCK.
-[SHORT CIRCUIT RATING] THIS INVERTER IS SUITABLE FOR USE ON A CIRCUIT CAPABLE OF DELIVERING NOT MORE THAN ___*1___ARMS SYMMETRICAL AMPERES, 480 VOLTS FOR HF TYPE AND 240 VOLTS FOR LF TYPEMAXIMUM. BRANCH CIRCUIT SHORT CIRCUIT PROTECTION SHALL BE PROVIDE BY FUSE ONLY *1 see each Model for exact kA
5KA
N700E-055LF/075LFP ~ N700E-370HF/450HFP All Model
10KA
N700E-450HF/550HFP ~ N700E-1320HF/1600HFP All Model
18KA
N700E-1600HF/2000HFP ~ N700E-2200HF/2500HFP All Model
30KA
N700E-2800HF/3200HFP ~ N700E-3500HF/3800HFP All Model
-[OVER SPEED PROTECTION] THIS INVERTER DOES NOT PROVIDE OVER SPEED PROTECTION.
-[MOTOR OVER LOAD PROTECTION] THIS INVERTER PROVIDES MOTOR OVER LOAD
PROTECTION.OVER LOAD PROTECTION LEVEL IS 20~120% OF FULL LOAD CURRENT. THE PROTECTION LEVEL MAY BE ADJUSTED BY CODE B04.REFER TO THE N700E USER GUIDE OR CATALOG.
- [MOTOR OVERTEMPERATURE]MOTOR OVERTEMPERATURE SENSING IS NOT PROVIDED BY THE
DRIVE.
-[ENVIRONMENT]
MAXIMUM AMBIENT TEMPERATURE
40℃
(WHEN CARRIER FREQUENCY EQUAL TO OR LESS THAN DEFAULT VALUE)
AMBIENT HUMIDITY
90% RH OR LESS(NO CONDENSING)
STORAGE TEMPERATURE
-20~60 VIBRATION
5.9OR LESS
ALTITUDE
ALTITUDE 1,000m OR LESS
AMBIENCE
INDOORS(NO CORROSIVE AND FLAMMABLE GASES,
OIL MIST, DUST AND DIRT)
POLLUTION DEGREE
2
N700E INSTRUCTION MANUAL
II
SAFETY
FOR THE BEST RESULTS WITH N700E SERIES INVERTER, READ THIS MANUAL AND ALL OF THE
WARNING SIGN ATTACHED TO THE INVERTER CAREFULLY BEFORE INSTALLING AND OPERATING IT, AND FOLLOW THE INSTRUCTION EXACTLY. KEEP THIS MANUAL HANDY FOR YOUR QUICK REFERENCE.
DEFINITIONS AND SYMBOLS
A SAFETY INSTRUCTION (MESSAGE) IS GIVEN WITH A HAZARD ALERT SYMBOL AND A SIGNED
WORD, WARNING or CAUTION.
EACH SIGNAL WORD HAS THE FOLLOWING MEANING THROUGHOUT THIS MANUAL.
THIS SYMBOL MEANS HAZARDOUS HIGH VOLTAGE. IT USED TO CALL YOUR ATTENTION TO ITEMS OR OPERATIONS THAT COULD BE DANGEROUS TO YOU OR OTHER PERSONS OPERATING THIS EQUIPMENT. READ THESE MESSAGES AND FOLLOW THESE INSTRUCTIONS CAREFULLY.
THIS IS THE “SAFETY ALERT SYMBOL”. THIS SYMBOL IS USED TO CALL YOUR ATTENTION TO ITEMS OR OPERATIONS THAT COULD BE DANGEROUS TO YOU OR OTHER PERSONS OPERATING THIS EQUIPMENT. READ THESE MESSAGES AND FOLLOW THESE INSTRUCTIONS CAREFULLY.
WARNING INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH, IF NOT AVOIDED, CAN RESULT IN SERIOUS INJURY OR DEATH.
CAUTION INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH, IF NOT AVOIDED, CAN RESULT IN MINOR TO MODERATE INJURY, OR SERIOUS DAMAGE OF PRODUCT. THE MATTERS DESCRIBED UNDER CAUTION MAY, IF NOT AVOIDED, LEAD TO SERIOUS RESULTS DEPENDING ON THE SITUATION. IMPORTANT MATTERS ARE DESCRIBED IN CAUTION (AS WELL AS WARNING), SO BE SURE TO OBSERVE THEM.
NOTENOTES INDICATE AN AREA OR SUBJECT OF SPECIAL MERIT,
EMPHASIZING EITHER THE PRODUCT`S CAPABILITIES OR COMMON ERRORS IN OPERATION OR MAINTENANCE.
HAZARDOUS HIGH VOLTAGE
MOTOR CONTROL EQUIPMENT AND ELECTRONIC CONTROLLERS ARE CONNECTED TO HAZARDOUS LINE VOLTAGE. WHEN SERVICING DRIVES AND ELECTRONIC CONTROLLERS, THERE MIGHT BE EXPOSED COMPONENTS WITHCASES OR PROTRUSIONS AT OR ABOVE LINE POTENTIAL. EXTREME CARE SHOULD BE TAKEN TO PRODUCT AGAINST SHOCK. STAND ON AN INSULATING PAD AND MAKE IT A HABIT TO USE ONLY ONE HAND WHEN CHECKING COMPONENTS. ALWAYS WORK WITH ANOTHER PERSON IN CASE AN EMERGENCY OCCURS. DISCONNECT POWER BEFORE CHECKING CONTROLLER OR PERFORMING MAINTENANCE. BE SURE EQUIPMENT IS PROPERLY GROUNDED. WEAR SAFETY GLASSES WHENEVER WORKING ON AN ELECTRIC CONTROLLER OR ROTATING ELECTRICAL EQUIPMENT.
N700E INSTRUCTION MANUAL
III
PRECAUTION
WARNING : THIS IS EQUIPMENT SHOULD BE INSTALLED, ADJUSTED AND SERVICED BY
QUALIFIED ELECTRICAL MAINTENANCE PERSONAL FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE EQUIPMENTS AND THE HAZARDS INVOLVED. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULTSIN BODILY INJURY.
WARNING : THE USER IS RESPONSIBLE FOR ENSURING THAT ALL DRIVEN MACHINERY, DRIVE TRAIN MECHANISM NOT SUPPLIED BY HYUNDAI AND PROCESS LINE MATERIAL ARE CAPABLE OF SAFE OPERATION AT AN APPLIED FREQUENCY OF 150% OF THE MAXIMUM SELECTED FREQUENCY RANGE TO THE AC MOTOR. FAILURE TO DO SO CAN RESULT IN DESTRUCTION OF EQUIPMENT AND INJURY TO PERSONNEL SHOULD A SINGLE POINT FAILURE OCCUR.
WARNING : FOR PROTECTION, INSTALL AN EARTH LEAKAGE BREAKER WITH A HIGH FREQUENCY CIRCUIT CAPABLE OF LARGE CURRENTS TO AVOID AN UNNECESSARY OPERATION. THE GROUND FAULT PROTECTION CIRCUIT IS NOT DESIGNED TO PROTECT PERSONAL INJURY.
CAUTION: HEAVY OBJECT. TO AVOID MUSCLE STRAIN OR BACK INJURY, USE LIFTING AIDS AND PROPER LIFTING TECHNIQUES WHEN REMOVING OR REPLACING.
CAUTION : THESE INSTRUCTIONS SHOULD BE READ AND CLEARLY UNDERSTOOD BEFORE WORKING ON N700E SERIES EQUIPMENT.
CAUTION : PROPER GROUNDS, DISCONNECTING DEVICES AND OTHER SAFETY DEVICES AND THEIR LOCATION ARE THE RESPONSIBILITY OF THE USER AND ARE NOT PROVIDED BY HYUNDAI.
CAUTION : BE SURE TO CONNECT A MOTOR THERMAL SWITCH OR OVERLOAD DEVICES TO THE N700E SERIES CONTROLLER TO ASSURE THAT INVERTER WILL SHUT DOWN IN THE EVENT OF AN OVERLOAD OR AN OVERHEATED MOTOR
CAUTION: ROTATING SHAFTS AND ABOVE GROUND ELECTRICAL POTENTIALS CAN BE HAZARDOUS. THEREFORE, IT IS STRONGLY RECOMMENDED THAT ALL ELECTRICAL WORK CONFORM TO THE NATIONAL ELECTRICAL CODES AND LOCAL REGULATIONS. ONLY QUALIFIED PERSONNEL SHOULD PERFORM INSTALLATION, ALIGNMENT AND MAINTENANCE. FACTORY RECOMMENDED TEST PROCEDURES, INCLUDE IN THE INSTRUCTION MANUAL, SHOULD BE FOLLOWED. ALWAYS DISCONNECT ELECTRICAL POWER BEFORE WORKING ON THE UNIT.
N700E INSTRUCTION MANUAL
IV
NOTE : POLLUTION DEGREE 2
THE INVERTER MUST BE USED IN THE ENVIRONMENT OF THE POLLUTION DEGREE 2. TYPICAL CONSTRUCTIONS THAT REDUCE THE POSSIBILITY OF CONDUCTIVE POLLUTION ARE,
1) THE USE OF AN UNVENTILATED ENCLOSURE.
2) THE USE OF A FILTERED VENTILATED ENCLOSURE WHEN THE VENTILATION IS FAN FORCED THAT IS, VENTILATION IS ACCOMPLISHED BY ONE MORE BLOWERS WITHIN THE ENCLOSURE THAT PROVIDE A POSITIVE INTAKE AND EXHAUST.
N700E INSTRUCTION MANUAL
V
CAUTIONFOR EMC (ELECTROMAGNETIC COMPATIBILITY)
TO SAFETY THE E MC DIRECTIVE AND TO COMPLY WITH STANDARD, FOLLOWS THE CHECKLIST BELOW.
THIS EQUIPMENT SHOULD BE INSTALLED, ADJUSTED, AND SERVICED BY QUALIFIED PERSONAL FAMILIAR WITH CONSTRUCTION AND OPERATION OF THE EQUIPMENT AND THE HAZARDS INVOLVED. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN BODILY INJURY.
1. THE POWER SUPPLY TO N700E INVERTER MUST MEET THESE SPECIFICATIONS a. VOLTAGE FLUCTUATION ±10% OR LESS. b. VOLTAGE IMBALANCE ±3% OR LESS. c. FREQUENCY VARIATION ±4% OR LESS. d. VOLTAGE DISTORTION THD = 10% OR LESS
2. INSTALLATION MEASURE : a. USE A FILTER DESIGNED FOR N700E INVERTER
3. WIRING a. SHIELDED WIRE (SCREENED CABLE) IS REQUIRED FOR MOTOR WIRING, AND THE
LENGTH MUST BE LESS THAN 20 METERS.
b. THE CARRIER FREQUENCY SETTING MUST BE LESS THAN 5KHZ TO SATISFY EMC
REQUIREMENTS. c. SEPARATE THE MAIN CIRCUIT FROM THE SIGNAL/PROCESS CIRCUIT WIRING. d. IN CASE OF REMOTE OPERATING WITH CONNECTOR CABLE, THE INVERTER DOES
NOT CONFORM TO EMC
4. ENVIRONMENTAL CONDITIONS – WHEN USING A FILTER, FOLLOW THESE GUIDELINES:
a. AMBIENT AIR TEMPERATURE : -10 - +40 b. HUMIDITY : 20 TO 90% RH(NON-CONDENSING) c. VIBRATION : 5.9 M/S2 (0.6G) 10 – 55HZ (N700E-5.5 ~ 380KW) d. LOCATION : 1000 METERS OR LESS ALTITUDE, INDOORS.
(NO CORROSIVE GAS OR DUST)
WARNING
N700E INSTRUCTION MANUAL
VI
CONFORMITY TO THE LOW VOLTAGE DIRECTIVE (LVD)
THE PROTECTIVE ENCLOSURE MUST CONFORM TO THE LOW VOLTAGE DIRECTIVE. THE INVERTER CAN CONFORM TO THE LVD BY MOUNTING INTO A CABINET OR BY ADDING COVERS AS FOLLOWS.
1. CABINET AND COVER
THE INVERTER MUST BE INSTALLED INTO A CABINET WHICH HAS THE PROTECTION DEGREE OF TYPE IP2X. IN ADDITION THE TOP SURFACES OF CABINET ARE EASILY ACCESSIBLE SHALL MEET AT LEAST THE REQUIREMENTS OF THE PROTECTIVE TYPE IP4X, OR WHICH IS CONSTRUCTED TO PREVENT SMALL OBJECTS FROM ENTERING INVERTER.
Fig 1. INVERTER CABINET
N700E INSTRUCTION MANUAL
VII
UL WARNINGS AND CAUTIONS MANUAL FOR N700E SERIES
THIS AUXILIARY INSTRUCTION MANUAL SHOULD BE DELIVERED TO THE END USER.
1. WIRING MARKING FOR ELECTRICAL PRACTICE AND WIRE SPECIFICATIONS
“USE COPPER CONDUCTOR ONLY, 75℃WITH A TORQUE RATING.
2. TIGHTENING TORQUE AND WIRE RANGE
TIGHTENING TORQUE AND WIRE RANGE FOR FIELD WIRING TERMINALS ARE MARKED ADJACENT TO THE TERMINAL OR ON THE WIRING DIAGRAM.
MODEL NAME
N700E-(Heavy Duty/Normal
Duty)
TIGHTENINGTORQUE
[LB-IN]
WIRE RANGE
(AWG)
RING
TERMINAL SIZE
MAXIMUM
WIDE [mm]
N700E-055LF/075LFP
12.4
8
10.6
N700E-075LF/110LFP
12.4
8
10.6
N700E-110LF/150LFP
26.6
6
13
N700E-150LF/185LFP
26.6
4
13
N700E-185LF/220LFP
35.4
3
17
N700E-220LF
35.4
1
17
N700E-055HF/075HFP
12.4
12
10.6
N700E-075HF/110HFP
12.4
10
10.6
N700E-110HF/150HFP
12.4
8
10.6
N700E-150HF/185HFP
26.6
8
13
N700E-185HF/220HFP
26.6
8
13
N700E-220HF/300HFP
26.6
6
13
N700E-300HF/370HFP
35.4
4
17
N700E-370HF/450HFP
35.4
2
17
N700E-450HF/550HFP
58.4
1
22
N700E-550HF/750HFP
58.4
2/0
22
N700E-750HF/900HFP
58.4
4/0
29
N700E-900HF/1100HFP
58.4
300 (kcmil)
29
N700E-1100HF/1320HFP
105.7
350 (kcmil)
30
N700E-1320HF/1600HFP
105.7
400 (kcmil)
30
N700E-1600HF/2000HFP
113
4/0*2P
38
N700E-2200HF/2500HFP
113
300 (kcmil)*2P
38
N700E-2800HF/3200HFP
113
4/0*4P
38
N700E-3500HF/3800HFP
113
300 (kcmil)*4P
38
*
RECOMMENDED RING TERMINAL SIZE (UL LISTED) FOR 055LF~110LF:MAXIMUM WIDE 12mm
N700E INSTRUCTION MANUAL
VIII
3. FUSE SIZE
DISTRIBUTION FUSE SIZE MARKING IS INCLUDED IN THE MANUAL TO INDICATE THAT THEUNIT SHALL BE CONNECTED WITH AN UL LISTED INVERSE TIME, RATED 600V WITH THECURRENT RATINGS OR AN UL LISTED FUSE AS SHOWN IN THE TABLE BELOW.
MODEL NAME
FUSE [A]
Manufacturer
N700E-055LF/075LFP
30
-
N700E-075LF/110LFP
40
-
N700E-110LF/150LFP
60
-
N700E-150LF/185LFP
80
-
N700E-185LF/220LFP
100
-
N700E-220LF
125
-
N700E-055HF/075HFP
15
-
N700E-075HF/110HFP
20
-
N700E-110HF/150HFP
30
-
N700E-150HF/185HFP
40
-
N700E-185HF/220HFP
50
-
N700E-220HF/300HFP
60
-
N700E-300HF/370HFP
80
-
N700E-370HF/450HFP
100
-
N700E-450HF/550HFP
125
-
N700E-550HF/750HFP
150
-
N700E-750HF/900HFP
200
-
N700E-900HF/1100HFP
250
-
N700E-1100HF/1320HFP
300
-
N700E-1320HF/1600HFP
400
-
N700E-1600HF/2000HFP
A50P800-4
Ferraz
N700E-2200HF/2500HFP
A50P1000-4
Ferraz
N700E-2800HF/3200HFP
A50P1200-4
Ferraz
N700E-3500HF/3800HFP
A50P1200-4
Ferraz
N700E INSTRUCTION MANUAL
IX
DEFINITIONS AND SYMBOLS
A SAFETY INSTRUCTION (MESSAGE) INCLUDES A HAZARD ALERT SYMBOL AND A SIGNAL WORD, DANGER OR CAUTION. EACH SIGNAL WORD HAS THE FOLLOWING MEANING :
THIS SYMBOL IS THE “SAFETY ALERT SYMBOL.” IT OCCURS WITH EITHER OF TWO SIGNAL WORDS : DANGER OR CAUTION, AS DESCRIBED BELOW.
: INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH, IF NOT
AVOIDED, CAN RESULT IN SERIOUS INJURY OR DEATH.
: INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH, IF NOT
AVOIDED, CAN RESULT IN MINOR TO MODERATE INJURY, OR SERIOUS DAMAGE TO THE PRODUCT.
THE SITUATION DESCRIBED IN THE CAUTION MAY, IF NOT AVOIDED, LEAD TO SERIOUS RESULTS. IMPORTANT SAFETY MEASURES ARE DESCRIBED IN CAUTION (AS WELL AS DANGER), SO BE SURE TO OBSERVE THEM. NOTE : INDICATES AN AREA OR SUBJECT OF SPECIAL MERIT, EMPHASIZING EITHER THE PRODUCT’S CAPABILITIES OR COMMON ERRORS DURING OPERATION OR MAINTENANCE.
General Safety Information
!
DANGER
!
CAUTION
N700E INSTRUCTION MANUAL
X
1. Installation
l Be sure to install the unit on flame resistant material such as metal.
Otherwise, there is a danger of fire.
l Be sure not to place anything highly flammable in the vicinity.
Otherwise, there is a danger of fire.
l Do not carry unit by top cover, always carry by supporting base of unit.
There is a risk of falling and injury.
l Be sure not to let foreign matter enter inverter such as cut wire refuse, spatter from welding,
iron refuse, wire, dust, etc. Otherwise, there is a danger of fire.
l Be sure to install inverter in a place which can bear the weight according to the specifications
in the text. (Chapter 6. Specifications) Otherwise, it may fall and there is a danger of injury.
l Be sure to install the unit on a perpendicular wall which is not subject to vibration
Otherwise, the inverter may fall and cause injury to personnel.
l Be sure not to install and operate an inverter which is damaged or has parts which are
missing. Otherwise, there is a danger of injury.
l Be sure to install the inverter in an area which is not exposed to direct sunlight and is well
ventilated. Avoid environments which tend to be high in temperature, high in humidity or to have dew condensation, as well as places with dust, corrosive gas, explosive gas, highly flammable gas, grinding-fluid mist, salt damage, etc. Otherwise, there is a danger of fire.
General Safety Information
N700E INSTRUCTION MANUAL
XI
2. Wiring
l Be sure to ground the unit.
Otherwise, there is a danger of electric shock and/or fire.
l Wiring work should be carried out by qualified electricians.
Otherwise, there is a danger of electric shock and/or fire.
l Implement wiring after checking that the power supply is off.
Otherwise, there is a danger of electric shock and/of fire.
l After installing the main body, carry out wiring.
Otherwise, there is a danger of electric shock and/or injury.
l Do not remove the rubber bushing where wiring connections are made.
Due to the possibility that a wire may be damaged, shorted or may have a ground fault with the edge of the wiring cover.
l Make sure that the input voltage is:
Three phase 200 to 240V 50/60Hz Three phase 380 to 480V 50/60Hz
l Be sure not to single phase the input.
Otherwise, there is a danger of fire.
l Be sure not to connect AC power supply to the output terminals(U, V, W).
Otherwise, there is a danger of injury and/or fire and/or damage to unit.
l Be sure not to connect a resistor to the DC terminals(PD, P and N) directly.
Otherwise, there is a danger of fire and/or damage to unit.
l Be sure to install an earth leakage breaker or the fuse(s) which is(are) the same phase as the
main power supply in the operation circuit. Otherwise, there is a danger of fire and/or damage to unit.
l As for motor leads, earth leakage breakers, and electromagnetic contactors, be sure to use
equivalent ones with the specified capacity(rated). Otherwise, there is a danger of fire and/or damage to unit.
l Do not stop operation by switching off the electromagnetic contactors on the primary or
secondary sides of the inverter. Otherwise, there is a danger of injury and/or machine breakage.
l Fasten the screws to the specified torque. Check so that there is no loosening of screws.
Otherwise, there is a danger of fire and/or injury to personnel.
General Safety Information
N700E INSTRUCTION MANUAL
XII
3. Control and operation
l While the inverter is energized, be sure not to touch the main terminal or to check
the signal or add or remove wires and/or connectors. Otherwise, there is a danger of electric shock.
l Be sure to turn on the power supply with the front case is closed.
While the inverter is energized, be sure not to open the front case. Otherwise, there is a danger of electric shock.
l Be sure not to operate the switches with wet hands.
Otherwise, there is a danger of electric shock.
l While the inverter is energized, be sure not to touch the inverter terminals even while the unit
is not running. Otherwise, there is a danger of electric shock.
l If the retry mode is selected, it may suddenly restart during the trip stop.
Be sure not to approach the equipment. (Be sure to design the equipment so that personnel safety will be secured even if equipment restarts.) Otherwise, there is a danger of injury.
l Be sure not to select retry mode for equipment running up and down or traversing because
there is output free-running mode in term of retry. Otherwise, there is a danger of injury and/or machine breakage.
l Even if the power supply is cut for a short period of time, the inverter may restart operation
after the power supply is restored if the operation command is given. If a restart may incur danger to personnel, be sure to make a circuit so that it will not restart after power recovery. Otherwise, there is a danger of injury.
l The stop key is valid only when a function is on. Ensure that there is a hard wired emergency
stop that is separate from the stop key of the inverter. Otherwise, there is a danger of injury.
l With the operation command on, if the alarm reset is ordered, the inverter can restart
suddenly. Be sure to set the alarm reset after checking the operation command is off. Otherwise, there is a danger of injury.
l Be sure not to touch the inside of the energized inverter or to put a shorting bar into it.
Otherwise, there is a danger of electric shock and/or fire.
General Safety Information
N700E INSTRUCTION MANUAL
XIII
l The cooling fins will have a high temperature. Be sure not to touch them.
Otherwise, there is a danger of getting burned.
l Low to high speed operation of the inverter can be easily set. Be sure to operate it after
checking the tolerance of the motor and machine. Otherwise, there is a danger of injury.
l Install an external breaking system if needed.
Otherwise, there is a danger of injury.
l If a motor is operated at a frequency outside of the standard setting value (50Hz/60Hz), be
sure to check the speeds of the motor and the equipment with each manufacturer, and after getting their consent, operate them. Otherwise, there is a danger of equipment breakage.
l Check the following before and during the test run.
Was the direction of the motor correct? Did the inverter trip for on acceleration or deceleration? Were the RPM and frequency motor correct? Were there any abnormal motor vibrations or noises? Otherwise, there is a danger of machine breakage.
l The AC reactor must be installed When the power is not stable.if not, inverter can be broken.
4. Maintenance, inspection and part replacement
l After turning off the input power supply, do not perform the maintenance and inspection for
at least 10 minutes. Otherwise, there is a danger of electric shock.
l Make sure that only qualified persons will perform maintenance, inspection and/or part
replacement. (Before starting the work, remove metallic objects(wristwatch, bracelet, etc.) from a worker. (Be sure to use insulated tools.)Otherwise, there is a danger of electric shock and/or injury.
5. Others
l Never modify the unit.
Otherwise, there is a danger of electric shock and/or injury.
l Heavy object(over 15kg).
To avoid muscle strain or back injury, use lifting aids and proper lifting techniques when removing or replacing.
General Safety Information
CAUTION
N700E INSTRUCTION MANUAL
XIV
CONTENTS
1. GENERAL DESCRIPTION ............................................................................... 1-1
1.1 Inspection upon Unpacking ........................................................................................... 1-1
1.1.1 Inspection of the unit ..................................................................................................... 1-1
1.1.2 Instruction manual ........................................................................................................ 1-1
1.2 Questions and Warranty of the Unit ............................................................................... 1-2
1.2.1 Questions on Unit ......................................................................................................... 1-2
1.2.2 Warranty for the unit ..................................................................................................... 1-2
1.3 Appearance .................................................................................................................. 1-3
1.3.1 N700E-055LF/075LFP ~ N700E-220HF/300HFP .......................................................... 1-3
1.3.2 N700E-300HF/370HFP ~ N700E-1320HF/1600HFP ..................................................... 1-4
1.3.3 N700E-1600HF/2000HFP ~ N700E-2200HF/2500HFP ................................................. 1-5
1.3.4 N700E-2800HF/3200HFP ~ N700E-3500HF/3800HFP ................................................. 1-6
2. Installation and Wiring ....................................................................................... 2-1
2.1 Installation .................................................................................................................... 2-1
2.1.1 Installation .................................................................................................................... 2-2
2.2 Wiring ........................................................................................................................... 2-4
2.2.1 Terminal Connection Diagram (sink type) ...................................................................... 2-5
2.2.2 Main circuit wiring ......................................................................................................... 2-8
2.2.3 Terminal connection diagram ...................................................................................... 2-15
3. Operation ............................................................................................................. 3-1
3.1 Operating...................................................................................................................... 3-3
3.1.1 Operation setting and a frequency setting by the terminal control .................................. 3-3
3.1.2 Operation setting and frequency setting with the digital operator ................................... 3-3
3.1.3 Operation setting and frequency setting from both the digital operator and the terminal
operator ........................................................................................................................ 3-3
3.2 Test Run ....................................................................................................................... 3-4
3.2.1 To input the operation setting and the frequency setting from the terminal control .......... 3-4
3.2.2 Operation setting and the frequency setting from the digital operator ............................. 3-5
4. Parameter Code List .......................................................................................... 4-1
4.1 About Digital Operator .................................................................................................. 4-1
4.1.1 Name and contents of each part of Standard-type digital operator ................................. 4-1
4.1.2 Key Definition and Operation of “SHIFT” ....................................................................... 4-4
4.2 Function List ................................................................................................................. 4-5
4.2.1 Monitor Mode (d-group) ................................................................................................ 4-5
4.2.2 Trip & Warning monitor mode (d-group) ...................................................................... 4-6
4.2.3 Basic Function Mode .................................................................................................... 4-7
4.2.4 Expanded Function Mode of A Group ............................................................................ 4-8
4.2.5 Expanded function mode of b group ............................................................................ 4-18
4.2.6 Expanded Function Mode of C Group ......................................................................... 4-26
4.2.7 Expanded Function mode of H Group ......................................................................... 4-30
5. Using intelligent terminals ................................................................................. 5-1
5.1 Intelligent terminal lists .................................................................................................. 5-1
5.2 Monitor terminal function ............................................................................................... 5-4
5.3 Intelligent Input Terminal Function ................................................................................. 5-6
5.4 Using Intelligent output terminals ................................................................................ 5-24
5.5 Alarm Terminal Function ............................................................................................. 5-29
5.6 Sensorless Vector Control ........................................................................................... 5-30
6. Protective function ............................................................................................. 6-1
N700E INSTRUCTION MANUAL
XV
7. Troubleshooting Tips ......................................................................................... 7-1
8. Maintenance and Inspection ............................................................................ 8-1
8.1 General Precautions and Notes .................................................................................... 8-1
8.2 Inspection Items ........................................................................................................... 8-1
8.3 General Inverter Electrical Measurements ..................................................................... 8-4
9. RS485 Communication ..................................................................................... 9-1
10. Specification ...................................................................................................... 10-1
10.1 Standard specification list ........................................................................................... 10-1
10.2 The selection of braking resistor and the breaking unit ................................................ 10-4
10.3 Dimension .................................................................................................................. 10-5
N700E INSTRUCTION MANUAL
1-1
1. GENERAL DESCRIPTION
1.1 Inspection upon Unpacking
1.1.1 Inspection of the unit
Please open the package, remove the inverter, please check the following items.
If you discover any unknown parts or the unit is damaged, please contact HYUNDAI. (1) Make sure that the package contains one operation manual for the inverter. (2) Make sure that there was no damage (broken parts in the body) during transportation of the unit. (3) Make sure that the product is the one you ordered by checking the label specification.
Fig1-1 Outlook of N700E Inverter
Fig1-2 Contents of Specification label
1.1.2 Instruction manual
This instruction manual is the manual for the N700E inverters.
Before operation of the inverter, read the manual carefully. After reading this manual, keep it on
hand for future reference
N700E INSTRUCTION MANUAL
1-2
1.2 Questions and Warranty of the Unit
1.2.1 Questions on Unit
• If you have any questions regarding damage to the unit, unknown parts or for general inquiries, please contact your LOCAL HYUNDAI BRANCH with the following information.
(1) Inverter Model (2) Production Number (Serial No.) (3) Date of purchase (4) Reason for Calling
Damaged part and its condition etc. Unknown parts and their contents etc.
1.2.2 Warranty for the unit
(1) The warranty period of the unit is one year after the purchase date. However the warranty will be void if
the fault is due to;
Incorrect use as directed in this manual, or attempted repair by unauthorized personnel. Any damage sustained other than from transportation (Which should be reported immediately). Using the unit beyond the limits of the specifications. Natural Disasters : Earthquakes, Lightning, etc
(2) The warranty is for the inverter only, any damage caused to other equipment by malfunction of the
inverter is not covered by the warranty.
(3) Any examination or repair after the warranty period (one-year) is not covered. And within the warranty
period any repair and examination which results in information showing the fault was caused by any of the items mentioned above, the repair and examination costs are not covered. If you have any questions regarding the warranty, please contact either your Local HYUNDAI Branch.
N700E INSTRUCTION MANUAL
1-3
1.3 Appearance
1.3.1 N700E-055LF/075LFP ~ N700E-220HF/300HFP
Fig1-3 Appearance from the front
Fig1-4 Front cover removed
Front Cover
Main circuit terminals
Control circuit terminals
Operator
N700E INSTRUCTION MANUAL
1-4
1.3.2 N700E-300HF/370HFP ~ N700E-1320HF/1600HFP
Fig1-5Appearance from the front
Fig1-6Front cover removed
Front Cover
Main circuit terminals
Control circuit terminals
Operator
N700E INSTRUCTION MANUAL
1.3.3 N700E-1600HF/2000HFP ~ N700E
Operator
Front Cover
Control circuit terminals
Main circuit terminals
1-5
Fig1-7Appearance from the front
Fig1-8Front cover removed
N700E INSTRUCTION MANUAL
1.3.4 N700E-2800HF/3200HFP ~ N700E
Operator
Front Cover
Control circuit terminals
Main Circuit Terminals
1-6
Fig1-9Appearance from the front
Fig1-10Front cover removed
N700E INSTRUCTION MANUAL
2-1
2. Installation and Wiring
2.1 Installation
l Be sure to install the unit on flame resistant material such as metal.
Otherwise, there is a danger of fire.
l Be sure not to place anything flammable in the vicinity.
Otherwise, there is a danger of fire.
l Do not carry the unit by the top cover, always carry by supporting the base of
unit. There is a risk of falling and injury.
l Be sure not to let foreign matter enter such as cut wire refuse, spatter from
welding, iron refuse, wire, dust, etc. Otherwise, there is a danger of fire.
l Be sure to install the inverter in a place which can bear the weight according to
the specifications in the text. Otherwise, it may fall and result in possible injury.
l Be sure to install the unit on a perpendicular wall which is not subject to vibration.
Otherwise, the inverter may fall and cause injury to personnel.
l Be sure not to install and operate an inverter which is damaged or parts of which
are missing. Otherwise, there is a danger of injury.
l Be sure to install the inverter in an area which is not exposed to direct sunlight
and is well ventilated. Avoid environments which tend to be high in temperature, high in humidity or to have dew condensation, as well as places with dust, corrosive gas, explosive gas, inflammable gas, grinding-fluid mist, salt damage, etc. Otherwise, there is a danger of fire.
N700E INSTRUCTION MANUAL
2-2
2.1.1 Installation
(1) Transportation
This inverter has plastic parts. So handle with care. Do not over tighten the wall mounting fixings as the mountings may crack, causing is a risk of falling. Do not install or operate the inverter if there appears to be damaged or parts missing.
(2) Surface for the mounting of inverter
The temperature of the inverter heatsink can rise very high. The surface, to which the inverter will be mounted, must be made of a non-flammable material(i.e. steel) due to the possible risk of fire. Attention should also be made to the air gap surrounding the inverter. Especially, when there is a heat source such as a breaking resistor or reactor.
Fig 2- 1Surface for the mounting of inverter
(3) Operating Environment-Ambient Temperature
The ambient temperature surrounding the inverter should not exceed the allowable temperature range (14 to 122°F, -10 to 50). The temperature should be measured in the air gap surrounding the inverter, shown in the diagram above. If the temperature exceeds the allowable temperature, component life will become shortened especially in the case of the Capacitors.
(4) Operating Environment-Humidity
The humidity surrounding the inverter should be within the limit of the allowable percentage range (20% to 90% / RH). Under no circumstances should the inverter be in an environment where there is the possibility of moisture entering the inverter. Also avoid having the inverter mounted in a place that is exposed to the direct sunlight.
(5) Operating Environment-Air
Install the inverter in a place free from dust, corrosive gas, explosive gas, combustible gas, mist of coolant and sea damage.
Ensure proper spacing for ventilation to prevent the unit from overheating.
(Note1) 10cm or more for 5.5kW to 55kW inverter 30cm or more for 75kW to 132kW inverter 50cm or more for 160kW to 375kW inverter
N700E INSTRUCTION MANUAL
2-3
(6) Mounting Position
Mount the inverter in a vertical position using screws or bolts. The mounting surface should also be free from vibration and can easily hold the weight of the inverter.
Fig 2-2Mounting Position
(7) Ventilation within an Enclosure
If you are installing one or more inverters in an enclosure a ventilation fan should be installed. Below is a guide to the positioning of the fan to take the airflow into consideration. The positioning of inverter, cooling fans and air intake is very important. If these positions are wrong, airflow around the inverter decreases and the temperature surrounding the inverter will rise. So please make sure that the temperature around is within the limit of the allowable range.
.
(8) External cooling of inverter
It is possible to install the inverter so that the heatsink is outside of the back of the enclosure. This method has two advantages, the cooling of the inverter is greatly increased and the size of the enclosure will be smaller. To install it with the heatsink outside of the enclosure, a metal fitting option is required to ensure heat transfer. Do not install in a place where water, oil, mist, flour, and/or dust etc. can come in contact with the inverter as there are cooling fans fitted to the heatsink.
N700E INSTRUCTION MANUAL
2-4
2.2 Wiring
l Be sure to ground the unit.
Otherwise, there is a danger of electric shock and/or fire.
l Wiring work should be carried out by qualified electricians.
Otherwise, there is a danger of electric shock and/or fire.
l Implement wiring after checking that the power supply is off.
Otherwise, there is a danger of electric shock and/of fire.
l After mounting the inverter, carry out wiring.
Otherwise, there is a danger of electric shock and/or injury.
l Do not remove the rubber bushings where wiring connections are made.
(5.5 to 22kW) Due to the possibility that a wire may be damaged, shorted or may have a ground fault with the edge of the wiring cover.
l Make sure that the input voltage is:
Three phase 200 to 240V 50/60Hz (Model : N700E-055LF/075LFP~220LF) Three phase 380 to 480V 50/60Hz (Model : N700E-055HF/075HFP~3500HF/3800HFP)
l Be sure not to power a three-phase-only inverter with single phase power.
Otherwise, there is a danger of fire.
l Be sure not to connect AC power supply to the output terminals(U, V, W).
Otherwise, there is a danger of injury and/or fire and/or damage to unit.
l Be sure not to connect a resistor to the DC terminals(PD, P) directly.
Otherwise, there is a danger of fire and/or damage to unit..
l Be sure to set a earth leakage breaker or the fuse(s) which is(are) the same
phase as the main power supply in the operation circuit. Otherwise, there is a danger of fire and/or damage to unit..
l As for motor leads, earth leakage breakers, and electromagnetic contactors,
be sure to use equivalent ones with the specified capacity(rated). Otherwise, there is a danger of fire and/or damage to unit..
l Do not stop operation by switching off the electromagnetic contactors on the
primary or secondary sides of the inverter. Otherwise, there is a danger of injury and/or machine breakage.
l Fasten the screws to the specified torque. Check so that there is no loosening of
screws. Otherwise, there is a danger of fire and/or damage to unit..
N700E INSTRUCTION MANUAL
2-5
2.2.1 Terminal Connection Diagram (sink type)
Fig.2-3 Terminal Connection Diagram (sink type)
N700E INSTRUCTION MANUAL
2-6
(1) Explanation of main circuit Terminals
Symbol
Terminal Name
Explanation of contents
R,S,T (L1,L2,L3)
Main power
Connect alternating power supply. When using regenerative converter and RG series, don’t connect.
U,V,W (T1,T2,T3)
Inverter output
Connect three-phase motor.
PD,P (+1,+)
D.Creactor
Remove the short bar between PD and P, connect optional Power factor reactor (DCL).
P, RB (+, -)
External braking resistor
Connect optional External braking resistor. (Please install the optional External braking resistor for 5.5~22 model.)
P, N
External braking Unit
Connect optional External braking Unit
(Please install the optional External braking Unit for 30~350 model.)
G
Inverter earth terminals
Grounding terminal.
Table 2-1Explanation of main circuit terminals
(2) Control circuit Terminals
Signal
Terminal
Symbol
Terminal name
Terminal function
Input
signal
P24
Interface power
24VDC ±10%, 35
6 (RS)
Intelligent Input Terminal
Forward run command(FW), Reverse runcommand(RV), multi-speed commands1-4(CF1-4),2-stage accel/decel(2CH), Reset(RS),Terminal software lock(SFT), Unattended start protection(USP), Current input selection(AT),Jogging operation(JG), External trip(EXT), 3 wires input(STA,STP,F/R) Up/Down(Up, Down), Local Keypad Operation(O/R), Local Terminal Input Operation(T/R), PID Integral Reset(PIDIR), PID Disable(PIDD)
Contact input : Close : ON (operating) Open : OFF(stop)
Minimum ON TIME :12msor more
5 (AT)
4 (CF2)
3 (CF1)
2 (RV)
1 (FW)
CM1
Common terminal for input or monitor signal
Monitor
signal
FM
Analog Monitor (Frequency, Current, Voltage, Power)
0~10Vdc, Max 1mA
AMI
Analog Monitor (Frequency, Current, Voltage, Power)
4~20mA, Max 250 Ω
Frequency
command
signal
H
Frequency power
12VDC
O
Frequency command power terminal (voltage)
0-10VDC, Input Impedance 10kΩ
OI
Frequency command terminal (current)
4-20mA, Input Impedance 250Ω
L
Analog power common
No.1
Channel
Communication
terminal
RJ-45
Basic Communication connect
Basic RS-485 Communication terminal
No.2
Channel
Communication
terminal
RXP
RS-485 Communication + terminal
No.2 Channel RS-485 Communication terminal
RXN
RS-485 Communication - terminal
N700E INSTRUCTION MANUAL
2-7
Signal
Terminal
Symbol
Terminal name
Terminal function
Output
signal RN0 RN1
Intelligent output terminal: Run status signal(RUN), Frequency arrival signal(FA1), Set frequency arrival signal(FA2), Overload advance notice signal(OL), PID error deviation signal(OD), Alarm signal(AL)
Contact rating: AC 250V2.5A
(resistor load)
0.2A (inductor load) DC 30V 3.0A (resistor load)
0.7A (inductor load)
RN2 RN3
Intelligent
Output
signal
AL0 AL1 AL2
Alarm output terminal:
Run status signal(RUN), Frequency arrival signal(FA1), Set frequency arrival signal(FA2), Overload advance notice signal(OL), PID error deviation signal(OD), Alarm signal(AL)
Alarm output signals : at normal status, power off : AL0-AL2 (closed)
at abnormal status : AL0-AL1(closed)
Contact rating: AC 250V2.5A
(resistor load)
0.2A (inductor load) DC 30V 3.0A (resistor load)
0.7A (inductor load)
Table2-2Control circuit Terminals
N700E INSTRUCTION MANUAL
2-8
2.2.2 Main circuit wiring
(1) Warning on wiring
When carrying out work on the inverter wiring make sure to wait for at least ten minutes before you remove the cover. Be sure to verify that the charge lamp is not illuminated. A final check should always be made with a voltage meter. After removing the power supply, there is a time delay before the capacitors will dissipate their charge.
Main power terminals (R(L1), S(L2) and T(L3))
l Connect the main power terminals (R(L1), S(L2) and T(L3)) to the power supply through an
electromagnetic contactor or an earth-leakage breaker. N700 recommends connecting the electromagnetic contactor to the main power terminals, because when the protective function of the inverter operates, it isolates the power supply and prevents the spread of damage and accident.
l This unit is for a three-phase power supply. Be sure not to power a three-phase only inverter
with single phase power. Otherwise, there is the possibility of damage to the inverter and the danger of fire.
l If you require a single phase power supply unit, please contact your local HYUNDAI Branch. l The inverter enters into the following condition at the occurrence of open phase if it is selected
open phase protection is valid :
- R phase, S phase or T phase, open phase condition:
It becomes single-phase operation condition. Trip operation, such as a deficiency voltage or over current, may occur.
l Don't use it under open phase condition. A converter module may be damaged as a result of
the following conditions. Use caution when
- an unbalance of the power supply voltage is more than 3%
- Power supply capacity is more than 10 times of the capacity of inverter and case beyond
500kVA.
- A drastic change in the power supply
(Example) Turning on/off of the power supply should not be done more than three times in one
minute. It has the possibility of damaging the inverter.
Inverter output terminals (U(T1), V(T2), and W(T3))
l Using a heavier gauge wire can prevent the voltage drop.
Particularly when outputting low frequencies, the torque of the motor will be reduced by the voltage drop of the wire. Do not install power factor correction capacitors or a surge absorber to the output. The inverter will trip or sustain damage to the capacitors or the surge absorber.
l In the case of the cable length being more than 65 feet, it is possible that a surge voltage will
be generated and damage to the motor is caused by the floating capacity or the inductance in the wire. When an EMC filter is to be installed, please contact your local HYUNDAI branch.
l In the case of two or more motors, install a thermal relay to each motor. l Make the RC value of the thermal relay the value of 1.1 times of motor rated electric current.
Direct current reactor (DCL) connection terminals (PD, P)
l
These are the terminals to connect the current reactor DCL (optional) to help improve the power factor.
l The short bar is connected to the terminals when shipped from the factory, if you are to connect
a DCL you will need to disconnect the short bar first.
l When you do not use a DCL, do not disconnect the short bar.
External braking resistor connection terminals (P, RB)
l The regenerative braking circuit (BRD) is built-in as standard l When braking is required, install an external-braking resistor to these terminals. l The cable length should be less than 16 feet, and twist the two connecting wires to reduce
inductance. Do not connect any other device other than the external braking resistor to these terminals.