Installation & Operation Manual
Central Air Conditioner
10 to 13 SEER 1.5 to 5 Tons Models: HC18-60A1VAR/S
HC18-60C1VAR
HC18-60D1VAR
No.0010572324
K
The information contained in this booklet is subject to change without notice.
! WARNING
These instructions are intended as an aid to qualified, licensed service personnel for proper installation, adjustment and operation of this unit. Read these instructions thoroughly before attempting installation or operation.Failure to follow these instructions may result in improper installation, adjustment, service or maintenance possibly resulting in fire, electrical shock, property damage, personal injury or death.
This product is designed and manufactured to permit installation in accordance with National CodesIt . is the installer's responsibility to install the product in accordance with National Codes and/or prevailing local codes and regulations. The manufacturer assumes no responsibility for equipment installed in violation of any codes or regulations.
The United States Environmental Protection Agency (EPA) has issued various regulations regarding the introduction and disposal of refrigerants in this unitFailure. to follow these regulations may harm the environment and can lead to the imposition of substantial fines. Because these regulations may vary due to the passage of new laws we suggest that any work on this unit be done by a certified technician. Should you have any questions please contact the local EPA office.
The manufacturer's warranty does not cover any damage or defect to the air conditioner caused by the attachment or use of any components, accessories or devices (other than those authorized by the manufacturer) into, onto, or in conjunction with the air conditionerYou. should be aware that the use of unauthorized components, accessories or devices may adversely affect the operation of the air conditioner and may also endanger life and property. The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such unauthorized components, accessories or devices.
Attach the service panel to the outdoor unit securely. If the service panel is not attached securely, it could result in a fire or an electric shock due to dust, water, etc.
These instructions are intended as an aid to qualified, licensed service personnel for proper installation, adjustment and operation of this unit. Read these instructions thoroughly before attempting installation or operation.Failure to follow these instructions may result in improper installation, adjustment, service or maintenance possibly resulting in fire, electrical shock, property damage, personal injury or death.
This product is designed and manufactured to permit installation in accordance with National CodesIt . is the installer's responsibility to install the product in accordance with National Codes and/or prevailing local codes and regulations. The manufacturer assumes no responsibility for equipment installed in violation of any codes or regulations.
The United States Environmental Protection Agency (EPA) has issued various regulations regarding the introduction and disposal of refrigerants in this unitFailure. to follow these regulations may harm the environment and can lead to the imposition of substantial fines. Because these regulations may vary due to the passage of new laws we suggest that any work on this unit be done by a certified technician. Should you have any questions please contact the local EPA office.
The manufacturer's warranty does not cover any damage or defect to the air conditioner caused by the attachment or use of any components, accessories or devices (other than those authorized by the manufacturer) into, onto, or in conjunction with the air conditionerYou. should be aware that the use of unauthorized components, accessories or devices may adversely affect the operation of the air conditioner and may also endanger life and property. The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such unauthorized components, accessories or devices.
Attach the service panel to the outdoor unit securely. If the service panel is not attached securely, it could result in a fire or an electric shock due to dust, water, etc.
Message to Owner
These instructions should be carefully read and kept near theoductpr for future reference. While the instructions are addressed primarily to the installer, useful maintenance information is included. Have your installer acquaint you with the operating characteristics of the product and periodic maintenance requirements.
TABLE OF CONTENT |
|
1.Introduction --------------------------------------------------------------------------------------- |
1 |
2.Nomenclature for Model Number ------------------------------------------------------------- |
1 |
3.Specification ------------------------------------------------------------------------------------- |
2 |
4.Unit Inspection ----------------------------------------------------------------------------------- |
5 |
5.Equipment Protection From Environment ---------------------------------------------------- |
5 |
6.Installation ---------------------------------------------------------------------------------------- |
5 |
6.1. General --------------------------------------------------------------------------------------- |
5 |
6.2.Unit clearances ------------------------------------------------------------------------------ |
6 |
6.3.Refrigerant piping --------------------------------------------------------------------------- |
6 |
6.4.Electrical wiring ----------------------------------------------------------------------------- |
10 |
7.System Startup ----------------------------------------------------------------------------------- |
11 |
8.Operation ---------------------------------------------------------------------------------------- |
12 |
9.Miscellaneous ----------------------------------------------------------------------------------- |
12 |
9.1.Replacement parts -------------------------------------------------------------------------- |
12 |
9.2.Troubleshooting guide --------------------------------------------------------------------- |
12 |
9.3.Wiring diagram ----------------------------------------------------------------------------- |
12 |
1.INTRODUCTION
This manual contains the installation and operating instructionsfor your new air conditioner. Improper installation can result in unsatisfactory operation or dangerous conditions. Carefully read this manual and any instructions packaged with separate equipment required to make up the system prior to installation. Give this manual to the ownerand explain its provisions. The owner should retain this manual for future reference.
2.NOMENCLATURE FOR MODEL NUMBER
H |
Brand symbol - H: Haier |
|
|
C |
System type - C: Air conditioner; R: Heat pump. |
|
|
24 |
Nominal capacity in (000) Btuh |
A |
SEER designation. A=10, B=11, C=12, D=13, E=14 |
|
|
1 |
Design series. 1 - st1 Generation |
V |
Electric: V=208/230-1-60; C=208/230-3-60, D=460-3-60, Y=575-3-60 |
A |
Body style |
|
|
R |
Compressor type |
|
Example: HC24A1VAR |
|
|
1
2
MODEL: |
|
HC18A1VAR |
HC24A1VAR |
HC30A1VAR |
HC36A1VAS |
HC42A1VAR |
HC48A1VAR |
HC60A1VAR |
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Unit Supply Voltage |
|
|
|
208/230-1-60 |
|
|
|
|
|
|
|
||
Normal Voltage Range |
|
|
|
197 - 253 |
|
|
|
|
|
|
|
||
Compressor Brand |
|
Bristol |
|
Sanyo |
Bristol |
Sanyo |
|
Bristol |
Sanyo |
Bristol |
|||
|
|
|
H20R |
H29A |
|||||||||
Minimum Circuit Amps |
10.1 |
12.9 |
16.2 |
19.4 |
24.3 |
21.2 |
28.1 |
|
31.9 |
35.1 |
37.6 |
29.7 |
|
Max Fuse or Max CKT. BKR. |
|
|
|
|
|
|
|
|
|
|
|
|
|
(HACR per NEC ) |
15 |
20 |
25 |
30 |
40 |
35 |
45 |
|
50 |
60 |
|
50 |
|
|
|
||||||||||||
|
Rated Load Amps |
7.4 |
9.6 |
11.8 |
14.4 |
18.3 |
15.8 |
21.3 |
|
24.4 |
26.9 |
28.9 |
22.6 |
Compressor |
Locked Running |
|
|
|
|
|
|
|
|
|
|
|
|
|
Amps |
48 |
60 |
73 |
88 |
130 |
90 |
130 |
|
140 |
149 |
165 |
147 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Full Load Amps |
0.86 |
0.86 |
1.4 |
1.4 |
1.43 |
1.43 |
|
1.43 |
|
|
||
Fan Motor |
|
|
|
|
|
|
|
|
|
|
|
|
|
Rated HP |
1/8 |
1/8 |
1/5 |
1/5 |
1/3 |
1/3 |
|
|
1/3 |
|
|
||
|
Nominal RPM |
850 |
1000 |
1075 |
1075 |
1075 |
1075 |
|
1075 |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Liquid Line OD - In (mm) |
3/8"[9.52] |
3/8"[9.52] |
3/8"[9.52] |
3/8"[9.52] |
3/8" [9.52] |
3/8"[9.52] |
3/8"[9.52] |
|
|||||
Vapor Line OD - In (mm) |
5/8"[15.88] |
5/8"[15.88] |
3/4"[19.05] |
3/4"[19.05] |
3/4"[19.05] |
3/4"[19.05] |
|
7/8"[22.2] |
|
||||
R-22 Charge -Oz (g) |
49.47[1400] |
63.60[1800] |
88.34[2500] |
93.64[2650] |
115.19[3260] |
122.97[3480]128.27[3630] |
137.81[3900] |
141.34[4000] |
|||||
Net Dimensions - In (mm) |
23*23*24 |
23*23*24 |
23*23*31 1/2 |
23*23*31 1/2 |
30 1/4*30 1/4*31 1/2 |
30 1/4*30 1/4*31 1/2 |
30 1/4*30 1/4*35 1/2 |
||||||
W*D*H |
|
[585 *585*605] |
[585 *585*605] |
[ 585 *585*805] |
[ 585 *585*805] |
[770 *770*805] |
[ 770 *770*805] |
[ 770 *770*905] |
|
||||
Shipping Dimensions - In (mm) |
25*25*28 1/4 |
25*25*28 1/4 |
25*25*36 |
25*25*36 |
32 3/4*32 3/4*36 |
32 3/4*32 3/4*36 |
32 3/4*32 3/4*40 1/2 |
||||||
W*D*H |
|
[632*632*719] |
[632*632*719] |
[632* 632*919] |
[632* 632*919] |
[832*832*930] |
[ 832*832*930] |
[832*832*1030] |
|
||||
Net Weight - Lbs (kg) |
123[56] |
125[57] |
134[61] |
141[64] |
209[95] |
198[90] |
209[95] |
|
200[91] |
220[100] |
216[98] |
||
Approx Shipping Weight - Lbs (kg) |
141[64] |
143 [65] |
158[72] |
165[75] |
231[105] |
222[101] |
231[105] |
|
222[101] |
246[112] |
242[110] |
|
for1 Tablein provided are specifications 60A1VAR/S-Model:HC18 1: Table |
unit condensing the for dimensions The |
SPECIFICATION.3 |
.respectively systems SEER 10 |
Physical .1 Figurein illustrated are |
|
|
electrical and |
|
D W
H
Figure 1
Table 2:System Cooling Capacity
Outdoor Unit |
|
|
With This Indoor Air handler |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||
Model Number |
|
Air Handler |
|
|
Compressor |
|
Cooling Capacity (Btu/h) |
|
SEER |
Rated |
|
|
|
|
|
||||||||||||
|
|
|
|
|
|
|
brand |
|
Sensible |
|
|
Total |
|
|
|
CFM(Outdoor) |
|
|
|
|
|||||||
HC18A1VAR |
|
HB2400VA1M20 |
|
Bristol |
|
|
13000 |
|
|
18000 |
|
10 |
1850 |
|
|
|
|
|
|||||||||
HC24A1VAR |
|
HB2400VA1M20 |
|
Bristol |
|
|
17000 |
|
|
24000 |
|
10 |
1850 |
|
|
|
|
|
|||||||||
HC30A1VAR |
|
HB3000VA1M20 |
|
Bristol |
|
|
20000 |
|
|
28000 |
|
10 |
1950 |
|
|
|
|
|
|||||||||
HC36A1VAS |
|
HB3600VA1M20 |
|
Bristol |
|
|
24000 |
|
|
34000 |
|
10 |
1950 |
|
|
|
|
|
|||||||||
HC42A1VAR |
|
HB4200VA1M25 |
|
Sanyo |
|
|
28400 |
|
|
40000 |
|
10 |
2700 |
|
|
|
|
|
|||||||||
|
|
|
|
|
|
|
Bristol |
|
|
29160 |
|
|
40500 |
|
10 |
2700 |
|
|
|
|
|
||||||
HC48A1VAR |
|
HB4800VA1M25 |
|
Sanyo |
|
|
33120 |
|
|
46000 |
|
10 |
2900 |
|
|
|
|
|
|||||||||
|
|
|
|
|
|
|
Bristol |
|
|
33120 |
|
|
46000 |
|
10 |
2900 |
|
|
|
|
|
||||||
HC60A1VAR |
|
HB6000VA1M25 |
|
Sanyo |
|
|
40170 |
|
|
55800 |
|
10 |
2900 |
|
|
|
|
|
|||||||||
|
|
|
|
|
|
|
Bristol |
|
|
40180 |
|
|
56000 |
|
10 |
2900 |
|
|
|
|
|
||||||
The dimensions for the condensing unit are illustratedFigurein |
1. Physical and electrical |
|
|
|
|
|
|||||||||||||||||||||
specifications are provided inTable 3for 12 SEER systems respectively. |
|
|
|
|
|
|
|
|
|||||||||||||||||||
Table 3: Model:HC18-60C1VAR |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||
MODEL: |
|
|
|
HC18C1VAR |
HC24C1VAR |
HC30C1VAR |
|
HC36C1VAR |
|
|
HC42C1VAR |
HC48C1VAR |
HC60C1VAR |
||||||||||||||
Unit Supply Voltage |
|
|
|
|
|
|
|
|
|
208/230-1-60 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
Normal Voltage Range |
|
|
|
|
|
|
|
|
|
197 - 253 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Bristol |
|
|
|
|
|
||
Compressor Brand |
|
|
|
|
Bristol |
|
|
|
|
|
|
|
H29A |
|
|
H20J |
H29A |
|
H23R |
H20R |
|
H23R |
|||||
Minimum Circuit Amps |
|
10.1 |
|
13.4 |
|
16.2 |
|
17.7 |
|
|
22.3 |
|
21.2 |
24.8 |
|
|
34.7 |
|
37.6 |
|
38.5 |
||||||
Max Fuse or Max CKT. BKR. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
(HACR per NEC ) |
|
15 |
|
25 |
|
25 |
|
|
30 |
|
|
|
40 |
|
35 |
40 |
|
|
60 |
|
60 |
|
60 |
||||
|
Rated Load Amps |
7.4 |
|
9.6 |
|
11.8 |
|
13.0 |
|
|
16.7 |
|
15.8 |
18.7 |
|
|
26.6 |
28.9 |
|
28.8 |
|||||||
Compressor |
Locked Running |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
Amps |
|
48 |
|
60 |
|
73 |
|
85 |
|
|
|
105 |
|
90 |
135 |
|
|
155 |
165 |
|
145 |
|||||
|
Full Load Amps |
0.86 |
|
1.4 |
|
1.4 |
|
1.43 |
|
|
|
1.43 |
1.43 |
|
|
1.43 |
|
2.5 |
|||||||||
Fan Motor |
Rated HP |
|
1/8 |
|
1/5 |
|
1/5 |
|
1/3 |
|
|
|
|
1/3 |
1/3 |
|
|
1/3 |
|
1/2 |
|||||||
|
Nominal RPM |
|
850 |
|
1075 |
|
1075 |
|
1075 |
|
|
|
1075 |
1075 |
|
|
1075 |
||||||||||
Liquid Line OD - In (mm) |
|
3/8"[9.52] |
|
3/8"[9.52] |
3/8"[9.52] |
|
3/8"[9.52] |
|
|
3/8" [9.52] |
3/8"[9.52] |
|
3/8"[9.52] |
||||||||||||||
Vapor Line OD - In (mm) |
|
5/8"[15.88] |
|
3/4"[19.05] |
3/4"[19.05] |
|
3/4"[19.05] |
|
|
7/8"[22.2] |
7/8"[22.2] |
|
7/8"[22.2] |
||||||||||||||
R-22 Charge -Oz (g) |
|
74.2 [2100] |
|
91.87[2600] |
88.34[2500] |
102.47[2900] |
|
132.51[3750] |
120.14[3400]125.44[3550] |
127.21[3600] |
171.38[4850] |
183.75[5200] |
|||||||||||||||
Net Dimensions - In (mm) |
|
23*23*27 3/4 |
23*23*27 3/4 |
23*23*31 1/2 |
|
30 1/4*30 1/4*27 3/4 |
30 1/4*30 1/4*35 1/2 |
301/4*30 1/4*35 1/2 |
30 1/4*30 1/4*31 1/2 |
||||||||||||||||||
W*D*H |
|
|
|
[585* 585*705] |
[585* 585*705] |
[585* 585*805] |
[770 *770*705] |
|
[770 *770*905] |
[770 *770*905] |
|
[ 770 *770*805] |
|||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||
Shipping Dimensions - In (mm) |
|
25*25*32 1/4 |
25*25*32 1/4 |
25*25*36 |
|
32 3/4*32 3/4*32 1/2 |
32 3/4*32 3/4*40 1/2 |
32 3/4*32 3/4*40 1/2 |
32 3/4*32 3/4*36 |
||||||||||||||||||
W*D*H |
|
|
|
[632* 632*819] |
[632* 632*819] |
[632* 632*919] |
[832*832*830] |
|
[832*832*1030] |
[832*832*1030] |
[832* 832*930] |
||||||||||||||||
Net Weight - Lbs (kg) |
|
123[56] |
|
125[57] |
139[63] |
|
196[89] |
|
|
231[105] |
238[108] |
|
298[135] |
||||||||||||||
Approx Shipping Weight - Lbs (kg) |
141[64] |
|
143[65] |
152[69] |
|
222[101] |
|
257 [117] |
264[120] |
|
321[146] |
3
Table 4:System Cooling Capacity
Outdoor Unit |
With This Indoor Air handler |
|
|
|
|
||
Model Number |
Air Handler |
Compressor |
Cooling Capacity (Btu/h) |
SEER |
Rated |
||
|
|
brand |
Sensible |
Total |
|
|
CFM(Outdoor) |
HC18C1VAR |
HB2400VC1M20 |
Bristol |
14820 |
19000 |
|
12 |
1950 |
HC24C1VAR |
HB2400VC1M20 |
Bristol |
18720 |
24000 |
|
12 |
1950 |
HC30C1VAR |
HB3600VA1M20 |
Bristol |
23400 |
30000 |
|
12 |
1950 |
HC36C1VAR |
HB3600VC1M25 |
Bristol |
25920 |
36000 |
|
12 |
2700 |
HC42C1VAR |
HB4800VA1M25 |
Bristol |
30240 |
42000 |
|
12 |
2900 |
HC48C1VAR |
HB4800VA1M25 |
Bristol |
34560 |
48000 |
|
12 |
2900 |
HC60C1VAR |
HB6000VC1M25 |
Bristol |
41800 |
58000 |
|
12 |
2900 |
The dimensions for the condensing unit are illustratedFigurein 1. Physical and electrical specifications are provided inTable 5for 13 SEER systems respectively.
Table 5: Model:HC18-60D1VAR
MODEL: |
|
HC18D1VAR |
HC24D1VAR |
HC30D1VAR |
HC36D1VAR |
HC42D1VAR |
HC48D1VAR |
HC60D1VAR |
|||||
Unit Supply Voltage |
|
|
|
|
|
208/230-1-60 |
|
|
|
|
|
||
Normal Voltage Range |
|
|
|
|
|
197 - 253 |
|
|
|
|
|
|
|
Compressor Brand |
|
|
|
|
|
Bristol |
|
|
|
|
|
|
|
Minimum Circuit Amps |
8.6 |
11.6 |
|
12.4 |
|
15.9 |
|
17.7 |
|
21.8 |
|
33.3 |
|
Max Fuse or Max CKT. BKR. |
|
|
|
|
|
|
|
|
|
|
|
|
|
(HACR per NEC ) |
15 |
20 |
|
20 |
|
25 |
|
30 |
|
35 |
|
55 |
|
|
Rated Load Amps |
6.2 |
8.6 |
|
9.2 |
|
11.7 |
|
13.0 |
|
15.8 |
|
25.0 |
Compressor |
Locked Running |
|
|
|
|
|
|
|
|
|
|
|
|
|
Amps |
41 |
60 |
|
60 |
|
73 |
|
85 |
|
90 |
|
150 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Full Load Amps |
0.86 |
0.86 |
|
0.86 |
|
1.3 |
|
1.43 |
|
2.0 |
|
2.0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fan Motor |
Rated HP |
1/8 |
1/6 |
|
1/6 |
|
1/4 |
|
1/3 |
|
1/3 |
|
1/3 |
|
Nominal RPM |
1000 |
840 |
|
840 |
|
850 |
|
1075 |
|
960 |
|
880 |
Liquid Line OD - In (mm) |
3/8"[9.52] |
3/8"[9.52] |
|
3/8"[9.52] |
|
3/8"[9.52] |
|
3/8" [9.52] |
3/8"[9.52] |
|
3/8"[9.52] |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Vapor Line OD - In (mm) |
3/4"[19.05] |
3/4"[19.05] |
|
3/4"[19.05] |
|
7/8"[22.2] |
|
7/8"[22.2] |
|
7/8"[22.2] |
|
7/8"[22.2] |
|
|
|
|
|
|
|
|
|
|
|||||
R-22 Charge -Oz (g) |
93.64[2650] |
102.47[2900] |
121.91[3450] |
134.28[3800] |
148.41[4200] |
178.45[5050] |
196.11[5550] |
||||||
|
|
|
|
|
|
|
|
|
|||||
Net Dimensions - In (mm) |
23*23*31 1/2 |
30 1/4*30 1/4*27 3/4 |
30 1/4*30 1/4*31 1/2 |
30 1/4*30 1/4*31 1/2 |
30 1/4*30 1/4*35 1/2 |
30 1/4*30 1/4*31 1/2 |
30 1/4*30 1/4*35 1/2 |
||||||
W*D*H |
|
[585* 585*805] |
[770* 770*705] |
[770* 770*805] |
[770 |
*770*805] |
[770 |
*770*905] |
[770 |
*770*805] |
[ 770 |
*770*905] |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Shipping Dimensions - In (mm) |
24 3/4*24 3/4*36 |
32 3/4*32 3/4*32 1/2 |
32 3/4*32 3/4*3632 |
3/4*32 3/4*36 |
32 |
3/4*32 3/4*40 1/2 |
32 |
3/4*32 3/4*36 |
32 3/4*32 3/4*40 1/2 |
||||
W*D*H |
|
[632* 632*919] |
[832* 832*830] |
[ 832* 832*930] |
|
[832*832*930] |
[832*832*1030] |
|
[832*832*930] |
[832*832*1030] |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Net Weight - Lbs (kg) |
156[71] |
194[88] |
|
198[90] |
|
203[92] |
|
231[105] |
|
244[111] |
258[117] |
||
Approx Shipping Weight - Lbs (kg) |
167[76] |
209[95] |
|
216[98] |
|
220[100] |
|
249 [113] |
|
262[119] |
|
282[128] |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Table 6:System Cooling Capacity
Outdoor Unit |
With This Indoor Air handler |
|
|
|
|
||
Model Number |
Air Handler |
Compressor |
Cooling Capacity (Btu/h) |
SEER |
Rated |
||
|
|
brand |
Sensible |
Total |
|
|
CFM(Outdoor) |
HC18D1VAR |
HB2400VD1M20 |
Bristol |
13300 |
18000 |
|
13 |
1350.0 |
HC24D1VAR |
HB2400VD1M20 |
Bristol |
17700 |
24000 |
|
13 |
1800.0 |
HC30D1VAR |
HB3600VD1M22 |
Bristol |
20669 |
28000 |
|
13 |
2100 |
HC36D1VAR |
HB3600VD1M22 |
Bristol |
25900 |
35000 |
|
13 |
2700 |
HC42D1VAR |
HB4800VD1M22 |
Bristol |
29600 |
40000 |
|
13 |
3200 |
HC48D1VAR |
HB4800VD1M22 |
Bristol |
34800 |
47000 |
|
13 |
3600 |
HC60D1VAR |
HB6000VD1M22 |
Bristol |
40700 |
55000 |
|
13 |
4000 |
4